ASME  A17.2,  Guide  for  Inspection  of  Elevators, 
Escalators,  and  Moving  Walks,  2010  Edition,  as 
required  by  States  and  Municipalities,  including 
Oregon  in  the  Administrative  Rules,  Chapter  918, 
Division  400,  Safety  Code  for  Elevators,  Section 
918-400-0455. 


T.sswa&.'v 


^*"*1 


a 


s£ 


m^mmk:*  *  *  *  mm^mmmxm 


Guide  for  Inspection  of 
Elevators,  Escalators, 
and  Moving  Walks 

Includes  Inspection  Procedures  for 
Electric  Traction  and  Winding  Drum 
Elevators,  Hydraulic  Elevators, 
Inclined  Elevators,  and  Escalators 
and  Moving  Walks 


AN   AMERICAN    NATIONAL  STANDARD 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers.  Ax 

No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME.     ^ 


INTENTIONALLY  LEFT  BLANK 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  Al  7.2-2010 

(Revision  of  ASME  A17.2-2007) 


Guide  for  Inspection  of 
Elevators,  Escalators, 
and  Moving  Walks 


Includes  Inspection  Procedures  for 
Electric  Traction  and  Winding  Drum 
Elevators,  Hydraulic  Elevators, 
Inclined  Elevators,  and  Escalators 
and  Moving  Walks 


AN   AMERICAN    NATIONAL   STANDARD 


Three  Park  Avenue  •  New  York,  NY  •  10016  USA 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers.  ^f 

No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME,     ^ 


Date  of  Issuance:  December  9,  2010 


The  next  edition  of  this  Guide  is  scheduled  for  publication  in  2013.  There  will  no  addenda  issued 
to  this  edition. 

ASME  issues  written  replies  to  inquiries  concerning  interpretations  of  technical  aspects  of  this  Guide. 
Interpretations  are  also  published  on  the  ASME  Web  site  under  the  Committee  Pages  at 
http://cstools.asme.org  as  they  are  issued. 


ASME  is  the  registered  trademark  of  The  American  Society  of  Mechanical  Engineers. 

This  Guide  was  developed  under  procedures  accredited  as  meeting  the  criteria  for  American  National  Standards.  The 
Standards  Committee  that  approved  the  Guide  was  balanced  to  assure  that  individuals  from  competent  and  concerned 
interests  have  had  an  opportunity  to  participate.  The  proposed  Guide  was  made  available  for  public  review  and  comment 
that  provides  an  opportunity  for  additional  public  input  from  industry,  academia,  regulatory  agencies,  and  the  public- 
at-large. 

ASME  does  not  "approve,"  "rate,"  or  "endorse"  any  item,  construction,  proprietary  device,  or  activity. 

ASME  does  not  take  any  position  with  respect  to  the  validity  of  any  patent  rights  asserted  in  connection  with  any 
items  mentioned  in  this  document,  and  does  not  undertake  to  insure  anyone  utilizing  a  standard  against  liability  for 
infringement  of  any  applicable  letters  patent,  nor  assume  any  such  liability.  Users  are  expressly  advised  that  determination 
of  the  validity  of  any  such  patent  rights,  and  the  risk  of  infringement  of  such  rights,  is  entirely  their  own  responsibility. 

Participation  by  federal  agency  representative(s)  or  person(s)  affiliated  with  industry  is  not  to  be  interpreted  as 
government  or  industry  endorsement  of  this  Guide. 

ASME  accepts  responsibility  for  only  those  interpretations  of  this  document  issued  in  accordance  with  the  established 
ASME  procedures  and  policies,  which  precludes  the  issuance  of  interpretations  by  individuals. 


No  part  of  this  document  may  be  reproduced  in  any  form, 

in  an  electronic  retrieval  system  or  otherwise, 

without  the  prior  written  permission  of  the  publisher. 


The  American  Society  of  Mechanical  Engineers 
Three  Park  Avenue,  New  York,  NY  10016 


Copyright  ©  2010  by 

THE  AMERICAN  SOCIETY  OF  MECHANICAL  ENGINEERS 

All  rights  reserved 

Printed  in  U.S.A. 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


CONTENTS 


Foreword x 

Committee  Roster   xiii 

Preface  xviii 

Summary  of  Changes  xxi 

Introduction 1 

1  Scope   1 

2  Application    1 

3  Qualifications  of  Inspectors  2 

4  Personal  Safety  2 

5  Duties  of  Inspectors   2 

6  Arrangement  for  Inspection 2 

7  Recommended  Equipment  2 

8  Reference  Documents 3 

Part  1               Elevator  —  Inside  of  Car 4 

1.1  Door  Reopening  Device    4 

1.2  Stop  Switches    4 

1.3  Operating  Control  Devices 5 

1.4  Sills  and  Car  Floor    5 

1.5  Car  Lighting  and  Receptacles  6 

1.6  Car  Emergency  Signal   7 

1.7  Car  Door  or  Gate 7 

1.8  Door  Closing  Force  8 

1.9  Power  Closing  of  Doors  or  Gates    8 

1.10  Power  Opening  of  Doors  or  Gates    8 

1.11  Car  Vision  Panels  and  Glass  Car  Doors    9 

1.12  Car  Enclosure   11 

1.13  Emergency  Exit 12 

1.14  Ventilation    12 

1.15  Signs  and  Operating  Device  Symbols    12 

1.16  Rated  Load,  Platform  Area,  and  Data  Plate 13 

1.17  Standby  Power  Operation    13 

1.18  Restricted  Opening  of  Car  or  Hoistway  Doors 14 

1.19  Car  Ride   15 

1.20  Earthquake  Inspection  and  Tests  (Seismic  Risk  Zone  2  or  Greater)    15 

Part  2               Elevator  —  Machine  Room 16 

2.1  Access  to  Machine  Space    16 

2.2  Headroom    16 

2.3  Lighting  and  Receptacles   16 

2.4  Machine  Space   17 

2.5  Housekeeping  17 

2.6  Ventilation    17 

2.7  Fire  Extinguisher  18 

2.8  Pipes,  Wiring,  and  Ducts    18 

2.9  Guarding  of  Exposed  Auxiliary  Equipment 18 

2.10  Numbering  of  Elevators,  Machines,  Controllers,  and  Disconnect 

Switches  18 

2.11  Disconnecting  Means  and  Control 19 

2.12  Controller  Wiring,  Fuses,  Grounding,  etc 20 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


2.13  Governor,  Overspeed  Switch,  and  Seal   21 

2.14  Code  Data  Plate  25 

2.15  Static  Control 25 

2.16  Overhead  Beam  and  Fastenings 26 

2.17  Drive  Machine  Brake  26 

2.18  Traction  Drive  Machines 27 

2.19  Gears,  Bearings,  and  Flexible  Couplings 28 

2.20  Winding  Drum  Machine  and  Slack  Rope  Device,  Stop  Motion  Switch,  and 

Rope  Fastening    28 

2.21  Belt-  or  Chain-Drive  Machine  29 

2.22  Motor  Generator    30 

2.23  Absorption  of  Regenerated  Power 30 

2.24  AC  Drives  From  a  DC  Source 30 

2.25  Traction  Sheaves 31 

2.26  Secondary  and  Deflector  Sheaves    31 

2.27  Rope  Fastenings 31 

2.28  Terminal  Stopping  Devices 32 

2.29  Car  and  Counterweight  Safeties 33 

2.30  Hydraulic  Power  Unit   38 

2.31  Relief  Valves    38 

2.32  Control  Valve    39 

2.33  Tanks  39 

2.34  Flexible  Hydraulic  Hose  and  Fitting  Assemblies  40 

2.35  Supply  Line  and  Shutoff  Valve 40 

2.36  Hydraulic  Cylinders 41 

2.37  Pressure  Switch    41 

2.38  Roped  Water  Hydraulic  Elevators  42 

2.39  Low  Oil  Protection   42 

2.40  Maintenance  Records  42 

2.41  Static  Control 42 

2.42  Earthquake  Inspection  and  Tests  (Seismic  Risk  Zone  2  or  Greater)    42 

Part  3  Elevator  -  Top  of  Car. 44 

3.1  Top-of-Car  Stop  Switch  44 

3.2  Car  Top  Light  and  Outlet 44 

3.3  Top-of-Car  Operating  Device    44 

3.4  Top-of-Car  Clearance,  Refuge  Space,  and  Standard  Railing 45 

3.5  Normal  Terminal  Stopping  Devices   46 

3.6  Final  and  Emergency  Terminal  Stopping  Devices  47 

3.7  Car  Leveling  and  Anticreep  Devices 48 

3.8  Top  Emergency  Exit   49 

3.9  Floor  and  Emergency  Identification  Numbering   49 

3.10  Hoistway  Construction    49 

3.11  Hoistway  Smoke  Control    50 

3.12  Pipes,  Wiring,  and  Ducts    50 

3.13  Windows,  Projections,  Recesses,  and  Setbacks    50 

3.14  Hoistway  Clearances    51 

3.15  Multiple  Hoistways 51 

3.16  Traveling  Cables  and  Junction  Boxes   52 

3.17  Door  and  Gate  Equipment 53 

3.18  Car  Frame  and  Stiles   55 

3.19  Guide  Rails  Fastening  and  Equipment    55 

3.20  Governor  Rope  56 

3.21  Governor  Releasing  Carrier  56 

3.22  Wire  Rope  Fastening  and  Hitch  Plate    56 

3.23  Suspension  Rope   58 

3.24  Top  Counterweight  Clearance 61 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


3.25  Car,  Overhead,  and  Deflector  Sheaves 61 

3.26  Broken  Rope,  Chain,  or  Tape  Switch    61 

3.27  Crosshead  Data  Plate  and  Rope  Data  Tags   61 

3.28  Counterweight  and  Counterweight  Buffer  62 

3.29  Counterweight  Safeties   62 

3.30  Speed  Test    63 

3.31  Slack  Rope  Device  —  Roped-Hydraulic  Elevators  Installed  Under 

A17.1b-1989  and  Later  Editions    63 

3.32  Traveling  Sheave  —  Roped-Hydraulic  Elevators  Installed  Under 

A17.1b-1989  and  Later  Editions    64 

3.33  Compensating  Ropes  and  Chains   64 

3.34  Earthquake  Inspection  and  Tests  (Seismic  Risk  Zone  2  or  Greater)    64 

Part  4  Elevator  —  Outside  Hoistway. 66 

4.1  Car  Platform  Guard    66 

4.2  Hoistway  Doors  66 

4.3  Vision  Panels 67 

4.4  Hoistway  Door  Locking  Devices   67 

4.5  Access  to  Hoistway 68 

4.6  Power  Closing  of  Hoistway  Doors    68 

4.7  Sequence  Operation   69 

4.8  Hoistway  Enclosure    69 

4.9  Elevator  Parking  Devices    69 

4.10  Emergency  Doors  in  Blind  Hoistways  69 

4.11  Separate  Counterweight  Hoistway    70 

4.12  Standby  Power  Selection  Switch    70 

Part  5  Elevator  -  Pit 71 

5.1  Pit  Access,  Lighting,  Stop  Switch,  and  Condition  71 

5.2  Bottom  Clearance,  Runby,  and  Minimum  Refuge  Space  72 

5.3  Final  and  Emergency  Terminal  Stopping  Devices  73 

5.4  Normal  Terminal  Stopping  Devices    74 

5.5  Traveling  Cables 74 

5.6  Governor-Rope  Tension  Devices 74 

57  Car  Frame  and  Platform  75 

5.8  Car  and  Counterweight  Safeties  and  Guiding  Members  —  Including 

Roped-Hydraulic  Elevators  Installed  Under  A17.1b-1989  and  Later 

Editions 75 

5.9  Buffer  and  Emergency  Terminal  Speed  Limiting  Devices 76 

5.10  Compensating  Chains,  Ropes,  and  Sheaves 78 

5.11  Plunger  and  Cylinder 78 

5.12  Car  Buffer 78 

5.13  Guiding  Members  79 

5.14  Supply  Piping 79 

5.15  Overspeed  Valve   79 

5.16  Earthquake  Inspection  and  Tests  (Seismic  Risk  Zone  2  or  Greater)    80 

Part  6  Elevator  -  Firefighters'  Service 81 

6.1  Operation  of  Elevators  Under  Fire  and  Other  Emergency  Conditions 

(A17.1b-1973  Through  A17.1b-1980)   81 

6.2  Operation  of  Elevators  Under  Fire  and  Other  Emergency  Conditions 

(A17.1-1981  Through  A17.1b-1983)    83 

6.3  Firefighters'  Service  (A17.1-1984  Through  A17.1a-1988  and  A17.3)  85 

6.4  Firefighters'  Service  (A17.1b-1989  Through  A17.1d-2000)   87 

6.5  Acceptance  Checklist  for  Firefighters'  Service  (ASME  A17.1-2000  and 

CSA  B44-00);  Automatic  Elevators   91 

Part  7  Escalator  —  External 94 

7.1  General  Fire  Protection   94 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


7.2  Geometry   94 

7.3  Handrails   95 

7.4  Entrance  and  Egress  Ends    96 

75  Lighting 98 

7.6  Caution  Signs  98 

7.7  Combplate  and  Comb  Step  Impact  Device    98 

7.8  Deck  Barricades  and  Antislide  Devices  100 

7.9  Steps  and  Upthrust  Device    102 

7.10  Operating  and  Safety  Devices 102 

7.11  Skirt  Obstruction  Device 106 

7.12  (Reserved)    106 

7.13  Egress  Restriction  (Rolling  Shutter)  Device   106 

7.14  Speed  106 

7.15  Balustrades 107 

7.16  Ceiling  Intersection  Guards  108 

7.17  Step  /Skirt  Clearances,  Panels,  and  Performance  Index  108 

7.18  Outdoor  Protection  Ill 

7.19  Maintenance  Records  Ill 

7.20  Earthquake  Inspection  and  Tests  (Seismic  Risk  Zone  2  or  Greater)    Ill 

Part  8  Escalator  -  Internal 113 

8.1  Machinery  Space  Access,  Lighting,  Receptacle,  and  Condition    113 

8.2  Machinery  Space  Stop  Switches  and  Inspection  Control 113 

8.3  Controller  and  Wiring   114 

8.4  Drive  Machine  and  Brake 114 

85  Speed  Governor  115 

8.6  Broken  Drive  Chain  and  Disconnected  Motor  Safety  Device    116 

8.7  Reversal  Stop  Switch   116 

8.8  Broken  Step  Chain  Device   117 

8.9  Step  Upthrust  Device 117 

8.10  Missing  Step  Device  117 

8.11  Step  Level  Device   117 

8.12  Steps,  Step  Chains,  and  Trusses  118 

8.13  Handrail  Systems  and  Safety  Devices   119 

8.14  Code  Data  Plate  120 

8.15  Response  to  Smoke  Detectors  120 

8.16  Step  Lateral  Displacement  Device  120 

8.17  Inspection  Control 120 

8.18  Earthquake  Inspection  and  Tests  (Seismic  Risk  Zone  2  or  Greater)    121 

Part  9  Moving  Walk  -  External 122 

9.1  General  Fire  Protection   122 

9.2  Geometry   122 

9.3  Handrails   122 

9.4  Entrance  and  Egress  Ends    125 

9.5  Lighting 125 

9.6  Caution  Signs   126 

9.7  Combplate  and  Comb  Step  Impact  Device    126 

9.8  Deck  Barricades   127 

9.9  Treadways 127 

9.10  Operating  and  Safety  Devices 128 

9.11  (Reserved)    129 

9.12  (Reserved)    129 

9.13  Egress  Restriction  (Rolling  Shutter)  Device   129 

9.14  Speed  129 

9.15  Balustrades 130 

9.16  Ceiling  Intersection  Guards  130 

9.17  Skirt  Panels   131 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


9.18  Outdoor  Protection  131 

9.19  Maintenance  Records  132 

9.20  Earthquake  Inspection  and  Tests  (Seismic  Risk  Zone  2  or  Greater)    132 

Part  10            Moving  Walk  -  Internal 133 

10.1  Machinery  Space  Access,  Lighting,  Receptacle,  and  Condition    133 

10.2  Stop  Switch  and  Inspection  Control  133 

10.3  Controller  and  Wiring   134 

10.4  Drive  Machine  and  Brake 134 

10.5  Speed  Governor  135 

10.6  Broken  Drive  Chain  and  Disconnected  Motor  Safety  Device    136 

10.7  Reversal  Stop  Switch   136 

10.8  Broken  Treadway  Device 136 

10.9  (Reserved)    137 

10.10  Missing  Pallet  Device 137 

10.11  Pallet  Level  Device   137 

10.12  Pallets,  Pallet  Chains,  and  Trusses 137 

10.13  Handrail  Systems  and  Safety  Devices   138 

10.14  Code  Data  Plate  139 

10.15  Response  to  Smoke  Detectors  139 

10.16  Inspection  Control 139 

10.17  Earthquake  Inspection  and  Tests  (Seismic  Risk  Zone  2  or  Greater)    139 

Part  11             Elevator  —  Machine-Room-Less  (MRL) 140 

11.1  Access  to  Machine  Room /Machinery  Space /Control  Room /Control 

Space  140 

11.2  Access  Door  and  Openings   140 

11.3  Enclosure  of  Rooms  and  Spaces 140 

11.4  Maintenance  Path  and  Clearance 141 

11.5  Machine /Control  Rooms  Containing  Overhead  Drive  Machines 141 

11.6  Temperature /Humidity 141 

11.7  Disconnecting  Means  141 

11.8  Remote  Machine  Rooms  and  Control  Rooms   141 

11.9  Inspection  and  Test  Panels 142 

11.10  Governor,  Overspeed  Switch 142 

11.11  Emergency  Brake 142 

11.12  Traction  Sheaves 143 

11.13  Secondary  and  Deflector  Sheaves    143 

11.14  Terminal  Stopping  Devices 143 

11.15  Working  Areas  Inside  the  Hoistway  and  in  the  Pit 143 

11.16  Location  of  Machinery  Spaces,  Machine  Rooms,  Control  Spaces, 

Control  Rooms,  and  Equipment 144 

11.17  Hydraulic  Elevators  —  Shutoff/ Manual  Lowering  Valves  144 

11.18  Hydraulic  Elevators  —  Pressure  Gauge  Fittings    144 

11.19  Hydraulic  Elevators  —  Atmosphere  Storage  and  Discharge  Tanks 144 

11.20  Hydraulic  Elevators  —  Pressure  Piping    145 

11.21  Explanatory  Figures  for  Definitions  of  Elevator  Machinery  Space,  Machine 

Room,  Control  Space,  Control  Room,  Remote  Machine  Room,  or  Remote 

Control  Room 145 

11.22  Inspection  Operation  and  Hoistway  Access  Switch  Operation 

Hierarchy  145 

Figures 

1.10.2                Door  Operation  Relative  to  Car  Position    10 

2.13.2.1  Dynamometer  Connections  for  Testing  the  Pull-Through  of 

Governor  Jaws    23 

2.29.2(a)            Safety  Marks  on  Guide  Rails,  Poor  Illumination   37 

2.29.2(b)           Safety  Marks  on  Guide  Rails,  Good  Illumination   37 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
I     No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


3.4.1.2  Top  Car  Clearance  and  Runby  (A17.1-1978  and  Later  Editions)  46 

3.16.1  Self-Tightening  Grips  53 

3.22.1  Cross-Section  Through  Tapered  Rope  Socket  Showing  Maximum  and 

Minimum  Projection  of  Loops  Above  Embedment  Medium 57 

3.23.1  Types  of  Lay    59 

3.23.2  Cross  Sections  of  Typical  Wire  Ropes 60 

5.2.3  Bottom  Car  Clearance  Hydraulic  Elevators   73 

6.4.2(b)(9)  Visual  Signal   88 

6.4.2(g)(1)  Phase  I  Instructions 89 

6.4.2(g)(2)  Phase  II  Instructions  (A17.1b-1989  Through  A17.1b~1995) 90 

6.4.2(g)(3)  Phase  II  Instructions  (A17.1-1996  Through  A17.1d-2000) 90 

7.2.1(a)  Dimensions  for  Existing  Escalators  (for  Escalators  Installed  Under 

A17.1-1955  and  A17.1-1960  Editions)  95 

7.2.1(b)  Dimensions  for  Existing  Escalators  (for  Escalators  Installed  Under 

A17.1-1965  Through  A17.1-1981)   96 

7.2.1(c)  Relationship  of  Escalator  Parts  (A17.1a-1982  and  Later  Editions) 97 

7.2.3  Checking  Incline    97 

7.4.1  Safety  Zone   98 

7.7.1  Checking  Step/Combplate  Mesh 99 

7.7.3  Test  of  Combplate/Landing  Plate  Assembly 100 

7.8.1(a)  Deck  Barricade  101 

7.8.1(b)  High  Deck  Balustrade  Antislide  Devices    101 

7.9.1(a)  Smooth  Riser 103 

7.9.1(b)  Cleated  Riser 104 

7.9.1(c)  Escalator  Step  Riser    104 

7.9.1(d)  Escalator  Step  Tread  [A17.1-1955  Through  A17.1-1990,  Rule  802.5 

(Requirement  6.1.3.5)]    105 

7.9.3  Example  of  Two  Flat  Steps 105 

7.11.1  Typical  Skirt  Obstruction  Device   107 

7.16.1  Ceiling  or  Soffit  Guard  [Requirements  6.1.3.3.9  and  6.2.3.3.7 

(Rules  802.3g  and  902.3g)]  109 

7.17.1  Measuring  Gap  Between  Step  and  Skirt  109 

7.17.2  Angle  of  Skirt  Panel  110 

7.18.3  Escalator  Cover  Overlap  112 

8.9.2  Typical  Step  Upthrust  Device   118 

8.12.2  Positioning  of  Steps  for  Inspection  of  Truss 119 

9.2.1(a)  Moving  Walk  Geometry  (for  Moving  Walks  Installed  Under 

A17.1-1965  Through  A17.1b-1980)  123 

9.2.1(b)  Moving  Walk  Geometry  (for  Moving  Walks  Installed  Under 

A17.1-1981  Through  A17.1a-1991)  124 

9.2.3  Maximum  Treadway  Angle   124 

9.3.3  Moving  Walk  Handrail  Extension  (A17.1-1971  and  Later  Editions)  126 

9.9.1  Moving  Walk  Treadway  Slots   128 

9.17.1  Treadway  Clearances   131 

11.21-1  Configuration  A 145 

11.21-2  Configuration  B   145 

11.21-3  Configuration  C  145 

11.21-4  Configuration  D 146 

11.21-5  Configuration  E   146 

11.21-6  Configuration  F   147 

Tables 

1  Procurement  Information  3 

2.13.2.1  Governor  Adjustment  Settings   22 

2.29.2(a)  Maximum  Safety  Rope  Pullout 33 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


2.29.2(b)  Minimum  and  Maximum  Stopping  Distances  for  Type  B  Car  Safeties 

With  Rated  Load,  and  Type  B  Counterweight  Safeties  With  No  Load 

in  the  Car 35 

2.29.2(c)            Gradual  Wedge  Clamp  Safety 36 

2.29.2(d)           Flexible  Guide  Clamp  Safety 36 

2.29.2(e)            Wedge  Clamp  Safety  (Constant  Retarding  Force)   36 

2.34.3               Minimum  Bend  Radius  for  SAE  100R2  Hose    40 

3.14.3(a)           Horizontal  Clearances   51 

3.14.3(b)           Horizontal  Distances    52 

3.22.1  Projection  of  Rope  Strands  Above  Embedment  Medium  for  6-  and 

8-Strand  Ropes 57 

9.2.3(a)              Treadway  Width  (A17.1-1965  Through  A17.1d-1970) 125 

9.2.3(b)             Treadway  Width  (A17.1-1971  and  Later  Editions) 125 

9.2.3(c)              Minimum  Treadway  Width    125 

9.14.3(a)            Treadway  Speed  (A17.1-1981  and  Later  Editions) 129 

9.14.3(b)            Treadway  Speed  (A17.1-1965  Through  A17.1b-1980)  129 

9.14.3(c)            Treadway  Speed  130 

11.21  Definitions  of  Elevator  Machinery  Space,  Machine  Room,  Control  Space, 

Control  Room,  Remote  Machine  Room,  or  Remote  Control 

Room  147 

11.22  Inspection  Operation  and  Hoistway  Access  Switch  Operation 

Hierarchy 148 

Mandatory  Appendix 

I                        Guide  for  Inspection  of  Inclined  Elevators 149 

Nonmandatory  Appendices 

A                       Inspection  Checklists   164 

B                       Acceptance  Checklist  189 

C                       Guidelines  for  B44.1/ A  17.5-2004 208 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers.  ^| 

No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME.     ^@ 


(10) 


FOREWORD 


Following  the  publication  of  the  1925  edition  of  the 
Safety  Code  for  Elevators,  Dumbwaiters,  and  Escalators, 
requests  for  a  handbook,  or  manual,  covering  the  inspec- 
tion of  elevators  were  received  by  the  A17  Committee. 
This  Committee  appointed  a  subcommittee  to  prepare 
such  a  manual.  Cities,  states,  insurance  companies,  ele- 
vator manufacturers  and  maintenance  companies,  and 
the  federal  government  furnished  the  Committee  with 
material  based  on  their  field  experiences.  A  final  draft 
was  prepared  and  was  unanimously  approved  by  the 
A 17  Committee,  the  Code  Sponsors,  and  the  American 
National  Association  (presently  known  as  the  American 
National  Standards  Institute,  Inc.)  and  the  first  edition 
of  the  Manual  was  published  in  1937  simultaneously 
with  the  fourth  edition  of  the  Code. 

A  second  edition  of  the  Manual  was  prepared  by  the 
Committee  to  bring  it  in  line  with  the  fourth  edition  of 
the  Code,  including  the  1942  supplement.  A  new  Part  to 
cover  the  inspection  of  escalators,  and  new  Appendices 
were  added  to  cover  descriptions  of  various  types  of 
safeties,  methods  for  determining  stopping  distances  of 
gradual-type  safeties,  guide  rail  data,  types  of  speed 
governors,  and  the  handling  and  socketing  of  wire  rope. 
The  second  edition  of  the  Manual  was  approved  by 
the  American  Standards  Association  and  was  published 
in  1945. 

The  third  edition  of  the  Manual  was  published  in  1960 
and  included  revision  to  bring  it  in  line  with  the  1960 
edition  of  the  Code. 

The  fourth  edition  of  the  Manual  was  published  in 
1973  to  bring  it  in  line  with  the  1971  editions  including 
the  1972  supplement  to  the  Code,  and  to  update  the 
inspection  procedures.  A  new  Part  was  also  added  to 
cover  the  inspection  of  moving  walks. 

The  Inspectors7  Manual  Subcommittee  was  reacti- 
vated in  1976  to  review  the  Manual  and  coordinate  it 
with  a  proposed  new  edition  of  the  Code.  The  Subcom- 
mittee, during  its  review,  felt  that  it  was  time  for  the 
Manual  to  take  on  a  new  format.  Thus,  the  fifth  edition 
of  the  Manual,  published  in  1979,  was  reorganized  into 
four  major  Parts:  Electric  Elevators,  Hydraulic  Elevators, 
Escalators,  and  Moving  Walks.  Each  Part  was  further 
divided  into  three  major  Divisions:  Routine  Inspection, 
Periodic  Inspection  and  Test,  and  Acceptance  Inspection 
and  Test.  New  Appendices  were  added  to  this  edition, 
containing  sample  inspection  checklists  for  electric  ele- 
vators, hydraulic  elevators,  escalators  and  moving 
walks.  A  considerable  amount  of  new  material  was  also 
added  to  the  Manual  to  bring  it  in  line  with  the  1978 
edition  of  the  Code. 


In  order  to  keep  the  Manual  as  current  as  possible, 
the  Committee  began  the  policy  of  publishing  supple- 
ments on  a  regular  basis.  Supplements  were  issued  in 
1980  and  1981  to  update  the  1979  edition. 

The  sixth  edition  of  the  Manual  contained  the  revi- 
sions included  in  the  1980  and  1981  supplements,  as 
well  as  many  other  revisions  made  to  keep  the  Manual 
abreast  of  new  Code  requirements  and  to  add  more 
comprehensive  inspection  and  testing  procedures.  The 
title  of  this  edition  was  also  changed  to 
ANSI/ASME  A17.2  Inspectors'  Manual  for  Elevators 
and  Escalators.  This  change  was  made  to  reflect  a  reorga- 
nization of  the  A17  Committee  structure,  and  to  shorten 
the  title  for  convenience. 

The  seventh  edition  of  the  Manual  included  the  revi- 
sions in  the  1983  and  1984  supplements  as  well  as  other 
new  revisions.  One  of  the  major  revisions  was  the 
Inspection  Checklists  in  Appendix  E,  which  were 
expanded  to  include  routine  and  periodic  inspections 
and  tests  in  addition  to  acceptance  inspections  and  tests. 

The  eighth  edition  included  revisions  in  the  1986  and 
1987  supplements  as  well  as  other  revisions  listed  in  the 
Summary  of  Changes  section. 

In  1989,  the  Inspectors'  Manual  Committee  polled  the 
inspection  community  to  determine  what  portions  of 
the  Manual  were  most  effective  and  the  direction  that 
should  be  taken  to  meet  the  need  of  the  inspector.  In 
response  to  requests  for  equipment,  specific  inspection 
guidelines,  techniques,  and  cautionary  notes  as  well  as 
field  convenience,  the  concept  of  individual  equipment 
inspection  manuals  was  developed.  The  Committee 
decided  to  concentrate  initially  on  three  major  segments. 
As  a  result,  the  Inspectors'  Manual  is  to  be  published 
in  three  volumes:  A17.2.1,  Electric  Elevators;  A17.2.2, 
Hydraulic  Elevators;  and  A17.2.3,  Escalators  and 
Moving  Walks.  Each  volume  addresses  inspection  proce- 
dures for  assuring  compliance  with  the  A17.1  Code  since 
1955  and  the  A17.3  Code.  It  is  the  Committee's  plan 
to  publish  additional  manuals  to  address  inspection  of 
other  equipments  such  as  roped-hydraulic  elevators, 
dumbwaiters,  sidewalk  elevators,  private  residence  ele- 
vators, hand  elevators,  material  lifts  and  dumbwaiters 
with  automatic  transfer  devices,  special  purpose  person- 
nel elevators,  rack  and  pinion  elevators,  inclined  eleva- 
tors, screw-column  elevators,  elevators  used  for 
construction,  wheelchair  and  stairway  chairlifts,  ship- 
board elevators,  and  rooftop  elevators. 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


In  1993,  the  Inspectors'  Manual  Committee  was 
requested  to  review  equipment  installed  prior  to  the 
1955  edition  of  A17.1.  ASME  A17.2.3  includes  inspection 
and  testing  procedures  for  assuring  compliance  with 
some  requirements  in  pre-1955  editions  of  A17.1. 

In  1999,  based  on  feedback  from  the  user  community, 
the  A17  Main  Committee  approved  the  Inspectors' 
Manual  Committee's  recommendation  to  consolidate 
the  three  existing  manuals:  A17. 2. 1-1996,  Inspectors' 
Manual  for  Electric  Elevators  (including  A17.2.1a-1997 
and  A17.2.1b-1998  Addenda);  A17 2.2-1997,  Inspectors' 
Manual  for  Hydraulic  Elevators  (including 
A17.2.2a-1998  Addenda);  and  A17.2.3-1998,  Inspectors' 
Manual  for  Escalators  and  Moving  Walks  (including 
A17.2.3a-2000  Addenda).  The  resulting  A17.2-2001, 


Guide  for  Inspection  of  Elevators,  Escalators,  and  Moving 
Walks,  represents  an  editorial  consolidation  of  the  three 
manuals.  The  revised  standard  also  includes  technical 
revisions,  which  have  been  approved  by  the 
A17.1  Committee  since  the  last  publications. 

The  second  edition  of  the  Guide  was  published  in 
2004.  Nonmandatory  Appendix  B  appears  for  the  first 
time  in  this  edition. 

The  third  edition  of  the  Guide  includes  revisions  listed 
in  the  Summary  of  Changes  section. 

The  fourth  edition  of  the  Guide  includes  revisions 
listed  in  the  Summary  of  Changes  section. 

The  following  is  a  list  of  past  editions  and  supple- 
ments and  the  dates  on  which  they  received  final 
approval.  The  dates  of  issuance  are  also  included  for 
documents  published  since  1979. 


Editions  and  Supplements 

First  Edition  ASA  A17.2-1937 

Second  Edition         ASA  A17.2-1945 


Third  Edition 
Addenda 
Supplement 

Fourth  Edition 

Fifth  Edition 
Supplement 
Supplement 

Sixth  Edition 
Supplement 
Supplement 

Seventh  Edition 
Supplement 
Supplement 

Eighth  Edition 
Addenda 
Addenda 

First  Edition 
Addenda 
Addenda 

Second  Edition 
Addenda 
Addenda 

First  Edition 
Addenda 
Addenda 

Second  Edition 
Addenda 

First  Edition 
Addenda 


ASA  A17.2-1960 
ASA  A17.2a-1965 
USAS  A17.2b-1967 

ANSI  A17.2-1973 

ANSI  A17.2-1979 
ANSI  A17.2a-1980 

ANSI  A17.2b-1981 

ANSI/ASME  A17.2-1982 
ANSI/ASME  A17.2a-1983 
ANSI/ASME  A17.2b-1984 

ANSI/ASME  A17.2-1985 
ANSI/ASME  A17.2a-1986 
ANSI/ASME  A17.2b-1987 

ANSI/ASME  A17.2-1988 
ANSI/ASME  A17.2a-1989 

ANSI/ASME  A!7.2b-1990 

ASME  A17.2.1-1993 
ASME  A17.2.1a-1994 
ASME  A17.2.1b-1995 

ASME  A17.2.1-1996 
ASME  A17.2.1a~1997 
ASME  A17.2.1b-1998 

ASME  A17.2.2-1994 
ASME  A17.2.2a-1995 
ASME  A17.2.2b-1996 

ASME  A17.2.2-1997 
ASME  A17.2.2a-1998 

ASME  A17.2.3-1994 
ASME  A17.2.3a-1996 


Approved 

July  1937 

October  22,  1945 

August  10,  1960 
July  29,  1965 
July  7,  1967 

May  29,  1973 

February  18,  1979 
August  11,  1980 
November  23,  1981 

September  22,  1982 
September  23,  1983 
August  16,  1984 

July  23,  1985 
September  8,  1986 
September  11,  1987 

August  25,  1988 
November  10,  1989 
October  8,  1990 

January  22,  1993 
August  18,  1994 
August  10,  1995 

September  6,  1996 
December  16,  1997 
November  13,  1998 

April  14,  1994 
August  10,  1995 
September  6,  1996 

November  18,  1997 
November  13,  1998 

August  19,  1994 
September  6,  1996 


Issued 


May  15,  1979 
September  15,  1980 
January  15,  1982 

November  30,  1982 
December  20,  1983 
September  16,  1984 

October  31,  1985 
October  31,  1986 
October  30,  1987 

October  31,  1988 
December  31,  1989 
January  21,  1991 

May  31,  1993 
December  31,  1994 
January  29,  1996 

January  31,  1997 
January  30,  1998 
February  19,  1999 

May  31,  1994 
January  10,  1996 
December  31,  1996 

December  31,  1997 
February  5,  1999 

October  21,  1994 
November  22,  1996 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


Editions  and  Supplements 


Addenda 

Second  Edition 

Addenda 

First  Edition 

Second  Edition 

Third  Edition 

Fourth  Edition 


ASME  A17.2.3b-1997 
ASME  A17.2.3-1998 
ASME  A17.2.3a-2000 

ASME  A17.2-2001 

ASME  A17.2-2004 

ASME  A17.2-2007 

ASME  A17.2-2010 


Approved 

November  18,  1997 
November  16,  1998 
June  22,  2000 

October  4,  2001 

July  22,  2004 

July  11,  2007 

September  8,  2010 


Issued 

December  31,  1997 
February  26,  1999 
August  10,  2000 

December  31,  2001 

March  31,  2005 

October  5,  2007 

December  9,  2010 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17  ELEVATOR 
AND  ESCALATOR  COMMITTEE 


(10) 


(March  2010) 


STANDARDS  COMMITTEE 

J.  W.  Coaker,  Chair 

N.  B.  Martin,  Vice  Chair 

H.  E.  Peelle  III,  Vice  Chair 

G.  A.  Burdeshaw,  Secretary 

E.  V.  Baker,  IUEC 

T.  D.  Barkand,  U.S.  Department  of  Labor 

R,  E.  Baxter,  Baxter  Residential  Elevators,  LLC 

K.  S.  Lloyd,  Jr.,  Alternate,  Abell  Elevator  International 

L.  Bialy,  Otis  Elevator  Co. 

N.  E.  March itto,  Alternate,  Otis  Elevator  Co. 

B.  D.  Black,  BDBlack  Codes,  Inc. 
J.  R.  Brooks,  Wagner  Consulting 

J.  W.  Adams,  Alternate,  North  Carolina  Department  of  Labor 
G.  A.  Burdeshaw,  The  American  Society  of  Mechanical  Engineers 
J.  W.  Coaker,  Coaker  &  Co.,  PC 

J.  Filippone,  Port  Authority  of  New  York  and  New  Jersey 
J.  H.  Humphrey,  Alternate,  Port  Authority  of  New  York  and  New 
Jersey 

C.  C.  Fox,  Rainbow  Security  Control  Ltd. 

G.  W.  Gibson,  George  W.  Gibson  and  Associates,  Inc. 

R.  A.  Gregory,  Vertex  Corp. 

R.  F.  Hadaller,  Technical  Standards  and  Safety  Authority 

M.  Tevyaw,  Alternate,  Technical  Standards  and  Safety  Authority 

P.  Hampton,  ThyssenKrupp  Elevator 

J.  T.  Herrity,  U.S.  Department  of  the  Navy 

A.  P.  Juhasz,  Kone,  Inc. 

D.  A.  Kalgren,  Kone,  Inc. 

D.  S.  Boucher,  Alternate,  Kone,  Inc. 

G.  A.  Kappenhagen,  Schindler  Elevator  Corp. 

J.  W.  Koshak,  Elevator  Safety  Solutions,  Inc. 

H.  Simpkins,  Alternate,  ThyssenKrupp  Elevator 

N.  B.  Martin,  State  of  Ohio 

Z.  R.  McCain,  Jr.,  McCain  Engineering  Associates,  Inc. 

M.  V.  Farinola,  Alternate,  MV  Farinola,  inc. 

D.  McColl,  Otis  Canada,  inc. 

H.  E.  Peelle  III,  The  Peelle  Company 

S.  P.  Reynolds,  Alternate,  The  Peelle  Company 

A.  Rehman,  Schindler  Elevator  Corp. 

V.  P.  Robibero,  Schindler  Elevator  Corp. 

C.  W.  Rogler,  State  of  Michigan  Elevator  Safety  Division 
R.  L  Seymour,  Robert  L.  Seymour  and  Associates,  Inc. 

R.  S.  Seymour,  Alternate,  Robert  L  Seymour  and  Associates,  Inc. 
J.  H.  Shull,  J.  H.  Shull  Engineering,  LLC 

D.  M.  Stanlaske,  NAESA  International 
D.  L  Steel,  David  L.  Steel  Escalators 

D.  L.  Turner,  Davis  L.  Turner  &  Associates,  LLC 

R.  S.  Caporale,  Alternate,  Elevator  World,  Inc. 

A.  H.  Verschell,  Dwan  Elevator 

D.  M.  Winkle,  Sr.,  Consultant 

G.  W.  Kosinski,  Alternate,  EIWPF 

D.  A.  Witham,  GAL  Manufacturing  Corp. 


Ex  Officio  Members 


G.A.  Burdeshaw,  Secretary 

R.E.  Baxter 

L.M.  Capuano 

G.W.  Gibson 

G.A.  Kappenhagen 

M.  Martin 

H.E.  Peelle  III 


J.B.  Peskuski 
j.H.  Shull 
D.L.  Steel 
M.  Tevyaw 
M.R.  Tilyou 
A.H.  Verschell 


Honorary  Members 

G.A.  Burdeshaw,  Secretary  C.  L  Kort 

L.  J.  Blaiotta  A.  A.  Mascone 

E.  A.  Donoghue  E.  M.  Philpot 

H.  E.  Godwin,  jr.  R.  L.  Rogers 

C.  E.  Hempel  L  E.  White 


Regulatory 

N.  B.  Martin,  Chair 

J.  R.  Brooks,  Vice  Chair 

G.  A.  Burdeshaw,  Secretary 

G.  Antona 

J.  L  Borwey 

J.  H.  Burpee 

A.  L.  Caine 

J.  R.  Calpini 

P.  Caploon 

j.  Day 

N.  C.  Dimitruck 

M.  Dorosk 

L.  A.  Giovannetti 

j.  M.  Gould 

A.  N.  Griffin 

R.  F.  Hadaller 

S.  J.  Hickory 

D.  Holmes 

I.  D.  Jay 

L.  C.  Kanicki 


Advisory  Council 

C.  C.  Mann 
M.  J.  Mellon,  Jr. 
I.  D.  Mercer 
S.  Mercier 
K.  P.  Morse 
M.  E.  Pedersen 
M.  R.  Poulin 
J.  P.  Roche 

C.  W.  Rogler 

D.  M.  Stanlaske 
M.  K.  Stewart 
S.  F.  Stout 

L  M.  Taylor 

D.  Tudor 

L.  E.  Watson 

W.  C.  Watson 

W.  J.  Witt 

D.  Melvin,  Alternate 

C.  D.  Wagner,  Alternate 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


NATIONAL  INTEREST  REVIEW  COMMITTEE 


G.  A.  Burdeshaw,  Secretary 

J.  P.  Andrew 

D.  M.  Begue 

R.  j.  Blatz 

J.  E.  Brannon 

M.  T.  Brierley 

B.  B.  Calhoun 
J.  A.  Caluori 

C.  S.  Carr 

M.  A.  Chavez 
R.  F.  Dieter 
B.  Faerber 
J.  G.  Gerk 
L.  A.  Giovannetti 
j.  M.  Gould 
N.  R.  Herchell 
J.  E.  Herwig 
J.  M.  Imgarten 
J.  Inglis 
T.  Isaacs 
F.  A.  Kilian 
M.  L.  Lane 


W.  R.  Larsen 

B.  H.  Larson 
M.  A.  Malek 
J.  J.  Mancuso 

C.  C.  Mann 

N.  E.  Marchitto 

D.  Mason 
J.  L.  Meyer 

T.  S.  Mowrey 
F.  G.  Newman 
J.  W.  O'Boyle 
j.  J.  O'Donoghue 
B.  Peyton 
M.  J.  Pfeiffer 
M.  R.  Poulin 
P.  M.  Puno 
L.  S.  Rigby 
j.  R.  Runyan 
R.  D.  Schloss 
S.  Shanes 
J.  L  Stabler 
D.  M.  Stanlaske 
D.  A.  Swerrie 


B44.1/A17.5  ELEVATOR  AND  ESCALATOR 
ELECTRICAL  EQUIPMENT  COMMITTEE 

J.  H.  Shult,  Chair  B.  T.  Irmacher 

M.  L  Hite,  Vice  Chair  J.  Lee 

G.  A.  Burdeshaw,  Staff  R.  A.  MacKenzie 

Secretary  P.  F.  McDermott 

M.  Dodd,  Secretary  M.  Mihai 

P.  D.  Barn  hart  V.  M.  Todt 

J.  W.  Blain  J.  M.  Weber 

A,  D,  Brown  D.  A.  Dormer,  Alternate 
J.  Caldwell  M.  L.  jaremko,  Alternate 
J.  L.  Delia  Porta  R.  S.  Williams,  Alternate 

CODE  COORDINATION  COMMITTEE 

B.  D.  Black,  Chair  G.  W  Gibson 

G.  A.  Burdeshaw,  Secretary  G.  A.  Kappenhagen 

L.  Bialy  J.  W.  Koshak 

R.  Bukowski  B.  Tubbs 

P.  Caploon  K.  Paarlberg,  Alternate 

R.  Cote 


CSA  B44 

M.  Dodd,  Secretary 
T.  Baik 
L  Bialy 
S.  Bornstein 
M.  T.  Brierley 
A.  D.  Byram 
R.  Cavan 

D.  Eastman 
A.  N.  Griffin 
R.  F.  Hadaller 
J.  Halge 

R.  E.  Haukeness 

A.  S.  Hopkirk 

U.  Huskic 

I.  D.  jay 

K.  Jenkins 

G.  A.  Kappenhagen 

F.  Kassem 

I.  M.  Kennedy 

R.  M.  Kennedy 

j.  W.  Koshak 

j.  Lee 

E.  MacArthur 
A.  J.  Marchant 
R.  Marion 


TECHNICAL  COMMITTEE 

R.  Marsiglio 
L.  Martineau 
T.  McCann 
D.  McColl 
B.  Mclntyre 
R.  A.  McKenzie 
D.  McLellan 
S.  Mercier 
M.  Mihai 
T.  Nguyen 
M.  Pedram 
H.  E.  Peelle  III 

A.  Rehman 

S.  P.  Reynolds 
T.  W.  Rieger 
J.  T.  Rooney 
R.  C.  Scharfe 
j.  H.  Shull 
F.  K.  Tawfik 
M.  Tevyaw 

B.  Virk 
D.  Warne 
P.  Yau 

A.  D.  Brown,  Alternate 
I.  D.  Mercer,  Alternate 


DUMBWAITER  AND  ATD  COMMITTEE 

J.  B.  Peskuski,  Chair  B.  P.  McCune 

R.  Mohamed,  Secretary  J.  W.  Ninness 


S.  S.  DuQuaine 
R.  A.  Gregory 


D.  Witt 


EARTHQUAKE  SAFETY  COMMITTEE 

G.  W.  Gibson,  Chair  W.  C.  Ribeiro 

M.  J.  Smith,  Vice  Chair  J.  K.  Ruth 

A.  B.  Byk,  Secretary  W.  C.  Schadrack  III 
L  C.  Barulich  A.  J.  Schiff 

B.  Blackaby  A.  J.  Shelton 

R.  Lorenzo  D.  A.  Kalgren,  Alternate 

J.  L.  Meyer 

EDITORIAL  COMMITTEE 

D.  McColl,  Chair  B.  D.  Black 

G.  A.  Burdeshaw,  Secretary  J.  Filippone 

ELECTRICAL  COMMITTEE 


A.  P.  Juhasz,  Chair 

B.  Blackaby,  Vice  Chair 
J.  D.  Busse,  Vice  Chair 
D.  R.  Sharp,  Secretary 
T.  D.  Barkand 

P.  D.  Barn  hart 
S.  H.  Benjamin 
j.  W.  Blain 
J.  Caldwell 
B.  C.  Castillo 
J.  P.  Donnelly 
R.  Elias 
S.  E.  Fisher 
G.  N.  Henry 
Y.  C.  Ho 
N.  E.  Marchitto 
P.  F.  McDermott 


T.  G.  Moskal 

A.  L.  Peck 

D.  K.  Prince 

P.  M.  Puno 

V.  P.  Robibero 

M.  Stergulc 

D.  Alley  Alternate 

J.  C.  Carlson,  Alternate 

J.  L.  Delia  Porte,  Alternate 

R.  L.  Frazier,  Alternate 

D.  Henderson,  Alternate 

M.  Mihai,  Alternate 

J.  C.  Ramos,  Alternate 

J.  P.  Rennekamp,  Alternate 

J.  H.  Shull,  Alternate 

J.  M.  Weber,  Alternate 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ELEVATORS  USED  FOR  CONSTRUCTION 
COMMITTEE 


EXISTING  INSTALLATIONS  COMMITTEE 


N.  B.  Martin,  Chair 

G.  A.  Burdeshaw,  Secretary 

R.  E.  Baxter 

C.  C.  Fox 


R.  A.  Gregory 
J.  R.  Quackenbush 
C.  W.  Rogler 


EMERGENCY  OPERATIONS  COMMITTEE 


M.  Martin,  Chair 

A.  Rehman,  Vice  Chair 

A.  B.  Byk,  Secretary 
M.  Abbott 

J.  Beamish 
D.  R.  Beste 

B.  D.  Black 
M.  T.  Brierley 
M.  W.  Bunker,  Jr. 
P.  Caploon 

G.  B.  Cassini 
D.  Cook 
R.  B.  Fraser 
D.  Henderson 
D.  Holmes 
S.  R.  James 

C.  Koenig 
J.  Latham 

D.  McColl 

C.  H.  Murphy 


T.  F.  Norton 

J.  J.  O'Donoghue 

B.  F.  O'Neill 

D.  K.  Prince 

P.  D.  Rampf 

L.  F.  Richardson 

R.  L  Seymour 

M.  Tevyaw 

D.  Warne 

D.  J.  Winslow 

D.  A.  Witham 

J.  C.  Carlson,  Alternate 

R.  F.  Hadaller,  Alternate 

J.  K.  O'Donnell,  Alternate 

G.  G.  Rees,  Alternate 

R.  Reiswig,  Alternate 

R.  J.  Roux,  Alternate 

A.  J.  Shelton,  Alternate 

J.  Varon,  Alternate 


ESCALATOR  AND  MOVING  WALK  COMMITTEE 


D.  L.  Turner,  Chair 

T.  R.  Nurnberg,  Vice  Chair 

R.  Mohamed,  Secretary 

P.  E.  Burge 

D.  R.  Evans 

J.  Filippone 

J.  G.  Gerk 

R.  A.  Glanzmann 

P.  L.  Hackett 

K.  M.  Harris 

H.  A.  Hausmann 

R.  Herndobler 

J.  A.  Kinahan 

D.  McLellan 


T.  G.  Moskal 

J.  D.  Shupe 

K.  J.  Smith 

J.  L.  Stabler 

D.  L.  Steel 

P.  Velasquez,  jr. 

P.  J.  Welch 

D.  Winkelhake 

C.  Anayiotos,  Alternate 

C.  S.  Carr,  Alternate 

K.  G.  Hamby,  Alternate 
T.  P.  Kenny,  Alternate 
A.  Rehman,  Alternate 

D.  E.  Rush,  Alternate 


EVACUATION  GUIDE  COMMITTEE 


D.  L.  Turner,  Chair 

R.  S.  Seymour,  Vice  Chair 

G.  A.  Burdeshaw,  Secretary 

J.  R.  Brooks 

D.  Cook 


C.  C  Fox 
J.  L  Meyer 
J.  J.  O'Donoghue 
C.  W.  Rogler 


D.  B.  Labrecque,  Chair 

A.  B.  Byk,  Secretary 

R.  E.  Baxter 

J.  Bera 

J.  H.  Butler 

J.  D.  Carlisle,  Jr. 

G.  B.  Cassini 

C.  J.  Duke 

A.  T.  Gazzaniga 

J.  G.  Gerk 

R,  A.  Gregory 

J.  T.  Herrity 

J.  A.  Jaudes 

R.  Kremer 

K.  S.  Lloyd,  Jr. 

G.  M.  Losey 

Z.  R.  McCain,  Jr. 


D.  McColl 

P.  McPartland 

N.  R.  Mistry 

R.  C.  Morrical 

G.  Nyborg  III 

S.  A.  Quinn 

J.  S.  Rearick 

A.  J.  Saxer 

G.  Stiffler 

H.  M.  Vyas 

T.  Waardenburg 

P.  J.  Welch 

L  E.  White 

C.  Buckley,  Alternate 

V.  P.  Robibero,  Alternate 

M.  Strachan,  Alternate 

S.  Swett,  Alternate 


HAND  AND  SIDEWALK  ELEVATOR  COMMITTEE 


R.  S.  Caporale,  Chair 
N.  J.  Montesano,  Vice  Chair 
G.  A.  Burdeshaw,  Secretary 
V.  G.  Bahna 
J.  Doyle 


J.  Duffy 

G.  Green berg 

H.  J.  Macuga 

G.  West 

J.  P.  Merkel,  Alternate 


HOISTWAY  COMMITTEE 


L.  M.  Capuano,  Chair 
D.  McColl,  Vice  Chair 

A.  B.  Byk,  Secretary 

B.  D.  Black 
L.  J.  Blaiotta 

D.  S.  Boucher 

F.  R.  Cooper 

G.  W.  Gibson 

H.  J.  Gruszynski 
R.  F.  Hadaller 
J.  L.  Harding 

E.  A.  Heath  III 
D.  Holmes 

K.  H.  Lewis 
G.  L.  Nuschler 
H.  E.  Peelle  III 


R.  L  Phillips 

F.  Regalado 

A.  Rehman 

S.  P.  Reynolds 

H.  Simpkins 

D.  Warne 

D.  A.  Witham 

W.  Ziegert 

L.  Bialy,  Alternate 

A.  S.  Conkling,  Alternate 

D.  P.  Kraft,  Alternate 

R.  K>  Leckman,  Alternate 

W.  M.  Miller,  Alternate 

M.  Tevyaw,  Alternate 

J.  Varon,  Alternate 


HYDRAULIC  COMMITTEE 


G.  A.  Kappenhagen,  Chair 

M.  G.  Miller,  Vice  Chair 

G.  A.  Burdeshaw,  Secretary 

L  Bialy 

P.  E.  Burge 

C.  C.  Fox 

H.  A.  Hammerstrom 

C.  B.  Jackson 

A.  Jahn 

T.  S.  Mowrey 

M.  J.  Paschke 

L  S.  Rigby 


C.  W.  Rogler 

J.  N.  Rouse  III 

W.  M.  Shrum,  Jr. 

H.  Simpkins 

B.  Giddens,  Alternate 

K.  A.  Grunden,  Alternate 

J.  W.  Koshak,  Alternate 

A.  M.  McClement,  Alternate 

S.  S.  Pearson,  Alternate 

A.  Rehman,  Alternate 

J.  L.  Shrum,  Alternate 


Copyright  ©  2010  by  tile  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


INCLINED  ELEVATOR  COMMITTEE 

A.  H.  Verschell,  Chair  J.  T.  Herrity 

G.  A.  Burdeshaw,  Secretary  T.  L.  Pope 

J.  R.  Carrick 

INSPECTIONS  COMMITTEE 


MAINTENANCE,  REPAIR,  AND  REPLACEMENT 
COMMITTEE 


M.  Tevyaw,  Chair 

J.  Filippone,  Vice  Chair 

R.  Mohamed,  Secretary 

G.  Antona 

C.  Archer 

R.  E.  Baxter 

J.  R.  Brooks 

C.  Buckley 

J.  W.  Coaker 

M.  V.  Farinola 

H.  S.  Frank 

R.  F.  Hadaller 

P.  Hampton 

J.  T.  Herrity 

L.  C.  Kanicki 

J.  J.  Knolmajer 

G.  W.  Kosinski 


K.  S.  Lloyd,  Jr. 
Z.  R.  McCain,  Jr. 
J.  S.  Rearick 

C.  W.  Rogler 

J.  D.  Rosen berger 
J.  R.  Runyan 
R.  D.  Schloss 
R.  S.  Seymour 
R.  D.  Shepherd 
W.  M.  Snyder 

D.  M.  Stanlaske 
J.  Strzelec 

D.  Warne 

P.  G.  Bender,  Alternate 
M.  Boutin,  Alternate 
D.  McLellan,  Alternate 
S.  Swett,  Alternate 


Z.  R.  McCain,  Jr.,  Chair 
R.  A.  Gregory,  Vice  Chair 
A.  B.  Byk,  Secretary 
R.  E.  Baxter 
G.  B.  Cassini 
J.  J.  DeLorenzi 

C.  J.  Duke 

M.  V.  Farinola 
J.  Filippone 
J.  G.  Gerk 
S.  P.  Greene 
R.  F.  Hadaller 
R.  E.  Haukeness 
J.  T.  Herrity 

A.  S.  Hopkirk 
J.  A.  Jaudes 

J.  J.  Knolmajer 
R.  Kremer 

D.  B.  Labrecque 
P.  W.  Lackler 

B.  H.  Larson 
K.  S.  Lloyd,  Jr. 


G.  M.  Losey 

D.  McColl 

P.  J.  McPartland 

N.  R.  Mistry 

R.  C.  Morrical 

J.  Murphy 

W.  B.  Pletch 

J.  R.  Quackenbush 

J.  S.  Rearick 

A.  Rehman 

V.  P.  Robibero 

P.  S.  Rosenberg 

A.  Saxer 

R.  D.  Schloss 

R.  D.  Shepherd 

J.  Strzelec 

H.  M.  Vyas 

T.  Waardenburg 

C.  Buckley,  Alternate 

D.  Kelly,  Alternate 

J.  L.  Stabler,  Alternate 


INTERNATIONAL  STANDARDS  COMMITTEE 


G.  W.  Gibson,  Chair 

L.  Bialy,  Vice  Chair 

G.  A.  Burdeshaw,  Secretary 

B.  D.  Black 

B.  Blackaby 

R.  S.  Caporale 

J.  W.  Coaker 

J.  T.  Herrity 

A.  P.  Juhasz 

G.  A.  Kappenhagen 


J.  W.  Koshak 

J.  A.  Pop 

V.  P.  Robibero 

D.  M.  Stanlaske 

J.  Strzelec 

D.  L.  Turner 

V.  Q.  Bates,  Jr.,  Alternate 

T.  Derwinski,  Alternate 

D.  R.  Evans,  Alternate 


MARINE  ELEVATOR  COMMITTEE 


LIMITED-USE/LIMITED-APPLICATION 
ELEVATOR  COMMITTEE 


R.  E.  Baxter,  Chair 

D.  C.  Balmer,  Vice  Chair 

M.  L.  Vazquez,  Secretary 

K.  L.  Brinkman 

P.  Chance 

C.  C.  Fox 

P.  W.  Lackler 

M.  L.  McDonald 

S.  J.  Mehalko 


J.  L.  Mickel 

C.  H.  Murphy 
R.  Murphy 

J.  P.  Schumacher 
A.  H.  Verschell 
R.  B.  Weber 

D.  M.  Winkle,  Jr. 

M.  B.  Hays,  Alternate 


M.  R.  Tilyou,  Chair 

G.  A.  Burdeshaw,  Secretary 

E.  J.  Crawford 


W.  D.  George 
T.  J.  Ingram 
R.  Wagner 


MECHANICAL  DESIGN  COMMITTEE 


G.  W.  Gibson,  Chair 
L.  Bialy,  Vice  Chair 

D.  L.  Turner,  Vice  Chair 
A.  B.  Byk,  Secretary 

K.  A.  Apperson 

E.  V.  Baker 
R.  J.  Bolen 
R.  E.  Creak 

C.  C.  Fox 
H.  S.  Frank 
R.  F.  Hadaller 

D.  K.  Kaczmarek 
D.  A.  Kalgren 

K.  Konyar 
J.  W.  Koshak 
R.  Kremer 


M.  P.  Lamb 
M.  L.  Lane 
T.  G.  Moskal 
A.  Rehman 
M.  Rhiner 
H.  Simpkins 

C.  E.  Vlahovic 
R.  J.  Walker 
S.  P.  Wurth 

D.  P.  Kraft,  Alternate 

R.  K.  Leckman,  Alternate 
W.  C.  Ribeiro,  Alternate 
W.  C.  Schadrack  III, 

Alternate 
P.  Winey,  Alternate 


MINE  ELEVATOR  COMMITTEE 


T.  D.  Barkand,  Chair 
A.  B.  Byk,  Secretary 
C.  D.  Barchet 
R.  M.  Bates 
W.  M.  Dietz 
P.  E.  Fernatt 
M.  G.  Kalich 
J.  B.  Ketchem 
A.  L.  Martin 


N.  B.  Martin 
G.  L.  Miller 
H.  E.  Newcomb 
A.  J.  Saxer 
D.  J.  Shook 
R.  L.  Sidwell 
M.  P.  Snyder 
J.  K.  Taylor 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


NEW  TECHNOLOGY  COMMITTEE 


J.  W.  Coaker,  Choir 

G.  A.  Burdeshaw,  Secretary 

Art.  H.  Bayyari 

L.  Bialy 

B.  D.  Black 

A.  D.  Brown 

A.  D.  Byram 

R.  S.  Caporale 

L.  Art.  Capuano 

M.  Dodd 

G.  W.  Gibson 

A.  N.  Griffin 

I.  D.  Jay 

A.  P.  Juhasz 


L  C.  Kanicki 

R.  M.  Kennedy 

J.  W.  Koshak 

G.  W.  Kosinski 

R.  H.  Laney 

K.  S.  Lloyd,  Jr. 

D.  McColl 

M.  Mihai 

Art.  Pedram 

V.  P.  Robibero 

D.  Art.  Stanlaske 

D.  L.  Turner 

R.  E.  Baxter,  Alternate 

Art.  Chan,  Alternate 


OUTSIDE  EMERGENCY  ELEVATOR  COMMITTEE 


G.  L.  Nuschler,  Chair 
W.  C.  Christensen 
R.  F.  Fahy 
J.  K.  O'Donnell 


J.  J.  O'Donoghue 
H.  E.  Peele  III 
J.  Shimshoni 
D.  Art.  Stanlaske 


RACK  AND  PINION  AND  SPECIAL  PURPOSE 
PERSONNEL  ELEVATOR  COMMITTEE 


A.  J.  Artarchant,  Chair 
K.  Art.  Harrison,  Vice  Chair 
G.  A.  Burdeshaw,  Secretary 
J.  L.  Borwey 
D.  F.  Grund 
S.  Harris 


R.  E.  Haukeness 

J.  W.  Koshak 

R.  C.  Arteiresonne 

B.  L  O'Neill 

P.  J.  Welch 

J.  A.  Harrison,  Alternate 


RESIDENCE  ELEVATOR  COMMITTEE 


A.  H.  Verschell,  Chair 

K.  L.  Brinkman,  Vice  Chair 

M.  L.  Vazquez,  Secretary 

D.  C.  Balmer 

R.  E.  Baxter 

R.  G.  Buonora 

P.  Chance 

D.  J.  DeGere 

P.  Edwards 

R.  Elias 

P.  Giannis 

F.  Art.  Hoch 

Art.  J.  Holat 

C.  S.  Jones 

P.  W.  Lackler 


K.  H.  Lewis 

Art.  Lewis 

J.  C.  Lund 

Art.  L.  McDonald 

W.  Art.  ArtcKinley 

S.  J.  AAehalko 

J.  L.  Aflickel 

W.  Art.  AAiddleton 

R.  J.  Murphy 

T.  L.  Pope 

J.  P.  Schumacher 

S.  S.  Duquaine,  Alternate 

Art.  B.  Hays,  Alternate 

J.  B.  Peskuski,  Alternate 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


(10) 


PREFACE 


FORM  AND  ARRANGEMENT 

This  Guide  addresses  how-to  inspection  guidelines, 
techniques,  and  cautionary  notes  in  a  logical  sequence. 
Subsections  are  arranged  to  focus  on  routine  inspection 
requirements,  followed  by  periodic  test  (annual  and  five 
year)  and  acceptance  criteria.  Appropriate  references  to 
the  latest  edition  of  the  Code,  in  effect  at  the  time  of 
this  Guide's  publication,  are  listed  at  the  end  of  each 
subsection.  The  referenced  numbers  may  not  be  the  same 
in  earlier  editions.  This  Guide  is  organized  as  follows: 
Parts  1  through  6  apply  to  electric  and  hydraulic  eleva- 
tors, Parts  7  and  8  apply  to  escalators,  Parts  9  and  10 
apply  to  moving  walks,  and  Part  11  applies  to  machine- 
room-less  (MRL)  elevators.  The  Parts  are  arranged  to 
show  the  location  of  the  inspection: 

Part  1  Elevator  —  Inside  of  Car 

Part  2  Elevator  —  Machine  Room 

Part  3  Elevator  —  Top  of  Car 

Part  4  Elevator  —  Outside  Hoistway 

Part  5  Elevator  —  Pit 

Part  6  Elevator  —  Firefighters'  Service 

Part  7  Escalator  —  External 

Part  8  Escalator  —  Internal 

Part  9  Moving  Walk  —  External 

Part  10  Moving  Walk  —  Internal 

Part  11  Elevator  —  Machine-Room-Less  (MRL) 

Each  inspection  location  is  further  subdivided  as 
follows: 

X  Location  of  inspection 

X.X  Item  to  be  inspected 

X.X.I  Periodic  inspections  (routine) 

X.X.  1.1  Electric  elevators  (as  applicable) 

X.X.  1.2  Hydraulic  elevators  (as  applicable) 

X.X.2  Periodic  test 

X.X.2.1  Electric  elevators  (as  applicable) 

X.X.2.2  Hydraulic  elevators  (as  applicable) 

X.X.3  Acceptance  inspection 

X.X.3.1  Electric  elevators  (as  applicable) 

X.X.3.2  Hydraulic  elevators  (as  applicable) 

X.X.4  Code  references 

X.X.4.1  Electric  elevators  (as  applicable) 

X.X.4.2  Hydraulic  elevators  (as  applicable) 

When  a  requirement  within  A17.1  or  A17.3  cross- 
references  another  requirement,  the  cross-reference  is 
shown  with  the  refering  requirement  in  braces,  {  ).  For 
the  Al  7. 1-2000  and  later  edition  requirements,  where 
no  direct  cross-reference  is  found  within  the  A 17. 1-2000 
Cross-Reference  Table,  the  prior  code  Rule  (A17.1d-2000 


and  earlier  editions)  is  shown  in  parentheses,  (  ),  with 
a  preceding  "NR"  designation. 

Subsection  numbering  of  items  may  not  be  sequential 
when  there  are  no  inspection  or  test  procedures  indi- 
cated within  this  Guide. 

NOTE:  This  Guide  addresses  the  requirements  of  A17.1-1955  and 
later  editions  and  latest  edition  of  A17.3.  Some  requirements  in 
earlier  editions  of  A17.1  are  also  addressed.  The  inspector  is 
referred  to  the  particular  edition  of  the  A17.1  Code  that  applies 
for  requirements  prior  to  1955. 

This  Guide  has  included  the  pertinent  requirement 
from  prior  editions  of  A17.1,  which  differ  from  the 
requirements  in  the  latest  edition.  As  the  inspector 
becomes  familiar  with  the  prescribed  order  of  inspection 
procedures,  variations  may  be  appropriate.  The 
Foreword,  Preface,  and  Appendix  that  are  included  in 
this  document  have  been  approved  by  the 
A17  Committee,  but  are  not  part  of  this  American 
National  Standard. 

NOTE:  See  also  para.  2,  Application,  under  the  Introduction  of 
this  Guide. 

REQUIREMENTS  FOR  EXISTING  INSTALLATIONS 

Elevators  and  escalators  in  jurisdictions  that  have 
adopted  the  Safety  Code  for  Existing  Elevators  and 
Escalators,  ASME  A17.3,  and  installations  that  have  been 
altered  in  accordance  with  Part  XII  of  the  Safety  Code 
for  Elevators  and  Escalators  ANSI/ASME  A17.1d-1986 
and  later  editions  must,  as  a  minimum,  conform  to  the 
requirements  identified  in  this  Guide  as  "A17.3."  If  an 
existing  installation  does  not  meet  the  requirements  of 
the  A17.3  Code,  it  must  be  upgraded.  If  an  existing 
installation  was  required  to  meet  more  stringent  require- 
ments, it  must  continue  to  meet  those  requirements. 

Alteration,  if  made,  must  conform  to  the  requirements 
of  A17.1,  Part  XII  and  the  entire  installation  must  con- 
form to  the  requirements  of  A17.3.  The  alteration 
requirements  in  A  17.1,  Part  XII  may  be  more  stringent 
than  the  requirements  of  A17.3.  The  equipment  must 
conform  to  the  more  stringent  of  the  two. 

METRIC  (SI)  UNITS 

This  edition  of  the  Guide  uses  both  imperial  and  met- 
ric (SI)  units.  The  units  used  in  the  Guide  are  the  units 
found  in  the  referenced  code  [e.g.,  imperial  (metric)  or 
metric  (imperial)].  Information  on  the  usage  of  SI  units 
and  conversion  to  imperial  units  is  contained  in  IEEE/ 
ASTM  SI  10-1997,  Standard  for  the  Use  of  the  International 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


System  of  Units  (SI):  The  Modern  Metric  System;  ASME 
Guide  SI-1,  Orientation  and  Guide  for  Use  of  SI  (Metric) 
Units;  or  CAN/CSA-Z234-1,  Canadian  Metric  Practice 
Guide. 


DEFINITIONS 

For  definitions,  see  Section  3  of  the 
ASME  A17.1d-2000  and  earlier  editions  (Section  1.3, 
A17.1-2000/B44-00  and  later  editions). 

ASME  ELEVATOR  PUBLICATIONS 

This  Guide  is  one  of  the  numerous  codes  and  stan- 
dards that  have  been  or  are  being  developed  and  pub- 
lished by  the  American  Society  of  Mechanical  Engineers. 
The  following  publications  are  of  special  interest  to  users 
of  this  Guide.  For  prices  and  availability,  contact: 

ASME  Order  Department 

22  Law  Drive 

Box  2900 

Fairfield,  NJ  07007-2900 

Tel:  800-843-2763 

Fax:  973-882-1717 

E-Mail:  infocentral@asme.org 

ASME  Website:  www.asme.org/catalog 

ASME  A17.1/CSA  B44  Safety  Code  for  Elevators  and 
Escalators.  This  American  National  Standard  Safety 
Code  covers  the  design  construction,  installation,  oper- 
ation, testing,  maintenance,  alteration,  and  repair  of  ele- 
vators, dumbwaiters,  escalators,  moving  walks,  and 
material  lifts  and  dumbwaiters  with  automatic  transfer 
devices. 

Inspection  Checklists.  The  checklist  forms  shown  in 
Nonmandatory  Appendices  A  and  B  of  this  book  are 
posted  on  the  ASME  Website:  www.asme.org. 

ASME  A17.3  Safety  Code  for  Existing  Elevators  and 
Escalators.  This  Code  covers  retroactive  requirements 
for  existing  elevators  and  escalators.  The  purpose  of  this 
Code  is  to  establish  minimum  requirements  that  will 
provide  a  reasonable  degree  of  safety  for  the  general 
public.  While  many  of  these  requirements  will  also 
increase  the  degree  of  safety  for  the  elevator  mechanic 
and  inspector,  this  area  has  not  been  addressed  at  this 
time. 

ASME  A17  CD-ROM  for  Elevators  and  Escalators.  This 
CD-ROM  contains  the  ASME  A17.1,  A17.2,  and  A17.3 
standards.  In  addition,  it  contains  the  published  inter- 
pretations applicable  to  these  standards. 

ASME  A17.4  Guide  for  Emergency  Personnel.  This 
Guide  for  emergency  personnel  (fire,  police,  etc.),  build- 
ing owners,  lessees,  and  building  operating  managers 
explains  the  proper  procedures  to  be  used  for  the  safe 
removal  of  passengers  from  stalled  cars. 


CSA  B44.1/ASME  A17.5  Elevator  and  Escalator 
Electrical  Equipment.  This  Code  contains  requirements 
for  obtaining,  labeling,  and  listing  electrical  equipment 
for  elevators,  escalators,  moving  walks,  dumbwaiters, 
material  lifts,  platform  lifts,  and  stairway  lifts. 

ASME  A17.7/CSA  B44.7  Performance-Based  Safety 
Code  for  Elevators  and  Escalators.  This  American 
National  Standard  performance-based  safety  code  cov- 
ers the  design,  construction,  installation,  operation,  test- 
ing, maintenance,  alteration,  and  repair  of  elevators, 
dumbwaiters,  escalators,  moving  walks,  and  material 
lifts. 

Published  Interpretations.  Interpretations  of  the  vari- 
ous A17  standards  are  published  periodically. 

Interpretations  of  A17.1  and  A17.2  approved  by  the 
A17  Committee  from  June  14,  1972  through  June  1979 
were  published  in  a  separate  book  in  1980. 

Starting  with  the  1981  edition  of  the  Code,  interpreta- 
tions are  published  with  each  new  edition  and  supple- 
ment of  the  applicable  standard.  A  compilation  of 
Interpretations  Nos.  2-13  (June  1979-May  1989)  has  also 
been  published  by  ASME.  A  compilation  of  all  interpre- 
tations can  also  be  obtained  through  the  A17  CD-ROM. 

Handbook  on  A17.1/B44  Safety  Code.  This  Handbook 
augments  the  A17.1/B44  Codes  with  commentary,  dia- 
grams, and  illustrations  that  are  intended  to  explain  the 
requirements  of  the  A17.1/B44  Code. 

The  commentary  contained  in  the  Handbook  is  the 
opinion  of  the  author  and  has  not  been  approved  by  the 
A 17  Committee  or  the  B44  Technical  Committee. 

QEI-1  Standard  for  the  Qualification  of  Elevator  Inspec- 
tors. This  Standard  covers  requirements  for  the  qualifi- 
cation and  duties  of  inspectors  and  inspection 
supervisors  engaged  in  the  inspection  and  testing  of 
equipment  within  the  scope  of  the  A17.1/B44  Code. 
It  also  includes  requirements  for  the  accreditation  of 
organizations  that  certify  inspectors  and  inspection 
supervisors  as  meeting  the  QEI  criteria. 

ASME  A18.1  Safety  Standard  for  Platform  Lifts  and 
Stairway  Chairlifts.  This  safety  Standard  covers  the 
design,  construction,  installation,  operation,  inspection, 
testing,  maintenance,  and  repair  of  inclined  stairway 
chairlifts  and  inclined  and  vertical  platform  lifts 
intended  for  transportation  of  a  mobility  impaired  per- 
son only. 


CORRESPONDENCE  WITH  THE  A17  COMMITTEE 

ASME  codes  and  standards  are  developed  and  main- 
tained with  the  intent  to  represent  the  consensus  of  con- 
cerned interests.  As  such,  users  of  this  and  other  ASME 
A17  codes  and  standards  may  interact  with  the  Commit- 
tee by  requesting  interpretations,  proposing  revisions, 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


Abbreviations  Used  in  This  Code 

Abbreviation 

Unit 

Abbreviation 

Unit 

A 

ampere 

lb 

pound  (mass) 

°C 

degree  Celsius 

tbf 

pound  (force) 

deg 

degree  (angle) 

Ix 

lux 

°F 

degree  Fahrenheit 

m 

meter 

ft/min 

foot  per  minute 

m2 

square  meter 

ft/s 

foot  per  second 

m3 

cubic  meter 

ft 

foot 

mA 

milliampere 

fc 

footcandle 

m/s 

meter  per  second 

ft2 

square  foot 

m/s2 

meter  per  second  per  second 

ft3 

cubic  foot 

mm 

millimeter 

ft/s2 

foot  per  second  per  second 

mm2 

square  millimeter 

h 

hour 

mm3 

cubic  millimeter 

Hz 

hertz 

MPa 

megapascal 

in. 

inch 

N 

newton 

in.2 

square  inch 

psi 

pound  per  square  inch 

in.3 

cubic  inch 

s 

second 

kg 

kilogram 

V 

volt 

kPa 

kilopascal 

and  attending  committee  meetings.  Correspondence 
should  be  addressed  to; 

Secretary,  A17  Standards  Committee 

The  American  Society  of  Mechanical  Engineers 

Three  Park  Avenue 

New  York,  NY  10016-5990 

E-mail:  infocentral@asme.org 

Proposing  Revisions.  Revisions  are  made  periodically 
to  the  Guide  to  incorporate  changes  that  appear  neces- 
sary or  desirable,  as  demonstrated  by  the  experience 
gained  from  the  application  of  the  procedures,  and  in 
order  to  conform  to  developments  in  elevator  technol- 
ogy. Approved  revisions  will  be  published  periodically. 

The  Committee  welcomes  proposals  for  revisions  to 
this  Guide,  Such  proposals  should  be  as  specific  as  possi- 
ble: citing  the  Item  number(s),  the  proposed  wording, 
and  a  detailed  description  of  the  reasons  for  the  proposal 
including  any  pertinent  documentation. 

Requesting  Interpretations.  On  request,  the 
A17  Committee  will  render  an  interpretation  of  any 
requirement  of  the  Guide.  Interpretations  can  only  be 
rendered  in  response  to  a  written  request  sent  to  the 
Secretary  of  the  Standards  Committee. 

The  request  for  interpretation  should  be  clear  and 
unambiguous.  It  is  further  recommended  that  the 
inquirer  submits  his  request  using  the  following  format: 

Subject:        Cite  the  applicable  Item  number(s)  and  a 
concise  description. 


Edition:  Cite  the  applicable  edition  and  supplement 
of  the  Guide  for  which  the  interpretation  is 
being  requested. 

Question:  Phrase  the  question  as  a  request  for  an  inter- 
pretation of  a  specific  item  suitable  for  gen- 
eral understanding  and  use,  not  as  a  request 
for  an  approval  of  a  proprietary  design  or 
situation.  The  inquirer  may  also  include  any 
plans  or  drawings  that  are  necessary  to 
explain  the  question;  however,  they  should 
not  contain  proprietary  names  or 
information. 

Requests  that  are  not  in  this  format  will  be  written  in 
this  format  by  the  Committee  prior  to  being  answered, 
which  may  inadvertently  change  the  intent  of  the  origi- 
nal request. 

ASME  procedures  provide  for  reconsideration  of  any 
interpretation  when  or  if  additional  information  that 
might  affect  an  interpretation  is  available.  Further,  per- 
sons aggrieved  by  an  interpretation  may  appeal  to  the 
cognizant  ASME  committee  or  subcommittee.  ASME 
does  not  "approve,"  "certify,"  "rate,"  or  "endorse"  any 
item,  construction,  proprietary  device,  or  activity 

Attending  Committee  Meetings.  The  A17  Standards 
Committee  and  the  various  Working  Committees  regu- 
larly hold  meetings,  all  of  which  are  open  to  the  public. 
Persons  wishing  to  attend  any  meeting  should  contact 
the  Secretary  of  the  Standards  Committee. 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 
SUMMARY  OF  CHANGES 


Following  approval  by  the  ASME  A 17  Elevator  and  Escalator  Committee  and  ASME,  and  after 
public  review,  ASME  A17.2-2010  was  approved  by  the  American  National  Standards  Institute 
on  September  8,  2010. 

The  2010  edition  of  ASME  A17.2  includes  revisions  that  are  identified  by  a  margin  note,  (10). 
Changes  made  to  correct  errors,  as  well  as  other  editorial  changes,  are  identified  by  (ED).  All 
references  to  A17.1-2000  have  been  changed  to  A17.1-2000/B44-00.  The  following  is  a  summary 
of  the  latest  revisions  and  changes: 


Page 

Location 

Change 

x-xii 

Foreword 

Updated 

xiii-xvii 

Committee  Roster 

Updated 

xviii,  xix 

Preface 

(1)  Under  Form  and  Arrangement,  first 
paragraph  revised 

(2)  Under  Definitions,  reference  correct* 

1 

1 

(1)  Last  paragraph  added 

(2)  Note  revised 

4 

7 
8,9 


11 
12 


Table  1 

1.2.1 

1.6.1 

1.8.2 

1.8.4 

1.10.2 

1.10.4.1 

1.12.1 

1.13.1.1 


Editorially  revised  to  include  Web  site 
URLs 

Reference  in  subpara.  (a)  corrected 

Reference  in  second  paragraph  corrected 

Added 

Revised 

Reference  in  subpara.  (a)  corrected 

Reference  added 

Reference  in  subpara.  (h)  corrected 

References  corrected 


14 

15 
17 
18 
19-21 


1.13.4.1 

1.15.1 

1.17.3.1 

1.18.1 

1.20 

2.5.1 

2.7.4 

2.11.3 

2.11.4 

2.12.1.1 


Revised 

Reference  corrected 

Subparagraph  (a)  revised 

References  corrected 

Added 

Last  sentence  in  second  paragraph  added 

References  added 

Revised  in  its  entirety 

Revised 

(1)  Subparagraph  (a)  revised 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers.  j^L  . 

No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME.     ^ 


25 

2.13.4 

26 

2.17.2.1 

27 

2.17.3 

2.18.2.1 

28,29 

2.18.4.1 

2.20 

2.21.1.1 

31 

2.25.2.1 

33-35 

2.29.2 

Page  Location  Change 

(2)  Subparagraphs  (a)(5)  and  (a)(6)  added 

2.12.4  Revised 

2.13.1.1  Subparagraph  (g)  added 

2.13.2.1  (1)  Second  paragraph  in  subpara.  (a) 

added 
(2)  Subparagraph  (b)(1)  revised 

24  2.13.2.2  (1)  Last  sentence  in  subparas.  (a)  and  (b) 

added 
(2)  Subparagraph  (b)(1)  revised 

Revised 

Last  sentence  in  subpara.  (a)  added 

Added 

Added 

Revised 

Revised  in  its  entirety 

Reference  in  subpara.  (b)  corrected 

Last  paragraph  added 

(1)  Fourth  sentence  in  subpara.  (c)(1) 
added 

(2)  Subparagraphs  (e)(2)  and  (e)(4) 
revised 

Last  sentence  in  subpara.  (a)  added 

Reference  in  third  paragraph  corrected 

References  added 

Added 

Reference  in  first  sentence  corrected 

References  in  third  and  fourth 
paragraphs  corrected 

Reference  in  subpara.  (b)  corrected 

Reference  in  subpara.  (a)  corrected 

Reference  in  first  sentence  corrected 

Reference  in  subpara.  (b)(2)  corrected 

Revised 

Subparagraph  (c)(1)(b)  revised 

Revised 

Added 

Paragraph  split  into  subparas.  (a)  and  (b) 

Revised 

Revised 

Added 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


38 

2.29.3 

40,41 

2.35.1 

42,43 

2.40.4 

2.42 

44 

3.2.1 

45 

3.4.1.2 

49 

3.8.1 

3.9.1 

50 

3.11.1 

53,54 

3.17.1 

58,59 

3.22.4 

3.23.1 

Fig.  3.23.1 

60 

Fig.  3.23.2 

61 

3.26.1 

62 

3.28.4 

64,65 

3.31.4.2 

3.34 

Page 

Location 

66 

4.2.1 

69 

4.8.1 

72 

5.2.1.1 

74 

5.3.4.1 

76,77 

5.9.1.1 

78-80 

5.9.4.1 

5.12.1.1 

5.15.3.2 

5.16 

90 

Fig.  6.4.2(g)(2) 

97 

Fig.  7.2.1(c) 

98,99 

7.5.1 

7.7.1 

100 

7.7.4 

102-106 

7.9.2 

107-110 


111 


113-115 


7.10.1 


Fig.  7.9.1(c) 

7.10.4 

7.11.1 

7.15.1 
7.16.1 

7.17.1 

7.19.4 

7.20 

8.1.2 

8.1.3 

8.1.4 

8.2 

8.3.2 

8.3.3 


Change 

Reference  in  subpara.  (b)(2)  corrected 

Subparagraph  (b)  revised 

Reference  in  last  paragraph  corrected 

Reference  added 

Reference  in  subpara.  (b)(5)  corrected 

References  added 

Reference  in  subpara.  (c)  corrected 

Revised 

Added 

Reference  in  caption  corrected 

References  in  callouts  corrected 

References  in  second  paragraph  corrected 

Reference  in  second  paragraph  corrected 

References  added 

References  in  first  sentence  and  subpara. 
(b)  corrected 

(1)  References  in  subparas.  (a)  and  (b) 
corrected 

(2)  References  in  subparas.  (b)(4)  and 
(b)(5)  corrected 

Revised 

Reference  added 

(1)  First  paragraph  revised 

(2)  Reference  in  second  paragraph 
corrected 

Reference  in  last  sentence  corrected 

Reference  in  first  and  second  paragraphs 
corrected 

References  in  subparas.  (b)  and  (c) 
corrected 

Reference  added 

Added 

Reference  in  second  paragraph  corrected 

Reference  in  second  paragraph  corrected 

Reference  added 

Revised  in  its  entirety 

(1)  First  paragraph  revised 

(2)  Reference  in  second  paragraph 
corrected 

Last  paragraph  revised 


C 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


Page 

Location 

8.3.4 

8.4.2 

117 

8.9.2 

8.10.2 

119,  120 

8.13.2 

8.13.4 

121 

8.18 

122,  123 

9.3.1 

Fig.  9.2.1(a) 

124 

Fig.  9.2.1(b) 

Fig.  9.2.3 

125 

Table  9.2.3(a) 

Table  9.2.3(c) 

128 
129 

130 
131 

132 

133-135 


9.4.1 


Change 

Revised 

Reference  in  fifth  paragraph  corrected 

Reference  corrected 

Reference  in  first  paragraph  corrected 

(1)  Subparagraph  (b)  revised 

(2)  Reference  in  subpara.  (c)  corrected 

References  added 

Added 

Reference  in  subpara.  (e)  corrected 

Reference  in  caption  corrected 

References  in  callouts  corrected 

Reference  in  callout  corrected 

Reference  in  title  corrected 

Reference  in  left  column  heading 
corrected 

References  in  subparas.  (a)  and  (b) 
corrected 


137 


9.4.4 

Reference  added 

Fig.  9.9.1 

References  in  callouts  corrected 

9.10.1 

Reference  in  subpara.  (b)  corrected 

9.10.3 

Last  sentence  added 

9.10.4 

Reference  added 

Table  9.14.3(b) 

Reference  in  title  corrected 

9.15 

Revised  in  its  entirety 

Fig.  9.17.1 

Reference  in  callout  corrected 

9.17.1 

Reference  in  last  sentence  corrected 

9.19.4 

Reference  added 

9.20 

Added 

10.1.4 

Reference  added 

10.2 

Title  revised 

10.2.2 

Last  paragraph  added 

10.2.4 

Reference  added 

10.3.2 

(1)  Revised 

(2)  Reference  in  last  sentence  correc 

10.3.3 

Revised 

10.3.4 

References  added 

10.4.2 

Seventh  paragraph  revised 

10.10.2 

Reference  in  first  paragraph  correct 

Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


Page 

Location 

Change 

138,  139 

10.13.2 

(1)  References  in  subparas.  (a)  and  (c) 
corrected 

(2)  Subparagraph  (b)  revised 

10.13.4 

References  added 

10.17 

Added 

140-148 

Part  11 

Added 

149-163 

Mandatory  Appendix  I 

Added 

164-188 

Nonmandatory 
Appendix  A 

Revised  in  its  entirety 

189-207 

Nonmandatory 

(1)  For  A17.1-2000  and  B44-00  table,  11 

Appendix  B 

6.5.13(f)  added 

(2)  A17.1-2002  and  B44-02  table  added 

(3)  A17.1-2004  and  B44-04  table  added 


XXV 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


INTENTIONALLY  LEFT  BLANK 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


GUIDE  FOR  INSPECTION  OF  ELEVATORS,  ESCALATORS, 

AND  MOVING  WALKS 


Introduction 


(io)    1     SCOPE 

This  Guide  covers  recommended  inspection  and  test- 
ing procedures  for  electric  and  hydraulic  elevators,  esca- 
lators, and  moving  walks  required  to  conform  to  the 
Safety  Code  for  Elevators  and  Escalators,  A17.1-1955 
and  later  editions  and  The  Safety  Code  for  Existing 
Elevators  and  Escalators,  A17.3.  This  Guide  also 
addresses  some  requirements  from  editions  of  A17.1 
prior  to  1955. 

This  guide  also  includes  Canadian  references  and 
applicable  exceptions  for  CSA  B44-00  and  later  editions. 
Exceptions  or  deviations  applicable  in  Canada  are  iden- 
tified with  the  same  ASME  requirement  number  pref- 
aced with  a  lowercase  "c"  for  CSA  B44-00  through 
CSA  B44-04  Update  1. 

NOTE:     This  Guide  may  not  reflect  the  latest  requirements  in  the 
current  ASME  A17.1/CSA  B44  and  ASME  A17.3  Codes. 


2     APPLICATION 

This  Guide  is  intended  to  assist  qualified  inspectors 
performing  routine  inspections  and  witnessing  periodic 
and  acceptance  inspections  and  tests.  It  is  not  intended 
to  serve  as  a  basis  for  government  regulations.  This 
Guide  does  not  contain  information  on  handling  dis- 
crepancies noted  during  an  inspection  and  test.  The 
authority  having  jurisdiction  in  their  legislation  adopt- 
ing the  Code  is  responsible  for  addressing  this  subject. 
The  acceptance  inspection  and  testing  procedures  apply 
only  to  the  extent  that  they  conform  to  the  latest  edition 
of  the  A17.1/B44  Code.  The  routine  and  periodic  inspec- 
tion and  testing  procedures  apply  only  to  the  extent  that 
they  conform  to  the  applicable  Code  requirements  that 
were  in  effect  at  the  time  of  installation  or  alteration. 
The  inspection  and  testing  procedures  do  not  take  into 
account  local  regulations  that  may  differ. 

It  is  recognized  that  inspectors  will  not  be  able  to 
accomplish  all  the  inspection  procedures  specified  in 
this  Guide,  during  each  inspection.  Qualified  inspectors 


have  the  knowledge  and  experience  to  recognize  poten- 
tial deficiencies  and  to  focus  the  inspection  in  those 
areas. 

This  Guide  uses  the  following  format  to  describe  the 
appropriate  inspection  and  test: 

(a)  For  inspections  and  tests  performed  in  compliance 
with  ASME  A17.1d-2000  and  earlier  editions 

(1)  Routine.  The  examination  and  operation  of 
equipment  at  specified  intervals  by  an  inspector  to  check 
for  compliance  with  the  applicable  Code  requirements. 

(2)  Periodic  Tests.  Routine  inspection  and  tests  plus 
additional  detailed  examination  and  operation  of  equip- 
ment at  specified  intervals  witnessed  by  an  inspector  to 
check  for  compliance  with  the  applicable  Code 
requirements. 

(3)  Acceptance.  The  initial  inspection  and  tests  of 
new  or  altered  equipment  to  check  for  compliance  with 
the  applicable  Code  requirements. 

(b)  For  inspections  and  tests  performed  in  compliance 
with  ASME  A17.1-2000/CSA  B44-00  and  later  editions: 

(1)  Periodic  Inspection.  The  examination  and  opera- 
tion of  equipment  at  specified  intervals  by  an  inspector 
to  check  for  compliance  with  the  applicable  Code 
requirements. 

(2)  Periodic  Tests.  The  testing  and  detailed  exami- 
nation and  operation  of  equipment  at  specified  intervals 
witnessed  by  an  inspector  to  check  for  compliance  with 
the  applicable  Code  requirements. 

(3)  Acceptance.  The  initial  inspection  and  test  of 
new  or  altered  equipment  to  check  for  compliance  with 
the  applicable  Code  requirements. 

The  procedures  in  this  Guide  are  recommendations 
only  and  are  intended  to  illustrate  a  method  of  comply- 
ing with  the  requirements  in  ASME  A17.1d-2000  and 
earlier  editions  and  A17.1-2000/B44-00  and  later  edi- 
tions, requirements  8.10  and  8.11.  The  person  per- 
forming the  inspection  and  test  may  employ  other 
methods  to  demonstrate  compliance  with  the  applicable 
code  requirement.  Qualified  inspectors  have  the  knowl- 
edge and  experience  to  recognize  potential  deficiencies 
and  to  focus  the  inspection  where  necessary 


1 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


Where  no  inspection  procedure  is  specified  for  routine 
inspections,  it  indicates  that  the  Code  requirements  need 
no  explanation.  This  does  not  indicate  that  no  inspection 
of  the  specified  item  is  required.  The  item  is  to  be 
inspected  for  compliance  with  the  applicable  Code 
requirements. 

Where,  as  an  example,  the  periodic  inspection  has  no 
specified  inspections,  the  inspections  specified  under 
routine  are  to  be  used  for  the  periodic  inspection.  If,  as 
an  example,  the  acceptance  inspection  has  a  test  proce- 
dure that  differs  from  the  test  procedure  specified  under 
periodic,  the  acceptance  test  procedure  should  be  fol- 
lowed for  acceptance  inspection  and  the  periodic  test 
procedure  should  be  followed  for  periodic  inspections. 

This  Guide  contains  inspection  procedures  for  compli- 
ance with  the  applicable  Code  only.  A17.1d-2000  and 
earlier  editions  Rule  1000.2  and  A17.1-2000/B44-00  and 
later  editions  requirements  8.10.1.2  and  8.11.1.2,  reads 
in  part  "the  inspection  and  test  required  by  this  Part 
are  to  determine  that  the  equipment  conforms  to  the 
applicable  Code  requirements  at  the  time  of  installation 
and  any  alteration."  This  Guide  contains  no  recommen- 
dations that  exceed  the  requirements  of  A17.1d-2000 
and  earlier  editions  Rule  1000.2  and  A17.1-2000/B44-00 
and  later  editions  requirements  8.10.1.2  and  8.11.1.2,  and 
A17.3. 

To  facilitate  making  inspections  and  tests,  sample 
checklists  can  be  found  in  Nonmandatory  Appendix  A 
of  this  Guide.  The  checklist  Item  numbers  correspond 
to  the  Item  numbers  in  this  Guide.  The  checklist  also 
contains  appropriate  A17.1  and  A17.3  references  for 
each  Item. 

NOTE:  See  also  Form  and  Arrangement  under  the  Preface  of 
this  Guide. 

3  QUALIFICATIONS  OF  INSPECTORS 

Inspectors  and  inspection  supervisors  are  required  by 
ASME  A17.1d-2000  and  earlier  editions  and 
A17.1-2000/B44-00  and  later  editions,  requirements 
8.10.1.1(c)  and  8.11.1.1  to  be  certified  by  an  organization 
accredited  by  The  American  Society  of  Mechanical 
Engineers  Qualifications  for  Elevator  Inspectors 
Committee  in  accordance  with  the  requirements  set  forth 
in  the  Standard  for  the  Qualification  of  Elevator 
Inspectors,  ASME  QEI-1  and  be  recognized  by  the 
authority  having  jurisdiction. 

4  PERSONAL  SAFETY 

Inspectors  should  have  knowledge  of  the  personal 
safety  practices  including,  but  not  limited  to,  the  safety 
practices  contained  in  The  Elevator  Industry  Field 
Employees'  Safety  Handbook  as  required  by  ASME  QEI-1. 

NOTE:  The  Elevator  Industry  Field  Employees'  Safety  Handbook  is 
available  from  Elevator  World,  Inc.,  P.O.  Box  6507,  Mobile,  Alabama 
36660  (http://www.elevator-world.com). 


5     DUTIES  OF  INSPECTORS 

The  duties  of  inspectors  are: 

(a)  when  witnessing  acceptance  inspections  and  tests 
of  new  or  altered  installations,  to  determine  whether  all 
parts  of  the  installation  conform  to  the  requirements 
of  the  applicable  code  or  regulations  and  whether  the 
required  safety  devices  function  as  required. 

(b)  when  making  routine  and /or  periodic  inspections 
and  tests,  to  determine  that  the  equipment  conforms 
to  the  applicable  Code  edition  (edition  which  it  was 
installed,  A17.3  and  local  requirements)  and  that  alter- 
ations conform  with  Code  requirements.  Determine  that 
periodic  tests  performed  by  the  owner  or  his  agent  are 
conducted  in  accordance  with  Code  requirements  and 
results  of  these  tests  demonstrate  Code  compliance. 

(c)  to  report  the  results  of  inspections  and  tests  in 
accordance  with  applicable  local  regulations. 

It  is  not  the  function  or  duty  of  inspectors  to  make 
any  repairs  or  adjustments  to  the  equipment,  nor  to 
recommend  methods  or  procedures  for  correction  of 
deficiencies. 


6  ARRANGEMENT  FOR  INSPECTION 

The  inspecting  authority  or  the  inspector  should 
request  the  owner  or  his  agent  to  make  the  following 
arrangements  prior  to  an  inspection  or  test: 

(a)  Provide  qualified  personnel  for  periodic  and 
acceptance  inspections  and  tests  to  perform  the  tests 
specified  in  the  applicable  code  or  regulations. 

(b)  Have  a  person  familiar  with  the  operation  of  the 
elevator  available  to  accompany  and  assist  during  the 
inspections.  The  inspector  should  be  accompanied  by  a 
person  familiar  with  the  operation  of  the  equipment  to 
assist  him  during  his  inspections. 

7  RECOMMENDED  EQUIPMENT 

(a)  It  is  recommended  that  the  inspector  have  the  fol- 
lowing equipment: 

(1)  flashlight  with  a  nonconductive  case 

(2)  6  ft  (2  m)  rule  of  nonconductive  material 

(3)  set  of  thick  gages 

(4)  small  hammer,  preferably  a  \  lb  (0.2  kg)  ball 
peen 

(5)  chalk  or  crayon 

(6)  small  metal  mirror 

(7)  safety  hat  (nonconductive) 

(8)  copy  of  the  latest  applicable  codes  and  stan- 
dards (i.e.,  A17.1,  A17.3,  ANSI/NFPA  70,  etc.) 

(9)  copy  of  the  applicable  local  regulations 

(10)  copy  of  the  latest  edition  of  The  Elevator 
Industry  Field  Employees  Safety  Handbook 

(11)  copy  of  the  checklists  as  contained  in  this 
Guide 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


(12)  padlock,  multiple  lock  device,  and  "Do  Not 
Start"  tags 

(13)  caliper 

(14)  telescoping  pointer  with  an  alligator  clip  and 
business  cards  or  stiff  paper 

(15)  other  items  such  as  an  eraser,  kitchen  spatula, 
etc.  (for  escalators  and  moving  walks) 

(16)  stop  watch  or  timer 

(17)  50  ft  (15  m)  nonconductive  tape  and  25  ft 
(75  m)  tape 

(18)  tachometer,  which  reads  directly  in  ft/min 
(m/s) 

(19)  multimeter 

(20)  level,  30  deg/60  deg  triangle,  and  protractor 
or  angle  finder 

(21)  door  test  scale  (gage)  to  check  closing  door 
force 

(22)  a  light  meter  that  can  accurately  measure  light 
level  from  0  fc  to  19  fc  (0  lx  to  200  lx) 

(23)  marking  chalk  or  crayon 

(b)  Periodic  and  Acceptance  Inspection  and  Tests.  In 
addition  to  the  equipment  specified  above,  the  following 
should  be  provided  by  the  owner  or  contractor: 

(1)  suitable  test  weights 

(2)  dynamometer 

(3)  copy  of  all  pertinent  drawings,  specification, 
data  sheets,  and  required  test  procedures 

(4)  transceiver 

(5)  come-along  and  "Chicago"  grip  or  mid-line 
rope  clamps 

(6)  "Out  of  Service"  signs  and/or  barricades  at 
hoistway  doors 

(7)  device  for  testing  smoke  detectors 

(8)  no.  16-gage  copper  wire  or  equivalent 

(9)  keys  for  access  and  operation  of  all  elevator 
equipment 

(10)  hydraulic  jack  and  4x4 

(11)  plumb  line  (for  escalators) 

(12)  torque  wrench  (for  escalators) 

(13)  skirt/ step  performance  index  test  apparatus 
and  accessory  apparatus 

NOTE:  If  iron  counterweight  sections  are  used  as  test  weights 
and  scales  are  not  available  to  accurately  determine  their  weight 
in  pounds,  their  approximate  weight  can  be  determined  by  multi- 
plying the  product  of  the  length,  breadth,  and  thickness  in  inches 
by  0.26.  If  weights  are  lead,  multiply  by  0.41.  If  weights  are  steel, 
multiply  by  0,28.  Deduct  for  volume  of  any  holes  or  slots. 


Table  1     Procurement  Information 


(ED) 


Organization 


Address  and  Phone  Number 


ANSI  American  National  Standards  Institute,  Inc. 

25  West  43rd  Street 
New  York,  NY  10036 
Telephone:  (212)  642-4900 
http://www.ansi.org 

ASME  The  American  Society  of  Mechanical  Engineers 

Three  Park  Avenue 
New  York,  NY  10016-5990 
Telephone:  (212)  591-8500 

http://www.asme.org 

ASME  Order  Department 
22  Law  Drive 
Box  2900 

Fairfield,  NJ  07007-2900 
Telephone:  (201)  882-1167 
(800)  843-2763 

ASTM  American  Society  for  Testing  and  Materials 

100  Barr  Harbor  Drive 
West  Conshohocken,  PA  19428-2959 
Telephone:  (610)  832-9500 
http://www.astm.org 

CSA  Canadian  Standards  Association 

5060  Spectrum  Way 
Mississauga,  Ontario  L4W  5N6,  Canada 
Telephone:  (416)  747-4044 
http://www.csa.ca 

IEEE  Institute  of  Electrical  and  Electronics 

Engineers,  Inc. 
445  Hoes  Lane 
Piscataway,  NJ  08854 
Telephone:  (800)  678-4333 
http://www.ieee.org 

NFPA  National  Fire  Protection  Association 

1  Batterymarch  Park 
Quincy,  MA  02169-7471 
Telephone:  (617)  770-3000 
http://www.nfpa.org 


8     REFERENCE  DOCUMENTS 

Table  1  lists  the  organizations  from  which  documents 
referenced  in  this  book  can  be  procured. 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Part  1 
Elevator  —  Inside  of  Car 


ITEM  1.1 
DOOR  REOPENING  DEVICE 

1.1.1  Periodic  Inspections 

For  elevators  installed  under  A17. 1-1955  through 
A17.1d-1975,  power  opening  of  the  car  door  was  permit- 
ted to  take  place  anywhere  in  the  hoistway.  For  elevators 
installed  under  A17.1e-1975,  power  opening  of  the  car 
door  was  permitted  to  take  place  only  within  the  land- 
ing zone. 

CAUTION:  In  any  of  the  following  tests  where  the  inspector 
uses  an  object  to  test  the  reopening  device,  the  object  must  not 
be  inserted  when  the  door  is  nearing  its  fully  closed  position. 

(a)  Mechanical  Reopening  Device  (Safety  Edge).  Actuate 
the  device  while  the  doors  are  being  closed  and  note 
whether  car  and  hoistway  doors  stop  and  reopen.  For 
vertically  sliding  car  doors  or  gates,  a  stop  and  reopen 
is  not  required  for  obstructions  within  5  in.  (127  mm) 
of  the  sides  of  the  opening. 

(b)  Electronic  Reopening  Device.  Place  an  object  in  front 
of  the  leading  edge  of  the  car  door  at  various  positions 
while  it  is  being  closed.  The  car  and  hoistway  doors 
should  stop  and  reopen.  For  vertically  sliding  car  doors 
or  gates,  a  stop  and  reopen  is  not  required  for  obstruc- 
tions within  5  in.  (127  mm)  of  the  sides  of  the  opening. 

(c)  Photoelectric  Reopening  Device.  To  qualify  as  a 
reopening  device  that  complies  with  the  Code,  the 
device  must  sense  the  presence  of  the  obstruction  any- 
where within  the  opening  along  the  leading  edge  of  the 
car  door.  Determine  the  location  of  the  light  beam  or 
beams  with  relation  to  the  car  floor.  Where  an  invisible 
beam  is  used,  the  position  of  the  beam  can  be  determined 
by  an  examination  of  the  equipment.  While  the  car  and 
hoistway  doors  are  being  closed,  obstruct  the  beam 
which  should  cause  the  doors  to  stop  and  reopen.  This 
type  of  device  is  usually  installed  in  addition  to  a 
mechanical  or  electronic  reopening  device. 

1.1.2  Periodic  Test 

1.1.3  Acceptance 

1.1.4  References 

1.1.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Section  112  and  Rule  1001.2(a)(1). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.13  and  8.11.2.1.1(a). 

A17.3  —  Section  2.8. 


1.1.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Section  112  {Rule  300.13);  and  Rules 
1001.2(a)(1)  and  1004.2(a)(1). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.13  {3.13};  and  8.11.2.1.1(a)  and 
8.11.3.1.1(a). 

A17.3  —  Section  2.8. 


ITEM  1.2 
STOP  SWITCHES 

1.2.1  Periodic  Inspections 

An  emergency  stop  switch  must  be  provided  on 
freight  elevators  and  existing  passenger  elevators  with 
perforated  enclosures.  An  emergency  stop  switch  or 
in-car  switch  must  be  provided  on  passenger  elevators. 

(a)  Emergency  Stop  Switch.  Operate  the  emergency 
stop  switch  and  note  whether  the  car  stops  promptly.  On 
elevators  installed  under  A17.1b-1980  and  later  editions, 
the  stop  switch  should  also  activate  an  audible  signaling 
device.  On  elevators  installed  under  A17.1a-1982  and 
later  editions,  an  emergency  stop  switch  is  required  to 
be  located  in  or  adjacent  to  each  car  operating  panel. 
Passenger  elevators  with  non-perforated  car  enclosures 
may  be  equipped  with  an  in-car  stop  switch  in  lieu  of 
the  emergency  stop  switch. 

(b)  In-Car  Stop  Switch.  Passenger  elevators  installed 
under  A17.1d-1986  and  later  editions  do  not  require  an 
in-car  emergency  stop  switch  but  do  require  an  in-car 
stop  switch.  The  in-car  stop  switch  must  be  key  operated 
or  behind  a  locked  panel.  Check  the  operation  of  this 
switch  by  placing  it  in  the  stop  position  and  attempt  to 
operate  the  car  by  the  normal  means. 

1.2.2  Periodic  Test 

1.2.3  Acceptance 

1.2.4  References 

1.2.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  210.2(e),  210.2(v),  and  1001.2(a)(2). 

A17.1-2000/B44-00      and      later     editions     — 
Requirements  2.26.2.5,  2.26.2.21,  and  8.11.2.1.1(b). 
A17.3  —  Paragraphs  3.10.4(t)  and  3.10.4(u). 

1.2.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  306.4(b)(1),  306.4(b)(6),  and 
1004.2(a)(2). 


(10) 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


A17.1-2000/B44-00     and     later     editions     — 
Requirements  3.26.4.2(a),  3.26.4.2(f),  and  8.11.3.1.1(b). 
A17.3  —  Paragraphs  3.10.4(t)  and  3.10.4(u)  {4.7.4}. 

ITEM  1.3 
OPERATING  CONTROL  DEVICES 

1.3.1  Periodic  Inspections 

(a)  Continuous-Pressure  Operation,  Operate  the  car  in 
each  direction  by  means  of  the  operating  buttons  or 
other  devices  in  the  car  to  verify  that  they  do  not  stick 
or  bind,  are  properly  marked,  and  that  the  car  stops 
when  the  operating  device  is  released. 

(b)  Automatic  Operation  and  Signal  Operation.  Operate 
the  car,  making  stops  in  both  the  up  and  down  direction. 
At  each  stop,  open  the  car  door  or  gate  and  note  the 
relation  of  the  car  platform  sill  to  the  landing  sill.  Note 
operating  push  buttons  work  properly. 

(c)  Hand  Rope,  Lever,  Wheel  or  Crank  Operation.  This 
type  of  operation  is  prohibited  for  elevators  installed 
under  A17.1-1955  and  later  editions  and  by  A17.3. 

(d)  Dual  and  Attendant  Operation.  Where  the  elevator 
can  be  operated  at  times  only  from  the  car  and  at  times 
as  an  automatic  elevator  (dual  or  attendant  operation), 
check  the  operation  under  both  operating  conditions. 

(e)  Emergency  Release  Switch  in  Car.  Emergency  release 
switches  that  permit  operation  with  the  car  door  or 
gate  open  and  other  permanent  devices  that  render  door 
interlocks  and  door  or  gate  electric  contacts  inoperative 
are  not  permitted  under  A17. 1-1955  and  later  editions 
or  by  A17.3. 

1.3.1.1  Electric  Elevators 

(a)  Car  Leveling  and  Truck  Zoning  Device.  When  an 
automatic  leveling  device  is  provided,  the  accuracy  of 
stopping  in  both  directions  of  travel  should  be  noted  at 
each  landing.  A  leveling  tolerance  may  be  required  by 
an  accessibility  or  handicapped  code.  Where  inching 
buttons  are  provided,  test  them  to  determine  that  they 
will  operate  the  car  only  within  the  zone  allowed  by  the 
Code.  While  the  car  is  leveling,  operate  the  emergency  or 
in-car  stop  switch  as  outlined  in  Item  1.2.1.  This  should 
stop  the  car. 

NOTE  [Item  1.3.1.1(a)]:     Leveling  devices  cannot  be  expected  to 
stop  the  car  exactly  level  with  the  landing  sill. 

(b)  Car-Switch  Operation.  Operate  the  car  switch  to 
determine  whether  the  operating  handle  returns  to  the 
stop  position  and  latches  in  this  position  when  the  hand 
is  removed.  Note  any  evidence  of  excessive  friction,  or 
weakened  or  broken  centering  springs. 

1.3.1.2  Hydraulic  Elevators 

(a)  Car  Leveling  and  Truck  Zoning  Device.  When  an 
automatic  leveling  device  is  provided,  the  accuracy  of 
stopping  in  both  directions  of  travel  should  be  noted  at 
each  landing.  A  leveling  tolerance  may  be  required  by 


an  accessibility  or  handicapped  code.  Where  inching 
buttons  are  provided,  test  them  to  verify  that  they  will 
operate  the  car  only  within  the  zone  allowed  by  the 
Code.  While  the  car  is  leveling,  operate  the  emergency 
or  in-car  stop  switch  as  outlined  in  Item  1.2.1. 

NOTE  [Item  1.3.1.2(a)]:  Leveling  devices  cannot  be  expected  to 
stop  the  car  exactly  level  with  the  landing  sill. 

1.3.2  Periodic  Test 

1.3.3  Acceptance 

1.3.4  References 

1.3.4.1  Electric  Elevators.    A17.1d-2000  and  earlier 
editions  —  Rules  210.1a,  210.16,  and  1001.2(a)(3). 

A17.1-2000/B44-00      and     later      editions     — 
Requirements  2.26.1.1,  2.26.1.6,  and  8.11.2.1.1(c). 
A17.3  —  Paragraphs  3.10.1,  3.10.2,  and  3.10.7. 

1.3.4.2  Hydraulic  Elevators.    A17.1d-2000  and  later 
editions  —  Rules  210.1a  {306.1},  306.3,  and  1004.2(a)(3). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.26.1.1  {3.26.1},  3.26.3,  and  8.11.3.1.1(c). 

A17.3  —  Paragraphs  3.10.1  and  3.10.2  {Section  4.7}, 
and  3.10.9  {4.7.6}. 

ITEM  1.4 
SILLS  AND  CAR  FLOOR 

1.4.1  Periodic  Inspections 

(a)  Hinged  Car  Platform  Sills 

(1)  Visually  examine  the  sill  plate  for  cracks,  wear, 
broken  welds,  or  loose  rivets.  Check  the  area  under  the 
sill  for  foreign  material,  which  would  prevent  proper 
operation  at  the  landing. 

(2)  Check  all  bolts  on  the  counterweight  housing 
and  stop  angles.  Inspect  the  ropes  or  chains  that  connect 
the  sill  to  the  counterweight.  Check  pivot  points  and 
sheaves  for  wear  and  proper  lubrication. 

(3)  Inspect  the  hand  lever  and  linkage  for  excess 
wear,  and  loose  or  missing  cotter  pins  or  bolts.  Check  the 
operation  of  the  hinged  car-platform  sill  electric  contact. 

(b)  Hinged  Hoistway  Landing  Sills 

(1)  Visually  examine  the  sill  plate  for  cracks,  wear, 
broken  welds,  or  loose  rivets.  Check  the  area  under  the 
sill  for  foreign  material,  which  would  prevent  proper 
operation  at  the  landing. 

(2)  Check  all  bolts  on  the  counterweight  housing 
and  stop  angles.  Inspect  the  ropes  or  chains  that  connect 
the  sill  to  the  counterweight.  Check  pivot  points  and 
sheaves  for  wear  and  proper  lubrication.  Check  the  oper- 
ation of  the  hinged  hoistway  landing  sill.  It  should  be 
possible  to  lower  the  hinged  sill  only  when  the  hoistway 
door  is  fully  opened. 

(c)  Sills  and  Car  Floor 

(1)  Determine  the  condition  of  the  car  floor  and  car 
and  landing  sills.  Look  especially  for  damage  to  floors 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


and  sills  as  well  as  loose  sills.  Verify  the  clearance 
between  the  car  and  landing  sills.  See  Table  3.14.3(a). 

(2)  A  floating  platform  is  not  permitted  by 
A17.1a-1957  and  later  editions  or  by  A17.3.  A  floating 
platform  is  a  car  platform  that  permits  operation  of  the 
car  with  the  car  gate  or  door  open. 

(3)  Elevator  systems  may,  however,  use  isolated 
platform  construction  that  may  have  load  weighing  sig- 
naling devices.  Such  use  is  not  prohibited.  Try  operating 
the  car  from  the  landing  operating  device  with  a  load 
of  30  lb  (13.6  kg)  on  the  platform  with  the  car  gate  or 
door  in  the  open  position.  This  test  is  to  be  repeated 
with  the  test  load  placed  in  various  locations.  The  car 
should  not  operate  under  such  conditions. 

1.4.2  Periodic  Test 

1.4.3  Acceptance 

Check  that  landing  sills  are  substantially  flush  with 
the  floor  surface  of  the  landings  and  the  sill  does  not 
present  a  tripping  hazard.  Changes  in  level  up  to  \  in. 
(6  mm)  may  be  vertical  and  without  edge  treatment. 
Changes  in  level  between  \  in.  (6  mm)  and  \  in.  (13  mm) 
must  be  beveled,  and  changes  in  level  above  V2  in. 
(13  mm)  must  be  ramped. 

1.4.4  References 

1.4.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  — Rules  108.1,  llO.lOd,  110.11a,  110.13a,  203.16, 
210.12,  and  1001.2(a)(4). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.5.1, 2.11.10.3, 2.11.11.1, 2.11.13.1, 2.15.16, 
(NR  210.12),  and  8.11.2.1.1(d). 

A17.3  —  Paragraphs  3.3.3  and  3.3.4. 

ANSI  A117.1. 

1.4.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  108.1  (300.9),  HO.lOd  {300.11}, 
110.11a,  110.13a,  203.16  {301.6},  210.12,  and  1004.2(a)(4). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.5.1  {3.5},  2.11.10.3  {3.11},  2.11.11.1, 
2.11.13.1,  2.15.16  {3.15},  (NR  210.12),  and  8.11.3.1.1(d). 

A17.3  —  Paragraphs  3.3.3  and  3.3.4  {4.2.2}. 

ANSI  A117.1. 


(b)  Auxiliary  Illumination.  A17.1b-1968  and  later  edi- 
tions, and  A17.3,  require  auxiliary  illumination  of  pas- 
senger elevator  cars  in  case  of  failure  of  the  normal 
car  lighting  power  supply.  When  auxiliary  lighting  is 
supplied,  check  its  operation  by  disconnecting  the  nor- 
mal lighting  supply  Where  the  auxiliary  lighting  is  sup- 
plied by  batteries,  check  that  such  batteries  are  in  good 
condition  and  properly  maintained,  and  that  any 
recharging  equipment  is  operable.  Check  that  the  auxil- 
iary power  supply  is  located  on  each  elevator. 

1.5.2  Periodic  Test:  Yearly  Test  (for  A17.1d-2000 
and  Earlier  Editions);  Category  1  Test  (for 
A17.1-2000/B44-00  and  Later  Editions) 

Car  lamps  and  diffusers,  if  provided,  should  be  in 
place  for  all  safety  and  buffer  tests.  They  must  remain 
in  place  during  the  test.  Where  there  is  a  question  as  to 
the  adequate  capacity  of  the  emergency  power  supply, 
an  endurance  test  should  be  made. 

1.5.3  Acceptance 

When  the  hoistway  doors  are  closed,  the  Code 
requires  a  minimum  illumination  at  the  landing  edge 
of  the  car  door  sill  of  5  fc  (54  lx)  for  passenger  elevators, 
2V2  fc  (27  lx)  for  freight  elevators,  and  0.2  fc  (2  lx)  auxiliary 
illumination  in  front  of  car  operating  panels  that  contain 
the  equipment  specified  in  the  Code.  If  there  is  any 
question  as  to  whether  the  normal  or  auxiliary  illumina- 
tion is  adequate,  require  that  light  intensity  readings  be 
taken. 

Determine  that  light  bulbs  and  tubes  are  guarded  or 
recessed  to  provide  protection  from  accidental  breakage. 
Glass  panels  and  their  structure  must  be  capable  of  with- 
standing the  required  elevator  tests  without  damage. 

Check  if  glass  exceeding  1  ft2  (0.093  m2)  in  area  and 
abutting  panels  whose  total  area  is  greater  than  1  ft2 
(0.093  m2)  meet  the  requirements  for  laminated  glass  or, 
in  jurisdictions  enforcing  NBCC,  safety  glass  or  safety 
plastic  in  compliance  with  the  applicable  standard. 

Car  lights  may  be  turned  off  automatically. 
A17.1b-1989  and  later  editions  specify  certain  condi- 
tions that  must  be  met  before  lights  can  be  automatically 
turned  off. 


ITEM  1.5 
CAR  LIGHTING  AND  RECEPTACLES 

1.5.1  Periodic  Inspections 

(a)  Normal  Illumination.  Examine  lighting  fixtures  to 
determine  whether  they  are  securely  fastened.  At  least 
two  lamps  must  be  provided.  Examine  the  electric  light- 
ing fixtures  to  verify  that  bulbs  or  tubes  are  guarded  to 
prevent  injury  to  persons  in  the  event  of  breakage.  For 
elevators  installed  under  A17.1d-2000  and  earlier  edi- 
tions, verify  means  are  provided  to  contain  shattered 
glass  if  the  light  diffuser  is  of  the  open  "egg-crate"  type. 


1.5.4  References 

1.5.4.1  Electric  Elevators.    A17.1d-2000  and  earlier 
editions  —  Rules  204.7  and  1001.2(a)(5). 

A17.1-2000/B44-00     and     later     editions     — 
Requirements  2.14.7  and  8.11.2.1.1(e). 
A17.3  —  Paragraphs  3.4.5  and  3.4.6. 

1.5.4.2  Hydraulic  Elevators.    A17.1d-2000  and  ear- 
lier editions  —  Rules  301.7  and  1004.2(a)(5). 

A17.1-2000/B44-00     and     later     editions     — 
Requirements  3.14  and  8.11.3.1.1(e). 
A17.3  —  Paragraphs  3.4.5  and  3.4.6  {4.2.3}. 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


ITEM  1.6 
CAR  EMERGENCY  SIGNAL 

(10)    1.6.1  Periodic  Inspections 

Elevators  installed  under  A17. 1-1955  through 
A17.1b-1980,  which  are  operated  without  a  designated 
attendant,  must  be  provided  with  an  emergency  signal 
audible  outside  the  hoistway,  or  with  a  telephone. 

All  elevators  installed  under  A17.1b-1980  and  later 
editions  and  A17.3  are  required  to  have  emergency  sig- 
naling devices.  A17.1a-1991  and  later  editions  require 
that  the  switch  marked  "ALARM"  be  illuminated  when 
activated  and  that  elevators  with  a  travel  greater  than 
100  ft  (30.4  m)  be  provided  with  a  second  audible  signal- 
ing device  at  the  designated  level.  Operate  the  audible 
signaling  device  (alarm)  and  the  means  of  two-way  con- 
versation. Disconnect  the  normal  power  source  to  check 
that  the  emergency  power  source  will  operate  the  light- 
ing, alarm,  and  means  of  two-way  conversation.  In 
buildings  that  do  not  have  someone  in  continuous  atten- 
dance, check  the  outdoor  signal  or  means  of  conversa- 
tion with  outside  emergency  service.  Elevators  installed 
under  A17.1-1955  through  A17.1a~1979  are  required  to 
have  an  emergency  signaling  device  only  if  the  car  is 
operated  at  any  time  without  a  designated  operator  in 
the  car. 

A17.1b~1968  through  A17.1-1971  require  means  of 
two-way  conversation  on  automatic  elevators  having  a 
travel  of  65  ft  (19.8  m)  or  more  or  a  distance  exceeding 
15  ft  (4.5  m)  between  landings.  A17. 1-1978  and  later 
editions  require  means  of  two-way  conversation  on  all 
automatic  elevators.  They  are  also  required  to  operate 
in  case  of  failure  of  the  normal  building  power  supply. 

1.6.2  Periodic  Test:  Yearly  Test  (for  A17.1d-2000 
and  Earlier  Editions);  Category  1  Test  (for 
A17.1-2000/B44-00  and  Later  Editions) 

When  there  is  a  question  as  to  the  adequate  capacity 
or  condition  of  the  emergency  power  supply,  a  test 
should  be  made. 

1.6.3  Acceptance 

1.6.4  References 

1.6.4.1  Electric  Elevators.    A17.1d-2000  and  earlier 
editions  —  Rules  211.1  and  1001.2(a)(6). 

A17.1-2000/B44-00     and     later     editions     — 
Requirements  2.27.1  and  8.11.2.1.1(f). 
A17.3  —  Paragraph  3.11.1. 

1.6.4.2  Hydraulic  Elevators.    A17.1d-2000  and  ear- 
lier editions  —  Rules  211.1  {306.11}  and  1004.2(a)(6). 

A17.1-2000/B44-00     and     later     editions     — 
Requirements  2.27.1  {3.27}  and  8.11.3.1.1(f). 
A17.3  —  Paragraph  3.11.1  {4.7.8}. 


ITEM  1.7 
CAR  DOOR  OR  GATE 

1.7.1  Periodic  Inspections 

(a)  Examination  of  Doors  or  Gates.  Examine  the  car 
door  or  gates  and  note  any  broken,  bent,  or  sprung 
members.  Operate  doors  or  gates  to  verify  that  they 
operate  freely  and  that  bottom  sill-guide  tracks  or  bot- 
tom guiding  members  are  in  place,  securely  fastened, 
and  are  not  worn  enough  to  permit  the  doors  or  gates 
to  come  out  of  their  tracks  at  any  position  of  their  travel. 
Verify  that  all  depressions  and  moldings  are  not  raised 
or  depressed  from  the  exposed  surface  more  than  per- 
mitted by  the  Code.  A17.1d-2000  and  earlier  editions 
allowed  up  to  \  in.  (6.3  mm).  Collapsible- type  gates  are 
not  permitted  on  passenger  elevators  installed  under 
A17.1a-1988  and  later  editions.  Check  collapsible  gates 
for  proper  restraint  of  vertical  members  to  restrict  hori- 
zontal deflection. 

(b)  Test  for  Closed  Position.  With  the  hoist  way  doors 
or  gates  in  the  closed  position,  check  the  closed  position 
of  the  car  doors  or  gates  as  outlined  in  Item  4.2.1(b) 
for  hoist  way  door  or  gate  interlocks.  A  door  or  gate  is 
considered  to  be  in  the  closed  position  when  the  clear 
open  space  between  the  leading  edge  of  the  door  or  gate 
and  the  nearest  face  of  the  jamb  or  sill  does  not  exceed 
2  in.  (51  mm)  or,  in  the  case  of  biparting  doors,  when 
the  door  panels  are  within  2  in.  (51  mm)  of  contact  with 
each  other. 

(c)  Location  of  Car  Doors  or  Gates.  A17.3  and 
A17.1-1937  and  later  editions  specify  the  maximum  dis- 
tance from  the  face  of  the  car  door  or  gate  to  the  face 
of  the  hoistway  door.  Where  the  distance  is  exceeded, 
verify  that  space  guards  are  provided  on  either  car  or 
hoistway  doors,  and  that  sight  guards  are  provided  for 
horizontally  sliding  hoistway  doors.  Take  measurements 
to  confirm  compliance  with  these  requirements. 

1.7.2  Periodic  Test 

1.7.3  Acceptance 

Verify  that  the  car  door  or  gate  electric  contact  or  car 
door  interlock  is  inaccessible  from  inside  the  car.  Verify 
that  the  distance  from  the  face  of  the  car  door  or  gate 
to  the  face  of  the  hoistway  door  does  not  exceed  the 
Code  requirements  or  a  car  door  interlock  is  provided 
and  the  car  door  complies  with  the  structural  require- 
ments in  the  Code.  Verify  openings  in  vertically  sliding 
gates  do  not  exceed  the  Code  requirements.  Verify  two 
independent  suspension  means  are  provided  for  verti- 
cally sliding  car  doors  or  gates  and  weights  for  balancing 
or  closing  comply  with  the  Code  requirements.  Verify 
that  when  the  car  is  stopped  within  the  unlocking  zone 
and  power  is  cut  off  to  the  door  operator,  the  car  door 
and  connected  hoistway  doors  can  be  opened  by  hand. 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


1.7.4  References 

1.7.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  112.2a,  204.4, 204.5, 204.6, 210.2(q)/  and 
1001.2(a)(7). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.5.1.5.3,  2.13.2.1,  2.14.4,  2.14.5,  2.14.6, 
2.26.2  (2.26.2.15),  and  8.11.2.1.1(g). 

A17.3  —  Paragraphs  3.4.2  and  3.4.3;  and  Appendix  A. 

1.7.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  ~~  Rules  111.7(c)  {300.12),  112.2a  {300.13}, 
204.4  through  204.6  {301.7},  210. 2(q)  {306.4},  and 
1004.2(a)(7). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2,5.1.5.3  {3.5},  2.12.7.3  {3.12},  2.13.2.1  {3.13}, 
2.14.4  through  2.14.6  {3.14},  2.26.2  (2.26.2.15),  {3.26.4}, 
and  8.11.3.1.1(g). 

A17.3  —  Paragraphs  3.4.2  and  3.4.3  {4.2.3};  and 
Appendix  A. 

ITEM  1.8 
DOOR  CLOSING  FORCE 

1.8.1  Periodic  Inspections 

To  test  the  door  closing  force,  park  the  car  at  floor 
level  and  start  the  doors  in  the  closing  direction.  Allow 
the  doors  to  close  between  one-third  and  two-thirds  of 
their  normal  travel  and  stop  them.  Push  a  force  measur- 
ing device  with  a  range  appropriate  to  measure  30  lbf 
(133  N)  against  the  stopped  door,  removing  the  stop  so 
the  door  is  held  stationary  by  the  force  measuring 
device.  Slowly  back  off  on  the  device  until  the  point  the 
door  just  starts  to  move.  At  this  point,  the  door  and 
measuring  forces  are  in  equilibrium  and  the  force  can 
be  read. 

(io)    1.8.2  Periodic  Test:  Category  1  (Annual)  Test 

Check  the  closing  speed  of  horizontal  sliding  door  for 
compliance  with  kinetic  energy  requirement.  For  eleva- 
tors installed  under  A17.1-2000/B44-00  and  later  edi- 
tions of  the  Code,  and  for  elevators  with  this  data  on 
the  door  operator  data  plate,  verify  that  closing  time  in 
the  code  zone  is  not  less  than  the  minimum  closing  time 
shown  on  the  door  operator  data  plate. 

1.8.3  Acceptance 

(io)    1.8.4  References 

1.8.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  112.4(b),  1001.2(a)(8),  and  1002.2h. 

A17.1-2000/B44-00  through  2007  editions  — 
Requirements  2.13.4.2.3,  8.11.2.1.1(h),  2.13.4.2.4,  and 
8.11.2.2.8. 

A17.1a-2008/B44a-08  and  later  editions  — 
Requirement  8.6.4.19.8. 

A17.3  —  Paragraph  2.8.1. 


1.8.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  112.4(b),  301.7,  and  1004.2(a)(8). 

A17.1-2000/B44-00  through  2007  editions  — 
Requirements  2.13.4.2.3,  3.14,  2.13.4.2.4,  and 
8.11.3.1.1(h). 

A17.1a~2008/B44a-08  and  later  editions  — 
Requirement  8.6.5.14.3(g). 

A17.3  —  Paragraph  2.8.1  {Section  4.1}. 

ITEM  1.9 

POWER  CLOSING  OF  DOORS 

OR  GATES 

1.9.1  Periodic  Inspections 

Where  a  door  open  button  is  provided,  check  that 
when  depressed  and  the  door  is  closing  it  causes  the 
door  to  stop  or  to  stop  and  reopen.  Where  sequence 
closing  is  provided  on  a  vertically  sliding  door,  check 
its  operation. 

1.9.2  Periodic  Test 

1.9.3  Acceptance 

1.9.4  References 

1.9.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  112.3  and  1001.2(a)(9). 

A17.1-2000/B44-00      and      later     editions     — 
Requirements  2.13.3  and  8.11.2.1.1(1). 
A17.3  —  Paragraph  2.8.2. 

1.9.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  112.3  (300.13)  and  1004.2(a)(9). 

A17.1-2000/B44-00     and     later     editions     — 
Requirements  2.13.3  (3.13)  and  8.11.3.1. l(i). 
A17.3  —  Paragraph  2.8.2  (Section  4.1). 

ITEM  1.10 

POWER  OPENING  OF  DOORS 

OR  GATES 

1.10.1  Periodic  Inspections 

If  collapsible  gates  are  power  operated,  check  that 
power  opening  is  limited.  Check  finger  guards  on  col- 
lapsible gates. 

1.10.2  Periodic  Test 

(a)  5-Year  Test,  Advance  Power  Opening  (for  All \ld-2000 
and  earlier  editions);  Category  5  Test,  Advance  Power 
Opening  (for  A17.1-2000/B44-00  and  later  editions).  Verify 
that  power  opening  of  the  doors  can  occur  only  when 
the  car  is  within  18  in.  (457  mm)  of  the  landing.  In  the 
case  of  static  control,  installed  under  A17.1a-1988  and 
later  editions,  the  person  or  firm  performing  the  test 
must  demonstrate  that  power  is  not  applied  to  open  the 
doors  when  the  car  is  more  than  12  in.  (305  mm)  from 
the  landing.  Verify  that  the  car  is  stopped  or  substantially 


(io) 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


level  with  the  landing  before  the  hoistway  door  is  fully 
open.  Also,  see  Fig.  1.10.2. 

(b)  5-Year  Test  of  Leveling  Zone  and  Leveling  Speed  (for 
A17.1d-2000  and  Earlier  Editions);  Category  5  Test  of 
Leveling  Zone  (for  A17 .1-2000 /B 44-00  and  Later  Editions). 
Check  that  the  zone  in  which  the  leveling  device  will 
move  the  car  toward  the  landing  does  not  exceed  30  in. 
(762  mm)  for  an  automatic  device  or  10  in.  (254  mm) 
for  a  manual  device.  The  leveling  speed  is  not  permitted 
to  exceed  150  ft/min  (0.76  m/s). 

For  static  control  elevators,  installed  under 
A17.1a-1988  and  later  editions,  the  person  or  firm 
installing  or  maintaining  the  elevator  must  provide  a 
written  checkout  procedure,  and  demonstrate  to  the 
authority  having  jurisdiction  that  the  leveling  speed 
with  the  doors  open  is  limited  to  a  maximum  of 
150  ft/min  (0.76  m/s)  and  that  the  limiting  (or  speed 
monitor)  means  is  independent  of  the  operation  of  the 
normal  means  to  control  this  speed. 

1.10.2.1  Electric  Elevators.  5-Year  Test  of  Inner 
Landing  Zone  (for  A17. ld-2000  and  Earlier  Editions); 
Category  5  Test  of  Inner  Landing  Zone  (for  A17. 1-2000/ 
B44-00  and  Later  Editions).  On  static  control  elevators, 
installed  under  A17.1a-1988  and  later  editions,  the  per- 
son or  firm  installing  or  maintaining  the  equipment  is 
required  to  submit  a  written  procedure  and  demonstrate 
that  the  zone  in  which  the  car  can  move  with  the  doors 
open  is  no  more  than  3  in.  (76  mm)  above  or  below  the 
landing. 

1.10.2.2  Hydraulic  Elevators.  For  static  control  ele- 
vators, installed  under  A17.1a-1988  and  later  editions, 
the  person  or  firm  installing  or  maintaining  the  elevator 
must  provide  a  written  checkout  procedure,  and  demon- 
strate to  the  authority  having  jurisdiction  that  the  level- 
ing speed  with  the  doors  open  is  limited  to  a  maximum 
of  150  ft/min  (0.76  m/s)  and  that  the  limiting  (or  speed 
monitor)  means  is  independent  of  the  operation  of  the 
normal  means  to  control  this  speed. 

1.10.3  Acceptance 

1.10.4  References 

(10)  1.10.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  111.12,  210.1e,  210.9c,  1001.2(a)(10), 
1002.3g,  1002.3h,  and  1002.3L 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  (NR  111.12),  2.26.1.6,  2.26.9  (2.26.9.3), 
8.11.2.1.1(3),  8.11.2.3.7,  8.11.2.3.8,  c8. 11.2. 3. 8,  and 
8.11.2.3.9. 

1.10.4.2  Hydraulic  Elevators.  A 1 7. ld-2000  and  ear- 
lier editions  —  Rules  111.5  {300.12},  210. le,  210.9(c), 
306.3,  and  1004.2(a)(10). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.12.5  {3.12},  2.26.1.6,  2.26.9  (2.26.9.3), 
3.26.3,  and  8.11.3.1. l(j). 


ITEM  1.11 

CAR  VISION  PANELS  AND  GLASS 

CAR  DOORS 

1.11.1  Periodic  Inspections 

If  the  glass  in  the  door  panel  is  less  than  60%,  or 
80%  for  elevators  installed  under  A17.1b-1989  through 
A17.1a-1994,  of  the  total  surface  area  of  the  door,  it  is 
a  vision  panel  and  must  conform  to  those  requirements. 
Car  vision  panels  are  required  to  be  of  wire  or  laminated 
glass  and  have  a  maximum  area  of  144  in.2  (0.093  m2)  and 
maximum  panel  width  of  6  in.  (152  mm).  A17.1d-1970 
through  A 17. 1-2004,  in  addition  to  the  above  require- 
ments, required  glazing  materials  to  conform  to 
ANSI  Z97.1  or  16  CFR  Part  1201.  A17.1a-2005, 
A17.1S-2005,  and  later  editions  required  glazing  materi- 
als to  conform  to  16  CFR  Part  1201.  These  Standards 
require  that  the  glazing  material  be  marked  as  follows: 
ANSI  Z97. 1-1984  or  16  CFR  Part  1201;  Manufacturer's 
mark  or  designation.  A17.1a-1997  through  A17.1d-2000 
required  vision  panels  to  comply  with  16  CFR  Part  1201 
or  be  made  of  wire  glass.  A17.1b-1989  and  later  editions 
require  glass  doors  to  be  provided  with  laminated  glass 
that  complies  with  ANSI  Z97.1  and  16  CFR  Part  1201. 
In  addition,  in  Canada  safety  glass  or  safety  plastic  is 
permitted  in  A17.1-2000.  Check  that  the  leading  edge 
of  the  panels  is  not  made  out  of  glass  and  that  the  glass 
surface  on  the  car  side  is  substantially  flush. 

Verify  that  the  glass  is  the  right  type  (wired  or  lami- 
nated), is  not  cracked  or  broken,  and  is  marked  with 
glazing  standard.  Since  ANSI  Z97.1  or  16  CFR  Part  1201 
covers  many  types  of  glazing  materials,  the  required 
marking  does  not  assure  that  the  glazing  is  laminated 
glass.  If  laminated  glass  is  tapped  lightly  with  the  edge 
of  a  coin,  the  sound  will  be  dampened  and  different 
from  nonlaminated  glass. 

1.11.2  Periodic  Test 

1.11.3  Acceptance 

When  a  glass  door  is  provided,  check  the  type  of  glass, 
thickness,  minimum  surface  area,  and  edging. 

1.11.3.2  Hydraulic  Elevators.  When  80%  of  the  sur- 
face area  of  the  door  is  glass,  it  is  classified  as  a  glass  door. 

1.11.4  References 

1.11.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  204.2e,  204.5i,  and  1001.2(a)(ll). 

A17.1-2000/B44-00      and      later     editions     — 
Requirements  2.14.2.5,  2.14.5.8,  and  8.11.2.1. l(k). 
A17.3  —  Paragraphs  3.4.2  and  3.4.3. 

1.11.4.2  Hydraulic  Elevators.  A 17. ld-2000  and  ear- 
lier editions  —  Rules  204. 2e  and  204.5i  (301.7),  and 
1004.2(a)(ll). 

A17.1-2000/B44-00     and     later     editions     — 
Requirements  2.14.2.5,  2.14.5.8  (3.14),  and  8.11.3.1.1(k). 
A17.3  —  Paragraphs  3.4.2  and  3.4.3  {4.2.3}. 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Fig.  1.10.2    Door  Operation  Relative  to  Car  Position 


66  in. 


Distance 
car  sill  is 
above  landing 


Landing 


Distance 
car  sill  is 
below  landing 


Truck  Zone 

Car  allowed  to  move  with  doors  open 
(Requirements  2.12  and  2.26.1.6) 


30  in. 


Landing  Zone  (Automatic  Operation  Elevators) 
Horizontal  slide  or  swing  doors  must  be  closed 
mechanically  when  outside  of  this  zone 
(Requirements  1.3  and  2.11.3) 


Unlocking  Zone  (Maximum) 

Opening  of  car  and/or  hoistway  doors  permitted 

(Requirements  2.11.6,  2.12,  and  2.14.5.7) 


18  in. 


12  in. 


10  in. 


Inner  Landing  Zone  (Static  Controls) 

Car  may  not  move  if  stopped  outside  of  this  zone 

unless  doors  are  fully  closed 

(Requirement  2.26.1.6.7) 


Unlocking  Zone  (Minimum) 

Manual  opening  of  car  and  hoistway  doors  required 

(Requirements  2.12  and  2.14.5.7) 


3  in. 


1  in. 


Landing 


1  in. 


3  in. 


10  in. 


12  in. 


18  in. 


30  in. 


Anticreep  Leveling  Zone  (Hydraulic  Elevators) 
Anticreep  leveling  device  shall  maintain  car  within 
this  zone 
(Requirement  3.26.3) 


Leveling  Zone  (Manual  Leveling)  Power  opening  of 

doors  permitted 

(Requirements  2.12.3.1,  2.13.2.1,  and  2.26.1.6) 


Leveling  Zone  (Automatic  Leveling  With  Static  Controls) 
Initiation  of  power  opening  of  doors  permitted 
(Requirements  2.12.3.1,  2.13.2,  and  2.26.1.6) 


Leveling  Zone  (Automatic  Leveling  Without  Static  Controls) 
Door  opening  cannot  occur  outside  of  unlocking  zone. 
Initiation  of  power  opening  of  doors  permitted 
(Requirements  2.12.3.1,  2.13.2,  and  2.26.1.6) 


GENERAL  NOTES: 

(a)  Refer  to  Requirement  numbers  for  details. 

(b)  1  in.  =  25.4  mm 

(c)  Refer  to  applicable  edition  of  the  Code. 


10 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


ITEM  1.12 
CAR  ENCLOSURE 

(10)    1.12.1  Periodic  Inspections 

Verify  that  the  car  enclosure  is  structurally  sound  and 
is  securely  fastened  to  the  platform.  Verify  that  capacity 
plates  and  any  required  certificates  are  posted  in  the 
car.  Note  any  evidence  of  alterations  or  additions  to  the 
car  that  have  materially  changed  the  car  weight.  Also, 
note  any  alteration  to  car  enclosure,  including  decorative 
panels.  (See  Item  1.12.3.) 

(a)  Freight  elevators  installed  under  A17.1a-1982  and 
later  editions  verify  that  signs  specifying  the  class  of 
loading  are  in  place  and  the  loading  imposed  on  the 
elevator  is  as  specified  on  the  sign.  Verify  that  signs 
restricting  passenger  use  are  posted. 

(b)  Freight  elevators  installed  under  A17. 1-1955 
through  Al 7. 1-1 981  are  required  to  have  one  of  the  fol- 
lowing signs: 

(1)  "THIS  ELEVATOR  DESIGNED  FOR  GENERAL 
FREIGHT  LOADING/7 

(2)  "THIS  ELEVATOR  DESIGNED  FOR  MOTOR- 
VEHICLE  LOADING." 

(3)  "THIS  ELEVATOR  DESIGNED  FOR  LOADED 

INDUSTRIAL      TRUCK      WEIGHING      LB 

MAXIMUM." 

On  elevators  not  permitted  to  carry  passengers,  the 
following  additional  sign  must  be  posted:  "THIS  IS  NOT 
A  PASSENGER  ELEVATOR,  NO  PERSONS  OTHER 
THAN  THE  OPERATOR  AND  FREIGHT  HANDLERS 
ARE  PERMITTED  TO  RIDE  ON  THIS  ELEVATOR." 

The  above  sign  regarding  passengers  is  also 
required  by  A17.3. 

In  elevators  permitted  to  carry  employees,  the  sign 
should  read:  "NO  PASSENGERS  EXCEPT  EMPLOYEES 
PERMITTED." 

(c)  For  freight  elevators  installed  under  A 17. 1-1984 
and  later  editions,  check  the  Code  for  required  sign 
wording. 

(d)  For  passenger  elevators  and  freight  elevators 
installed  under  A17.1-1987  and  later  editions  that  are 
permitted  to  carry  passengers,  check  to  see  that  there 
are  no  openings,  other  than  those  required  for  signal, 
operating  or  communication  equipment,  entrances, 
vision  panels,  emergency  exits,  or  ventilation.  In  addi- 
tion, A17.1-2000  and  later  editions  permit  access  panels 
for  maintenance  and  cleaning  of  glass  on  observation 
elevators. 

(e)  Napped,  tufted,  woven,  looped,  or  similar  materi- 
als are  allowed  on  car  enclosure  walls  if  they  meet  the 
test  requirements.  Test  reports  should  be  available  to 
indicate  compliance  with  acceptance  criteria. 

(f)  Note  any  equipment  inside  cars  other  than  that 
used  for  the  operation  of  the  elevator.  The  Code  permits 
lighting,  heating,  ventilating,  and  air-conditioning 
devices  to  be  installed  inside  all  cars,  and  permits  con- 
veyor tracks,  lift  hooks,  and  support  beams  mounted 


in  the  ceiling  of  passenger  elevators.  Check  structural 
supports  and  clearances  from  floor. 

(g)  A17.1-1990  and  later  editions  required  the  car  to 
have  an  identification  number  on  the  car  control  station 
where  more  than  one  elevator's  machinery  is  in  a 
hoistway  or  machine  room. 

(h)  A17.1a-1991  and  later  editions  required  that  pan- 
els be  attached  to  the  enclosure  with  tamper-resistant 
fasteners,  or  when  the  panels  are  removed  any  perfora- 
tions greater  than  \  in.  (13  mm)  diameter  be  guarded. 

(i)  Perforations  in  car  enclosures  for  freight  elevators 
installed  under  A17.1d-2000  and  earlier  editions  should 
reject  a  ball  1V2  in.  (38  mm)  in  diameter. 

(j)  Check  that  a  written  procedure  is  available  for 
cleaning  inside  the  hoistway  for  observation  elevators. 
Verify  that  the  elevator  will  not  operate  unless  all  access 
panels  are  in  the  closed  and  locked  position. 

1.12.2  Periodic  Test 

1.12.3  Acceptance 

Check  the  headroom  in  the  car.  Check  laminated  glass 
or,  in  jurisdictions  enforcing  NBCC,  safety  glass  or  safety 
plastic  for  the  required  markings.  Where  glass  is  used 
in  wall  panels,  check  that  the  opening  is  guarded.  Check 
access  panels  for  cleaning  transparent  enclosures,  when 
provided. 

NOTE:  Bonded  glass  is  considered  equivalent  to  laminated  glass 
since  it  must  meet  testing  requirements  of  ANSI  Z97.1  or 
16  CFR  Part  1201;  it  will  bond  fragments  and  retain  broken  glass, 
and  it  prohibits  the  use  of  film  coatings  (organic-coated  glass)  that 
is  easily  damaged,  which  would  render  them  ineffective. 

Check  that  the  car  enclosure  material  (exposed  to  the 
car  interior  or  the  hoistway)  is  metal,  laminated  glass, 
or  has  been  type-tested  in  its  end-use  configuration  and 
that  the  flame  spread  smoke  contribution,  vertical  burn, 
test  and  critical  radiant  flux  of  the  enclosure  material 
conform  to  the  Code  requirements.  Material  V4  in. 
(6.4  mm)  or  less  in  thickness  can  be  installed  over  an 
existing  car  enclosure,  without  type  testing  in  the 
end-use  configuration.  The  flame  spread  rating  for  the 
added  material  and  adhesive  is  more  severe  than  that 
required  for  a  new  car  enclosure  tested  in  its  end-use 
configuration.  If  in  doubt,  request  a  copy  of  the  test 
report. 

Verify  that  ventilation  openings  are  properly  located, 
sized,  and  where  required,  guarded  against  through 
openings.  Check  for  the  minimum  clear  headroom. 

1.12.4  References 

1.12.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  (NR  2.7.5.1.4),  204,  204.1b,  204.1h, 
(NR  2.14.2.6),  207.2b,  207.4,  207.5,  211.9,  1104,  1206.9, 
1202.5,  and  1001.2(a)(12);  and  Sections  204.2b, 
(NR  2.14.2.6),  and  (NR  8.1). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.7.5.1.4,  2.14,  2.14.1.2,  2.14.1.8,  2.14.2.6, 


11 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


2.16.2.2,  2.16.4,  2.16.5, 2.29.1,  8.3.7,  8.6.10.3,  8.7.2.14,  and 
8.11.2.1.1(1);  and  requirements  2.14.2.2,  2.14.2.6,  and  8.1. 

A17.3  —  Paragraphs  3.4.1  and  3.7.5. 

NFPA  70  or  CSA  C22.1,  as  applicable. 

1.12.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Sections  204.1b,  204. lh  {Rule  301.7},  and 
1104;  and  Rules  204. 2d  {301.7},  211.9  {306.11}, 
1004.2(a)(12),  1202.5,  and  1203.2e. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.14  (3.14)  and  8.3.7;  and  requirements 
2.29.1  {3.27},  8.11.3.1.1(1),  8.7.2.14,  and  8.7.3.13. 

A17.3  —  Paragraphs  3.4.1  {4.2.3}  and  3.7.5  {4.2.4}. 

ITEM  1.13 
EMERGENCY  EXIT 

1.13.1  Periodic  Inspections 

(10)  1.13.1.1      Determine  that  top  emergency  exit  panels 

are  in  place  and  not  obstructed  (see  Item  3.8);  and  deter- 
mine whether  on  elevators  installed  under  A17. 1-2000/ 
B44-00  and  earlier  editions,  side  emergency  exit  doors 
are  closed  and  locked.  Check  the  electric  contact  on 
the  side  emergency  exit  doors.  Check  that  the  key  for 
unlocking  the  side  emergency  exit  is  available  to  elevator 
personnel  only.  Verify  that  any  side  emergency  exit  door 
is  so  hinged  as  to  swing  in,  that  it  can  be  opened  from 
the  inside  only  by  using  a  special-shaped  removable  key, 
that  it  can  be  opened  from  the  outside  by  means  of  a 
nonremovable  handle,  and  that  it  is  provided  with  a 
properly  functioning  contact  to  cause  power  to  be 
removed  from  the  driving  machine  and  brake  when 
opened.  Side  emergency  exits  were  required  on  passen- 
ger elevators  installed  to  A17. 1-1955  through  1990,  and 
were  permitted  on  passenger  and  freight  elevators 
installed  or  altered  to  A17.1a~1991  through  A17. 1-2000/ 
B44-00;  where  there  is  an  adjacent  elevator  within  30  in. 
(762  mm)  and  no  intervening  obstructions.  Side  emer- 
gency exits  were  required  on  hydraulic  passenger  eleva- 
tors with  safeties  installed  to  A17.1-1955  through  1995, 
and  were  permitted  on  passenger  and  freight  elevators 
installed  to  A17.1-1996  and  later  editions.  A17.1a-2002 
and  later  editions  prohibit  side  emergency  exits. 

1.13.2  Periodic  Test 

1.13.3  Acceptance 

1.13.4  References 

(10)  1.13.4.1   Electric  Elevators.    A17.1d-2000  and  earlier 

editions  — Rules  204.1e,  204.1),  204.2d,  and  1001.2(a)(13). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.14.1.5,  2.14.1.10,  2.14.2.4,  8.1.2,  8.6.10.2 
(not  applicable  in  jurisdictions  enforcing  the  NBCC), 
and  8.11.2.1.1(m). 

A17.3  —  Paragraph  3.4.4. 

1.13.4.2  Hydraulic  Elevators.  A 1 7. ld-2000  and  ear- 
lier editions  —  Rules  204.1J  {301.7}  and  1004.2(a)(13). 


A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.14.1.10,  3.14,  8.1.2,  8.6.10.2,  and 
8.11.3.1. l(m). 

A17.3  —  Paragraph  3.4.4  {4.2.4}. 

ITEM  1.14 
VENTILATION 

1.14.1  Periodic  Inspections 

If  ventilating  fans  are  installed  inside  the  car,  verify 
that  they  are  properly  guarded,  adequately  supported, 
and  securely  fastened  in  place  and  not  obstructing  the 
emergency  exit.  Ventilating  fan  blowers,  if  provided,  are 
to  be  located  above  the  car  ceiling  or  outside  the  car 
enclosure. 

Check  that  observation  elevators  exposed  to  direct 
sunlight,  which  are  installed  under  A17.1a-1985  and 
later  editions,  are  provided  with  forced  ventilation  and 
that  an  emergency  power  source  is  on  each  car  that  is 
capable  of  operating  the  ventilation  for  1  h.  The  mini- 
mum capacity  for  this  ventilation  is  one  air  change  per 
minute. 

1.14.2  Periodic  Test 

1.14.3  Acceptance 

1.14.4  References 

1.14.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  204.1i,  204.2c,  204.3c,  and  1001.2(a)(14). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.14.1.9.1(f),  2.14.2.3,  2.14.3.3,  and 
8.11.2.1.1(n). 

NFPA  70  or  CSA  C22.1,  as  applicable. 

1.14.4.2  Hydraulic  Elevators.  A 17. ld-2000  and  ear- 
lier editions  —  Rules  204.1i,  204.2c,  and  204.3c  {301.7}, 
and  1004.2(a)(14). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.14.1.9.1(f),  2.14.2.3,  and  2.143.3  {3.14}, 
and  8.11.3.1.1(n). 

NFPA  70  or  CSA  C22.1,  as  applicable. 

ITEM  1.15 
SIGNS  AND  OPERATING  DEVICE  SYMBOLS 

1.15.1  Periodic  Inspections 

Check  that  symbols  are  substituted  for,  or  used  in 
conjunction  with,  the  required  wording  for  operating 
devices  on  elevators  installed  under  A17.1a~1979  and 
later  editions  and  that  the  main  floor  is  identified  by 
a  star. 

1.15.2  Periodic  Test 

1.15.3  Acceptance 

1.15.4  References 

1.15.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  210.13  and  1001.2(a)(15). 


(io) 


12 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.26.12  and  8.11.2.1.1(o). 

1.15.4.2  Hydraulic  Elevators.    A17.1d-2000  and  ear- 
lier editions  —  Rules  210.13  1306.12}  and  1004.2(a)(15). 
A17.1-2000/B44-00  and  later  editions  -  Requirements 
2.26.12  (NR  306.12)  and  8.11.3.1.1(o). 

ITEM  1.16 
RATED  LOAD,  PLATFORM  AREA,  AND  DATA  PLATE 

1.16.1  Periodic  Inspections 

Check  that  the  data  (capacity)  plate  is  installed  inside 
the  car. 

1.16.2  Periodic  Test 

1.16.3  Acceptance 

Measure  the  inside  dimensions  of  the  car  36  in. 
(914  mm)  above  the  floor,  inside  of  any  panels  or  wall 
surfaces,  but  exclusive  of  any  handrails  and  space  for 
doors,  and  compute  the  inside  net  platform  area.  Com- 
pare this  area  with  the  maximum  area  permitted  for  the 
rated  load.  The  Code  includes  limitations  of  inside  net 
platform  area  in  relation  to  the  rated  load  for  freight 
elevators  for  three  classes  of  loading,  including  special 
requirements  where  the  loading  is  by  industrial  trucks. 
Determine  that  signs,  and  capacity  and  data  plates  are 
provided. 

1.16.4  References 

1.16.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Section  207  and  Rule  1001.2(a)(16). 

A17.1-2000/B44-00     and     later     editions     — 
Requirements  2.16  and  8.11.2.1. l(p). 
A17.3  —  Section  3.7. 

1.16.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Section  207  {Rule  301.10},  and  Rule 
1004.2(a)(16). 

A17.1-2000/B44-00      and      later      editions     — 
Requirements  2.16  {3.16)  and  8.11.3.1. l(p). 
A17.3  —  Section  3.7  {para.  4.2.4}. 


ITEM  1.17 
STANDBY  POWER  OPERATION 

1.17.1  Periodic  Inspections 

Visually  inspect  transfer  switch  and  means  of  transfer 
for  evidence  of  damage  or  misuse.  Verify  that  the  key 
used  to  operate  the  selection  switch  is  adequately 
controlled. 

1.17.2  Periodic  Test 

1.17.2.1   Electric   Elevators:   Yearly  Test   (for 
A17.1d-2000  and  Earlier  Editions);  Category  1  Test  (for 


A17.1-2000/B44-00  and  Later  Editions).  Have  the  ele- 
vators) taken  out  of  normal  service  and  placed  at  the 
floor  where  the  ELEVATOR  EMERGENCY  POWER 
selector  switch  is  located,  if  provided.  Otherwise,  have 
the  elevator(s)  taken  out  of  normal  service  and  placed 
at  the  bottom  terminal.  Have  the  system  transferred,  by 
the  responsible  party,  to  standby  or  emergency  power. 
Verify  that  the  ELEVATOR  EMERGENCY  POWER  selec- 
tor switch  (automatic  sequence  operation  override 
switch),  if  provided,  functions  as  required  to  manually 
select  each  elevator,  one  at  a  time,  when  on  standby  or 
emergency  power.  Verify  that  the  elevator  selected  can 
be  taken  out  of  service  with  the  ELEVATOR 
EMERGENCY  POWER  selector  switch  only  when  the 
elevator  is  stopped.  Operate  each  elevator  selected  to 
be  operated  on  standby  or  emergency  power,  one  at  a 
time,  with  no  load  in  the  car.  Make  several  trips  and 
stops  checking  for  proper  operation.  Verify  that  the  ele- 
vator is  running  at  normal  speed  especially  in  the  up 
direction  (speed  must  not  attain  the  governor  electrical 
overspeed  trip  setting  or  125%  of  rated  speed  in  both 
directions,  whichever  is  the  lesser).  If  a  separate  power 
absorption  means  such  as  a  resistor  bank  is  used  to 
absorb  regenerative  power,  verify  that  it  is  provided  on 
the  load  side  of  each  elevator  disconnect  switch,  or  a 
common  resistor  load  bank  is  provided  on  the  elevator 
feeder.  Have  the  system  transferred,  by  the  responsible 
party,  back  to  normal  power  and  verify  that  the  eleva- 
tors) tested  operate  properly  in  normal  service. 

1.17.2.2  Hydraulic  Elevators:  Yearly  Test  (for 
A17.1d-2000  and  Earlier  Editions);  Category  1  Test  (for 
A17.1-2000/B44-00  and  Later  Editions).  Have  the  ele- 
vators) taken  out  of  normal  service  and  placed  at  the 
floor  where  the  ELEVATOR  EMERGENCY  POWER 
selector  switch  is  located,  if  provided.  Otherwise,  have 
the  elevator(s)  taken  out  of  normal  service  and  placed 
at  the  bottom  terminal.  Have  the  system  transferred,  by 
the  responsible  party,  to  standby  or  emergency  power. 
Verify  that  the  ELEVATOR  EMERGENCY  POWER  selec- 
tor switch  (automatic  sequence  operation  override 
switch),  if  provided,  functions  as  required  to  manually 
select  each  elevator,  one  at  a  time,  when  on  standby  or 
emergency  power.  Verify  that  the  elevator  can  be  taken 
out  of  service  with  the  ELEVATOR  EMERGENCY 
POWER  selector  switch  only  when  that  elevator  is 
stopped.  Operate  each  elevator  designated  to  be  oper- 
ated on  the  standby  or  emergency  power,  one  at  a  time, 
with  no  load  in  the  car.  Make  several  trips  and  stops 
checking  for  proper  operation.  Have  the  system  trans- 
ferred, by  the  responsible  party,  back  to  normal  power 
and  verify  that  the  elevator(s)  tested  operate  properly 
in  normal  service. 

1.17.3  Acceptance 

In  addition  to  the  test  outlined  in  Item  1.17.2.1,  verify 
that  the  ELEVATOR  EMERGENCY  POWER  selector 


13 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


switch  (automatic  sequence  operation  override  switch), 
if  provided,  is  key  operated  or  behind  a  locked  cover. 
Verify  that  the  key  is  available  to  only  emergency  person- 
nel and  complies  with  Group  3  security  level. 

(10)         1.17.3.1  Electric  Elevators 

(a)  Verify  with  the  authorized  personnel  if  there  are 
other  building  loads  used  to  absorb  elevator  regenera- 
tive power,  and  that  they  are  automatically  connected 
to  the  standby  or  emergency  power  system  when  the 
elevator  is  transferred  to  standby  or  emergency  power. 
If  other  building  loads  used  to  absorb  elevator  regenera- 
tive power  are  not  automatically  connected,  verify  that 
a  separate  regenerative  power  absorption  means,  such 
as  a  resistor  load  bank,  is  provided  on  the  load  side  of 
each  elevator  disconnect  switch,  or  a  common  resistor 
load  bank  is  provided  on  the  elevator  feeder. 

(b)  Have  the  elevator  taken  out  of  normal  service  and 
placed  at  the  top  terminal  with  rated  load  in  the  car  for 
freight  elevators  or  125%  of  rated  load  for  passenger 
elevators  and  freight  elevators  that  are  permitted  to  carry 
passengers  in  the  car.  Have  the  system  transferred,  by 
the  responsible  party,  to  standby  or  emergency  power 
as  in  Item  1.17.2.1.  For  each  elevator  designated  to  be 
operated  on  the  standby  or  emergency  power,  run  the 
elevator  down,  one  at  a  time,  nonstop,  to  the  bottom 
terminal.  The  speed  of  each  operating  elevator  must  not 
attain  governor  electrical  over  speed  trip  or  125%  of  rated 
speed,  whichever  is  the  lesser.  Then  for  passenger  eleva- 
tors and  freight  elevators  that  are  permitted  to  carry 
passengers  in  the  car,  reduce  the  load  in  the  car  to  rated 
load  (full  load)  and  run  the  elevator,  one  at  a  time, 
up  and  down  with  several  stops,  checking  for  proper 
operation.  Have  the  system  transferred,  by  the  responsi- 
ble party,  back  to  normal  power  and  verify  that  the 
elevators  tested  operate  properly  in  normal  service. 

1.17.3.2  Hydraulic  Elevators.  The  testing  of  hydrau- 
lic elevators  is  as  specified  in  Item  1.17.3.1(b)  with  the 
exception  that  100%  of  the  load  is  used. 

1.17.4  References 

1.17.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  207.8,  210.10,  211.2,  1001.2(a)(17), 
1002.2g,  and  1002.3e. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.16.8,  2.26.10,  2.27.2,  8.11.2.1. l(q), 
8.11.2.2.7,  and  8.11.2.3.5. 

1.17.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  211.2  {306.11},  1002.2g  {1005.2c(6)}, 
and  1004.2(a)(17). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.27.2  {3.27},  8.11.2.2.7  {8.11.3.2.3(f)},  and 
8.11.3.1.1(q). 

A17.3  —  Paragraph  3.11.2  {4.7.8}. 


ITEM  1.18 

RESTRICTED  OPENING  OF  CAR  OR  HOISTWAY 

DOORS 

1.18.1  Periodic  Inspections 

(a)  All  passenger  elevators  installed  under 
A17.1b-1980  and  later  editions  must  comply  with 
restricted  opening  of  the  hoistway  or  car  doors.  When 
the  car  is  outside  a  specified  zone,  this  requires  that 
either  the  hoistway  door  or  car  door  can  be  opened  no 
more  than  4  in.  (102  mm)  from  inside  the  car  but  the 
car  door  can  be  opened  from  outside  the  car  without 
special  tools.  The  specified  zone  in  which  restricted 
opening  applies  depends  on  when  an  elevator  was 
installed  as  follows: 

(1)  On  elevators  installed  under  A17.1tM980 
through  A17.1a-1982,  the  specified  zone  is  outside  the 
landing  zone  [18  in.  (457  mm)  above  or  below  the 
landing]. 

(2)  On  elevators  installed  under  A17.1b-1983 
through  A17.1a-1988  and  those  that  must  comply  with 
A17.3,  the  specified  zone  is  outside  the  unlocking  zone. 
The  unlocking  zone  is  a  distance  set  by  the  manufacturer 
between  0  in.  and  18  in.  (457  mm)  above  and  below  the 
landing.  (An  unlocking  zone  is  not  required.) 

(3)  On  elevators  installed  under  A17.1b-1989  and 
later  editions,  the  doors  must  be  able  to  be  opened  from 
0  in.  to  3  in.  (76  mm)  above  and  below  the  landing  [an 
unlocking  zone  is  required  and  doors  may  be  opened 
up  to  18  in.  (457  mm)  above  and  below  the  landing].  The 
car  or  hoistway  door  must  meet  the  restricted  opening 
requirements  when  the  car  is  more  than  18  in.  (457  mm) 
above  and  below  the  landing. 

(b)  Some  manufacturers  comply  with  this  by  locking 
the  car  door  rather  than  the  hoistway  door.  Some  manu- 
facturers incorporate  the  locking  into  the  door  operator, 
and  some  install  vanes  or  other  mechanisms  on  the  doors 
and  hoistway  to  achieve  compliance.  Follow  the  proce- 
dure below  to  verify  compliance  with  this  requirement. 

(1)  For  elevators  installed  under  A17.1b-1980  and 
later  editions  and  elevators  required  to  comply  with 
A17.3,  have  the  car  stopped  at  a  point  beyond  18  in. 
(457  mm)  above  and  then  below  the  landing.  With  the 
power  off,  attempt  to  manually  open  the  car  door.  If  the 
car  door  opens  more  than  4  in.  (102  mm),  the  hoistway 
door  must  not  open  more  than  4  in.  (102  mm)  from 
inside  the  car  with  the  car  in  any  position  more  than 
18  in.  (457  mm)  above  or  below  the  landing. 

(2)  For  elevators  installed  under  A17.1b-1989  and 
later  editions,  follow  the  previous  procedure.  If  found 
satisfactory,  have  the  car  stopped  at  the  3  in.  (76  mm) 
point  and  verify  that  the  doors  can  be  manually  opened. 

(3)  Both  of  the  previous  checks  will  only  be 
required  at  one  or  two  landings  if  the  restricted  opening 
mechanism  can  be  inspected  from  the  car  top. 


(io) 


14 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


1.18.2  Periodic  Test 

1.18.3  Acceptance 

See  Fig.  1.10.2. 

1.18.4  References 

1.18.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  111.12  and  1001.2(a)(18). 

A17.1-2000/B44-00     and     later     editions     — 
Requirements  (NR  111.12)  and  8.11.2.1.1(r). 
A17.3  —  Paragraph  2.7.4. 

1.18.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  111.5  {300.12)  and  1004.2(a)(18). 

A17.1-2000/B44-00      and      later      editions     — 
Requirements  2.12.5  (3.12}  and  8.11.3.1.1(r). 
A17.3  —  Paragraph  2.7.4  {Section  4.1}. 

ITEM  1.19 
CAR  RIDE 

1.19.1  Periodic  Inspections 

Operate  the  car  at  normal  operation  speed  from  one 
terminal  landing  to  the  other,  listen  for  unusual  noise, 
and  observe  whether  there  is  excessive  or  irregular 
motion  of  the  car,  which  may  indicate  that  the  car  or 
counterweight  guide  rails  are  not  properly  aligned.  If 
such  motion  occurs,  when  on  top  of  the  car,  check  for 
loose  or  worn  guide  shoes  or  rollers  and  proper  align- 
ment of  the  guide  rails. 

1.19.2  Periodic  Test 

1.19.3  Acceptance 

1.19.4  References 

1.19.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Section  200;  and  Rules  203.2  and 
1001.2(a)(19). 


A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.23,  2.15.2,  and  8.11.2.1.1(s). 

1.19.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  301.1a,  301.6,  1004.2(a)(19),  and 
1206.1a  {1206.5a}. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  3.23.1,  3.15,  8.11.3.1.1(s),  and  8.6.1.6.2 
{8.6.5}. 


ITEM  1.20 
EARTHQUAKE  INSPECTION  AND  TESTS 
(SEISMIC  RISK  ZONE  2  OR  GREATER) 

1.20.1  Periodic  Inspections 

Verify  that  the  top  emergency  exit  is  secured  with  a 
spring  return  cylinder  lock  and  can  be  opened  with  a 
key  from  inside  the  car.  Verify  that  the  key  is  available 
only  to  authorized  personnel.  Where  hoistway  access 
key  is  used  for  this  purpose,  it  shall  be  Group  1  Security. 

NOTE:     Hoistway  access  key  is  permitted  to  unlock  the  top  emer- 
gency exit. 

1.20.2  Periodic  Test 

1.20.3  Acceptance 

Verify  proper  operation  when  top  exit  is  open  in  seis- 
mic risk  zone  2  or  greater. 

1.20.4  References 

A17.1-1993  through  A17.1d-2000  editions  —  Rule 
2406. 

A17.1-2000/B44-00  and  later  editions  — 
Requirement  8.4. 


(10) 


15 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Part  2 
Elevator  —  Machine  Room 


ITEM  2.1 
ACCESS  TO  MACHINE  SPACE 

2.1.1  Periodic  Inspections 

(a)  Check  that  permanent,  safe,  and  convenient  means 
of  access  to  machine  rooms  and  machinery  spaces  have 
been  provided  and  maintained.  Check  stairways  and 
ladders  to  see  they  are  stable  and  secure. 

(b)  Check  that  the  access  door  is  maintained  in  the 
closed  and  locked  position.  It  must  be  self-closing  and 
openable  from  the  inside  without  a  key  For  elevators 
installed  under  A17.1-1978  and  later  editions,  also  check 
that  the  door  is  self-locking. 

2.1.2  Periodic  Test 

2.1.3  Acceptance 

2.1.3.1  Electric  Elevators.  Check  that  access  to  the 
machine  room  meets  the  accessibility  requirements  of 
the  Code.  For  access  doors  required  to  have  fire- 
protection  ratings,  check  for  proper  labeling.  Access  to 
the  machine  room  includes  passage  from  the  top  build- 
ing floor  to  the  machine  room. 

2.1.3.2  Hydraulic  Elevators.  Check  that  access  to 
the  machine  room  meets  the  accessibility  requirements 
of  the  Code.  For  access  doors  required  to  have  fire- 
protection  ratings,  check  for  proper  labeling. 

2.1.4  References 

2.1.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  101.1a,  101.3a,  101.3b,  101.3c,  101.3d, 
and  1001.2(b)(1). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.7.1.1,  2.7.3.1,  2.7.3.2,  2.7.3.3,  2.7.3.4,  and 
8.11.2.1.2(a). 

A17.3  —  Paragraph  2.2.2. 

NFPA  70  or  CSA  C22.1,  as  applicable. 

2.1.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  300.1,  300.2,  and  1004.2(b)(1). 

A17.1-2000/B44-00     and     later     editions     — 
Requirements  3.1,  3.7,  and  8.11.3.1.2(a). 
A17.3  —  Paragraph  2.2.2  {Section  4.1}. 
NFPA  70  or  CSA  C22.1,  as  applicable. 


ITEM  2.2 
HEADROOM 

2.2.1  Periodic  Inspections 

2.2.2  Periodic  Test 

2.2.3  Acceptance 

Verify  that  machine  and  control  rooms  have  the  mini- 
mum overhead  clearances.  Clear  headroom  measure- 
ments are  taken  from  the  floor  to  the  bottom  of  the 
lowest  obstruction  below  the  ceiling  (e.g.,  wiring  race- 
ways, conduit,  beams). 

2.2.4  References 

2.2.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  101.4  and  1001.2(b)(2). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.7.4  and  8.11.2.1.2(b). 

2.2.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  101.4  {300.2}  and  1004.2(b)(2). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.4.7  {3.7}  and  8.11.3.1.2(b). 

ITEM  2.3 
LIGHTING  AND  RECEPTACLES 

2.3.1  Periodic  Inspections 

Check  machine  room  for  adequate  lighting.  For  eleva- 
tors installed  under  A17.1a-1988  and  later  editions, 
check  that  a  duplex  receptacle  has  been  provided  in 
the  machine  room  and  machinery  spaces,  and  that  it  is 
operable. 

2.3.2  Periodic  Test 

2.3.3  Acceptance 

2.3.4  References 

2.3.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  101.5a,  101.5c,  and  1001.2(b)(3). 

A17.1-2000/B44-00     and     later     editions     — 
Requirements  2.7.5.1,  (NR  101.5c),  and  8.11.2.1.2(c). 
A17.3  —  Paragraph  2.2.3. 
NFPA  70  or  CSA  C22.1,  as  applicable. 

2.3.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  101.5a  and  101.5c  {300.2},  and 
1004.2(b)(3). 


16 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.7.5.1  and  (NR  101.5c)  {3.7},  and 
8.11.3.1.2(c). 

A17.3  —  Paragraph  2.2.3  {Section  4.1}. 

NFPA  70  or  CSA  C22.1,  as  applicable. 

ITEM  2.4 
MACHINE  SPACE 

2.4.1  Periodic  Inspections 

Check  the  condition  of  the  equipment  in  the  machine 
room,  overhead  machinery  spaces,  and  machinery  space 
located  in  the  hoist  way  by  examining  the  following: 

(a)  Check  that  overhead  gratings  or  platforms  are 
properly  supported,  and  secure. 

(b)  Check  the  machine  room  and  secondary  machine 
rooms  for  any  leaks  in  the  roof  or  windows.  Machines, 
control  equipment,  sheaves,  and  other  machinery  should 
be  protected  from  the  elements. 

2.4.1.1  Electric  Elevators.  For  elevators  installed 
under  A17. 1-1993  and  later  editions  where  remote 
machine  rooms  or  control  rooms  are  provided,  check  the 
access  to  ropes  and  sheaves.  Check  the  communications 
between  the  elevator  car  and  machine  room. 

2.4.1.2  Hydraulic  Elevators.  Check  that  machinery 
is  separated  from  other  parts  of  the  building  by  required 
enclosure.  A17.1b-1989  and  later  editions  prohibit  loca- 
tion of  machine  and  control  rooms  in  the  hoistway. 

2.4.2  Periodic  Test 

2.4.3  Acceptance 

2.4.3.1  Electric  Elevators.  For  elevators  installed 
under  A17.1-1996  and  earlier  editions,  check  that  a  sign 
stating  the  maximum  allowable  floor  load  has  been 
prominently  displayed  in  all  main  and  secondary 
machine  rooms.  The  sign  is  required  to  be  metal  with 
black  letters  and  figures  at  least  4  in.  (102  mm)  high  on 
a  white  background. 

Bar- type  overhead  gratings  and  platform  openings 
and  fabricated  or  expanded  metal  must  comply  with 
Code  size  requirements.  Measure  and  verify  openings 
for  compliance. 

2.4.4  References 

2.4.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  100.3c,  100.3d,  100.5,  101.1a,  101.2, 
101.8,  and  1001.2(b)(4). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.1.3.3,  2.1.3.4,  2.1.5,  2.7.1.1,  2.7.2.1,  2.7.8, 
and  8.11.2.1.2(d). 

A17.3  —  Paragraphs  2.2.1  and  2.2.6. 

2.4.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  101.1a  {300.2),  105.2  and  105.4 
{300.6},  and  1004.2(b)(4). 


A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.7.1.1  {3.7),  2.9.2  and  2.9.4  (3.9),  and 
8.11.3.1.2(d). 

A17.3  —  Paragraphs  2.2.2  and  2.2.6  {Section  4.1). 

ITEM  2.5 
HOUSEKEEPING 

2.5.1  Periodic  Inspections 

Check  that  the  machine  room  area  is  not  used  for  the 
storage  of  any  flammable  liquids  with  a  flash  point  less 
than  110°F  (43°C),  and  for  materials  and  articles  not 
necessary  for  the  maintenance  and  operation  of  the  ele- 
vator. Check  the  floor  area  for  cleanliness,  noting  any 
accumulation  of  oil,  grease,  or  dirt. 

For  observation  elevators  with  glass  car  enclosures  or 
hoistway  enclosures,  check  to  see  that  a  written  proce- 
dure for  cleaning  the  glass  exists.  The  written  procedure 
is  not  required  to  be  kept  in  the  machine  room,  but  must 
be  kept  on  premises.  In  jurisdictions  enforcing  NBCC, 
if  access  openings  in  the  hoistway  or  car  for  cleaning 
are  not  provided,  cleaning  must  be  performed  under 
the  direct  supervision  of  a  maintenance  mechanic. 

Check  that  the  tops  of  cars  are  kept  clean,  dry,  and 
are  not  being  used  for  storage. 

2.5.2  Periodic  Test 

2.5.3  Acceptance 

2.5.4  References 

2.5.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  1001.2(b)(5),  1206.2b,  and  1206.9. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  8.11.2.1.2(e),  8.6.4.8,  and  8.6.10.3. 

2.5.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  1004.2(b)(5)  and  1206.1,  1206.2b 
{1206.5a),  and  1206.9. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  8.11.3.1.2(e)  and  8.6.1.2, 8.6.4.8  (8.6.5),  and 
8.6.10.3. 


ITEM  2.6 
VENTILATION 

2.6.1  Periodic  Inspections 

Check  that  mechanical  ventilation  and  air  condition- 
ing are  in  operating  condition.  Check  that  natural 
machine  room  ventilation  is  open  and  functioning. 

2.6.2  Periodic  Test 

2.6.3  Acceptance 

Check  that  adequate  ventilation  is  provided  by  natu- 
ral or  mechanical  means  to  ensure  safe  and  normal  oper- 
ation of  the  elevator. 


(10) 


17 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


2.6.4  References 

2.6.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  101.5b,  102.4,  and  1001.2(b)(6). 

A17.1-2000/B44-00     and     later     editions     — 
Requirements  2.7.5.2,  2.8.4,  and  8.11.2.1.2(f). 
A17.3  —  Paragraph  2.2.4. 

2.6.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  101.5b  {300.2},  102.4,  and 
1004.2(b)(6). 

A17.1-2000/B44-00     and     later     editions     — 
Requirements  2.7.5.2  {3.7},  2.8.4,  and  8.11.3.1.2(f). 
A17.3  —  Paragraph  2,2.4  {Section  41}. 

ITEM  2.7 
FIRE  EXTINGUISHER 

2.7.1  Periodic  Inspections 

Check  to  see  that  a  class  "ABC7  fire  extinguisher  is 
mounted  convenient  to  the  access  door.  The  extinguisher 
should  be  tagged  to  indicate  monthly  check  and  required 
annual  maintenance. 

2.7.2  Periodic  Test 

2.7.3  Acceptance 
(10)    2.7.4  References 

2.7.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  1001.2(b)(7)  and  1206.1h. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  8.11.2.1.2(g)  or  c8.11.2.1.2(g)  and  8.6.1.6.5. 

2.7.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  1004.2(b)(7),  and  1206.2f  {1206.5a}. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  8.11.3.1.2(g)  or  c8.11.3.1.2(g),  and  (NR 
1206.2f)  {8.6.5}. 

ITEM  2.8 
PIPES,  WIRING,  AND  DUCTS 

2.8.1  Periodic  Inspections 

Only  such  pipes,  wiring,  and  ducts  used  in  direct 
connection  with  the  elevator  are  permitted  to  be 
installed  in  the  machine  room  or  machinery  spaces. 
Check  permitted  sprinkler  piping  for  any  leakage.  For 
elevators  required  to  meet  A17.3,  pipes  conveying  gases, 
vapors,  or  liquids  not  connected  with  the  operation  of 
the  elevator  must  be  guarded  so  that  any  discharge  will 
not  affect  the  operation  of  the  elevator. 

2.8.2  Periodic  Test 

2.8.3  Acceptance 

Check  that  sprinkler  risers  and  return  piping  have 
been  located  outside  the  machine  room  and  machinery 
spaces.  Check  to  see  that  an  automatic,  nonresetting 


means  independent  of  the  elevator  control  is  provided  to 
disconnect  the  main  line  power  to  the  affected  elevators 
before  the  sprinkler  water  is  discharged  into  the  machine 
room  or  machinery  spaces.  A  shunt  trip  circuit  breaker 
activated  by  a  heat  detector  is  one  method  of  meeting 
these  requirements.  The  Code  prohibits  sprinkler  activa- 
tion or  disconnection  of  main  line  power  by  smoke 
detectors. 

2.8.4  References 

2.8.4.1  Electric  Elevators.  A17.1d~2000  and  earlier 
editions  —  Rules  102.1,  102.2,  and  1001.2(b)(8). 

A17.1-2000/B44-00     and     later     editions     — 
Requirements  2.8.1,  2.8.2,  and  8.11.2.1.2(h). 
A17.1  —  Inquiry  88-26. 
A17.3  —  Paragraph  2.2.5. 
ANSI/NFPA  13. 

2.8.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  102.1  and  102.2  {300.3},  and 
1004.2(b)(8). 

A17.1-2000/B44-00     and     later     editions     — 
Requirements  2.8.1  and  2.8.2  {3.8},  and  8.11.3.1.2(h). 
A17.1  —  Inquiry  88-26. 
A17.3  —  Paragraph  2.2.5  {Section  4.1}. 
ANSI/NFPA  13. 

ITEM  2.9 
GUARDING  OF  EXPOSED  AUXILIARY  EQUIPMENT 

2.9.1  Periodic  Inspections 

Check  that  guards  of  auxiliary  equipment  are  in  place 
and  secure. 

2.9.2  Periodic  Test 

2.9.3  Acceptance 

2.9.4  References 

2.9.4.1  Electric  Elevators.  A17.1d— 2000  and  earlier 
editions  —  Rules  104.1  and  1001.2(b)(9). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.10.1  and  8.11.2.1.2(i). 

2.9.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  104.1  {300.5}  and  1004.2(b)(9). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.10.1  {3.10}  and  8.11.3.1.2(i). 

ITEM  2.10 

NUMBERING  OF  ELEVATORS,  MACHINES, 

CONTROLLERS,  AND  DISCONNECT  SWITCHES 

2.10.1  Periodic  Inspections 

For  elevators  installed  under  Al 7.1-1960  through 
A17.1b-1989,  where  the  machinery  of  more  than  one 
elevator  is  in  a  single  machine  room,  check  that  the 
number  for  each  car  has  been  painted,  or  securely 


18 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


attached  to  the  drive  machine,  controllers,  and  discon- 
nect switch.  A17.1-1990  through  A17.1d-2000  numbers 
to  be  at  least  lV2  in.  (38  mm)  in  height. 

2.10.2  Periodic  Test 

2.10.3  Acceptance 

Where  there  is  more  than  one  elevator  in  the  building, 
verify  that  they  are  properly  identified. 

2.10.4  References 

2.10.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  208.10,  210.4,  211.9,  and  1001.2(b)(10). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  (NR  208.10),  2.26.4,  2.29.1,  and 
8.11.2.1.2(j). 

NFPA  70  or  CSA  C22.1,  as  applicable. 

2.10.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  210.4,  211.9  {306.11},  and  306.6. 

A17.1-2000/B44-00     and     later     editions     — 
Requirements  2.26.4,  2.29.1  {3.27),  and  3.26. 
NFPA  70  or  CSA  C22.1,  as  applicable. 

ITEM  2.11 

DISCONNECTING  MEANS  AND 

CONTROL 

2.11.1  Periodic  Inspections 

Check  that  the  main  line  disconnecting  means  is  in 
good  working  order  and  securely  mounted. 

2.11.1.1  Hydraulic  Elevators.  For  elevators  installed 
under  ASME  A17.1a-1994  and  later  editions,  verify  that 
the  sign  "KEEP  SWITCH  CLOSED  EXCEPT  DURING 

MAINTENANCE,  REPAIRS,  AND  INSPECTIONS"  is 
placed  on  the  switch  when  the  anticreep  device  is  depen- 
dent on  availability  of  power. 

2.11.2  Periodic  Test 
(10)    2.11.3  Acceptance 

(a)  Location.  Check  that  the  main  line  disconnecting 
means  has  been  located  where  it  is  readily  accessible  to 
qualified  persons.  Also,  see  2.11.3.1  for  electric  elevators 
and  2.11.3.2  for  hydraulic  elevators. 

Check  that  the  disconnecting  means  for  the  car  light- 
ing, receptacles  and  ventilation;  and  the  disconnecting 
means  for  any  car  heating  or  air  conditioning  are  located 
in  the  machine  room  or  control  room.  If  there  is  no 
machine  room  or  control  room,  check  that  these  discon- 
necting means  are  in  the  same  space  as  the  main  line 
disconnecting  means. 

For  elevators  subject  to  NFPA  70  and  CSA  22.1,  where 
power  is  supplied  from  more  than  one  source  and  there 
is  not  a  single  means  for  disconnecting  all  ungrounded 
conductors  within  a  single  controller,  check  that  the 
warning  sign  mounted  on  or  next  to  the  disconnecting 


means  indicates  that  there  are  parts  of  the  controller  that 
are  not  de-energized  by  this  switch. 

(b)  Power  —  Prom  More  Than  One  Source.  For  elevators 
with  more  than  one  power  source,  check  to  see  that  a 
separate  disconnecting  means  has  been  provided  for 
each  source  of  electrical  power,  and  that  the  main  line 
disconnecting  means  is  within  sight  of  the  equipment 
served.  Check  to  see  that  warning  signs  for  multiple 
disconnecting  means  indicating  parts  of  the  control 
panel  are  not  de-energized  by  one  switch  are  mounted 
on  or  adjacent  to  the  disconnecting  means. 

(c)  Type.  Verify  that  the  main  line  disconnecting 
means  does  not  control  the  car  lighting,  receptacles,  ven- 
tilation, heating  or  air  conditioning;  or  the  pit  lighting 
or  receptacles. 

(d)  Signage  —  Car  Light  Disconnecting  Means.  If  the 
disconnecting  means  for  more  than  one  elevator  light 
source  are  in  the  same  machine  room,  the  disconnecting 
means  must  be  numbered  or  identified  to  correspond 
to  the  unique  alphabetical  or  numerical  identification 
assigned  to  correspond  to  the  elevator  car  whose  light 
source  the  disconnecting  means  controls. 

Verify  that  a  sign  is  provided  for  each  disconnecting 
means  that  indicates  the  location  of  the  supply  side 
overcurrent  protective  device  (fuse  or  circuit  breaker). 

Verify  that  arc  flash  warning  signs,  where  required,  are 
in  place  and  clearly  visible. 

Check  that  the  disconnecting  means  for  the  cab  light- 
ing/ventilation circuit  does  not  disconnect  power  to  the 
door  operator  or  the  means  of  two-way 
communications. 

2.11.3.1  Electric  Elevators 

(a)  For  elevators  without  generator  field  control,  the 
main  line  disconnecting  means  must  be  located  within 
sight  of  the  motor  controller.  When  the  driving  machine 
or  motion  and  operation  controllers  are  not  within  sight 
of  the  disconnecting  means,  an  additional  manually 
operated  switch  is  required  to  be  installed  adjacent  to 
the  remote  equipment  connected  in  the  control  circuit 
to  prevent  starting. 

When  the  driving  machine  or  motion  controller  and 
operation  controllers  are  not  within  sight  of  the  discon- 
necting means,  an  additional  manually  operated  switch 
is  required  to  be  installed  adjacent  to  remote  equipment 
that  is  connected  in  the  control  circuit  to  prevent  starting. 

(b)  For  elevators  with  generator  field  control,  the  main 
line  disconnecting  means  must  be  located  within  sight 
of  the  motor  controller  (motor  starter)  for  the  driving 
motor  of  the  motor-generator  set.  When  driving 
machines,  motor-generator  sets,  or  motion  and  opera- 
tion controllers  are  not  within  sight  of  the  disconnecting 
means,  an  additional  manually  operated  switch  is 
required  to  be  installed  adjacent  to  the  remote  equip- 
ment connected  in  the  control  circuit  to  prevent  starting. 


19 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


When  the  driving  machine  or  motion  controller  and 
operation  controllers  are  not  within  sight  of  the  discon- 
necting means,  an  additional  manually  operated  switch 
is  required  to  be  installed  adjacent  to  remote  equipment 
that  is  connected  in  the  control  circuit  to  prevent  starting. 

2.11.3.2  Hydraulic  Elevators.  The  main  line  discon- 
necting means  is  required  to  be  installed,  located  within 
sight  of  the  motor  starter,  and  required  to  remove  power 
from  both  the  motor  and  control  valve. 

Where  the  driving  machine  of  a  hydraulic  machine 
of  a  hydraulic  elevator  is  located  in  a  remote  machine 
room  or  remote  machinery  space,  verify  that  a  single 
means  for  disconnecting  all  ungrounded  main  power 
supply  conductors  is  provided  and  is  capable  of  being 
locked  in  the  open  position. 

For  hydraulic  elevators  equipped  with  auxiliary 
power  lowering,  verify  that  with  the  main  disconnect 
in  the  open  position,  the  additional  power  source  is 
disconnected  from  its  load  and  the  car  does  not  lower. 

(10)    2.11.4  References 

2.11.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  210.4  and  1001.2(b)(ll). 

A17.1-2000/B44-00      and      later      editions     — 
Requirements  2.26.4  and  8.11.2.1.2(p). 
A17.3  —  Paragraph  3.10.5. 
NFPA  70  or  CSA  C22.1,  as  applicable. 
A17.5-1991  —  Clause  20.7. 

2.11.4.2  Hydraulic  Elevators.  A 1 7. ld-2000  and  ear- 
lier editions  —  Rules  306.3a(5)(b),  306.4,  306.6,  and 
1004.2(b)(ll). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  3.26.3.1  [3.26.3.1.4(b)],  3.26.4,  3.26,  and 
8.11.3.1.2(p). 

A17.3  —  Paragraph  3.10.5  {4.7.5}. 

NFPA  70  or  CSA  C22.1,  as  applicable. 

ITEM  2.12 
CONTROLLER  WIRING,  FUSES,  GROUNDING,  ETC 

2.12.1   Periodic  Inspections 

(10)         2.12.1.1  Electric  Elevators 

(a)  Inspection  Made  With  Power  Off.  Examine  all  con- 
troller and  selector  relays,  switches,  contactors,  control 
circuit  rectifiers,  transformers,  capacitors,  resistors,  vac- 
uum tubes,  printed  circuit  boards,  etc.,  and  note 

(1)  any  excessively  worn  or  burned  contacts,  bro- 
ken connectors,  broken  or  cracked  resistance  grids  or 
resistance  tubes. 

(2)  proper  fuse  type  and  rating.  No  fuses  should 
be  jumped  or  shorted. 

(3)  check  for 

(a)  jumper  wires  or  temporary  wiring  changes 

(b)  whether  the  equipment  is  clean 


(c)  any  accumulation  of  combustible  materials, 
especially  on  resistance  grids  or  wires,  or  on  control 
circuit  rectifiers 

(d)  whether  contacts  of  reverse-phase  relay, 
where  provided,  are  open 

(e)  excessively  worn  hinge  pins  and  shunt  wiring 
on  relays  or  contactors 

(f)  check  mechanical  interlock  between  relays 

(g)  visually  check  for  blocked  relays  or  circuits 
defeated  by  any  other  means  and  ensure  that  there  is  no 
evidence  of  a  safety  device  being  rendered  inoperative 

(4)  verify  that  jumpers  are  not  stored  in  the  machine 
space,  truss,  or  pits. 

(5)  Check  that  signage  is  legible  and  maintained. 
For  elevators  subject  to  NFPA  70  and  CSA  22.1  where 
power  is  supplied  from  more  than  one  source,  check  for 
warning  signs. 

(6)  Check  that  all  "no  touch"  shields  (barriers)  and 
guards,  where  provided,  are  in  place  and  not  damaged. 

(b)  Inspection  Made  With  Power  On.  Observe  the  oper- 
ation of  the  control  equipment  when  the  elevator  is  run 
in  each  direction.  Note  any  arcing  of  contacts,  excessive 
heating  of  coils  or  resistance,  and  misalgnment  of  relays, 
contactors,  and  switches. 

2.12.1.2  Hydraulic  Elevators.  Hydraulic  elevators 
installed  under  A17.1c-1986  and  later  editions  require 
a  reverse-phase  relay  or  other  means  to  prevent  over- 
heating in  the  event  of  a  phase  failure  or  reversal.  If  a 
reverse-phase  relay  is  not  provided,  a  low  oil  timer, 
line  starters  with  phase  protection,  rotation  sensors,  and 
thermistors  in  motor  and  oil,  etc.,  may  be  used  to  meet 
the  requirement  to  prevent  overheating  in  the  event  of 
a  phase  reversal  and  /or  failure.  The  condition  of  the 
control  provided  should  be  checked. 

2.12.2  Periodic  Test 

2.12.3  Acceptance 

Check  that  sufficient  clear  working  space  has  been 
provided  around  control  panels  and  disconnecting 
means,  to  provide  safe  and  convenient  access  to  all  live 
parts  of  the  equipment  necessary  for  maintenance  and 
adjustment. 

2.12.4  References 

2.12.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  102.1,  210.4, 1001.2(b)(12),  and  1206.1f. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.8.2,  2.26.4,  8.11.2. 1.2(q),  8.6.1.6.1, 
C8.6.12.3.1.3,  8.6.1.6.3,  and  c8.6.12.2.6. 

A17.3  —  Paragraph  3.10. 

NFPA  70  or  CSA  C22.1,  as  applicable. 

2.12.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  102.1  (300.3),  306.5,  306.6, 
1004.2(b)(12),  1206.lt  and  1206.5a. 


do) 


20 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.8.2  {3.8},  3.26.5,  3.26,  8.11.3.1.2(q), 
8.6.1.6.3,  c8.6.12.2.6,  8.6.1.6.1,  c8.6.12.3.1.3,  and  8.6.5. 

NFPA  70  or  CSA  C22.1,  as  applicable. 

ITEM  2.13 

GOVERNOR,  OVERSPEED  SWITCH, 

AND  SEAL 

2.13.1  Periodic  Inspections 

(io)  2.13.1.1  Inspection  Made  With  Power  Off 

(a)  Examine  governor  fastening  bolts  to  verify  that 
the  governor  is  securely  fastened  in  place  and  that  the 
governor  rope  is  free  of  the  governor  jaws  or  other 
obstructions. 

(b)  Examine  all  linkages,  gears,  pins,  collars,  bush- 
ings, and  latches  that  are  used  to  connect  the  weights 
and  the  rope  gripping  devices  for  evidence  of  excessive 
wear  and  lost  motion,  and  note  whether  all  bearings 
and  rubbing  surfaces  are  not  restricted  by  paint  or  other 
foreign  substances. 

(c)  Manually  lift  the  weights  or  flyballs  and  note 
whether  all  moving  parts,  including  the  governor-rope 
jaws,  operate  freely  and  that  there  is  ample  room  for  the 
rotation  of  governor  weight  or  flyballs  in  their  extreme 
extended  position.  Check  all  parts  of  the  governor  for 
lubrication. 

(d)  Examine  rope  gripping  surfaces. 

(e)  Where  the  governor  is  provided  with  a  speed- 
reducing  switch  and  an  overspeed  (stopping)  switch, 
determine  by  manually  operating  the  governor  mecha- 
nism, where  practical,  whether  these  switches  operate. 

(f)  Verify  that  means  of  adjusting  tripping  speed  and 
pull-through  force  are  sealed. 

(g)  Where  special  or  unique  methods  are  required 
to  test  the  governor,  refer  to  the  maintenance  control 
program  for  the  appropriate  procedure. 

2.13.2  Periodic  Test 

(io)         2.13.2.1  Electric  Elevators 

(a)  Yearly  Test  of  Governor  (for  A17.1d-2000  and  Earlier 
Editions);  Category  1  Test  of  Governor  (for  A17. 1-2000/ 
B44-00  and  Later  Editions).  Make  a  general  examination 
of  the  governor-rope  system,  including  the  condition 
of  the  governor,  governor  rope,  governor-rope  tension 
sheave  assembly,  and  releasing  carrier.  Check  that  the 
proper  type  of  rope,  identified  on  the  governor  marking 
plate,  has  been  installed. 

Where  special  or  unique  methods  are  required  to  test 
the  governor,  refer  to  the  maintenance  control  program 
for  the  appropriate  procedure. 

(1)  Inspection  With  Power  Off.  With  the  main  line 
switch  in  the  open  position,  inspect  governors  by  a  man- 
ual extension  of  the  governor  weights  to  make  sure  there 
is  no  restriction  of  motion  and  verify  that  all  parts, 
including  the  rope  gripping  jaws,  operate  freely.  Check 


all  bearings,  pins,  governor-rope  grip  jaws,  and  rubbing 
surfaces  to  make  sure  they  are  not  worn  excessively  and 
are  properly  lubricated  and  free  of  paint. 

(2)  Inspection  Made  With  Power  On.  Open  the  gover- 
nor overspeed  (stopping)  switch,  where  provided,  and 
check  to  be  sure  that  the  elevator  cannot  be  operated. 
Reset  the  governor  switch,  and  have  the  car  operated 
at  normal  speed  in  each  direction  and  note 

(a)  any  tendency  of  the  governor  rope  to  slide 
on  the  sheave  groove  when  the  car  is  started  or  stopped 

(b)  any  eccentric  or  lateral  motion  of  the  governor 
sheave 

(c)  whether  the  rope  runs  free  of  the  jaws  at  all 
times 

(3)  Adjustment  Means  Seal.  A  test  of  the 
governor-tripping  speed  is  not  required  unless  the  seal 
on  the  governor  has  been  disturbed  or  the  inspection 
indicates  that  for  other  reasons  a  test  is  necessary.  If  a 
test  is  made,  the  governor  must  be  sealed  and  tagged 
after  the  test. 

(b)  5-Year  Test  (for  A17.1d-2000  and  Earlier  Editions); 
Category  5  Test  (for  A17 .1-2000/B44-00  and  Later  Editions). 
Where  special  or  unique  methods  are  required  to  test 
the  governor,  refer  to  the  maintenance  control  program 
for  the  appropriate  procedure. 

After  the  car  and  counterweight  guide  shoes,  safety 
parts,  and  governors  have  been  inspected,  check  as 
follows: 

(1)  Determine  the  acceptable  range  of  tripping 
speed  of  the  governor  using  Table  2.13.2.1  based  on  the 
rated  speed.  Also,  the  tripping  speed  should  be  stamped 
on  the  governor  marking  plate  for  elevators  installed 
under  Al 7.1-1955  and  later  editions. 

(2)  Have  governors  calibrated  to  the  setting  as 
shown  in  Table  2.13.2.1. 

(3)  The  sheave  must  be  free  to  rotate  with  no 
obstruction  by  the  governor  rope.  To  accomplish  this, 
have  the  person  performing  the  test  park  the  elevator 
car  about  12  in.  (305  mm)  below  the  top  opening  and 
open  the  main  line  disconnect  switch. 

(a)  Lift  the  governor  rope  to  ensure  sufficient 
slack  to  spin  sheave.  When  installing  a  clamp  on  a  gover- 
nor rope,  be  careful  not  to  damage  the  rope.  [See 
Item  2.13.2(b)(5).] 

(b)  With  a  rubber  drive  wheel  held  against  the 
governor  sheave  driven  by  a  variable  speed  drill  motor, 
gradually  build  up  the  governor  speed  until  it  trips. 

(c)  To  read  the  tripping  speed,  use  a  calibrated 
tachometer  reading  in  ft/min  (m/s).  Hold  the  wheel 
inside  the  governor  sheave  groove  at  the  centerline  of 
the  rope.  Take  several  readings  and  record  the  average. 

(4)  If  any  adjustments  are  made,  be  sure  the  lock- 
nuts  are  tight  and  install  a  new  seal.  Use  a  No.  36 
[0.106  in.  (2.69  mm)]  drill  or  smaller.  Install  the  seal  with 
a  sealing  tool.  Retest  as  outlined  above,  and  record  the 
tripping  speed.  Check  the  tripping  speed  of  the  governor 


21 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Table  2.13.2.1     Governor  Adjustment  Settings 


Car  Governor 

Cwt. 

Car  Governor-Tripping 

Cwt.  Governor-Tripping 

Car  Governor  Overspeed  Switch 

Overspeed 

Governor 

Speed 

Speed  [Note  (1)] 

Settings,  Down  Direction 

Switch 

Settings, 

Up  Direction 

Overspeed 

Rated 

Rqmt. 

Rqmt. 

Rqmt. 

Rqmt 

Rqmts. 

Switch 
Settings 

Car 

2.18.2.1, 

2.18.2.1, 

2.18.2.2, 

2.18.2.2, 

2.18.4.2.1 

Speed, 

Minimum, 

Maximum, 

Minimum, 

Maximum, 

and 

Rqmt. 

Rqmt. 

Rqmt. 

Rqmt. 

ft/min 

ft/min 

ft/min 

ft/min 

ft/min 

2.18.4.2.2 

2.18.4.2.3 

2.18.4.2.5 

2.18.4.2.4 

2.18.4.1 

Oto  125 

144 

175 

145 

192 

Not 

Not 

Not 

150 

173 

210 

174 

231 

Required 

Required 

Required 

175 

202 

250 

203 

275 

200 

230 

280 

231 

308 

Not  more 

225 

259 

308 

260 

338 

than  90% 

250 

288 

337 

289 

370 

of  car 

Not  more 

Not  more 

Not  more 

Counter- 

300 

345 

395 

346 

434 

governor 

than  90% 

than  100% 

than  100% 

weight 

350 

403 

452 

404 

497 

down 

of  car 

of  car 

of  car 

governor 

400 

460 

510 

461 

561 

tripping 

governor 

governor 

governor 

overspeed 

450 

518 

568 

519 

624 

setting 

down 

down 

down 

switch 

500 

575 

625 

575 

687 

tripping 
setting 

for 
elevators 

tripping 

setting  if  a 

speed 

reducing 

tripping 
setting 

required 

600 
700 

690 
805 

740 
855 

691 
806 

814 
940 

for  any 

speed 

800 

920 

970 

921 

1,067 

with 

switch  is 

900 

1,035 

1,085 

1,036 

1,193 

Not  more 

static 

provided 

1,000 

1,150 

1,200 

1,151 

1,320 

than  95% 

controls 

1,100 

1,265 

1,320 

1,266 

1,452 

of  car 

1,200 

1,380 

1,440 

1,381 

1,584 

governor 

1,300 

1,495 

1,560 

1,496 

1,716 

down 

1,400 

1,610 

1,680 

1,611 

1,848 

tripping 

1,500 

1,725 

1,800 

1,726 

1,980 

setting 

1,600 

1,840 

1,920 

1,841 

2,112 

1,700 

1,955 

2,040 

1,956 

2,244 

1,800 

2,070 

2,160 

2,071 

2,376 

1,900 

2,185 

2,280 

2,186 

2,508 

2,000 

2,300 

2,400 

2,301 

2,640 

NOTE: 

(1)  The  counterweight  governor-tripping  speed  must  exceed  the  car  governor-tripping  speed. 


switches  using  the  same  procedure.  Place  the  rope  on 
the  governor  sheave. 

Remove  the  clamp  and  inspect  the  governor  rope  for 
any  damage  or  kinks.  Reinstall  all  sheave  and  switch 
covers.  Check  the  releasing  carrier.  On  drum-operated 
safeties,  check  for  slack  rope  between  the  releasing  car- 
rier and  drum. 

NOTE:     If  an  elevator,  for  any  reason,  is  running  below  the  rated 
speed,  the  governor  calibration  must  be  based  on  the  rated  speed. 

(5)  For  Class  B-type  safeties,  check  the  force  neces- 
sary to  pull  the  governor  rope  through  the  governor.  In 
no  case  may  the  pull-through  force  exceed  one-fifth  of 
the  rated  ultimate  strength  of  the  governor  rope.  The 
force  required  to  pull  the  governor  rope  from  the  releas- 
ing carrier  is  required  to  be  no  more  than  60%  of  the 
pull-through  force. 

One  method  of  performing  this  test  is  as  follows:  The 
best  place  to  check  this  is  from  the  top  of  the  car  since  the 
governor  rope  and  release  carrier  are  usually  accessible 


from  there  (see  Fig.  2.13.2.1).  Make  this  connection  fairly 
direct  with  minimum  angle  between  the  governor  rope 
and  the  sling.  Take  special  care  that  the  attachment  does 
not  damage  the  governor  rope.  In  most  cases  the  attach- 
ment can  be  made  to  a  portion  of  the  governor  rope  that 
does  not  reach  the  governor  when  the  car  is  at  the  upper 
landing.  When  clamps  (fist  grip)  are  used  for  this  pur- 
pose, they  should  comply  with  non-babbitted  rope  fas- 
tenings as  outlined  in  Item  3.29,  and  the  nuts  tightened 
with  a  torque  wrench  to  the  torque  recommended  by 
the  manufacturer.  Typical  torques  are  45  ft-lb  (61  N-m) 
for  %  in.  (9.5  mm)  rope,  65  ft-lb  (88  N-m)  for  7/16  in. 
(11  mm)  and  V2  in.  (13  mm)  rope,  and  130  ft-lb  (176  N-m) 
for  9/16  in.  (14  mm)  and  %  in.  (16  mm)  rope;  either  over- 
or  under-tightening  will  likely  damage  the  governor 
rope  and  require  its  replacement.  A  so-called  "Chicago" 
grip  that  is  used  for  pulling  large  diameter  electrical 
conductors  is  also  recommended  for  this  connection 
since  it  would  be  less  likely  to  damage  the  governor 


22 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Fig.  2.13.2.1     Dynamometer  Connections  for  Testing  the  Pull-Through  of  Governor  Jaws 


Governor 


Come-along 


Crosshead 


Attachment 
to  governor  rope 


Dynamometer 


Governor-rope 
releasing  carrier 


rope.  These  grips  can  be  ordered  with  jaws  that  are 
machined  to  the  diameter  of  the  rope.  Midline  rope 
clamps  that  grip  with  a  wedge  conforming  to  the  rope 
size  may  also  be  used.  Regardless  of  the  method  used, 
extra  care  must  be  taken  to  provide  a  secure  connection 
that  will  not  damage  the  governor  rope.  Note  the  spring 
tension  of  the  safety  releasing  carrier  so  that  it  can  be 
restored  to  its  original  setting  after  completion  of  the 
test. 

Remove  the  spring  tension  from  the  releasing  carrier 
so  that  it  will  not  restrain  the  rope.  Trip  the  governor, 
and  pop  up  the  governor-rope  tension  sheave  to  allow 
approximately  1  ft  (0.305  m)  movement  of  the  governor 
rope  without  lifting  the  tension  sheave.  Operate  the 
come-along  pulling  at  least  6  in.  (152.4  mm)  of  the  gover- 
nor rope  through  the  governor.  Note  the  reading  on 


the  dynamometer  and  compare  it  to  the  rated  ultimate 
strength  of  the  rope.  If  a  release  carrier  is  used,  it  must 
release  at  no  more  than  60%  of  the  governor  pull-through 
force.  This  can  be  checked  with  the  same  equipment  by 
connecting  the  dynamometer  and  come-along  between 
the  governor  rope  at  the  releasing  carrier  and  the  existing 
connection  and  the  governor  rope. 

After  this  test,  perform  the  following  three  steps: 

(a)  Carefully  inspect  the  governor  rope  at  the 
point  of  connection  to  assure  that  it  has  not  been 
damaged. 

(b)  Restore  the  governor  release  carrier. 

(c)  Reset  and  inspect  the  governor. 

(6)  Ensure  the  governor  has  been  sealed  and 
tagged. 


23 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


(10)         2.13.2.2  Hydraulic  Elevators 

(a)  Yearly  Test  (for  A17.1d-2000  and  Earlier  Editions); 
Category  1  Test  (for  A17.1-2000/B44-00  and  Later  Editions). 
Make  a  general  examination  of  the  governor-rope  sys- 
tem, including  the  condition  of  the  governor,  governor 
rope,  governor-rope  tension  sheave  assembly,  and 
releasing  carrier.  Check  to  verify  that  the  type  of  rope, 
identified  on  the  governor  marking  plate,  has  been 
installed.  Where  special  or  unique  methods  are  required 
to  test  the  governor,  refer  to  the  maintenance  control 
program  for  the  appropriate  procedure. 

(1)  Inspection  Made  With  Power  Off.  With  the  main 
line  switch  in  the  open  position,  governors  shall  be 
inspected  by  a  manual  extension  of  the  governor  weights 
to  make  sure  there  is  no  restriction  of  motion  and  verify 
that  all  parts,  including  the  rope  gripping  jaws,  operate 
freely  All  bearings,  pins,  rope  grip  jaws,  and  rubbing 
surfaces  shall  be  checked  to  make  sure  they  are  not  worn 
excessively,  are  properly  lubricated,  and  free  of  paint. 

(2)  Inspection  Made  With  Power  On.  Open  the  gover- 
nor overspeed  (stopping)  switch,  where  provided,  and 
check  to  be  sure  that  the  elevator  cannot  be  operated  in 
either  direction.  Reset  the  governor  switch,  and  have  the 
car  operated  at  normal  speed  in  each  direction  and  note 

(a)  any  tendency  of  the  governor  rope  to  slide 
on  the  sheave  groove  when  the  car  is  started  or  stopped 

(b)  any  eccentric  or  lateral  motion  of  the  governor 
sheave 

(h)  5-Year  Test  (for  AU.ld-2000  and  Earlier  Editions); 
Category  5  Test  (for  A17.1-2000/B44-00  and  Later  Editions). 
Where  special  or  unique  methods  are  required  to  test 
the  governor,  refer  to  the  maintenance  control  program 
for  the  appropriate  procedure.  After  the  car  and  counter- 
weight guide  shoes,  safety  parts,  and  governors  have 
been  inspected,  check  as  follows; 

(1)  The  acceptable  range  of  tripping  speed  for  the 
governor  shall  be  determined  using  Table  2.13.2,  except 
that  the  tripping  speed  shall  be  based  on  the  elevator 
operating  speed  in  the  down  direction.  The  governor 
switch  should  operate  before  or  at  the  application  of  the 
safety.  If  a  tripping  speed  is  stamped  on  the  governor 
marking  plate,  it  should  be  considered  the  maximum 
for  that  governor. 

(2)  Governors  shall  be  calibrated  to  the  setting  as 
shown  in  Table  2.13.2  or  manufacturer's  marking  plate, 
whichever  is  less. 

(3)  The  sheave  must  be  free  to  rotate  with  no 
obstruction  by  the  governor  rope.  To  accomplish  this, 
park  the  elevator  car  about  12  in.  (305  mm)  below  the 
top  opening  and  open  the  main  line  disconnect  switch. 

(a)  Lift  the  governor  rope  to  ensure  sufficient 
slack  to  spin  the  sheave.  When  installing  a  clamp  on  a 
governor  rope,  be  careful  not  to  damage  the  rope. 

(b)  With  a  rubber  drive  wheel  held  against  the 
governor  sheave  driven  by  a  variable  speed  electric  drill, 
gradually  build  up  the  governor  speed  until  it  trips. 


(c)  To  read  the  tripping  speed,  use  a  tachometer 
reading  in  ft/min  (m/s).  Hold  the  tachometer  wheel  at 
the  pitch  diameter  of  the  governor  sheave.  Take  several 
readings  and  record  the  average. 

(4)  If  any  adjustments  are  made,  be  sure  the  lock- 
nuts  are  tight  and  install  a  new  seal.  Use  a  No.  36 
[0.106  in.  (2.69  mm)]  drill  or  smaller.  Install  the  seal  with 
a  sealing  tool.  Retest  as  outlined  above  and  record  the 
tripping  speed.  Check  the  tripping  speed  of  the  governor 
switches  using  the  same  procedure.  Place  the  rope  on 
the  governor  sheave.  Remove  the  clamp  and  inspect  the 
governor  rope  for  any  damage  or  kinks.  Reinstall  all 
sheave  and  switch  covers. 

NOTE:    If  an  elevator,  for  any  reason,  is  running  below  the  rated 
speed,  the  governor  calibration  must  be  based  on  the  rated  speed. 

(5)  For  Type  B  safeties,  the  force  necessary  to  pull 
the  governor  rope  through  the  governor  shall  be 
checked.  In  no  case  may  the  pull-through  force  exceed 
one-fifth  of  the  rated  ultimate  strength  of  the  governor 
rope.  The  force  required  to  actuate  the  releasing  carrier, 
where  provided,  shall  be  no  more  than  60%  of  the  pull- 
through  force.  One  method  of  performing  this  test  is  as 
follows:  the  best  place  to  check  this  is  from  the  top  of 
the  car  since  the  governor  rope  and  release  carrier,  where 
provided,  are  usually  accessible  from  there  (see 
Fig.  2.13.2).  Make  this  connection  fairly  direct  with  mini- 
mum angle  between  the  governor  rope  and  the  sling. 
Take  special  care  that  the  attachment  does  not  damage 
the  governor  rope.  In  most  cases  the  attachment  can  be 
made  to  a  portion  of  the  governor  rope  that  does  not 
reach  the  governor  when  the  car  is  at  the  upper  landing. 
When  clamps  (fist  grip)  are  used  for  this  purpose,  they 
shall  comply  with  non-babbitted  rope  fastenings,  and 
the  nuts  tightened  with  a  torque  wrench  to  the  torque 
recommended  by  the  manufacturer.  This  is  usually 
45  ft-lb  (61  N-m)  for  %  in.  (9.5  mm)  rope,  65  ft-lb  for 
(88  N-m)  for  7/16  in.  (11  mm)  and  V2  in.  (13  mm)  rope, 
and  130  ft-lb  (176  N-m)  for  9/16  in.  (14  mm)  and  %  in. 
(16  mm)  rope.  Either  over-  or  under-tightening  will 
likely  damage  the  governor  rope  and  require  its  replace- 
ment. A  so-called  "Chicago"  grip  that  is  used  for  pulling 
large  diameter  electrical  conductors  is  also  recom- 
mended for  this  connection  since  it  would  be  less  likely 
to  damage  the  governor  rope.  These  grips  can  be  ordered 
with  jaws  that  are  machined  to  the  diameter  of  the  rope. 
Midline  rope  clamps  that  grip  with  a  wedge  conforming 
to  the  rope  size  may  also  be  used.  Regardless  of  the 
method  used,  extra  care  must  be  taken  to  provide  a 
secure  connection  that  will  not  damage  the  governor 
rope.  Note  the  spring  tension  of  the  safety  releasing 
carrier  so  that  it  can  be  restored  to  its  original  setting 
after  completion  of  the  test. 

Remove  the  spring  tension  from  the  releasing  carrier 
so  that  it  will  not  restrain  the  rope.  The  governor  shall 
be  tripped,  and  the  governor-rope  tension  sheave 


24 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


propped  up  to  allow  approximately  1  ft  (0.305  m)  move- 
ment of  the  governor  rope  without  lifting  the  tension 
sheave.  Operate  the  come-along  pulling  at  least  6  in. 
(152  mm)  of  the  governor  rope  through  the  governor. 
Note  the  reading  on  the  dynamometer  and  compare  it 
to  the  rated  ultimate  strength  of  the  rope.  If  a  release 
carrier  is  used,  it  must  release  at  no  more  than  60%  of 
the  governor  pull-through  force.  This  can  be  checked 
with  the  same  equipment  by  connecting  the  dynamome- 
ter and  come-along  between  the  governor  rope  at  the 
releasing  carrier  and  the  existing  connection  and  the 
governor  rope. 

After  this  test,  perform  the  following  three  steps: 

(a)  Carefully  inspect  the  governor  rope  at  the 
point  of  connection  to  assure  that  it  has  not  been 
damaged. 

(b)  Restore  the  governor  release  carrier. 

(c)  Reset  and  inspect  the  governor. 

(6)  The  governor  should  be  sealed  and  a  metal  test 
tag  installed  by  the  person  that  performed  the  test. 

2.13.3  Acceptance 

2.13.3.1  Electric  Elevators 

(a)  Governor  Tests.  Check  the  governor  marking  plate 
to  determine  that  it  is  marked  with  size,  material,  and 
construction  of  the  governor  rope  used  and  the 
governor- tripping  speed. 

(b)  Speed-Load  Tests.  The  use  of  a  tachometer  in  mak- 
ing speed-load  tests  is  required.  The  tachometer  reading 
must  be  taken  after  the  car  has  reached  its  constant 
speed.  Take  and  record  speed  readings  with  no  load  in 
the  car  and  with  rated  load  in  the  car  in  both  the  up 
and  down  directions.  Tachometer  readings  must  be 
taken  from  the  side  of  the  governor  rope  or  hoisting 
ropes.  Speed  readings  from  any  other  position  on  the 
governor  rope  or  hoisting  ropes  will  be  inaccurate. 
Where  the  car  is  roped  2:1,  the  car  speed  is  one-half  the 
hoist  rope  speed. 

2.13.3.2  Hydraulic  Elevators 

(a)  Governor  Tests.  Check  the  governor  marking  plate 
to  verify  that  it  is  marked  with  size,  material,  and  con- 
struction of  the  governor  rope  for  which  it  was  designed 
and  the  governor- tripping  speed. 

(b)  Speed-Load  Tests.  The  tachometer  reading  must  be 
taken  after  the  car  has  reached  its  constant  speed.  Speed 
readings  shall  be  taken  and  recorded  with  no  load  in 
the  car  and  with  rated  load  in  the  car  in  both  the  up 
and  down  direction.  Tachometer  readings  must  be  taken 
by  holding  the  tachometer  wheel  at  the  pitch  diameter 
of  the  governor  sheave. 

NOTE:  For  consistency  of  measurement,  the  oil  should  be  at 
normal  operating  temperature  when  checking  rate  speed, 
operating  speed  in  the  down  direction,  relief  valve  setting,  etc. 


2.13.4  References 

2.13.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Section  206  and  Rules  205.15,  210.2(j), 
1001.2(b)(28),  1002.2c,  1002.3a,  1002.3b,  1003.2a,  and 
1206.1a. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.18,  2.17.15,  2.26.2  (2.26.2.10), 
8.11.2.1.2(bb),  8.11.2.2.3,  8.11.2.3.1,  8.11.2.3.2, 
c8.11.2.3.2(c),  8.10.2.2.2(cc)(l),  and  8.6.1.6.2. 

A17.1a-2008/B44a-08  —  8.11.2.2  was  redesignated 

8.6.4.19  [Category  1  tests],  8.11.2.3  was  redesignated 

8.6.4.20  [Category  5  tests]. 

A17.3  —  Paragraphs  3.6.1  and  3.10.4(g). 

2.13.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Sections  205  and  206;  and  Rules  301.8, 
1002.2(b),  1005.2c,  1005.4,  1202.7,  and  1206.1. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.17  and  2.18,  3.17.1,  8.11.2.2.2,  8.11.3.2.3, 
8.11.3.4,  8.7.2.19,  and  8.6.1.2. 

A17.1a-2008/B44a-08  —  8.11.3.2  was  redesignated 

8.6.5.14  [Category  1  tests],  8.11.3.3  was  redesignated 

8.6.5.15  [Category  3  tests],  8.11.3.4  was  redesignated 

8.6.5.16  [Category  5  tests]. 
A17.3  —  Paragraph  4.9.7. 

ITEM  2.14 
CODE  DATA  PLATE 

2.14.1  Periodic  Inspections 

Check  that  the  Code  Data  Plate  is  installed.  This  is 
the  Code  that  is  to  be  used  for  the  inspection  and  test. 

2.14.2  Periodic  Test 

2.14.3  Acceptance 

2.14.4  References 

2.14.4.1  Electric  Elevators.  Al 7. ld-2000  and  earlier 
editions  —  Section  215  and  Rule  1200.6. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  8.9  and  8.7.1.8. 

2.14.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Section  309  and  Rule  1200.6. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  8.9  and  8.7.1.8. 

NOTE:     Items  2.15  through  2.29  apply  to  electric  elevators  only. 

ITEM  2.15 
STATIC  CONTROL 

2.15.1  Periodic  Inspections 

2.15.2  Periodic  Test 

2.15.2.1  Electric  Elevators:  Yearly  Test  (for 
A17.1d-2000  and  Earlier  Editions);  Category  1  Test  (for 
A17.1-2000/B44-00  and  Later  Editions).    The  person  or 


do) 


25 


C 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


firm  installing  or  maintaining  an  elevator  with  a  driving 
motor  employing  static  control  without  MG  set  should 
demonstrate  conformance  with  the  Code  as  follows: 

(a)  Run  the  car  and  demonstrate  that  there  are  two 
devices  that  each  independently  will  remove  power 
from  the  driving-machine  motor  and  cause  the  car  to 
stop.  At  least  one  of  the  devices  is  required  to  be  an 
electromechanical  contactor,  which  also  opens  the 
driving-machine  brake  circuit. 

(b)  Prevent  the  above  electromechanical  contactor 
from  being  energized  and  register  a  call.  Demonstrate, 
with  the  doors  closed,  that  the  brake  will  not  lift  and 
the  car  will  not  move. 

(c)  Demonstrate  that  either  of  two  contactors  in  the 
brake  circuit  will  prevent  the  brake  from  lifting. 

(d)  Demonstrate  that  the  operation  of  any  of  the  elec- 
trical protective  devices  will  cause  both  devices  specified 
in  Item  2.13.2(a)  to  remove  power  from  the 
driving-machine  motor  and  brake. 

2.15.3  Acceptance 

2.15.4  References 

2.15.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  210.2,  210.9(d),  1001.2(b)(13),  and 
1003.2h. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.26.2,  2.26.9.5,  8.11.2.1.2(m),  and 
8.10.2.2.2(m). 


ITEM  2.16 
OVERHEAD  BEAM  AND  FASTENINGS 

2.16.1  Periodic  Inspections 

2.16.1.1  Electric  Elevators.  Examine  overhead 
beams  to  determine  whether  they  are  securely  fastened 
to  supports  or  firmly  embedded  in  walls.  Note  any  set- 
tlement of  supports.  Examine  all  exposed  bolt  fastenings 
of  beams  supporting  machinery  or  sheaves. 

2.16.2  Periodic  Test 

2.16.3  Acceptance 

2.16.3.1  Electric  Elevators.  Examine  overhead 
machine  and  sheave  beam  supports.  Record  the  dimen- 
sions and  span  of  beams  and  check  them  against  layout 
drawings. 

2.16.4  References 

2.16.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  105.1,  105.2,  105.3,  and  1001.2(b)(14). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.9.1,  2.9.2,  2.9.3,  and  8.11.2.1.2(n). 


ITEM  2.17 
DRIVE  MACHINE  BRAKE 

2.17.1  Periodic  Inspections 

2.17.1.1  Electric  Elevators 

(a)  Inspection  Made  With  Power  On.  Run  the  car  and 
observe  the  operation  of  the  brake.  The  brake  should 
not  chatter.  It  may  apply  on  or  before  the  completion 
of  the  slowdown  and  leveling  operation.  Check  to  see 
that  the  brake  is  automatically  applied  on  or  after  normal 
stops.  The  clearance  between  the  brake  shoe  and  the 
brake  drum  when  the  car  is  running  should  not  be 
greater  than  necessary  to  permit  free  running.  Examine 
the  brake  pins  to  determine  whether  they  are  properly 
lubricated  and  not  frozen,  and  that  retainers  are  in  place. 
Note  any  harsh  and  abrupt  brake  action.  Examine  brake- 
activated  contacts  (if  provided)  for  proper  operation. 

(b)  Inspection  Made  With  Power  Off 

(1)  Examine  the  brake  and  drum  to  determine  that 
the  brake  linings  are  free  of  oil  and  whether  there  is  any 
scoring  of  the  drum. 

(2)  If  the  elevator  has  been  running,  the  brake  drum 
may  be  warm  but  should  not  be  uncomfortable  to  the 
touch.  A  hot  drum  usually  indicates  a  dragging  brake 
shoe. 

NOTE:  The  design  of  the  actuating  linkage  of  some  brakes  is 
such  that  a  single  unit  or  link  is  used  both  to  govern  the  spring 
pressure  applying  the  brake  shoes  when  the  brake  applies  and  the 
amount  of  clearance  between  the  brake  shoes  and  the  brake  drum 
when  the  brake  is  released.  With  this  type  of  design,  it  is  possible 
to  improperly  adjust  the  releasing  feature  so  that  it  will  prevent 
the  brake  shoes  from  gripping  the  brake  drum  when  the  brake 
applies.  The  adjustment  of  this  type  of  brake  should  be  examined 
to  determine  that  the  adjustment  is  such  that  the  brake  shoes  are 
not  prevented  from  properly  applying  and  that  there  is  sufficient 
margin  in  the  adjustment  for  the  brake  lining  wear  (no  part  of  the 
brake  should  contact  the  machine  for  at  least  the  thickness  of  the 
lining). 

2.17.2  Periodic  Test 

2.17.2.1  Electric  Elevators 

(a)  Yearly  Test  (for  A17.1d-2000  and  Earlier  Editions); 
Category  1  Test  (for  A17.1-2000/B44-00  and  Later  Editions) 
For  elevators  installed  under  Al 7. 1-2000 /B44-00  and 
later  editions,  have  the  brake  setting  verified  in  accor- 
dance with  the  data  on  the  brake  marking  plate. 

(b)  5-Year  Test  (for  A17.1d-2000  and  Earlier  Editions); 
Category  5  Test  (for  A17 .1-2000 /BU-OO  and  Later  Editions). 
At  an  upper  landing  from  which  the  maximum  attain- 
able speed  in  the  down  direction  can  be  attained  with 
125%  load,  place  125%  load  in  the  car  for  passenger 
elevators  and  freight  elevators  permitted  to  carry  pas- 
sengers, and  for  freight  elevators  place  the  rated  load 
in  the  car. 

(1)  Run  the  car  to  the  lowest  landing  by  the  normal 
operating  means.  The  driving  machine  must  safely 
lower,  stop,  and  hold  the  car  with  this  overload.  The 


do) 


26 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


elevator  is  not  required  to  attain  rated  load  performance 
under  overload  conditions,  but  should  stop  the  car 
within  a  reasonable  distance  (e.g.,  the  distance  between 
the  initial  slowdown  and  the  bottom  terminal  landing 
sill).  The  driving  machine  is  not  required  to  raise  this 
load  or  stop  level  within  normal  limits,  but  the  car 
should  not  activate  the  final  terminal  stopping  device. 
After  the  elevator  has  stopped,  have  the  main  line  dis- 
connect means  opened  and  verify  that  the  brake  will 
hold  the  elevator. 

(2)  For  elevators  installed  to  A17.1-2000  and  later 
editions,  in  addition  to  the  procedure  performed  above, 
run  the  car  down  by  the  normal  operating  means  and 
have  the  safety  circuit  opened  after  the  car  has  reached 
constant  speed.  It  is  not  recommended  that  the  main 
line  disconnect  switch  be  opened  as  the  means  to  stop 
the  car  due  to  the  possibility  of  a  flash  over.  The  braking 
system  must  safely  stop  and  hold  the  load. 

For  freight  elevators  designed  for  Class  C2  loading, 
with  the  car  parked  at  the  landing,  increase  the  load 
inside  the  car  up  to  the  maximum  load  indicated  on 
the  freight  elevator  loading  sign.  The  driving-machine 
motor,  brake,  and  available  traction  must  hold  and  level 
this  load. 

2.17.2.2  Hydraulic  Elevators.  For  freight  elevators 
designed  for  Class  C2  loading,  with  the  car  parked  at 
the  landing,  increase  the  load  inside  the  car  up  to  the 
maximum  load  indicated  on  the  freight  elevator  loading 
sign.  The  hydraulic  system  must  hold  and  level  this  load. 

(10)    2.17.3  Acceptance 

Verify  that  the  brake  marking  plate  is  permanently 
attached  to  the  driving  machine. 

2.17.4  References 

2.17.4.1  Electric  Elevators.  Al 7. ld-2000  and  earlier 
editions  —  Rules  207.2b,  207.8,  (NR  2.24.8),  210.8, 
1001.2(b)(15),  [NR  8.11.2.3.10(a)],  and  1002.3d. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.16.2.2,  2.16.8,  2.24.8,  2.26.8,  8.11.2.1.2(o), 
8.11.2.3.10(a),  and  8.11.2.3.4. 

A17.3  —  Paragraph  3.8.4. 

2.17.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rule  301.10. 

A17.1-2000/B44-00  and  later  editions  — 
Requirement  3.16. 

A17.3  —  Paragraph  4.2.4. 

ITEM  2.18 
TRACTION  DRIVE  MACHINES 

2.18.1  Periodic  Inspections 

2.18.1.1  Electric  Elevators 

(a)  Inspection  Made  With  Power  On 


(1)  Have  the  elevator  operated  in  each  direction, 
making  frequent  stops,  and  observe  the  operation  of  the 
motor.  Observe  commutators  for  excessive  sparking  or 
brush  chatter.  Observe  bearings  for  excessive  noise 
and  wear. 

(2)  Inspect  all  motor  fastening  bolts  for  tightness. 

(3)  Inspect  the  brushes;  note  any  sparking  or 
chattering. 

(b)  Inspection  Made  With  Power  Off  Examine  brush 
holders,  commutators  or  slip  rings,  and  determine 

(1)  the  condition  of  the  brush  holders  and  brushes. 

(2)  whether  commutator  or  slip  rings  are  burned, 
pitted,  grooved,  or  scored,  and  are  clean  and  free  from 
oil;  and  also  that  the  commutators  are  free  from  high 
mica. 

(3)  any  accumulation  of  carbon,  copper  dust,  oil,  or 
other  substances  in  the  slot  of  an  undercut  commutator. 

(4)  that  exposed  armature  and  field  terminal  condi- 
tions are  tight.  Give  special  attention  to  the  shunt  field 
connections  of  DC  motors. 

(5)  that  the  leads  are  not  broken  or  their  insulation 
is  not  cracked  or  broken. 

(6)  that  the  motor  windings  are  free  of  oil,  dust,  or 
lint  deposits. 

2.18.2  Periodic  Test 

2.18.2.1  Electric  Elevators  —  Category  5.    Slipping    (10) 
traction  or  drive  motor  stalling  test  procedure  is  as 
follows: 

(a)  Verify  with  the  empty  car  moving  in  up  direction 
at  inspection  speed,  car  and  hoistway  doors  in  the  closed 
position,  the  top  terminal  stopping  devices  temporarily 
rendered  ineffective  and  the  counterweight  is  stopped 
by  the  buffer: 

(1)  the  hoist  ropes  shall  slip  on  the  drive  machine 
sheave  or 

(2)  the  driving  machine  motor  shall  stall 

(b)  All  the  top  terminal  stopping  devices  shall  be 
restored  to  their  normal  operating  condition  in  confor- 
mity with  the  applicable  requirements  prior  to  returning 
equipment  to  service. 

(c)  Verify  with  the  empty  car  moving  in  down  direc- 
tion at  inspection  speed,  car  and  hoistway  doors  in  the 
closed  position,  the  bottom  terminal  stopping  devices 
temporarily  rendered  ineffective  and  the  car  is  stopped 
by  the  buffer: 

(1)  the  hoist  ropes  shall  slip  on  the  drive  machine 
sheave  or 

(2)  the  driving  machine  motor  shall  stall 

(d)  All  the  bottom  terminal  stopping  devices  shall  be 
restored  to  their  normal  operating  condition  in  confor- 
mity with  the  applicable  requirements  prior  to  returning 
equipment  to  service. 

NOTE  [2.18.2.1(a)  and  (c)]:  Power  may  be  removed  by  the  control 
from  the  driving  machine  motor  and  brake  after  loss  of  traction 
or  the  drive  machine  motor  has  stalled. 


27 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


2.18.3  Acceptance 

2.18.4  References 

(10)  2.18.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Section  208,  Rule  1001.2(b)(16),  1003.2,  and 
[NR  8.11.2.3.10(b)]. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.24,  8.11.2.1.2(p),  8.10.2.2.2(v)(b)(3),  and 
8.11.2.3.10(b). 

A17.3  —  Paragraph  3.8.1. 

ITEM  2.19 
GEARS,  BEARINGS,  AND  FLEXIBLE  COUPLINGS 

2.19.1  Periodic  Inspections 

2.19.1.1  Electric  Elevators 

(a)  Inspection  Made  With  Power  On 

(1)  Have  the  elevator  operated  in  each  direction, 
making  frequent  stops.  Observe  if  there  is  any  excessive 
play  or  backlash  in  the  bearings  or  gearing.  Unusual 
noise  or  play  is  usually  an  indication  of  gear  or  thrust 
bearing  trouble,  or  damage  to  bearing  liners,  rollers, 
or  balls.  It  may  be  constructive  to  run  the  elevator  at 
inspection  speed  as  well  as  rated  speed  to  fully  observe 
any  deterioration. 

(2)  Observe  through  the  access  covers  to  determine 
whether  gears  are  carrying  oil  and  that  oil  rings,  chains, 
or  other  methods  of  feeding  lubricant,  where  used,  oper- 
ate freely. 

(b)  Inspection  Made  With  Power  Off.  Examine  the  oil 
in  the  gear  case  and  bearing  oil  wells  to  determine  that 
it  is  free  of  damaging  metallic  particles  or  other  foreign 
substances.  Check  the  oil  level  and  note  any  leakage. 
Visually  check  the  gears  and  sleeve  bearings,  where  fea- 
sible, for  excessive  wear  and  scoring.  Examine  for  any 
oil  leaks  that  may  damage  the  flexible  part  of  the  cou- 
pling and  for  any  excessive  wear. 

Verify  that  when  the  flexible  part  of  the  coupling  fails, 
it  will  not  completely  disengage  from  each  unit.  Inspect 
flexible  couplings  for  wear  and  excess  slack. 

2.19.2  Periodic  Test 

2.19.2.1  Electric  Elevators.  If  possible,  visually 
inspect  flexible  couplings  to  determine  that  failure  of 
the  flexible  element  will  not  result  in  disengagement. 

2.19.3  Acceptance 

2.19.4  References 

2.19.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Section  208  and  Rules  1001.2(b)(17)  and 
1206.1a. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.24,  8.11.2.1.2(q),  and  8.6.1.6.2. 

A17.3  —  Paragraph  3.8.1. 


ITEM  2.20 

WINDING  DRUM  MACHINE  AND  SLACK  ROPE 

DEVICE,  STOP  MOTION  SWITCH,  AND  ROPE 

FASTENING 

2.20.1   Periodic  Inspections 

2.20.1.1  Electric  Elevators 

(a)  Winding  Drum  Machine.  Winding  drum  machines 
installed  under  A17.1  editions  prior  to  A17.1-1937  hav- 
ing winding-drum  machines  driven  by  two-phase  or 
three-phase  alternating-current  motors  shall  be 
equipped  with  adjustable  machine  automatic  terminal 
stop  mechanisms  set  to  directly  open  the  main  line  circuit 
to  the  driving  machine  motor  and  brake  before  or  coinci- 
dent with  the  opening  of  the  final  terminal  stopping 
switch  located  in  the  hoistway. 

(b)  Winding  Dram  Machine.  Winding  drum  machines 
installed  under  A17. 1-1937  and  later  editions  having 
winding-drum  machines  driven  by  two-phase  or  three- 
phase  alternating-current  motors  require  that  the  main- 
line circuit  to  the  motor  and  brake  be  directly  opened 
either  by  the  contacts  in  the  machine  stop-motion  switch 
(machine  final)  or  by  hoistway  final  limit  switches  oper- 
ated by  a  cam  attached  to  the  car.  This  requirement  does 
not  apply  to  elevator  machines  with  alternating-current 
motors  and  direct-current  brakes  and  direct-current 
main-line  or  potential  switches  controlled  by  final  termi- 
nal stopping  switches 

(c)  Winding  Drum  Machine.  For  elevators  installed 
under  A17. 1-1955  and  later  editions,  winding  drum 
machines  may  be  used  for  freight  elevator  only  and 
require  final  terminal  stopping  devices  located  in  the 
hoistway  operated  by  cams  attached  to  the  car  as  well 
as  terminal  stopping  devices  machine  final  (stop  motion 
switch)  located  on  and  operated  by  the  driving  machine. 

(d)  Terminal  Stopping  Device.  Chain,  belt,  or  rope- 
driven  mechanisms  shall  not  be  used  to  operate  the 
terminal  stopping  device  machine  final  (stop  motion 
switch). 

(e)  Inspection  and  Tests  —  Rope  Fastening  and  Drum 

(1)  Open  the  main  line  switch  and  examine  hoist 
rope  fastenings  in  the  drum. 

(2)  Note  that  the  required  tag  indicates  that  the 
ropes  have  been  refastened  within  12  mo  for  machines 
located  over  the  hoistway  and  within  24  mo  for  machines 
located  at  the  bottom  or  at  the  side  of  the  hoistway, 
except  where  provided  with  an  auxiliary  rope  fastening 
device. 

(3)  Visually  examine  and  hammer  test  the  drum 
for  defects  or  cracks. 

(4)  Where  ropes  extend  beyond  their  clamps  or 
sockets,  check  to  see  that  means  have  been  provided  to 
prevent  the  rope  ends  from  coming  out  of  the  inside  of 
the  drum  and  interfering  with  other  parts  of  the 
machine. 


(10) 


28 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


(/)  Slack  Rope  Device,  Slack  rope  devices  are  required 
on  winding  drum  machines. 

(1)  Inspection  Made  With  Power  Off.  Determine  that 
there  is  no  interference  with  free  and  complete  move- 
ment of  the  slack  rope  device.  Determine  that  it  is  located 
as  close  as  possible  to  the  machine  drum  so  that  the 
switch  will  open  with  a  minimum  of  slack  rope. 

(2)  Inspection  Made  With  Power  On.  Manually  trip 
the  slack  rope  device  and  attempt  to  run  the  car.  The 
enclosed  contact  must  remain  open  until  manually  reset. 

NOTE:    The  location  of  slack  rope  switches  can  be  found  in 

(a)  the  basement  machine,  in  the  machine  itself 

(b)  the  overhead  machine,  on  top  of  the  crosshead  or  inside  or 
near  the  machine 

(c)  the  pulley  type,  on  overhead  machine 

(g)  Final  Terminal  Stopping  Switch.  Inspect  both  the 
final  terminal  stopping  switches  located  on  and  oper- 
ated by  the  driving  machine  (stop  motion  switch)  and 
the  additional  stopping  switches  located  in  the  hoistway 
and  operated  by  cams  attached  to  the  car  for  condition 
and  operation. 

(1)  Verify  that  these  final  limits  directly  open  all 
contacts  in  the  power  circuit  for  machines  equipped  with 
single-  or  two-speed  AC  motors  and  AC  brake  coils. 

(2)  For  machines  equipped  with  DC  motors  and  DC 
brakes,  verify  that  each  final  limit  operates  independent 
relays  to  remove  power  from  the  driving  machine  and 
brake, 

(3)  Verify  that  the  machine  stopping  switches  are 
not  driven  by  chains,  ropes,  or  belts. 

2.20.2  Periodic  Test 

2.20.2.1  Electric  Elevators 

(a)  Machine.  With  the  car  resting  on  its  fully  com- 
pressed buffers,  check  that  at  least  one  turn  of  rope  is 
remaining  on  the  drum. 

(b)  Slack  Rope  Device 

(1)  With  the  car  running,  trip  the  device  manually 
using  a  piece  of  wood  or  similar  object.  The  enclosed 
contact  must  remain  open  until  manually  reset.  If  there 
is  any  question  about  the  operation  of  the  device,  lower 
the  car  onto  suitable  blocking  in  the  pit  and  determine 
that  the  resulting  slack  rope  will  actually  trip  the  device 
and  stop  the  car. 

(2)  For  double-belt  drum  machine,  check  that  the 
driving  belt  is  shifted  to  the  idler  pulley 

(c)  Final  Limits.  Test  operation  of  both  final  limits 
(machine  limit  and  limit  located  in  the  hoistway  oper- 
ated by  cams  on  the  car)  by  disabling  the  normal  stop- 
ping means  and  normal  terminal  stopping  means.  Then 
run  the  car  to  each  terminal  and  verify 

(1)  that  the  machine  final  located  on  the  driving 
machine  operates  before  or  coincident  with  the  final 
limit  located  in  the  hoistway 

(2)  that  the  final  limit  located  in  the  hoistway  oper- 
ates before  the  car  contacts  the  spring  buffer 


2.20.3  Acceptance 

2.20.3.1  Electric  Elevators.  Check  that  the  speed 
and  Code  limits  of  travel  are  not  exceeded  and  that  no 
counterweight  is  provided.  Verify  that  the  terminal  lim- 
its will  continue  to  operate,  at  the  bottom,  until  the  car 
rests  on  the  fully  compressed  buffer  and,  at  the  top,  until 
the  car  has  reached  its  maximum  upward  movement. 

2.20.4  References 

2.20.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  208.1,  209.3c(2),  209.3e,  210.2,  212.6, 
212.7,  212.10,  1001.2(b)(18),  1002.2d,  and  1206.3. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.24.1,  2.25.3.3.2,  2.25.3.5,  2.26.2,  2.20.2, 
2.20.7, 2.20.10, 8.11.2.1.2(w),  8.6.4.19.4, 8.6.4.19.5, 8.6.4.10, 
and  C8.6.12.4.2. 

A17.3  —  Paragraphs  3.8.2,  3.10.4,  3.12.6,  3.12.7,  and 
3.12.9. 


BELT- 


ITEM  2.21 
OR  CHAIN-DRIVE  MACHINE 


2.21.1  Periodic  Inspections 

2.21.1.1  Electric  Elevators 

(a)  The  installation  of  belt-drive  machines  or  chain- 
drive  machines  was  permitted  for  freight  elevators  in 
Al 7. 1-1937  and  previous  editions  when  rated  speeds 
did  not  exceed  60  ft/min  (0.30  m/s)  subject  to  the 
following: 

(1)  Single  belt-drive  machines  and  chain-drive 
machines  were  permitted,  if  provided  with  electrically 
released  brakes  applied  directly  to  the  driving  machine 
and  with  terminal  stopping  devices  as  required  for  elec- 
tric elevators. 

(2)  Chains  for  chain-drive  machines  were  required 
to  be  of  the  multiple-link  belt  type. 

(3)  Double  belt-drive  machines  were  permitted 
only  when  driven  from  a  line  shafting  supplying  power 
for  other  purposes. 

(b)  Belt-drive  and  chain-drive  machines  were  prohib- 
ited in  A17.1-1955  through  A17.1b-1983.  In  A17.1b-1983 
and  later  editions,  belt-drive  and  chain-drive  machines, 
also  known  as  indirect-drive  machines,  were  permitted 
subject  to  limitations. 

Check  for  proper  number  of  belts  or  chains.  Examine 
belts  for  splice  condition,  proper  tension,  wear,  burns, 
and  for  cuts  and  breaks  in  the  surface.  Check  drive 
chains  for  excessive  wear.  Belts  and  chains  are  required 
to  be  replaced  in  matched  sets.  Check  that  all  machine 
belt  guards  and  chain  guards  are  in  place  and  secure. 

Check  that  the  broken  belt  or  broken  chain  device 
interrupts  power  to  the  drive  machine  and  applies  the 
brake  if  any  belt  of  chain  becomes  slack.  Examine  belt- 
shifting  forks  of  double-belt  machines  to  determine 
whether  they  are  worn  excessively  by  the  edge  of  the 


do) 


29 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


belts,  and  check  their  operation  while  the  car  is  being 
operated  up  and  down  the  hoistway;  note  that  the  belts 
shift  to  the  proper  pulley  without  excessive  effort. 

Check  all  machine  fastening  bolts,  belt  guards,  and 
chair  guards.  Also,  check  the  fastenings  of  any  platforms 
under  ceiling  machinery.  Verify  that  the  brake  is  located 
on  the  traction  sheave  or  drum  assembly  side  of  the 
drive  machine. 

2.21.2  Periodic  Test 

2.21.3  Acceptance 

2.21.4  References 

2.21.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  208.9  and  1001.2(b)(19). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.24.9  and  8.11.2.1.2(s). 

A17.3  —  Paragraph  3.8.3. 

ITEM  2.22 
MOTOR  GENERATOR 

2.22.1  Periodic  Inspections 

2.22.1.1  Electric  Elevators.  Motor-generator  sets 
and  exciters  that  are  part  of  the  elevator  control  system 
should  operate  smoothly,  without  excessive  noise  or 
vibration.  Inspect  brushes  and  commutators  as  indicated 
in  Item  2.18.1. 

2.22.2  Periodic  Test 

2.223  Acceptance  Test  of  Generator  Suicide  Circuit 

2.22.3.1  Electric  Elevators.  Make  a  full  speed  run, 
without  releveling,  with  either  an  empty  car  to  the  bot- 
tom landing  or  a  fully  loaded  car  to  the  top  landing. 
Observe  the  suicide  circuit  operation  in  the  machine 
room. 

(a)  If  the  loop  circuit  is  of  the  type  that  is  not  opened 
when  the  car  stops,  connect  a  voltmeter  to  brushes  on 
the  adjacent  brush  stems  of  the  motor.  With  the  suicide 
circuit  temporarily  defeated,  observe  whether  the  volt- 
age steadily  increases.  If  so,  immediately  reestablish  the 
suicide  circuit  and  observe  a  decrease  in  voltage,  which 
verifies  that  the  suicide  circuit  is  operating. 

(b)  If  the  loop  circuit  is  the  type  that  is  opened  when 
the  car  stops,  connect  a  voltmeter  to  brushes  on  adjacent 
brush  stems  of  the  motor  generator  and  check  for  zero 
voltage  with  the  brake  set. 

(c)  Make  a  full  speed  run,  without  releveling,  either 
with  an  empty  car  to  the  bottom  landing  or  a  fully 
loaded  car  to  the  top  landing,  and  allow  the  brake  to 
set.  Observe  that  the  machine  does  not  pull  through  the 
brake,  thereby  ensuring  that  the  restored  suicide  circuit 
is  effective. 


2.22.4  References 

2.22.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  210.9f,  1001.2(b)(20),  and  1003.2J. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.26.9.7,  8.11.2.1.2(t),  and  8.10.2.2.2(t). 

ITEM  2.23 

ABSORPTION  OF  REGENERATED 

POWER 

2.23.1  Periodic  Inspections 

2.23.2  Periodic  Test 

2.23.3  Acceptance 

2.23.3.1  Electric  Elevators.  If  the  normal  power 
source  is  incapable  of  absorbing  the  energy  generated 
by  an  overhauling  load,  a  separate  means  such  as  a 
resistor  bank  must  be  provided  on  the  load  side  of  each 
elevator  power  supply  line  disconnecting  means  to 
absorb  the  regenerated  power. 

2.23.4  References 

2.23.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  210.10,  1001.2(b)(21),  and  1003.2k. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.26.10,  8.11.2.1.2(u),  and  8.10.2.2.2(u). 

A17.3  —  Paragraph  3.10.10. 

ITEM  2.24 
AC  DRIVES  FROM  A  DC  SOURCE 

2.24.1  Periodic  Inspections 

2.24.2  Periodic  Test 

2.24.2.1  Electric  Elevators:  Yearly  Test  of  AC  Drives 
From  a  DC  Source  (for  A17.1d-2000  and  Earlier  Editions); 
Category  1  Test  of  AC  Drives  From  a  DC  Source  (for 
A17.1-2000/B44-00  and  Later  Editions).  The  person  or 
firm  installing  or  maintaining  an  AC  drive  from  a  DC 
source  should  demonstrate  that  the  elevator  conforms 
to  Code  requirements. 

(a)  Run  the  car  and  demonstrate  that  either  of  two 
devices  will  prevent  the  flow  of  alternating  current  to 
the  AC  motor  and  cause  the  car  to  stop.  At  least  one  of 
the  devices  must  be  an  electromechanical  relay,  which 
in  its  de-energized  position  prevents  alternating  current 
from  flowing  in  the  hoist  motor. 

(b)  Prevent  the  above  relay  from  being  energized  and 
register  a  call.  Demonstrate,  with  the  doors  closed,  that 
the  brake  will  not  lift  and  the  car  will  not  move. 

(c)  Demonstrate  that  either  of  two  contactors  in  the 
brake  circuit  will  prevent  the  brake  from  lifting. 

(d)  Demonstrate  that  the  operation  of  any  of  the  elec- 
trical protective  devices  will  cause  both  devices  specified 
in  Item  2.24.2.1(a)  to  prevent  the  flow  of  alternating 
current  to  the  hoist  motor. 


30 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


(10) 


2.24.3  Acceptance 

Conduct  the  tests  described  in  Item  2.24.2. 

2.24.4  References 

2.24.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  210.2,  210.9(e),  1001.2(b)(22),  and 
1003.2L 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.26.2,  2.26.9.6,  8.11.2.1.2(v),  and 
8.10.2.2.2(m)(3). 

ITEM  2.25 
TRACTION  SHEAVES 

2.25.1  Periodic  Inspections 

2.25.1.1  Electric  Elevators 

(a)  Inspection  Made  With  Power  Off.  Inspect  fastenings 
for  tightness  where  demountable  sheaves  are  attached 
to  the  sheave  spider.  Note  any  evidence  of  lost  motion  or 
misalignment  of  the  traction  sheaves  with  other  sheaves. 

Examine  the  traction  sheaves  for  worn  grooves  and 
determine  that  all  ropes  seat  to  the  same  depth  in  the 
grooves.  Particles  of  metal  under  rope  sheaves  are  evi- 
dence of  groove  or  sheave  wear.  Carefully  examine  the 
sheave  for  cracks  or  other  deficiencies.  See  Item  2.24.1. 

(b)  Inspection  Made  With  Power  On.  Excessive  lubrica- 
tion of  the  wire  ropes  or  wear  of  the  sheave  grooves 
may  result  in  reduction  of  traction.  Test  traction  by 
operating  the  empty  car  in  the  up  direction  and  stop  it 
by  opening  the  emergency  stop  switch.  Any  material 
reduction  of  traction  may  be  noted  by  observing  slip- 
page between  ropes  and  traction  sheaves. 

(c)  Regrooving.  Prior  to  regrooving  any  sheave  or 
drum,  check  that  the  minimum  groove  bottom  diameter 
will  be  maintained  for  structural  integrity.  For  elevators 
installed  under  A17.1d-1986  and  later  editions,  the 
sheave  or  drum  must  be  marked  to  indicate  the  mini- 
mum permissible  groove  bottom  diameter. 

(d)  Rope  Changes.  Where  the  material,  grade,  number, 
or  diameter  of  ropes  have  changed  and  the  existing 
sheave  has  been  retained,  check  for  approval  by  a 
licensed  professional  engineer  or  the  original  equipment 
manufacturer. 

2.25.2  Periodic  Test 

2.25.2.1  Electric  Elevators:  5-Year  Test  (for 
A17.1d-2000  and  Earlier  Editions);  Category  5  Test  (for 
A17.1-2000/B44-00  and  Later  Editions).  For  passenger 
elevators  and  freight  elevators  permitted  to  carry 
employees,  the  driving  machine  must  safely  stop  and 
hold  the  car  with  125%  of  the  rated  load.  See  Item  2.15.2. 
See  Items  2.18.2.1  and  2.29.2.1(e)  for  the  test  procedure 
(when  the  car  or  counterweight  bottoms  on  its  buffer 
and  when  the  car  or  counterweight  safeties  are  applied, 
respectively)  for  checking  that  the  ropes  will  either  slip 
in  the  traction  sheave  or  that  the  machine  stalls. 


2.25.3  Acceptance 

2.25.3.1  Electric  Elevators.  Check  that  the  sheaves 
and  drums  are  permanently  and  legibly  marked  to  state 
the  minimum  groove  bottom  diameter  permissible  for 
regrooving  and  required  to  maintain  structural  integrity. 

2.25.4  References 

2.25.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  207.8,  208.2,  208.3,  212,  1001.2(b)(23), 
1202.14,  1206.1a,  and  1206.1b. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.16.8,  2.24.2,  2.24.3,  2.20,  8.11.2.1.2(w), 
8.7.2.21,  8.6.1.6.2,  and  8.6.4.1. 

A17.3  —  Paragraph  3.8.1. 

ITEM  2.26 

SECONDARY  AND  DEFLECTOR 

SHEAVES 

2.26.1  Periodic  Inspections 

2.26.1.1  Electric  Elevators.  Examine  the  overhead 
secondary  and  deflector  sheaves  and  test  them  with  light 
blows  from  a  small  hammer.  If  the  sound  resulting  from 
the  blows  is  dull  and  flat,  unlike  the  ring  given  by  sound 
metal,  sheave  parts  should  be  examined  carefully  for 
cracks. 

Examine  the  sheaves  for  worn  grooves  and  determine 
whether  all  ropes  seat  to  the  same  depth  in  the  grooves. 
Look  for  evidence  of  any  misalignment  of  sheaves. 
Determine  whether  bearing  bolts  are  secure. 

Inspect  sheave  shafts  and  bearings  for  wear  and  other 
defects.  Determine  whether  the  shafts  and  bearings  are 
adequately  lubricated. 

2.26.2  Periodic  Test 

2.26.3  Acceptance 

2.26.3.1  Electric  Elevators.  Record  and  check  for 
conformity  to  approved  drawings  and  specifications; 
the  diameter  of  drums,  overhead  sheaves,  and  secondary 
sheaves. 

2.26.4  References 

2.26.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Section  208  and  Rules  1001.2(b)(24)  and 
1206.1a. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.24,  8.11.2.1.2(x),  8.6.1.6.2. 

A17.3  —  Paragraph  3.8.1. 

ITEM  2.27 
ROPE  FASTENINGS 

2.27.1   Periodic  Inspections 

2.27.1.1  Electric  Elevators.  Examine  that  section  of 
rope  between  the  top  of  the  car  and  the  point  on  the 


31 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


counterweight  side  which  could  not  be  examined  from 
the  top  of  the  car  or  from  openings  in  the  counterweight 
runway  enclosure. 

Where  multiple  roping  is  used,  examine  overhead 
rope  anchorages  (dead-end  hitches).  Verify  that  the  hitch 
plate  supporting  the  wire  rope  fastenings  is  mounted 
on  the  top  of  supporting  members.  (See  Item  3.22.) 

Verify  that  all  lock  nuts  and  cotter  pins  are  in  place. 
Verify  the  data  shown  on  the  rope  data  tag  attached  to 
one  of  the  wire  rope  fastenings. 

2.27.2  Periodic  Test 

2.27.3  Acceptance 

2.27.4  References 

2.27.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  105.3c  and  1001.2(b)(25)  and  Section 
212. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.9.3.3  and  8.11.2.1.2(y)/  and  2.20. 

A17.3  —  Section  3.12. 


ITEM  2.28 
TERMINAL  STOPPING  DEVICES 

2.28.1  Periodic  Inspections 

2.28.1.1  Electric  Elevators 

(a)  Traction  Machines.  In  some  cases,  the  normal  ter- 
minal stopping  switches  are  located  in  the  machine  room 
and  operated  by  a  rope,  tape,  or  chain  attached  to  the 
car.  Examine  these  switches  for  alignment,  fastening, 
cleanliness,  and  general  condition  of  operation 
mechanisms. 

(b)  Winding  Drum  Machines.  Examine  the  final  termi- 
nal stopping  switch  operated  by  the  machine  for  align- 
ment fastening,  cleanliness,  lubrication,  and  general 
operating  condition. 

2.28.2  Periodic  Test 

2.28.2.1   Electric  Elevators 

(a)  Yearly  Test  of  Normal  Terminal  Stopping  Devices  (for 
A17.1d-2000  and  Earlier  Editions);  Category  1  Test  of 
Normal  Stopping  Devices  (for  A17.1-2000/B 44-00  and  Later 
Editions).  Check  normal  terminal  stopping  devices  as 
follows: 

(1 )  Render  inoperative  the  normal  elevator  stop- 
ping means. 

(2)  Render  inoperative  the  emergency  terminal 
stopping  device.  Do  not  disable  the  emergency  terminal 
speed  limiting  device. 

(3)  Run  the  car  at  contract  speed  into  the  bottom 
terminal  and  demonstrate  that  the  car  slows  down  and 
stops  in  the  vicinity  of  the  bottom  terminal. 

(4)  Repeat  the  above  test  at  the  top  terminal. 


(5)  Restore  the  normal  stopping  means  and  emer- 
gency terminal  stopping  device.  Check  normal  elevator 
operation. 

(b)  5-Year  Test  of  Emergency  Terminal  Stopping  and 
Emergency  Speed  Limiting  Devices  (for  A17.1d-2000  and 
Earlier  Editions);  Category  5  Test  of  Emergency  Terminal 
Stopping  and  Emergency  Speed  Limiting  Devices  (for 
A17.1-2000/B44-00  and  Later  Editions).  For  static  control 
elevators  with  rated  speeds  over  500  ft/min  (2.54  m/s), 
installed  under  A17.1b-1983  through  A17.1a-1991,  or 
with  rated  speeds  over  200  ft/min  (1.02  m/s)  installed 
under  A17.1b-1992  and  later  editions,  use  emergency 
terminal  stopping  devices  where  required,  except  if  an 
emergency  terminal  speed  limiting  device  is  used  (see 
Item  3.5.2)  or  if  the  normal  terminal  stopping  device 
limits  the  generator  shunt  field  directly.  Check  as 
follows: 

(1)  Have  the  normal  elevator  stopping  means 
disabled. 

(2)  Have  the  normal  terminal  stopping  device 
disabled. 

(3)  Have  the  car  run  at  rated  speed  into  the  bottom 
terminal  and  verify  that  the  car  stops  and  power  is 
removed  from  the  driving-machine  motor  and  brake.  It 
is  permissible  for  the  car  to  restart  automatically,  pro- 
vided that  no  other  electrical  protective  device  has 
operated. 

(4)  Have  the  above  test  repeated  at  the  top  terminal. 

(5)  Restore  the  normal  stopping  means  and  normal 
terminal  stopping  device.  Check  normal  operation. 

2.28.3  Acceptance 

2.28.3.1  Electric  Elevators.  Perform  the  test  in  Item 
2.28.2(a)  for  the  bottom  normal  terminal  stopping  device 
in  the  down  direction  with  125%  of  rated  load  for  passen- 
ger elevators  and  freight  elevators  permitted  to  carry 
passengers.  The  bottom  normal  terminal  stopping 
devices  of  freight  elevators  not  permitted  to  carry  pas- 
sengers are  to  be  tested  with  rated  load.  The  top  normal 
terminal  stopping  devices  for  all  elevators  must  be  tested 
with  no  load.  The  car  should  stop  at  or  near  the  terminal 
landings  with  all  loads,  except  where  an  automatic  level- 
ing device  is  provided,  in  which  case  the  normal  terminal 
stopping  device  should  stop  the  car  within  the  range  of 
the  leveling  device. 

2.28.4  References 

2.28.4.1  Electric  Elevators.  A17.1d-2000/B44-00 
and  earlier  editions  —  Section  209  and  Rules 
1001.2(b)(26)  and  1002.3f. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.25,  8.11.2.1.2(z),  and  8.11.2.3.6. 

A17.3  —  Paragraphs  3.8.2,  3.9.1,  3.9.2,  and  3.10.4. 


32 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


Table  2.29.2(a)     Maximum  Safety  Rope  PulLout 


For  Car  Safeties: 

200  ft/min  or  less 

201  to  375  ft/min 
Over  375  ft/min 

For  Counterweight  Safeties: 
All  speeds 


42  in. 
36  in. 
30  in. 


42  in. 


GENERAL  NOTES: 

(a)  1  in.  =  25.4  mm 

(b)  1  ft/min  =  5.08  E  -  03  m/s 

ITEM  2.29 
CAR  AND  COUNTERWEIGHT  SAFETIES 

2.29.1  Periodic  Inspections 

See  Item  5.8.1.1. 

(io)    2.29.2  Periodic  Test 

(a)  Yearly  Inspection  (Power  Off)  of  Steel  Guide  Rail 
Safeties  (for  A17.1d-2000  and  Earlier  Editions);  Category  1 
Test  (Power  Off)  of  Steel  Guide  Rail  Safeties  (for  A17.  1-2000/ 
B44-00  and  Later  Editions) 

(1)  Examine  the  car  and  counterweight  guide  shoes 
and  their  fastenings  to  determine  that  they  are  properly 
secured,  aligned,  and  adjusted.  Check  the  gibs  or  rollers 
for  excessive  wear. 

(2)  See  Item  5.8.1  for  the  running  clearances 
between  the  guide  rails  and  the  gripping  face  of  the 
safeties. 

(3)  Determine  that  all  moving  parts  of  the  safety 
are  clean,  lubricated,  not  corroded,  and  free  to  operate. 

(4)  On  drum-operated  Type  B  safeties,  inspect  the 
safety  rope  and  its  deflecting  sheaves  and  their  fasten- 
ings to  determine  that  they  are  not  worn  excessively  or 
corroded,  and  that  the  rope  sheaves  are  securely  fastened 
and  are  in  operating  condition. 

Safety  drum  rope  must  be  of  a  corrosion-resistant 
material  and  not  be  of  tiller  rope  construction.  Before 
any  test  is  made  on  drum  safeties,  ensure  that  the  proper 
safety  wrench  is  available,  then  pull  out  the  safety  drum 
rope  until  the  safety  jaws  contact  the  rail  and  start  to 
exert  pressure.  The  movement  of  the  safety  drum  rope, 
starting  from  a  fully  retracted  position,  must  not  exceed 
the  values  based  on  rated  speed  shown  in  Table  2.29.2(a). 

The  number  of  turns  of  rope  remaining  on  the  safety 
drum  must  be  sufficient  to  allow  for  additional  pullout 
of  the  safety  drum  rope  to  ensure  proper  operation  of 
the  safety  when  the  governor  is  operated  due  to  an 
overspeed  condition. 

Reset  the  safety  on  completion  of  the  above  inspection. 
Keep  sufficient  tension  on  the  safety  drum  rope  to  pre- 
vent kinking  and  to  ensure  that  the  rope  will  be  evenly 
and  uniformly  wound  on  the  safety  drum  with  no  slack. 

(5)  On  Type  A  and  Type  B  safeties  that  are  self- 
releasing,  it  is  not  necessary  to  actuate  the  safety  prior 


to  a  test.  Inspect  the  mechanism  to  see  that  it  is  clean 
and  lubricated  and  that  there  is  no  corrosion  present. 

(6)  Before  checking  the  adjustments  of  the  trip  (fin- 
ger) rods  and  rollers,  examine  all  crosshead  pivot  points 
and  linkage  for  lost  motion,  loose  or  missing  set  screws, 
and  excessive  friction.  Any  lost  motion  in  the  actuation 
lever  should  be  removed.  Lost  motion  and  the  inertia  of 
the  governor-rope  system  may  cause  safety  applications 
under  normal  starting  conditions. 

(7)  With  the  elevator  car  platform  at  a  convenient 
height,  the  safety  can  readily  be  checked  from  the  pit 
to  determine  that 

(a)  all  rollers  are  properly  in  place. 

(b)  trip  (finger)  rods  are  in  position  to  pick  up 
the  rollers. 

(c)  when  the  governor  rope  is  pulled  to  impart 
motion  to  the  trip  (finger)  rods,  the  roller  must  move 
upward  into  the  ultimate  wedged  positions  in  the  safety 
block  without  restriction.  The  operation  shall  be 
repeated  several  times  observing  that  the  rollers  fall 
toward  the  rail.  When  the  "finger"  engages  the  roller,  if 
there  is  any  tendency  for  the  roller  to  fall  away  from 
the  rail,  a  jam  between  the  roller  and  safety  block  can 
result  in  a  safety  failure. 

(d)  normally,  the  rollers  should  be  at  the  lowest 
point  of  travel  resting  against  the  guard;  have  the  trip 
(finger)  rods  adjusted  so  that  the  rollers  engage  simulta- 
neously when  wedged  between  the  roller  pocket  and 
the  guide  rail. 

(8)  The  Code  requires  a  safety  mechanism  switch, 
operated  by  the  car  safety,  to  be  installed  on  all  safeties. 
While  inspecting  the  safety,  determine  that  the  switch 
contacts  open  before  the  safety  jaws  or  rollers  contact 
the  guide  rails.  Then  open  the  switch  manually  and 
determine  that  the  car  will  not  run  when  the  switch 
is  open. 

(b)  Yearly  Inspection  (Power  Off)  of  Wood  Guide  Rail 
Safeties  (for  A17.1d-2000  and  Earlier  Editions);  Category  1 
Test  (Power  Off)  of  Wood  Guide  Rail  Safeties  (for 
A17.1-2000/B44-00  and  Later  Editions) 

(1)  The  effectiveness  of  safeties  of  this  type  depends 
on  a  substantial  initial  engagement  of  the  toothed  safety 
jaw  with  the  wood  guide  rail  in  a  manner  to  produce 
an  increasing  engagement  with  the  rail  until  the  car  or 
counterweight  is  brought  to  rest.  Therefore,  the  condi- 
tion of  the  guide  rails  is  a  prime  consideration  in  making 
an  examination  of  the  equipment. 

(2)  The  guide  rails  must  be  of  first  quality  selected 
wood  with  the  width  sized  to  fill  the  car  guide  shoe 
minus  the  normal  running  clearance.  Guide  rails  that 
are  more  than  %  in.  (3.2  mm)  undersize  in  width  or 
show  evidence  of  "combing"  by  the  safety  jaws  should 
be  replaced. 

(3)  From  the  top  of  the  car,  examine  all  safety 
operating  parts  including  levers  and  linkage  to  be  sure 
that  all  keys  and  set  screws  are  in  place  and  tight.  There 


33 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
^  No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


should  not  be  an  excessive  amount  of  lost  motion  in  the 
transmittal  of  movement  to  the  finger  rods  actuating  the 
safety  jaws. 

(4)  From  the  pit,  with  the  elevator  car  platform  at 
a  convenient  height,  the  safety  jaws  can  be  readily  exam- 
ined and  applied  against  the  guide  rails  by  pulling  the 
governor  rope.  Bring  the  safety  jaws  in  contact  with  both 
guide  rails  in  such  a  manner  that  any  downward  motion 
of  the  car  would  cause  the  jaw  teeth  to  dig  into  the  rails. 

(5)  When  a  safety  operating  switch  is  provided,  the 
motion  of  bringing  the  safety  jaws  in  contact  with  the 
rails  must  be  sufficient  to  operate  the  switch. 

(6)  See  Item  5.8.1  for  the  running  clearances 
between  the  guide  rails  and  the  gripping  face  of  the 
safeties. 

(c)  Yearly  Test  of  Safeties  (for  A17.1d-2000  and  Earlier 
Editions);  Category  1  Test  of  Safeties  (for  All 1-2000/844-00 
and  Later  Editions) 

(1)  After  the  safety  has  been  inspected,  position  the 
car  or  counterweight  in  the  lower  portion  of  the  hoistway 
so  that  it  will  be  accessible  after  the  test.  Jump  out  the 
switches  on  the  governor  and  safety  (or  that  part  of  the 
safety  circuit)  that  would  prevent  a  full  setting  of  the 
safety  Start  the  car  or  counterweight,  whichever  is  being 
tested,  in  the  down  direction  at  the  slowest  operating 
speed  and  manually  trip  the  governor.  Type  A  safeties 
without  governors  that  are  operated  as  a  result  of  the 
breaking  or  slackening  of  the  hoisting  ropes  shall  be 
tested  by  obtaining  the  necessary  slack  rope  to  cause  it 
to  function.  On  centrifugal  governors  that  do  not  have 
a  dropping  jaw,  engage  the  flyweight  into  the  actuating 
device  before  starting  the  car  down.  Run  the  car  down 
until  the  machine  stalls  or  drives  through  the  hoisting 
ropes.  Next,  open  the  main  line  disconnect  switch, 
remove  any  jumpers,  and  proceed  to  the  safety  being 
tested. 

NOTE:  Examine  all  parts  of  the  safety  equipment  to  determine 
if  anything  is  broken  or  out  of  order.  See  that  all  ropes  are  properly 
on  the  drum  to  fully  apply  the  safety,  be  sure  that  not  less  than 
three  turns  of  rope  remain  on  the  drum.  This  is  necessary  to  meet 
the  requirement  of  not  less  than  three  turns  remaining  on  the  drum 
after  a  rated  load,  rated  speed  test-  Flexible  guide  clamp  safeties 
that  are  drum-operated  do  not  require  any  turns  of  rope  to  remain 
on  the  drum  after  a  test.  Verify  that  there  is  no  excess  slack  in  the 
suspension  ropes  that  could  result  in  the  car  falling  should  the 
safety  slip.  Examine  all  parts  of  the  safety  equipment  to  determine 
if  anything  is  broken  or  out  of  order. 

(2)  Check  the  platform  for  level.  All  elevators 
installed  under  A17. 1-1955  and  later  editions  must  not 
be  out  of  level  more  than  %  in. /ft  (31  mm/m)  in  any 
direction. 

Elevators  installed  prior  to  A17.1-1955  must  not  be  out 
of  level  more  than  \  in. /ft  (42  mm/m)  in  any  direction. 
Counterweight  safeties  may  be  set  in  the  pit  or  just  above 
the  car.  In  either  case,  be  careful  of  the  final  location  so 
that  it  will  be  accessible  after  the  test. 


After  the  safety  has  been  examined,  restore  power 
and,  if  necessary,  jump  the  slack  rope  switch.  Then 
release  the  safety.  Restore  and  reset  the  governor  to 
operating  position. 

(3)  Type  A  and  self -releasing  Type  B  safeties  are 
released  by  moving  the  car  or  counterweight  in  the  up 
direction.  This  should  be  accomplished  with  one  short 
move.  After  one  move,  be  sure  that  the  governor  has 
released  the  governor  rope.  If  it  is  not  released,  move 
the  governor  sheave  or  the  jaw  to  gain  this  release. 

(4)  The  drum-operated  Type  B  safety  is  released 
with  a  safety  wrench  from  inside  the  car  or  at  the  coun- 
terweight. This  is  a  two-person  operation.  One  person 
must  be  stationed  on  top  of  the  car,  or  in  the  pit,  to  hold 
the  governor  rope  so  it  does  not  overhaul  while  the 
second  person  releases  and  resets  the  governor.  The  sec- 
ond person  should  then  proceed  to  the  car  or  counter- 
weight and  release  the  safety  while  the  first  person  is 
holding  back  on  the  rope  and  reinsert  into  the  releasing 
carrier. 

(5)  Examine  all  of  the  safety  parts  to  determine  that 
they  have  returned  to  the  normal  running  positions,  and 
be  sure  that  there  is  no  slack  in  the  safety  rope. 

(6)  Inspect  the  guide  rails  for  scoring  and  loose 
hardware.  Dress  any  scored  rail  surface. 

(7)  It  is  not  necessary  to  record  the  stopping  dis- 
tance in  this  test. 

(8)  Determine  that  all  jumpers  have  been  removed. 

(d)  Yearly  Test  of  Wood  Guide  Rail  Safeties  (for 
A17.U-2000  and  Earlier  Editions);  Category  1  Test  of  Wood 
Guide  Rail  Safeties  (for  A17.1-2000/B44-00  and  Later 
Editions).  With  governor-operated  safeties,  set  the  gov- 
ernor in  the  applied  position  and  run  the  car  in  the 
down  direction  from  the  controller  to  see  that  it  will 
operate  the  safety.  Continue  to  operate  until  the  ropes 
slip  on  traction  machines  or  slacken  on  drum  machines. 
For  Type  A  safeties  without  governors,  set  blocking  in 
the  pit  securely  and  run  the  car  down  slowly  to  see  that 
the  jaws  come  into  proper  position  when  a  slack  rope 
is  obtained. 

(e)  5-Year  Test  of  Steel  Guide  Rail  Safeties  (Rated  Load, 
Rated  Speed)  (for  A17  Ad-2000  and  Earlier  Editions); 
Category  5  Test  of  Steel  Guide  Rail  Safeties  (Rated  Load, 
Rated  Speed)  (for  A17.1-2000/B44-00  and  Later  Editions) 

(1)  Place  the  rated  load  on  the  elevator  car  platform 
using  test  weights,  centered  on  each  quarter  symmetri- 
cally with  relation  to  the  centerline.  Test  counterweight 
safeties  with  no  load  in  the  car.  Jump  out  any  governor 
switches,  or  any  part  of  the  safety  circuit,  that  will  pre- 
vent a  full  setting  of  the  safety.  Shut  down  adjacent  cars 
during  test.  If  you  are  testing  a  drum-type  safety,  you 
must  shut  down  any  car  adjacent  to  the  releasing  carrier, 
and  keep  it  shut  down  until  all  slack  in  the  safety  rope 
is  under  control.  If  a  safety  wrench  is  to  be  used,  put  it 
in  the  elevator  car  and  remove  the  release  hole  cover  on 


34 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


the  car  floor.  Do  not  insert  the  wrench  into  the  release 
hole  until  after  the  safety  is  applied. 

(2)  For  Type  B  and  C  safeties,  the  safety  mechanism 
switch  (plank  switch)  must  not  be  jumped  out.  The 
switch  shall  be  tested  for  proper  operation  and,  for  the 
duration  of  the  test,  temporarily  adjusted  to  open  as 
close  as  possible  to  the  position  at  which  the  car  safety 
mechanism  is  in  the  fully  applied  position.  The  opening 
of  this  switch  has  an  effect  on  the  safety  slide,  which 
must  be  taken  into  consideration. 

(3)  When  testing  safeties,  the  following  steps  must 
be  considered: 

(a)  Before  setting  the  car  safety,  tie  down  any 
counterweight  safety  lift  lever  with  four  wraps  of  No.  16 
gage  copper  wire  or  equivalent.  This  will  avoid  an  acci- 
dental setting  of  the  counterweight  safety  by  inertia. 
Do  not  block  the  counterweight  safety;  it  must  remain 
workable.  Reverse  the  procedure  for  testing  counter- 
weight safeties. 

(b)  Most  compensating-rope  sheaves  have  a 
tie-down  device.  This  device  will  probably  lock  when 
a  safety  is  set.  To  avoid  the  work  required  to  release 
the  device,  it  is  recommended  that  the  device  be  made 
inoperative  or  be  removed  and  the  compensating-rope 
sheave  be  tied  down  with  a  line  to  keep  it  in  place. 

(c)  Make  sure  that  any  adjustable  stops  on  the 
governor  tension  sheave  are  set  very  close  to  the  mov- 
able unit. 

(d)  Make  sure  that  the  buffers  are  fully  extended 
and  filled  to  a  normal  level  with  oil. 

(4)  Add  the  dimension  of  the  safety  rope  pullout 
to  the  estimated  stopping  distance  in  order  to  determine 
the  distance  the  car  will  travel  after  the  governor  is 
tripped.  Spot  the  car  or  counterweight  this  distance 
above  the  point  where  the  stop  is  desired.  Put  a  reference 
mark  on  a  suspension  rope  (chalk  mark  or  tape).  Move 
the  car  or  counterweight  up  a  few  floors,  far  enough  to 
reach  your  mark  at  full  speed.  Start  the  car  or  counter- 
weight down  and  manually  trip  the  governor  when  you 
see  the  mark.  Let  the  elevator  run  until  either  the  suspen- 
sion ropes  slip  in  the  traction  sheave  or  the  driving 
machine  stalls  (on  winding  drum  machines,  stop  at  the 
first  indication  of  slack  rope),  then  immediately  remove 
power  from  the  hoisting  machine.  Type  A  safeties  with- 
out governors  that  are  operated  as  a  result  of  the  break- 
ing or  slackening  of  the  hoisting  ropes  shall  be  tested 
by  obtaining  the  necessary  slack  rope  to  cause  it  to  func- 
tion. If  a  normal  safety  setting  occurs,  put  all  the  cars 
back  in  service,  except  the  one  being  worked  on  and 
the  one  adjacent  to  the  releasing  carrier.  On  an  elevator 
with  a  winding  drum  machine,  be  sure  to  take  up  any 
slack  rope  before  the  safety  is  released. 

(5)  Remove  electrical  jumpers  and  reset  the  gover- 
nor, unless  it  is  a  drum-operated  safety.  If  it  is  drum 
operated,  one  person  will  go  to  the  car  top  and  hold 


Table  2.29.2(b)    Minimum  and  Maximum 

Stopping  Distances  for  Type  B  Car  Safeties  With 

Rated  Load,  and  Type  B  Counterweight  Safeties 

With  No  Load  in  the  Car 


Rated 

Stopping  Distances 

Speed, 

Minimum,                           Maximum, 

ft/min 

ft-in. 

ft-in. 

0  to  125 

0-1 

1-0 

150 

0-1 

1-1 

175 

0-2 

1-3 

200 

0-2 

1-4 

225 

0-3 

1-6 

250 

0-3 

1-7 

300 

0-5 

1-11 

350 

0-7 

2-4 

400 

0-9 

2-10 

450 

0-11 

3-4 

500 

1-1 

3-11 

600 

1-7 

5-3 

700 

2-2 

6-10 

800 

2-9 

8-9 

900 

3-6 

10-10 

1,000 

4-4 

13-2 

1,100 

5-2 

15-9 

1,200 

6-2 

18-7 

1,300 

7-3 

21-8 

1,400 

8-5 

25-0 

1,500 

9-8 

28-7 

1,600 

11-0 

32-5 

1,700 

12-5 

36-5 

1,800 

13-11 

40-9 

GENERAL  NOTES: 

(a)  This  table  is  for  rated  load,  rated  speed  test  only.  Use 
Table  2.17.3  in  the  Code  for  rated  load,  overspeed  test  only. 

(b)  Use  Table  2.17.3  of  the  A17.1  Code  when  performing  accept- 
ance tests. 

(c)  1  ft/min  =  5.08  E  -  m/s 

(d)  1  in.  =  25.4  mm 


the  safety  rope  as  the  governor  is  reset.  Inspect  the  gover- 
nor for  any  damage. 

(6)  Proceed  to  the  elevator  car  to  release  the  safety. 
Before  the  safety  is  released,  check  the  platform  for  level. 
On  all  elevators  installed  under  A17.1-1955  and  later 
editions,  it  must  not  be  out  of  level  more  than  %  in. /ft 
(31  mm/m)  in  any  direction.  On  elevators  installed  prior 
to  A17.1-1955,  it  must  not  be  out  of  level  more  than 
l/2  in. /ft  (42  mm/m)  in  any  direction.  Elevators  installed 
prior  to  A17.1-1955  are  allowed  a  greater  flexibility  of 
stopping  distance  than  shown  in  Table  2.29.2(b).  For 
gradual  wedge  clamp,  flexible  guide  clamp,  and  wedge 
clamp  (constant  retarding  force)  Type  B  safeties,  see 
Tables  2.29.2(c),  2.29.2(d),  and  2.29.2(e). 

(7)  Generally  it  will  not  be  possible  to  inspect  the 
safety  due  to  the  location  of  the  car;  therefore,  the  safety 
must  be  released.  To  do  this  on  other  than  drum- 
operated  Type  B  safeties,  move  the  car  or  counterweight, 


35 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Table  2.29.2(c)    Gradual  Wedge  Clamp  Safety 


Table  2.29.2(e)    Wedge  Clamp  Safety  (Constant 


Maximum 
Stopping 

Ketard 

ing  i-orcej 

Maximum 

Distance 

Minimum  Stopping  Distance 

Stopping 
Distance 

Minimum  Stc 

Governor- 
Tripping 

Car  +  Rated 
Load  or  for 

Car  +  Rated 
Load  or  for 

)pping  Distance 

Governor- 

Car  +  Rated 

Car  +  Rated 

Speed, 

Counterweight, 

Car+  150 

Counterweight, 

Tripping 

Load  or  for 

Load  or  for 

ft/min 

ft-in. 

lb,  ft-in. 

ft-in. 

Speed, 

Counterweight, 

Car  +  150 

Counterweight, 

175 

6-2 

1-5 

1-11 

ft/min 

ft-in. 

lb,  ft-in. 

ft-in. 

200 

6-3 

1-5 

2-0 

175 

1-4 

0-10 

0-10 

300 

6-11 

1-6 

2-4 

200 

1-6 

0-11 

1-0 

400 

7-10 

1-8 

2-7 

300 

2-0 

1-0 

1-2 

500 

8-10 

1-11 

2-11 

400 

2-10 

1-2 

1-7 

600 

9-11 

2-1 

3-4 

500 

3-11 

1-5 

2-0 

700 

11-1 

2-4 

3-10 

600 

5-2 

1-7 

2-5 

800 

12-4 

2-7 

4-6 

700 

6-8 

1-11 

3-0 

900 

13-6 

3-0 

5-4 

800 

8-6 

2-2 

3-7 

1,000 

14-8 

3-6 

6-1 

900 

10-8 

2-7 

4-4 

1,100 

16-0 

4-0 

7-0 

1,000 

12-11 

3-0 

5-1 

1,200 

17-4 

4-7 

8-0 

1,100 

15-6 

3-6 

6-0 

1,300 

18-6 

5-1 

9-0 

1,200 

18-5 

4-0 

7-1 

1,400 

19-8 

5-8 

10-1 

1,300 

21-8 

4-7 

8-2 

1,500 

21-1 

6-2 

11-1 

1,400 

25-0 

5-1 

9-4 

1,500 

28-3 

5-7 

10-5 

GENERAL  NOitb: 

(a)   For  elevators  installed  prior  to  A17. 1-1955. 

GENERAL  NOTES: 

(b)  1  ft/min 

-  5.08  E  -  03  m/s 

(a)  For  elevators  installed  prior 

to  A17.1-1955. 

(c)    1  in.  = 

25.4  mm 

(b)  1  ft/min 

(c)  1  in.  = 

=  5.08  E  -  03  m/ 
25.4  mm 

5 

Table  2.29.2(d)    Flexible  Guide  Clamp  Safety 


Maximum 

Stopping 

Distance 

Minimum 

Stopping  Distance 

Governor- 

Car  +  Rated 

Car  +  Rated 

Tripping 

Load  or  for 

Load  or  for 

Speed, 

Counterweight, 

Car+  150 

Counterweight, 

ft/min 

ft-in. 

lb,  ft-in. 

ft-in. 

175 

0-10 

0-5 

0-6 

200 

0-11 

0-6 

0-7 

300 

1-7 

0-7 

0-8 

400 

2-5 

0-8 

1-1 

500 

3-5 

0-11 

1-6 

600 

4-10 

1-2 

1-11 

700 

6-5 

1-6 

2-5 

800 

8-2 

1-10 

3-2 

900 

10-4 

2-2 

3-11 

1,000 

12-7 

2-7 

4-8 

1,100 

15-2 

3-0 

5-8 

1,200 

18-0 

3-6 

6-8 

1,300 

21-1 

4-0 

7-10 

1,400 

24-7 

4-7 

8-11 

1,500 

28-0 

5-2 

10-0 

GENERAL  NOTES: 

(a)   ft/min 

=  5.08  E  -  03  m/s 

(b)   1  in.  = 

25.4  mm 

whichever  is  being  tested,  in  the  up  direction.  On  drum- 
operated  safeties,  after  checking  for  at  least  three  turns 
of  rope  remaining  on  the  drum,  wind  in  the  safety  drum 
rope  while  a  second  person  is  standing  on  top  of  the 
car  holding  back  on  the  rope.  To  complete  the  winding, 
he  must  insert  the  minie  ball  into  the  releasing  carrier. 
Move  the  car,  or  counterweight,  and  measure  the  safety 
slide  mark  on  the  rails.  The  stopping  distance  is  the 
average  length  of  the  continuous  marks  on  all  four  rail 
faces  after  deducting  the  length  of  the  safety  jaw  or 
wedge.  See  Item  2.29.2.1(f)  for  a  detailed  description  of 
measuring  safety  slide  marks. 

(8)  The  stopping  distance  must  be  within  the  range 
shown  in  Table  2.29.2(b).  The  stopping  distance  permit- 
ted is  determined  by  the  tripping  speed  of  the  governor. 
When  performing  a  rated  load,  rated  speed  test,  the 
rated  speed  is  the  speed  at  which  the  governor  is  tripped 
during  this  test. 

(9)  Check  the  rails  and  dress  any  scored  surface. 
Also,  check  for  any  loose  rail  or  bracket  fastenings. 

(10)  To  inspect  a  car  safety,  move  the  car  to  a  conve- 
nient height  above  the  pit  floor.  A  counterweight  safety 
can  be  inspected  from  the  car  top.  Examine  all  parts  of 
the  equipment  to  determine  if  any  are  broken  or  out  of 
order.  Be  sure  that  the  ropes  are  in  their  sheave  grooves 
and  are  properly  wound  on  the  drum.  Be  sure  that  the 
safety  has  returned  to  the  normal  running  position. 


36 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Fig.  2.29.2(a)    Safety  Marks  on  Guide  Rails,  Poor 
Illumination 


Guide  rail 


CO     o 

to  ^Z 

o    CD 

2  = 

CD 


Fig.  2.29.2(b)    Safety  Marks  on  Guide  Rails,  Good 
Illumination 


Guide  rail 


CO 


I 


GENERAL  NOTE:     A  =  start  of  slide;  B  =  end  of  slide. 


GENERAL  NOTE:     A  =  start  of  slide;  B  =  end  of  slide. 


(11)  After  the  safety  tests  are  complete 

(a)  remove  any  jumpers  from  the  safety  switches 

(b)  remove  any  line  from  the  compensating-rope 
sheave 

(c)  replace  the  tie-down  device  or  any  of  its  parts 
that  were  removed 

(d)  remove  any  tie  down  that  was  wrapped  on 
the  car  or  counterweight  safety  lift  lever 

(e)  readjust  the  safety-mechanism  switch 

(12)  Ensure  the  required  test  tags  are  installed. 

(f)  Determination  of  Slide  on  the  Guide  Rails  for 
Type  B  Safeties 

(1)  General.  Following  a  safety  test,  there  is  often 
considerable  difficulty  in  determining  the  actual  slide 
of  the  safety  jaws  on  the  guide  rails.  In  the  case  of  a 
well-lubricated  rail,  the  first  action  of  the  closing  jaws 
is  to  squeeze  out  the  film  of  oil  or  grease.  This  area  of 
reduced  lubrication  is  often  mistaken  for  part  of  the 
mark  but  should  not  be  included  in  the  measured  sliding 
distance.  Start  the  measurement  at  the  point  where 
actual  contact  is  made  by  a  jaw  on  the  guide  rail  and  is 
generally  indicated  by  a  slight  roughening  along  the 
line  of  travel  of  the  jaw.  This  has  a  somewhat  different 
color;  the  guide  rail  looks  gray  in  contrast  with  the  pol- 
ished surface. 

(2)  Effect  of  Illumination.  The  angle  of  illumination 
and  the  position  of  the  observer  have  much  to  do  with 
the  ease  with  which  the  marks  may  be  identified.  The 
marks  showing  in  Figs.  2.29.2(a)  and  2.29.2(b)  are  the 


same  marks  viewed  from  the  same  position  with  identi- 
cal exposures  but  with  the  illumination  changed  from 
60  deg  with  the  light  level  with  the  end  of  the  marks, 
to  45  deg  with  the  light  considerably  below  the  marks. 
Often  it  is  possible  to  pick  up  the  marks  with  the  light 
source  almost  in  line  with  the  face  of  the  guide  rail. 

(3)  Marks  on  Dry  Guide  Rails.  When  the  guide  rail 
is  dry,  as  is  the  case  with  roller  guides,  the  mark  may 
be  very  difficult  to  determine  as  there  is  no  disturbed 
film  of  lubricant  to  aid  in  its  location.  However,  by  care- 
fully adjusting  the  position  of  the  light  source  and  chang- 
ing the  angle  of  vision,  it  is  generally  possible  to 
determine  the  point  at  which  the  mark  starts. 

(4)  Determination  of  Final  Position  of  Jaws.  As  the 
jaws  tend  to  bite  more  deeply  into  the  guide  rail  after 
full  application,  even  with  types  where  the  pressure  of 
the  jaws  on  the  guide  rail  is  designed  to  remain  constant, 
there  is  little  difficulty,  as  a  rule,  in  determining  the  final 
position  of  the  jaws.  Where  the  guide  rails  are  lubricated, 
the  terminal  mark  may  generally  be  indicated  by  the 
piling  up  of  oil  or  grease  below  the  safety  shoe;  fre- 
quently the  entire  print  of  the  shoe  or  gib  may  be  seen 
on  the  guide  rail  in  the  final  stop  position. 

(5)  Interrupted  Marks.  It  occasionally  happens  that 
the  safety  jaws  will  come  in  contact  with  the  guide  rail 
and  leave  a  mark  for  a  certain  distance,  and  then  the 
mark  will  be  lost  for  a  distance  of  a  few  inches  or  perhaps 
a  foot.  This  may  be  due  to  several  causes,  among  them 
slight  deviations  in  the  alignment  of  the  guide  rails, 
variations  in  thickness,  or  the  sudden  engagement  of 


37 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


the  governor  rope  by  the  governor,  with  a  following 
jump  of  the  governor  rope  that  will  permit  the  jaws  to 
clear  for  a  small  fraction  of  a  second.  In  no  case  should 
these  preliminary  marks  be  considered  in  the  measure- 
ment of  the  slide.  Measure  the  slide  from  the  highest 
point  of  the  continuous  marking  only. 

(6)  Measurement  of  Stopping  Distance.  Determine 
the  stopping  distance  by  measuring  the  length  of  the 
marks  made  by  the  safety  on  both  sides  of  each  guide 
rail,  deducting  the  length  of  the  safety  jaw  or  wedge, 
and  taking  the  average  of  the  four  measurements. 

(10)    2.29.3  Acceptance  Test  of  Governor  and  Safeties 

(a)  Test  Type  A  governor-operated  safeties  by 
operating  the  car  at  its  normal  speed  in  the  down  direc- 
tion by  manually  tripping  the  governor  jaws.  Also,  test 
the  inertia  application  of  safety.  Type  A  safeties  without 
governors  that  are  operated  as  a  result  of  the  breaking 
or  slackening  of  the  hoisting  ropes  shall  be  tested  by 
obtaining  the  necessary  slack  rope  to  cause  them  to 
function. 

(b)  Type  B  and  Type  C  safeties  on  electric  elevators 
are  tested  as  outlined  in  Item  2.29.2.1(e),  and  must  be 
subject  to  overspeed  tests.  The  acceptance  test  for 
hydraulic  elevators  is  the  same  as  the 
Category  5/five-year  test  [see  Item  2.29.2.1(e)].  Gradu- 
ally increase  the  speed  of  the  car  until  the  governor 
causes  application  of  the  safety.  Determine  that  the  stop- 
ping distance  is  in  compliance  with  the  maximum  and 
minimum  slide  distances  allowed.  On  elevators 
equipped  with  AC  driving  machine  motors,  where  the 
car  with  its  rated  load  does  not  cause  sufficient 
overspeed  when  the  machine  brake  is  released  to  trip 
the  governor  jaws,  the  safeties  must  be  tested  by 
operating  the  car  at  its  normal  speed  in  the  down  direc- 
tion and  manually  tripping  the  governor  jaw. 

(c)  Counterweight  safeties,  where  provided,  must  be 
tested  with  no  load  in  the  car. 

2.29.4  References 

2.29.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Sections  205  and  1306,  Table  205.3,  and  Rules 
1001.2(b)(29),  1002.2b,  1002.3a,  1003.2,  and  1202.6. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.17  and  8.2.6,  Table  2.17.3,  and 
Requirements  8.11.2.1.2(cc),  8.11.2.2.2, 8.11.2.3.1, 8.10.2.2, 
and  8.7.2.18. 

A17.3  —  Sections  3.5  and  3.6  and  para.  3.10.4(m). 
NOTE:     Items  2.30  through  2.37  apply  to  hydraulic  elevators  only. 

ITEM  2.30 
HYDRAULIC  POWER  UNIT 

2.30.1  Periodic  Inspections 

2.30.1.2  Hydraulic  Elevators 

(a)  Motor.  Have  the  elevator  operated  in  the  up  direc- 
tion, making  several  starts,  and  observe  the  operation 


of  the  motor,  pump,  and  drive.  Check  for  excessive  noise, 
misalignment,  and  loose  mounting. 

(b)  Pump.  The  pump  should  be  checked  for  leaks 
around  the  shaft  and  for  unusual  noise  that  could  be 
caused  by  cavitation  due  to  a  partially  plugged  suction 
line  or  strainer  or  low  oil  level. 

2.30.3  Acceptance 

2.30.4  References 

2.30.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Section  304;  and  Rules  1004.2(b)(13)  and 
1206.5. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  3.24,  8.11.3.1.2(m),  and  8.6.5. 

NFPA  70  or  CSA  C22.1,  as  applicable. 

ITEM  2.31 
RELIEF  VALVES 

2.31.1  Periodic  Inspections 

2.31.1.2  Hydraulic  Elevators:  Relief  Valve.  Examine 
the  relief  valve  and  verify  that  it  is  sealed  to  prevent 
tampering.  If  the  means  of  sealing  the  valve  is  not  intact, 
test  adjustment  and  sealing  must  be  required. 

2.31.2  Periodic  Test 

2.31.2.2  Hydraulic  Elevators:  Yearly  Test  (for 
A17.1d-2000  and  Earlier  Editions);  Category  1  Test  (for 
A17.1-2000/B44-00  and  Later  Editions).  Have  an 
inspector's  pressure  gauge  installed  in  the  system.  There 
is  usually  a  fitting  provided  for  this  in  the  machine  room. 
Test  the  relief  valve  by  inching  the  car  at  slow  speed 
against  the  stop  ring.  Then  cause  the  controls  to  attempt 
to  run  the  car  at  full  speed  and  read  the  gauge.  The  full 
output  of  the  pump  should  bypass  at  a  gauge  reading 
150%  or  less  of  the  working  pressure. 

After  the  test,  check  the  car  for  proper  operation  and 
visually  inspect  the  system  for  leaks.  After  this  test,  the 
means  of  adjustment  must  be  sealed.  The  annual  test  of 
flexible  hydraulic  hose  and  fitting  assembly  (Item  2.17) 
may  be  conducted  concurrently  with  this  relief  valve  test. 

Al 7. 1-1971  and  later  editions  require  that  the  working 
pressure  be  on  a  plate  mounted  on  the  power  unit. 

2.31.3  Acceptance 

2.31.3.2  Hydraulic  Elevators.  Check  the  working 
pressure  given  on  the  elevator  layout  with  that  on  the 
tank  plate.  If  these  agree,  verify  them  by  installing  an 
inspector's  pressure  gauge  in  the  system,  at  or  near  the 
cylinder;  run  the  car  up  at  rated  speed  with  rated  load. 
The  gauge  should  read  the  working  pressure.  For  eleva- 
tors with  Class  C2  loading,  place  the  maximum  static 
load  on  the  elevator  then  run  it  down  about  2  in.  (54  mm) 
to  3  in.  (76  mm)  on  inspection.  Then  turn  it  back  on 
automatic  and  read  the  pressure  as  the  car  levels  up.  If 


38 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


the  gauge  is  installed  at  the  power  unit,  the  pressure 
will  be  slightly  more  than  the  pressure  at  the  cylinder. 
This  difference  is  dependent  on  the  length  and  configu- 
ration of  the  supply  piping  and  speed  of  the  elevator. 
In  some  cases  this  difference  is  very  small  and  can  be 
ignored. 

2.31.4  References 

2.31.4.2  Hydraulic  Elevators.  Al 7. ld-2000  and  ear- 
lier editions  —  Section  308;  Rules  303.1,  303.2,  303.4b, 
1004.2(b)(13),  1005.2a,  and  1006.2b;  and  Section  3 
(Definitions). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  3.28,  3,19.1,  3.19.2,  3.19.4.2,  8.11.3.1.2(m), 
8.11.3.2.1,  and  8.10.3.2.2(m);  and  1.3  (Definitions). 

A17.3  —  Paragraph  4.4.1. 

ITEM  2.32 
CONTROL  VALVE 

2.32.1  Periodic  Inspections 

2.32.1.2  Hydraulic  Elevators 

(a)  Control  Valve.  The  valves,  fittings,  and  intercon- 
necting piping  should  be  checked  for  pressure  rating, 
leakage,  and  adequate  support. 

(b)  Manual  Lowering  Valve  and  Anticreep  Elevators. 
Manual  lowering  valve  and  anticreep  elevators  installed 
under  the  A17.1-1984  and  later  editions  are  required  to 
have  a  manual  lowering  valve  identified  and  located  on 
or  adjacent  to  the  control  valve. 

Check  the  operation  of  the  manual  lowering  valve 
and  the  anticreep  leveling  device  as  follows: 

(1)  Position  the  car  at  a  landing  in  response  to  oper- 
ation by  the  normal  landing  device. 

(2)  Lower  the  car  by  opening  the  manual  lowering 
valve  to  initiate  a  downward  movement.  The  pump 
motor  should  start  when  or  before  the  car  exceeds  1  in. 
(25  mm)  from  the  floor. 

(3)  Close  the  manual  lowering  valve  [the  car  should 
be  within  1  in.  (25  mm)  of  the  floor  when  the  pump 
motor  stops]. 

See  Item  3.7  for  additional  information  and  procedure 
for  testing  the  anticreep  device  when  there  is  no  manual 
lowering  valve. 

2.32.2  Periodic  Test 

2.32.3  Acceptance 

2.32.3.2  Hydraulic  Elevators.  Check  the  manual 
lowering  valve  for  identification  function  and  location. 

2.32.4  References 

2.32.4.2  Hydraulic  Elevators.  A17. ld-2000  and  ear- 
lier editions  —  Section  303  and  Rule  1004.2(b)(15). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  3.19  and  8.11.3.1.2(o). 

A17.3  —  Section  4.4. 


ITEM  2.33 
TANKS 

2.33.1  Periodic  Inspections 

2.33.1.2  Hydraulic  Elevators 

(a)  Atmospheric  Storage  and  Discharge  Tanks.  Visually 
inspect  the  tank  for  defects  such  as  leaks,  corrosion, 
damage,  and  cover  to  prevent  entrance  of  foreign 
materials. 

(1)  Have  the  car  moved  to  the  top  landing  and 
check  the  hydraulic  fluid  level.  While  the  car  is  moving 
up,  listen  for  sounds  that  may  indicate  cavitation  or 
obstructed  strainers.  The  liquid  should  be  above  the 
minimum  level  indicated.  A17. 1-1955  through 
Al 7. 1-1965  required  that  the  minimum  liquid  level  be 
clearly  indicated.  A17. 1-1971  and  later  editions  require 
that  the  means  of  checking  the  liquid  level  be  accessible 
without  removal  of  any  cover  or  other  parts. 

(2)  Observe  drip  pans  for  excess  accumulation  of 
hydraulic  fluid  that  leaked  from  the  system. 

(b)  Pressure  Tanks 

(1)  Determine  whether  the  tank  installed  under 
A17.1-1971  and  later  editions,  or  any  replacement  tank, 
is  marked  to  indicate  that  it  was  made  and  tested  in 
conformance  with  Section  VIII  of  the  ASME  Boiler  and 
Pressure  Vessel  Code.  This  may  be  stamped  on  the  tank 
or  on  a  data  plate  attached  in  such  a  manner  that  removal 
would  result  in  its  destruction.  The  following  informa- 
tion should  be  included: 

(a)  name  of  manufacturer 

(b)  maximum  allowable  working  pressure  at 
temperature 

(c)  minimum  design  metal  temperature 
id)  manufacturer's  serial  number 

(e)  the  year  built 

(2)  Examine  for  corrosion,  leaks,  badly  corroded 
surfaces,  or  any  indication  of  cracking  or  failure  of  the 
metal.  If  any  of  the  above  conditions  exist,  recommend 
that  a  hydraulic  elevator's  static  test  be  performed  in 
accordance  with  the  ASME  Pressure  Vessel  Code.  Check 
the  tank  for 

(a)  a  pressure  gauge 

(b)  a  place  to  install  an  inspector's  gauge 

(c)  a  liquid  level  gauge 

Verify  that  these  are  in  good  working  order  and  install 
an  inspector's  gauge  to  check  the  accuracy  of  the  perma- 
nently installed  gauge. 

2.33.2  Periodic  Test 

2.33.2.2  Hydraulic  Elevators:  3-Year  Inspection  and 
Test  of  Pressure  Tanks  (for  A17. ld-2000  and  Earlier 
Editions);  Category  3  Test  and  Test  Pressure  Tanks  (for 
A17.1-2000/B44-00  and  Later  Editions) 

WARNING:     Hydraulic  elevator's  static  test  can  be  dangerous 
if  not  performed  by  qualified  persons. 


39 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


The  pressure  tank  should  be  thoroughly  cleaned  and 
inspected  both  internally  and  externally.  It  should  be 
subjected  to  hydraulic  elevator's  static  test  at  150%  of  the 
working  pressure.  This  is  done  by  removing  all  control 
devices,  and  isolating  the  tank.  A  calibrated  inspector's 
gauge  with  maximum  reading  twice  the  test  pressure 
must  be  installed. 

The  tank  is  then  filled  completely  with  water.  Care 
must  be  taken  to  remove  all  of  the  air  from  the  tank.  If 
air  or  any  compressible  gas  is  trapped  in  the  tank,  the 
test  will  become  dangerous.  A  hand  pump  can  then  be 
used  to  provide  the  test  pressure.  The  tank  should  be 
held  at  the  test  pressure  for  at  least  1  min  and  inspected 
for  leaks,  distortions,  or  damage.  Since  there  is  no  com- 
pressible fluid  (air  or  other  gas)  in  the  tank,  a  very  small 
leak  will  cause  a  rapid  loss  of  pressure.  This  may  be 
cause  for  replacement  of  the  tank. 

After  the  test,  the  tank  must  be  thoroughly  cleaned 
before  returning  to  service. 

2.33.3  Acceptance 

2.33.3.2  Hydraulic  Elevators.  The  tank  should  be 
visually  inspected  for  damage  that  may  have  resulted 
from  handling  and  installation.  The  data  required  by 
the  ASME  Boiler  and  Pressure  Vessel  Code  should  be 
verified  (see  Item  2.16.1.2). 

2.33.4  References 

2.33.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Section  304;  and  Rules  1004.2(b)(16), 
1005.3b,  1203.6,  and  1206.5b. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  3.24,  8.11.3.1.2(p)/  8.11.3.3.2,  8.7.3.29, 
8.6.5.1,  8.6.5.2,  8.6.5.5,  and  8.6.5.6. 

A17.3  —  Section  4.5. 

ITEM  2.34 

FLEXIBLE  HYDRAULIC  HOSE  AND 

FITTING  ASSEMBLIES 

2.34.1  Periodic  Inspections 

2.34.1.2  Hydraulic  Elevators.  Visually  examine  flex- 
ible hydraulic  hoses,  fitting  assemblies,  and  flexible  cou- 
plings for  evidence  of  leakage,  slippage  of  hose  fittings, 
and  damage  to  outer  hose  covering  sufficient  to  expose 
reinforcement  or  cause  distortion  or  bulging  of  hose 
body.  Such  damage  will  warrant  further  test.  Check  hose 
and  fitting  assemblies  for  proper  identification  and  per- 
manent marking  and  replacement  date. 

2.34.2  Periodic  Test 

2.34.2.2  Hydraulic  Elevators:  Yearly  Test  (for 
A17.1d-2000  and  Earlier  Editions);  Category  1  Test  (for 
A17.1-2000/B44-00  and  Later  Editions).  From  the 
machine  room  have  the  car  inched  up  at  slow  speed 
until  the  stop  ring  is  engaged.  Then  operate  the  system 


Table  2.34.3    Minimum  Bend  Radius  for 
SAE  100R2  Hose 


From  5AEJ517  100R2  Hose 

ID 

OD 

Minimum  Burst 

Minimum  Bend 

in. 

in. 

Pressure,  psi 

Radius,  in. 

v2 

31/32 

14,000 

7 

% 

l3/32 

11,000 

8 

% 

I1/* 

9,000 

9% 

% 

iVs 

8,000 

11 

i 

l9/l6 

8,000 

12 

iy« 

2 

6,500 

I6V2 

iv2 

2Y< 

5,000 

20 

2 

2% 

4,000 

25 

GENERAL  NOTE:     1  in.  =  25.4  mm 

at  rated  speed  to  provide  full  relief  valve  bypass  pressure 
for  30  s.  While  under  pressure,  observe  the  hose  for  any 
signs  of  leakage,  slippage  of  hose  fittings,  damage  to 
outer  hose  covering,  bulging,  or  distortion  of  the  hose 
body.  Any  of  these  signs  require  replacement  of  the  hose. 
Have  a  metal  tag  attached  to  the  hose  in  a  permanent 
manner  indicating  the  date  of  the  test  and  the  name  of 
the  person  or  firm  that  performed  the  test. 

2.34.3  Acceptance  Test 

2.34.3.2  Hydraulic  Elevators.  Check  that  the  hose 
is  not  installed  in  the  hoist  way  or  projects  into  or  through 
any  wall.  Check  for  twists,  kinks,  or  sharp  bending 
radius.  See  Table  2.34.3. 

2.34.4  References 

2.34.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  303.3c,  1004.2(b)(17),  and  1005.2d. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  3.19.3.3,  8.11.3.1.2(q),  and  8.11.3.2.4. 

ITEM  2.35 

SUPPLY  LINE  AND  SHUTOFF 

VALVE 

2.35.1  Periodic  Inspections 

Inspect  the  supply  line  between  the  cylinder  and  the 
pumping  unit  for  leaks,  adequate  support,  vibration,  or 
other  evidence  of  damage.  A  careful  examination  of  the 
piping  and  fittings  will  indicate  if  a  replacement  has 
been  made  that  does  not  match  the  rest  of  the  system. 
In  such  cases,  the  replacement  part  pressure  rating 
should  be  checked  by  examining  the  rating  supplied  by 
the  manufacturer.  Also,  inspect  the  piping  for  support 
to  prevent  undue  stress  due  to  weight  of  pipe  or  other 
equipment. 

Check  fittings  for  absence  of  corrosion,  leaks,  and 
evidence  of  excessive  vibration.  On  grooved  fittings, 
check  that  the  housing  segments  are  bolt  pad  to  bolt 


(10) 


40 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


pad,  that  coupling  keys  are  in  the  pipe  groove,  that  bolt 
heads  are  seated  and  nuts  are  tight. 

Inspect  the  manual  shutoff  valve  in  the  machine  room 
for  condition  and  leaks.  Manual  shutoff  valves  are 
required  for  elevators  installed  under  A17. 1-1978  and 
later  editions  with  unexposed  cylinders.  A17.1-1996  and 
later  editions  require  a  manual  shutoff  valve  for  all  eleva- 
tors. Editions  of  the  Code  prior  to  A17.1-1993  required 
a  material  safety  factor  of  5  and  elongation  of  not  less 
than  10%  for  valves,  fittings,  and  supply  piping.  Some 
valves  and  fittings  are  rated  with  a  material  safety  factor 
of  3.  In  such  a  case,  the  manufacturer's  published  rating 
should  be  down-rated  for  elevator  application.  This  can 
be  done  by  multiplying  the  published  rating  by  3  and 
dividing  by  5. 
EXAMPLE:     Manufacturer's  rating  1,000  psi 

1000  x  %  =  600  psi 

If  the  material  elongation  for  the  material  in  this  exam- 
ple is  at  least  10%,  the  valve  or  fitting  could  be  used  for 
working  pressure  up  to  600  psi. 

2.35.2  Periodic  Test 
235.3  Acceptance 

Inspect  the  valves  and  fittings  as  indicated  under  rou- 
tine inspection.  However,  for  new  equipment,  the  factor 
of  safety  may  vary  inversely  with  the  elongation  of  the 
material.  This  will  allow  a  lower  factor  of  safety  if  the 
elongation  is  increased.  Likewise,  if  the  elongation  is 
decreased,  the  factor  of  safety  must  be  increased.  There- 
fore, it  is  recommended  that  the  installer  furnish  docu- 
mentation that  the  presure  rating  complies  with  the 
requirements  of  ASME  A17.1  for  the  applicable  working 
pressure,  with  data  from  the  valve,  fitting,  and  pipe 
manufacturers.  Review  this  to  verify  compliance  with 
pressure  rating  requirements. 

If  the  elevator  supplier  has  obtained  a  type  approval 
from  the  jurisdiction,  verify  that  all  installed  compo- 
nents are  included  in  the  type  approval. 

Determine  that  pipe  fittings  have  been  installed  in 
locations  that  permit  disassembly  and  inspection  of 
components. 

2.35.4  References 

2.35.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Section  303. 

A17.1-2000/B44-00  and  later  editions  — 
Requirement  3.19. 

A17.3  —  Paragraph  4.4.4. 

ITEM  2.36 
HYDRAULIC  CYLINDERS 

2.36.1  Periodic  Inspections 

2.36.2  Periodic  Test 

2.36.2.2  Hydraulic  Elevators:  Yearly  Test  (for 
A17.1d-2000  and  Earlier  Editions);  Category  1  Test  (for 
A17.1-2000/B44-00  and  Later  Editions).    This  test 


should  be  performed  after  the  relief  valve  test  in 
Item  2.31  and  the  flexible  hose  test  in  Item  2.34.  Cylin- 
ders that  cannot  be  inspected  visually  should  be  tested 
in  the  following  manner  with  no  load  in  the  car.  Mark 
the  location  of  the  car  at  any  convenient  position.  Open 
the  disconnect  switch  for  15  min.  Note  the  position  of 
the  car  platform  with  respect  to  the  reference  mark.  A 
change  in  car  position  that  cannot  be  accounted  for  by 
visible  oil  leakage,  valve  leakage,  or  temperature  change 
of  the  oil  indicates  a  leak  of  the  cylinder  or  in  the  under- 
ground piping  and  a  need  for  further  inspection,  tests, 
or  repairs. 

2.36.3  Acceptance 

2.36.4  References 

2.36.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  302.3,  1004.2(b)(19),  and  1005.2b. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  3.18.3,  8.11.3.1.2(s),  and  8.11.3.2.2. 

ITEM  2.37 
PRESSURE  SWITCH 

2.37.1  Periodic  Inspections 

2.37.1.2  Hydraulic  Elevators.  For  elevators  installed 
under  A17. 1-1981  and  later  editions,  a  pressure  switch 
is  required  if  the  top  of  the  cylinder  is  above  the  storage 
tank.  This  switch  is  to  prevent  operation  of  the  valves 
if  there  is  no  pressure  in  the  line  between  the  down 
valve  and  cylinder.  Visually  inspect  for  condition  and 
damage. 

2.37.2  Periodic  Test 

2.37.2.2  Hydraulic  Elevators:  Yearly  Test  (for 
A17.1d-2000  and  Earlier  Editions);  Category  1  Test  (for 
A17.1-2000/B44-00  and  Later  Editions).  Test  the  pres- 
sure switch  in  the  following  manner: 

(a)  Place  the  car  at  any  landing  except  the  bottom 
landing. 

(b)  Remove  one  electrical  lead  from  the  pressure 
switch  and  try  to  run  the  car  in  the  down  direction.  If 
the  car  will  not  run  by  normal  means,  open  the  main 
line  disconnect  switch.  Connect  a  circuit  continuity  tes- 
ter, such  as  an  ohmmeter,  across  the  pressure  switch  and 
lower  the  car  on  the  buffer  with  the  manual  lowering 
valve. 

(c)  The  ohmmeter  should  indicate  that  the  pressure 
switch  is  open  when  the  car  comes  to  rest  on  the  buffer. 

2.37.3  Acceptance 

2.37.4  References 

2.37.4.2  Hydraulic  Elevators.    A17.1d-2000  and  ear- 
lier editions  —  Rules  306.14,  1004.2(b)(20),  and  1005.2e. 
A17.1-2000/B44-00     and     later     editions     — 
Requirements  3.26.8,  8.11.3.1.2(t),  and  8.11.3.2.5. 


41 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers.  /^ 

No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME.       vfi 


ASME  A17.2-2010 


ITEM  2.38 

ROPED  WATER  HYDRAULIC 

ELEVATORS 

2.38.1  Periodic  Inspections 

2.38.2  Periodic  Test:  3-Year  Test  (for  A17.1d-2000 
and  Earlier  Editions);  Category  3  Test  (for 
A17.1-2000/B44-00  and  Later  Editions) 

Check  the  condition  of  the  rod  at  the  thread  end, 
which  is  where  the  bolt  and  nut  are  against  the  plunger. 
This  should  be  done  on  the  bottom  and  top  ends.  It  is 
very  common  for  the  rod  to  break  where  the  thread  and 
nut  end  are  against  the  plunger  of  packing  thread. 

2.38.3  Acceptance 

2.38.4  References 

ITEM  2.39 
LOW  OIL  PROTECTION 

2.39.1  Periodic  Inspections 

2.39.2  Periodic  Test 

For  elevators  installed  under  A17.1-1993  and  later 
editions,  check  that  a  means  is  provided  to  detect  when 
the  liquid  level  in  the  tank  falls  below  the  minimum 
required  for  the  car  to  reach  the  topmost  landing.  Verify 
that  when  activated,  the  car  will  automatically  travel  to 
the  lowest  landing,  cycle  power-operated  horizontally 
sliding  passenger  elevator  doors  that  are  equipped  with 
reopening  devices,  and  shut  down.  Also,  verify  that 
the  in-car  door  open  button  (where  provided)  remains 
operative.  Also,  see  requirement  2.11.3  of  A17.1. 

2.393  Acceptance 

2.39.4  References 

A17.1d-2000  and  earlier  editions  —  Rule  306.15. 
A17.1-2000/B44-00  and  later  editions  —  Requirement 
3.26.9. 


ITEM  2.40 
MAINTENANCE  RECORDS 

2.40.1   Periodic  Inspections 

Review  the  maintenance  records  and  verify  that  they 
are  available  to  elevator  personnel  and  that  they  are 
legible  and  up  to  date.  They  should  include  the 
following: 

(a)  description  of  maintenance  task  performed  and 
dates 

(b)  description  and  dates  of  examinations,  tests, 
adjustments,  repairs,  and  replacements 

(c)  description  and  dates  of  call  backs  (trouble  calls) 
or  reports  that  are  reported  to  elevator  personnel  by  any 
means,  including  corrective  action  taken 


(d)  written  record  of  the  findings  on  the  firefighter's 
service  operation  monthly  test  is  maintained 

2.40.1.1  Hydraulic  Elevators.  Check  the  record  of 
oil  usage  where  required.  Investigate  any  unaccountable 
fluid  loss. 

2.40.4  References  do) 

2.40.4.1  Electric  Elevators.  A17.1-2000/B44-00  and 
later  editions  —  Requirements  8.6.1.4,  c8.6.12.2.5,  and 
8.6.10.1. 

2.40.4.2  Hydraulic  Elevators.  A17.1-2000/B44-00 
and  later  editions  —  Requirements  8.6.1.4,  c8.6.12.2.5, 
8.6.10.1,  and  8.6.5.7. 

ITEM  2.41 
STATIC  CONTROL 


2.41.1  Periodic  Inspections 

2.41.2  Periodic  Test 

2.41.3  Acceptance 

The  person  or  firm  installing  or  maintaining  an  eleva- 
tor employing  static  control  should  demonstrate  confor- 
mance with  the  Code  as  follows: 

(a)  If  in  the  up  direction,  the  pump  motor  is  the  only 
control  means,  run  the  car  and  demonstrate  that  there  are 
two  devices  provided  to  remove  power  independently 
from  the  pump  motor.  At  least  one  device  shall  be  an 
electromechanical  contactor. 

(b)  If  in  the  up  direction,  the  pump  motor  is  one  con- 
trol means  and  there  is  a  second  control  means  (e.g.,  a 
valve),  run  the  car  and  demonstrate  that  a  device  is 
provided  to  remove  power  independently  from  each 
control  means.  At  least  one  device  shall  be  an  electrome- 
chanical contactor  or  relay. 

(c)  Prevent  the  above  electromechanical  contactor  or 
relay  from  being  energized  and  register  a  call.  Demon- 
strate, with  the  doors  closed,  that  the  car  will  not  move. 

(d)  Demonstrate  that  the  operation  of  the  devices 
specified  in  Items  2.21.2(a)  and  (b)  will  remove  power 
from  each  control  means. 

2.41.4  References 

ITEM  2.42  (10) 

EARTHQUAKE  INSPECTION  AND  TESTS  (SEISMIC 
RISK  ZONE  2  OR  GREATER) 

2.42.1  Periodic  inspection 

(a)  Verify  that  all  rope  retainers  or  rope  guards  are  in 
place. 

(b)  Verify  that  equipment  in  the  machine  room,  con- 
trol panels,  machines,  machine  beams,  support  beams, 
and  sheaves  are  properly  fastened  to  the  overhead  beams 
and  floor  to  prevent  overturning,  where  required. 


42 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


2.42.1.1  Electric  Elevators 

(a)  If  the  seismic  switch  is  used  exclusively  for  control 
of  the  elevator,  check  to  see  that  the  switch  is  located 
in  the  machine  room  and  on  a  vertical  structural  member 
or  at  the  nearest  accessible  vertical  load-bearing  member. 

(b)  Verify  that  there  is  a  momentary  reset  button  or 
switch,  for  each  elevator,  located  in  its  control  panel 

2.42.1.2  Hydraulic  Elevators 

(a)  Verify  that  a  means  is  provided  which  will  prevent 
the  tank  from  overturning  during  seismic  activity. 

(b)  Verify  that  all  the  pipe  supports  are  in  place. 

2.42.2  Periodic  Test 

2.42.3  Acceptance 

Verify  that  rope  retainers  are  continuous  over  not  less 
than  %  of  the  arc  of  contact  between  the  rope  and  its 
sheave  or  drum  and  located  so  not  more  than  \  of  the 
arc  of  contact  is  exposed.  For  double  wrap,  the  arc  of 
contact  is  the  length  of  arc  that  is  uninterrupted  by 
the  entry /exit  of  the  ropes  leading  to /from  the  car  or 
counterweight.  Rope  restraints  may  be  used  in  lieu  of 
retainers  and,  if  they  are  used,  there  must  be  one  for 
each  30  deg  or  less  of  arc  contact. 

2.42.3.1  Electric  Elevators 

(a)  Verify  that  the  seismic  switch  operates  properly. 
When  the  switch  is  tripped,  the  elevator  in  motion  shall 
proceed  to  the  nearest  available  floor,  the  doors  shall 
open,  and  the  elevator  shall  shut  down.  If  Phase  II  emer- 
gency in-car  operation  is  in  effect,  the  door  operation 
shall  conform  to  2.27.3.3. 

(b)  Check  the  operation  of  the  displacement  switch. 
When  this  switch  is  actuated,  the  elevator,  if  in  motion, 
shall  stop  (emergency  stop)  and  then  proceed  away  from 
the  counterweight  at  a  speed  not  to  exceed  150  ft/min 
(0.75  m/s)  to  the  nearest  available  floor,  open  the  doors, 
and  shut  down.  If  Phase  II  operation  is  in  effect,  door 
operation  must  conform  to  2.27.3.3. 

(c)  If  a  car  with  power-operated  doors  is  just  reaching 
a  landing,  the  doors  shall  open  and  remain  open.  If  an 
elevator  is  standing  at  a  floor  with  its  doors  open,  the 


elevator  shall  remain  at  that  floor.  If  an  elevator  is  stand- 
ing at  a  floor  with  the  doors  to  the  elevator  closed,  the 
doors  shall  open.  If  Phase  II  operation  is  in  effect,  door 
operation  shall  conform  to  2.27.3.3.  If  an  elevator  is  not 
in  operation  when  an  earthquake  protective  device  is 
actuated,  the  elevator  shall  remain  at  the  floor  on  which 
it  is  located. 

(d)  An  elevator  may  be  operated  at  a  speed  not 
exceeding  150  ft/min  (0.75  m/s)  as  long  as  the  displace- 
ment switch  operated  by  the  counterweight  is  the  contin- 
uous monitoring  type  and  is  not  actuated.  If  the 
displacement  switch  is  actuated  then  the  car  shall  not 
operate  except  with  the  top-of-car  inspection  operating 
devices  and  shall  prevent  operation  of  the  car  by  the 
Phase  I,  Phase  II,  hospital  emergency  keys,  or  any  other 
similar  types  of  operation.  In  a  power  loss  situation,  the 
status  of  the  earthquake  protective  device  or  slow  speed 
status  of  the  elevator  shall  not  be  cancelled  when  power 
is  restored.  The  electric  protective  devices  of  2.26.2  shall 
not  be  rendered  inoperative  or  bypassed  by  any  earth- 
quake devices. 

2.42.3.2  Hydraulic  Elevators 

(a)  If  the  building  is  designed  with  an  expansion  joint, 
the  machine  room  and  the  hoistway  shall  be  located  on 
the  same  side  of  the  expansion  joint. 

(b)  Verify  that  the  proper  number  of  supports  are  used 
to  support  the  hydraulic  lines  and  that  supports  to  resist 
transverse  motion  are  provided  near  changes  in  direc- 
tion and  at  valves  and  joints. 

2.42.4  References 

2.42.4.1  Electric  Elevators.  A17.1-1993  through 
A17.1d-2000  editions  —  Rules  2401,  2400.1,  2408,  and 
2409. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  8.4.2,  8.4.3.1,  8.4.9,  and  8.4.10. 

2.42.4.2  Hydraulic  Elevators.  A17. 1-1993  through 
A17.1d-2000  editions  —  Rules  2401,  2400.1,  2410.1,  and 
2410.7. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  8.4.2, 8.4.3.1, 8.4.11.1, 8.4.11.3,  and  8.4.11.6. 


43 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Part3 
Elevator  —  Top  of  Car 


(10) 


ITEM  3.1 
TOP-OF-CAR  STOP  SWITCH 

3.1.1  Periodic  Inspections 

Check  the  top-of-car  stop  switch  in  both  directions  to 
ensure  it  is  functioning  properly  and  in  compliance  with 
the  Code  before  proceeding  with  the  inspection. 

3.1.2  Periodic  Test 

3.1.3  Acceptance 

3.1.4  References 

3.1.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  210.2(h)  and  1001.2(c)(1). 

A17.1-2000/B44-00      and     later     editions     — 
Requirements  2.26.2.8  and  8.11.2.1.3(a). 
A17.3  —  Paragraph  3.10.4(e). 

3.1.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  306.4  and  1004.2(c)(1). 

A17.1-2000/B44-00      and     later     editions     — 
Requirements  3.26.1,  3.26.4,  and  8.11.3.1.3(a). 
A17.3  —  Paragraph  4.7.4(a). 

ITEM  3.2 
CAR  TOP  LIGHT  AND  OUTLET 

3.2.1  Periodic  Inspections 

For  elevators  installed  under  A17.1a-1979  and  later 
editions,  check  that  a  light  and  outlet  have  been  provided 
and  that  they  are  operational.  The  light  must  be  guarded 
to  prevent  damage  when  accidentally  hit  by  a  person 
moving  onto  or  around  on  the  car  top.  For  elevators 
installed  under  the  1993  ANSI/NFPA  70,  verify  that 
the  outlet  is  GFCI  protected.  The  1996  ANSI/NFPA  70 
requires  the  receptacle  be  the  GFCI  type.  Test  GFCI  oper- 
ation with  either  the  built-in  test  button  or  GFCI  tester. 

NOTE:     If  the  GFCI  protection  is  not  in  the  receptacle,  the  top  car 
light  will  go  out  when  it  is  tested. 

3.2.2  Periodic  Test 

3.2.3  Acceptance 

Check  the  GFCI  receptacle  operation  using  the  test 
button.  Use  a  receptacle  tester  to  check  the  receptacle 
for  grounding  and  polarity.  The  inspector  is  not  required 
to  have  the  unit  disassembled  but  should  visually 
inspect  the  installation  for  evidence  of  nonlisted  compo- 
nents. Also,  see  Item  2.11.3(c)  for  car  lighting  disconnect 
located  in  the  machine  room. 


3.2.4  References 

3.2.4.1  Electric  Elevators.    A17.1d-2000  and  earlier 
editions  —  Rules  204.7  and  1001.2(c)(2). 

A17.1-2000/B44-00     and     later     editions     — 
Requirements  2.14.7  and  8.11.2.1.3(b). 
A17.3  —  Paragraph  3.4.5. 
NFPA  70  or  CSA  C22.1,  as  applicable. 

3.2.4.2  Hydraulic  Elevators.    A17.1d-2000  and  ear- 
lier editions  —  Rules  204.7  {301.7}  and  1004.2(c)(2). 

A17.1-2000/B44-00     and     later     editions     — 
Requirements  2.14.7  {3.14}  and  8.11.3.1.3(b). 
A17.3  —  Paragraph  3.4.5  {4.2.3}. 
NFPA  70  or  CSA  C22.1,  as  applicable. 


ITEM  3.3 
TOP-OF-CAR  OPERATING  DEVICE 

3.3.1  Periodic  Inspections 

Check  top-of-car  operating  device  for  proper  opera- 
tion. A17.1d-1970  and  later  editions  and  A17.3  require 
that  the  means  to  transfer  control  be  on  top  of  the  car 
between  the  crosshead  and  the  access  entrance.  If  sepa- 
rate additional  means  are  provided  for  making  power 
door  or  automatic  car  leveling  devices  operative,  verify 
that  operation  is  by  constant  pressure  means. 

3.3.2  Acceptance 

Confirm  that  top-of-car  inspection  operation  has  pri- 
ority over  in-car  inspection  operation. 

3.3.3  References 

3.3.3.1  Electric  Elevators.    A17.1d-2000  and  earlier 
editions  —  Rules  204. lg,  210.1d,  and  1001.2(c)(3). 

A17.1-2000/B44-00     and     later     editions     — 
Requirements  2.14.1.7,  2.26.1.4,  and  8.11.2.1.3(c). 
A17.3  —  Paragraph  3.10.3. 

3.3.3.2  Hydraulic  Elevators.    A17.1d-2000  and  ear- 
lier editions  —  Rules  306.2  and  1004.2(c)(3). 

A17.1-2000/B44-00      and      later      editions     — 
Requirements  3.26.1,  3.26.2,  and  8.11.3.1.3(c). 
A17.3  —  Paragraphs  3.10.3  and  4.7.2. 


44 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


ITEM  3.4 

TOP-OF-CAR  CLEARANCE, 

REFUGE  SPACE,  AND  STANDARD  RAILING 

3.4.1   Periodic  Inspections 

3.4.1.1  Electric  Elevators.  Check  the  refuge  space 
for  elevators  installed  under  A17. 1-1978  and  later 
editions. 

Before  making  any  inspections  or  tests,  determine  the 
available  top  car  clearance.  Where  possible,  determine 
this  by  placing  the  car  with  its  floor  level  with  the  top 
terminal  landing.  Care  must  be  exercised  in  measuring 
this  clearance  from  the  car  top  as,  in  many  existing 
elevators,  the  top  clearance  may  be  insufficient  to  permit 
a  person  to  stand  when  the  car  floor  is  level  with  the 
top  terminal  landing.  Where  the  clearance  appears  to 
be  insufficient,  stop  the  car  at  or  below  the  top  landing 
and  the  top  car  clearance  determined  as  follows: 

(a)  Measure  the  distance  from  the  top  of  the  car  cross- 
head  to  the  nearest  obstruction  directly  above  it. 

(b)  Measure  the  projection  of  any  sheaves,  or  other 
equipment  mounted  in  or  on  the  car  crosshead,  above 
the  top  of  the  crosshead. 

(c)  Measure  the  distance  from  the  top  of  any  equip- 
ment mounted  on  top  of  the  car  (not  the  car  crosshead) 
to  the  nearest  obstruction  directly  above  it. 

(d)  For  underslung  car  frames,  measure  the  distance 
between  the  overhead  car  rope  dead-end  hitch  or  over- 
head car  sheave  and  the  portions  of  the  car  structure 
directly  below  them. 

(e)  Subtract  the  distance,  if  any,  the  car  floor  is  below 
the  top  terminal  landing  from  the  distances  measured 
in  Items  3.4.1(a),  (c),  and  (d).  The  question  of  whether 
or  not  the  top  car  clearance,  as  measured,  is  adequate 
or  conforms  to  Code  requirements  cannot  be  determined 
until  the  counterweight  runby  and  counterweight  buffer 
stroke  have  been  measured.  (See  Item  5.2.3.) 

(f)  Where  an  oil  buffer  is  used  for  the  counterweight 
and  no  provision  is  made  to  prevent  the  jump  of  the  car 
upon  counterweight  engagement,  add  one-half  of  the 
gravity  stopping  distance. 

NOTE:  The  projection  of  rope  fastenings  or  guide  shoes  above 
the  car  structure  is  not  to  be  considered  an  encroachment  on  the 
top  car  clearance.  However,  excessive  projection  is  not  permitted 
if  interference  with  sheaves  or  other  equipment  would  be  encoun- 
tered on  maximum  overtravel. 

(10)  3.4.1.2  Hydraulic  Elevators.  Check  the  refuge  space 
for  elevators  installed  under  A17. 1-1978  and  later  edi- 
tions. For  elevators  installed  under  A17. 1-1978  to 
A17.1b-1995,  verify  that  the  refuge  space  is  at  least 
650  in.2  (0.419  m2)  and  at  least  16  in.  (406  mm)  on  any 
side  with  minimum  vertical  clearance  of  at  least  42  in. 
(1  067  mm). 

Before  making  any  inspections  or  tests,  determine  the 
available  top  car  clearance.  Where  possible,  determine 


this  by  placing  the  car  with  its  floor  level  with  the  top 
terminal  landing. 

Prior  to  Al 7. 1-1978,  neither  the  refuge  space  nor  the 
6  in.  (152  mm)  clearance  shown  in  Fig.  3.4.1.2  was 
required.  A17. 1-1955  through  1977  (located  in  the  1978 
edition)  required  only  that  the  top  car  clearance  be  equal 
to  the  sum  of  the  top  car  runby  plus  2  ft  (609  mm),  or 
the  distance  that  any  equipment  projected  above  the 
crosshead  or  car  top  if  there  is  no  crosshead  provided. 

For  elevators  installed  under  A17. 1-1955  through 
A17.1a-1985,  overhead  beams  or  hoistway  construction 
located  vertically  over  the  car  must  be  located  at  least  2  ft 
(609  mm)  horizontally  from  the  crosshead.  For  elevators 
installed  under  A17.1-1987  and  later  editions,  the  mea- 
surement should  be  made  from  the  lowest  part  of  the 
obstruction  or  beam  over  the  car. 

Care  must  be  exercised  in  measuring  this  clearance 
from  the  car  top  as,  in  many  existing  elevators,  the  top 
clearance  may  be  insufficient  to  permit  a  person  to  stand 
when  the  car  floor  is  level  with  the  top  terminal  landing. 
Where  the  clearance  appears  to  be  insufficient,  stop  the 
car  at  or  below  the  top  landing  and  the  top  car  clearance 
determined  as  follows: 

(a)  Measure  the  distance  from  the  top  of  the  car  cross- 
head  to  the  nearest  obstruction  directly  above  it. 

(b)  Measure  the  projection  of  any  sheaves,  or  other 
equipment  mounted  in  or  on  the  car  crosshead,  above 
the  top  of  the  crosshead. 

(c)  Measure  the  distance  from  the  top  of  any  equip- 
ment mounted  on  top  of  the  car  (not  the  car  crosshead) 
to  the  nearest  obstruction  directly  above  it. 

(d)  For  underslung  car  frames,  measure  the  distance 
between  the  overhead  car  rope  dead-end  hitch  or  over- 
head car  sheave  and  the  portions  of  the  car  structure 
directly  below  them. 

(e)  Subtract  the  distance,  if  any,  the  car  floor  is  below 
the  top  terminal  landing  from  the  distances  measured 
in  Items  3.4.1(a),  (c),  and  (d). 

The  question  of  whether  or  not  the  top  car  clearance, 
as  measured,  is  adequate  or  conforms  to  Code  require- 
ments cannot  be  determined  until  the  top  car  runby  is 
determined. 

NOTE:  The  projection  of  rope  fastenings  or  guide  shoes  above 
the  car  structure  is  not  to  be  considered  an  encroachment  on  the 
top  car  clearance.  However,  excessive  projections  are  not  permitted 
if  interference  with  sheaves  or  other  equipment  would  be  encoun- 
tered on  maximum  overtravel. 

3.4.2  Periodic  Test 

3.4.3  Acceptance 

3.4.3.1  Electric  Elevators 

(a)  Measure  and  record  the  top  car  and  counterweight 
clearances. 

(b)  Measure  and  verify  dimensions  of  the  refuge 
space. 


45 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Fig.  3.4.1-2    Top  Car  Clearance  and  Runby  (A17.1-1978  and  Later  Editions) 


6  in.  (152  mm), 
Requirement  3.8 
(Rule300.3e) 


Door  operator,  or 
other  equipment 
on  top  of  car 


Top  car  runby > 


Possible  obstruction 
at  top  of  hoistway 


Any  equipment  on  top 
of  crosshead  (junction 
box,  light  fixture,  etc.) 


42  in.  (1067  mm), 
Requirement  3.8 
(Rule300.3g) 


Top  terminal  landing 


(c)  Check  that  a  standard  railing  is  provided  where 
required. 

3.4.3.2  Hydraulic  Elevators.  For  elevators  installed 
under  A17. 1-1996  and  later  editions,  check  that  the  ref- 
uge space  is  outlined  with  a  contrasting  color. 

(a)  Determine  the  top  car  runby  and  verify  existence 
of  stop  ring  by  inching  the  car  against  the  stop  ring, 
from  outside  the  car  (not  from  car  top)  then  open  the 
top  hoistway  door  and  measure  the  distance  from  the 
car  platform  to  the  top  landing.  The  runby  should  be 
recorded. 

(b)  The  top  car  clearances  should  be  measured  and 
recorded. 

(c)  Measure  and  verify  dimensions  of  the  refuge 
space. 

(d)  Check  that  a  standard  railing  is  provided  where 
required. 

3.4.4  References 

3.4.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rule  1206.8  and  Sections  107  and  1304. 


A17.1-2000/B44-00      and      later     editions     — 
Requirements  8.6.4.11,  2.4,  2.10.2,  2.14.1.7,  and  8.2.4. 
A17.3  —  Paragraph  2.4.4. 

3.4.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  300.8,  302.4,  1004.2(c)(4),  1006.2a, 
and  1006.2c. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  3.4,  2.10.2,  2.14.1.7(3.14},  3.18.4, 
8.11.3.1.3(d),  8.10.3.2.2(s),  and  8.10.3.2.3(d). 

A17.3  —  Paragraph  2.4.4  {Section  4.1}. 

ITEM  3.5 

NORMAL  TERMINAL  STOPPING 

DEVICES 

3.5.1   Periodic  Inspections 

3.5.1.1  Electric  Elevators.  Observe  caution  if  the 
top  car  clearance  is  limited.  Run  the  car  to  the  top  of 
its  travel  at  inspection  speed  to  examine  the  normal 
terminal  stopping  device. 


46 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Normal  terminal  stopping  devices  of  traction  eleva- 
tors may  be  located  in  the  machine  room  or  overhead 
machinery  space  and  mechanically  connected  to  and 
driven  by  the  car.  If  mechanically  attached  to  the  car, 
manually  open  the  broken  drive  device  switch  with  the 
car  at  rest.  This  should  prevent  the  car  from  starting. 
When  the  normal  terminal  stopping  devices  are  located 
in  the  hoistway  determine  that  stopping  switches  and 
cams  are  in  correct  alignment  and  are  securely  fastened. 
The  alignment  of  the  bottom  terminal  stopping  device 
can  be  checked  by  stopping  the  car  near  the  bottom 
terminal  and  sighting  the  alignment  of  the  car  and 
switch  roller  (see  Item  5.5).  The  switch  roller  should 
strike  the  bevel  of  the  cam.  Also,  determine  the  condition 
of  the  limit  switch  rollers,  as  reduction  of  the  effective 
roller  diameter  due  to  either  wear  or  loss  of  the  tires 
may  interfere  with  or  prevent  proper  switch  operation. 
The  combination  of  excessively  worn  car  guide  shoes 
and  limit  switch  rollers  may  cause  cars  to  overrun  their 
terminals. 

3.5.1.2  Hydraulic  Elevators.  Observe  caution  if  the 
top  car  clearance  is  limited.  Run  the  car  up  at  inspection 
speed  to  examine  the  normal  terminal  stopping  device. 

Normal  terminal  stopping  devices  are  usually  located 
in  the  hoistway  Verify  that  stopping  switches  and  cams 
are  in  correct  alignment  and  are  securely  fastened.  The 
alignment  of  the  bottom  terminal  stopping  device  can 
be  checked  by  stopping  the  car  near  the  bottom  terminal 
and  sighting  the  alignment  of  the  cam  and  switch  roller 
(see  Item  5.5).  The  switch  roller  should  strike  the  bevel 
of  the  cam.  Also,  determine  the  condition  of  the  limit 
switch  rollers,  as  reduction  of  the  effective  roller  diame- 
ter due  to  either  wear  or  loss  of  roller(s)  may  interfere 
with  or  prevent  proper  switch  operation.  The  combina- 
tion of  excessively  worn  car  guide  shoes  and  limit  switch 
rollers,  may  cause  cars  to  malfunction. 

Test  the  operation  of  the  normal  terminal  stopping 
device  by  operating  the  car  at  inspection  speed  until 
the  normal  terminal  stopping  device  can  be  reached  by 
hand.  Use  an  insulated  object  to  actuate  this  device  and 
try  to  move  the  car  in  the  direction  of  the  device.  The 
car  should  not  move  in  the  direction  of  the  device,  but 
should  be  able  to  move  in  the  opposite  direction. 

3.5.2  Periodic  Test 

3.5.2.1  Electric  Elevators:  Yearly  Test  (for 
A17.1d-2000  and  Earlier  Editions);  Category  1  Test  (for 
A17.1-2000/B44-00  and  Later  Editions).  Test  the  opera- 
tion of  the  normal  terminal  stopping  device  by  operating 
the  car  at  inspection  speed  until  the  normal  terminal 
stopping  device  can  be  reached  by  hand.  Use  an  insu- 
lated object  to  actuate  this  device  and  try  to  move  the 
car  in  the  direction  of  the  device.  The  car  should  not 
move  in  the  direction  of  the  device,  but  must  be  able  to 
move  in  the  opposite  direction. 


3.5.2.2  Hydraulic  Elevators:  Yearly  Test  (for 
A17.1d-2000  and  Earlier  Editions);  Category  1  Test  (for 
A17.1-2000/B44-00  and  Later  Editions) 

(a)  Render  the  normal  elevator  stopping  means  and 
the  emergency  terminal  stopping  inoperative. 

(b)  Do  not  disable  the  emergency  terminal  speed  lim- 
iting device  or  the  normal  terminal  stopping  device. 

(c)  Run  the  car  at  rated  speed  (from  outside  the  car) 
into  the  bottom  terminal  and  demonstrate  that  the  car 
slows  down  and  stops  in  the  vicinity  of  the  bottom 
terminal. 

(d)  Repeat  the  above  test  for  the  top  terminal. 

(e)  Restore  all  stopping  means  and  check  for  proper 
operation. 

3.5.3  Acceptance 

3.5.3.1  Electric  Elevators.    See  Item  2.28.3. 

3.5.4  References 

3.5.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  207.4, 209.2, 210.2, 1001.2(c)(7),  1002.2e, 
1003.2f,  and  1003.3(k). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.25.1,  2.25.2,  2.26.2,  8.11.2.1.3(g), 
8.11.2.2.5,  8.10.2.2.2(z),  and  8.10.2.3.2(k). 

A17.3  —  Paragraphs  3.9.1  and  3.10.4. 

3.5.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  305.1a,  1002.2e  {1005.2c},  1003.3(k), 
and  1004.2(c)(5). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  3.25.1.1,  8.11.2.2.5  {8.11.3.2.3}, 
8.10.2.3.2(k),  and  8.11.3.1.3(e). 

A17.3  —  Paragraphs  3.9.1  {Section  4.6}  and  3.10.4. 

ITEM  3.6 

FINAL  AND  EMERGENCY  TERMINAL  STOPPING 

DEVICES 

3.6.1  Periodic  Inspections 

3.6.1.1  Electric  Elevators.  Observe  caution  if  the 
top  car  clearance  is  limited.  Run  the  car  to  the  top  of  its 
travel  at  inspection  speed  and  examine  the  final  terminal 
stopping  device. 

(a)  The  upper  final  terminal  stopping  device  must 
be  located  as  close  to  the  terminal  landing  as  possible 
without  interfering  with  the  normal  terminal  stopping 
device,  but  actuate  before  the  car  strikes  the  overhead. 

(b)  Check  the  fastening  and  alignment  of  the  switch 
and  cam.  The  switch  roller  should  strike  the  bevel  sur- 
face of  the  cam.  If  properly  located  and  adjusted,  the 
roller  will  center  laterally  on  the  cam,  assuring  free 
motion  of  the  roller  arm  and  positive  opening  of  the 
switch  contact  without  damaging  the  switch. 

3.6.1.2  Hydraulic  Elevators.  A17.1d-1970  and  later 
editions  require  an  emergency  terminal  speed  limiting 


47 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


device  at  the  top  terminal  landing  where  the  rated  speed 
exceeds  100  ft/min  (0.51  m/s)  and  at  the  bottom  landing 
where  reduced  stroke  buffers  are  used.  In  A17.1-1955 
through  A17.1c-1969  an  emergency  terminal  stopping 
device  was  required  where  a  reduced  stroke  buffer  was 
used  or  the  speed  was  over  100  ft/min  (0.51  m/s).  Verify 
that  the  emergency  terminal  stopping  device  functions 
independent  of  the  normal  stopping  means  and  the  nor- 
mal terminal  stopping  device.  Verify  that  the  emergency 
terminal  speed  limiting  device  functions  independent 
of  the  normal  terminal  stopping  device  and  that  its  car 
speed  sensing  device  functions  independent  of  the  nor- 
mal speed  control  system. 

Where  mechanical  or  hydraulic  emergency  terminal 
speed  limiting  devices  are  provided,  refer  to  the  manu- 
facturer's recommended  test  procedures. 

Inspect  the  device  for  condition  and  alignment.  Slowly 
move  the  car  up  and  verify  that  the  device  will  be  oper- 
ated by  movement  of  the  car. 

3.6.2  Periodic  Test 

3.6.2.1  Electric  Elevators 

(a)  Yearly  Test  (for  A17,ld-2000  and  Earlier  Editions); 
Category  1  Test  (for  All .1-2000/B44-00  and  Later  Editions). 
Before  testing  final  terminal  stopping  devices  from  the 
top  of  the  car,  determine  whether  the  potential  switch 
on  the  controller  is  of  the  manually  or  electrically 
restored  type.  If  it  is  the  manually  restored  type,  opera- 
tion of  the  final  terminal  stopping  device  should  not  be 
tested  from  the  car  unless  someone  is  in  the  machine 
room  to  reset  the  controller  switch  when  instructed  to 
do  so  by  the  inspector. 

Run  the  car  up  the  hoistway  at  inspection  speed  until 
the  upper  final  terminal  stopping  device  may  be  reached 
by  hand.  Use  an  insulated  object  to  actuate  this  device, 
and  try  to  move  the  car  in  each  direction.  The  car  should 
not  move;  if  it  does,  the  inspection  should  not  be  contin- 
ued until  this  defect  is  corrected. 

The  operation  of  the  final  terminal  stopping  device 
(final  limit)  and  its  relation  to  the  cam  can  be  tested  by 
jumping  out  the  normal  terminal  stopping  device  and 
running  the  car  past  the  terminal  floor  at  inspection 
speed.  The  car  should  stop  close  to  the  floor.  It  may  be 
necessary  to  jump  out  the  final  terminal  stopping  device 
to  move  the  car  back  to  floor  level.  After  the  final  termi- 
nal stopping  device  has  been  tested,  remove  all  jumpers. 

(b)  5-Year  Test  of  Emergency  Terminal  Stopping  Means 
(for  A17.1d-2000  and  Earlier  Editions);  Category  5  Test  of 
Emergency  Terminal  Stopping  Means  (for  A17. 1-2000  and 
Later  Editions).  For  static  control  elevators,  see  Item 
2.28.2.1(b)  and  for  emergency  terminal  speed  limiting 
devices,  see  Item  5.3.2. 

3.6.2.2  Hydraulic  Elevators:  Yearly  Test  (for 
A17.1d-2000  and  Earlier  Editions);  Category  1  Test  (for 
A17.1-2000/B44-00  and  Later  Editions).  Block  or  tie 
the  device  in  the  functioning  position  and  move  the  car 


down.  Then  attempt  to  run  the  car  up  at  rated  speed. 
The  emergency  terminal  speed  limiting  device  should 
prevent  the  car  from  running  in  excess  of  100  ft/min 
(0.51  m/s).  The  car  should  not  run  with  the  emergency 
terminal  stopping  device  in  the  functioning  position. 

3.6.3  Acceptance 

3.6.4  References 

3.6.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  209.3,  1001.2(c)(8),  1002.2e,  and 
1003.3(k). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.25.3,  8.11.2.1.3(h),  8.11.2.2.5,  and 
8.10.2.3.2(k). 

A17.3  —  Paragraph  3.9.2. 

3.6.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  305.2,  1004.2(c)(6),  and  1005.2. 

A17.1-2000/B44-00     and     later     editions     — 
Requirements  3.25.2,  8.11.3.1.3(f),  and  (NR  1005.2). 
A17.1-1955  —  Rule  320.2. 

ITEM  3.7 
CAR  LEVELING  AND  ANTICREEP  DEVICES 

3.7.1  Periodic  Inspections 

3.7.1.1  Electric  Elevators.  Examine  fastenings  and 
clearances  of  car  leveling  devices,  including  cams  and 
vanes  located  in  the  hoistway. 

3.7.1.2  Hydraulic  Elevators.  Examine  fastenings 
and  clearances  of  car  leveling  devices,  including  cams 
and  vanes  located  in  the  hoistway.  With  the  car  level 
with  the  floor,  place  a  mark  on  the  rail  relative  to  a  guide 
shoe  or  roller.  Lower  it  slightly  more  than  1  in.  (25  mm) 
by  using  inspection  operation.  Turn  the  car  back  on 
normal  operation  and  observe  that  it  levels  within  1  in, 
(25  mm)  of  the  floor  level  for  elevators  installed  under 
A17.1-1978  and  later  editions.  For  elevators  installed 
prior  to  A17.1-1978  edition  and/or  required  to  comply 
with  A 17. 3,  observe  that  the  car  will  level  to  within 
3  in.  (76  mm)  of  the  floor.  If  a  manual  lowering  valve 
is  available  in  the  machine  room,  required  under 
A17. 1-1984  and  later  editions,  it  is  used  as  described  in 
Item  2.32.1  for  testing  the  anticreep  device.  Check  that 
the  anticreep  device  remains  operative  regardless  of  the 
position  of  the  car  and  hoistway  doors,  emergency  stop 
switch  or  in-car  stop  switch,  hinge  car  platform  sill  elec- 
tric contacts  and  broken  rope,  tape,  or  chain  switch  for 
normal  stopping  devices. 

For  maintained  pressure  hydraulic  elevators,  operate 
the  car  in  both  directions. 

3.7.2  Periodic  Test 

3.7.3  Acceptance 

3.7.4  References 

3.7.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  210.1e  and  1001.2(c)(10). 


48 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.26.1.6  and  8.11.2.1.3(j). 

3.7.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  306.3,  306.4,  and  1004.2(c)(7). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  3.26.3,  3.26.4,  and  8.113.1.3(g). 

A17.3  —  Paragraphs  4.7.3  and  4.7.4. 

ITEM  3.8 
TOP  EMERGENCY  EXIT 

(to)    3.8.1  Periodic  Inspections 

(a)  For  elevators  installed  under  A17. 1-1955  through 
A 17. 1-1 960,  check  that  the  top  emergency  exit  opens 
outward.  Verify  that  the  exit  is  hinged  or  otherwise 
attached  to  the  car  and  can  be  opened  from  both  inside 
and  from  the  top  of  the  car  without  the  use  of  special 
tools.  For  elevators  installed  under  A17.1-1965  and  later 
editions,  and  those  elevators  required  to  meet  A17.3, 
verify  that  the  top  emergency  exit  is  locked,  and  open- 
able  from  the  top  of  the  car  only  without  the  use  of 
special  tools.  For  elevators  installed  under  A17. 1-2000/ 
B44-00  and  later  editions,  check  the  emergency  exit  elec- 
tric contact. 

(b)  For  elevators  in  unenclosed  hoistways,  top  emer- 
gency exits  are  prohibited  for  elevators  installed  under 
A17.1b-1989  through  A17.1d-2000.  On  elevators  in  par- 
tially enclosed  hoistways,  installed  under  Al  7. 1-2000/ 
B44-00  and  later  editions,  check  the  means  to  facilitate 
emergency  evacuation. 

3.8.2  Periodic  Test 

3.8.3  Acceptance 

Measure  the  top  emergency  exit  size  and  clearances. 

3.8.4  References 

3.8.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  204.1e  and  1001.2(c)(12). 

A17.1-2000/B44-00      and     later     editions     — 
Requirements  2.14.1.5  and  8.11.2.1.3(1). 
A17.3  —  Paragraph  3.4.4. 

3.8.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  204.1e  {301.7}  and  1004.2(c)(9). 

A17.1-2000/B44-00      and      later      editions     — 
Requirements  2.14.1.5  {3.14}  and  8.11.3.1.3(i). 
A17.3  —  Paragraph  3.4.4  {4.2.3}. 

ITEM  3.9 

FLOOR  AND  EMERGENCY  IDENTIFICATION 

NUMBERING 

(io)    3.9.1  Periodic  Inspections 

(a)  For  elevators  installed  under  A17.1b-1973  and 
later  editions,  check  that  floor  numbers  have  been  pro- 
vided in  the  hoistways,  not  less  than  4  in.  (102  mm)  in 


height,  placed  on  the  walls  and /or  doors  of  the  hoistway 
at  intervals  where  a  person  on  top  of  the  car  can  deter- 
mine the  floor  position.  Check  that  floor  numbers  are 
provided  and  legible. 

(b)  For  elevators  installed  under  A17.1-1990  and  later 
editions,  check  that  emergency  identification  numbers 
are  provided  on  the  crosshead,  or  the  car  frame  where 
there  is  no  crosshead  where  more  than  one  elevator's 
machinery  is  in  a  hoistway  or  machine  room. 

3.9.2  Periodic  Test 

3.9.3  Acceptance 

3.9.4  References 

3.9.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  100.7,  211.9,  and  1001.2(c)(15). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.29.2,  2.29.1,  and  8.11.2.1.3(o). 

3.9.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  100.7  {300.1},  211.9  {306.11},  and 
1004.2(c)(10). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.29.2  {3.1},  2.29.1  {3.27},  and  8.11.3.1.3(j). 

ITEM  3.10 
HOISTWAY  CONSTRUCTION 

3.10.1  Periodic  Inspections 

Check  the  condition  of  the  hoistway  enclosure,  and 
remote  counterweight  hoistway;  note  any  damage  or 
loose  materials. 

For  elevators  installed  under  A17.1-2000  and  later 
editions,  projections  greater  than  4  in.  (102  mm)  are 
required  to  be  beveled. 

For  elevators  installed  under  A17.1d-2000  and  earlier 
editions,  projections  greater  than  2  in.  (51  mm)  are 
required  to  be  beveled. 

3.10.2  Periodic  Test 

3.10.3  Acceptance 

Determine  if  the  hoistway  enclosure  conforms  to  the 
building  code  requirements.  Inspect  the  hoistway  enclo- 
sure for  substantially  flush  construction.  Projections 
should  be  properly  beveled  or  protected.  For  elevators 
with  no  top  emergency  exit  installed  in  unenclosed 
hoistways,  determine  that  all  landings  are  provided  with 
either  hoistway  entrances  or  emergency  doors. 

3.10.4  References 

3.10.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Section  100  and  Rule  1001.2(c)(16). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.1  and  8.11.2.1.3(p). 

A17.3  —  Section  2.1. 


49 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


3.10.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  300.1  and  1004.2(c)(ll). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  3.1  and  8.11.3.1.3(k). 

A17.3  —  Section  2.1  {4.1}. 

ITEM  3.11 
HOISTWAY  SMOKE  CONTROL 

(io)    3.11.1   Periodic  Inspections 

For  elevators  installed  under  A17.1-1955  through 
A17.1b-1980/  that  serve  more  than  three  floors,  check 
that  one-third  of  the  required  venting  is  permanently 
open  or  automatically  opened  by  a  damper.  All  venting 
should  be  to  the  outside.  Portions  of  the  required  vents 
may  be  closed  with  glass.  This  should  consist  of  plain 
glass,  a  maximum  of  %  in-  (3.2  mm)  thick.  The  vent  area 
was  required  to  be  a  minimum  of  3.5%  of  the  cross- 
sectional  area  of  the  hoistway  (3  ft2  min.)  for  each  car. 

Verify  that  elevators  installed  under  A17.1-1981  and 
later  editions  are  provided  with  an  approved  means  to 
prevent  the  accumulation  of  smoke  and  hot  gases  in 
case  of  fire.  Assure  ventilation  is  in  accordance  with 
building  code  requirements  and  is  in  working  order. 
Check  that  any  required  openings  are  in  the  open  posi- 
tion and  not  locked  or  blocked. 

3.11.2  Periodic  Test 

3.11.3  Acceptance 

Check  that  means  to  prevent  the  accumulation  of 
smoke  and  hot  gases  in  case  of  fire  is  in  accordance  with 
the  requirements  of  the  building  code. 

3.11.4  References 

3.11.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  100.4  and  1001.2(c)(17). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.1.4  and  8.11.2.1.3(q). 

3.11.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  100.4  {300.1}  and  1004.2(c)(12). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.1.4  {3.1}  and  8.11.3.1.3(1). 


ITEM  3.12 
PIPES,  WIRING,  AND  DUCTS 

3.12.1  Periodic  Inspections 

Only  pipes,  wiring,  and  ducts  used  in  connection  with 
the  elevator  may  be  installed  in  the  hoistway.  Check 
sprinkler  piping  for  leakage.  For  elevators  required  to 
meet  A17.3,  pipes  conveying  gases,  vapors,  or  liquids 
not  connected  with  the  operation  of  the  elevator  must 
be  guarded  so  that  any  discharge  will  not  affect  the 
operation  of  the  elevator. 


3.12.2  Periodic  Test 

3.12.3  Acceptance 

Check  that  sprinkler  risers  and  return  piping  have 
been  located  outside  the  hoistway.  Check  that  shutoff 
valves  have  been  provided  for  each  branch  line  and  are 
accessible  outside  the  hoistway.  Check  to  see  that  an 
automatic,  non-resetting  means  is  provided  to  discon- 
nect the  main  line  power  to  affected  elevators  before 
water  is  discharged  into  the  hoistway.  The  Code  prohib- 
its sprinkler  activation  or  disconnection  of  main  line 
power  by  smoke  detectors. 

3.12.4  References 

3.12.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Section  102  and  Rule  1001.2(c)(18). 

A17.1-2000/B44-00     and     later     editions     — 
Requirements  2.8  and  8.11.2.1.3(r). 
A17.3  —  Paragraph  2.1.4. 

3.12.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Section  102  {Rule  300.3}  and  Rule 
1004.2(c)(13). 

A17.1-2000/B44-00      and      later      editions     — 
Requirements  2.8  {3.8}  and  8.11.3.1.3(m). 
A17.3  —  Paragraph  2.1.4  {Section  4.1}. 

ITEM  3.13 

WINDOWS,  PROJECTIONS,  RECESSES,  AND 

SETBACKS 

3.13.1  Periodic  Inspections 

(a)  Hoistway  Windows.  Elevators  installed  under 
A 17. 1-1971  and  later  editions  are  not  permitted  to  have 
windows  in  the  hoistways. 

Where  windows  are  provided  in  hoistways  of  existing 
elevators,  verify  that  they  are  guarded  on  the  inside  or 
outside  as  required  by  local  regulations  or  the  Code 
edition  in  effect  at  the  time  of  installation. 

For  elevators  required  to  meet  A  17.3,  check  that  every 
hoistway  window  ten  stories  or  less  above  a  thorough- 
fare, and  every  such  window  opening  three  stories  or 
less  above  a  roof  of  an  adjacent  building  are  guarded. 
Also,  check  that  every  exterior  hoistway  window  has 
been  identified  with  4  in.  (102  mm)  high  letters  marked 
"ELEVATOR." 

(b)  Projections,  Recesses,  and  Setbacks.  Determine  that 
guards  for  recesses  in  the  hoistway  enclosure  opposite 
car  openings,  other  than  landing  entrances,  are  in  place 
and  secured.  Check  that  landing  sill  guards,  dust  covers, 
and  landing  entrance  toe  guards  are  securely  in  place. 

3.13.2  Periodic  Test 

3.13.3  Acceptance 

3.13.4  References 

3.13.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  100.5,  100.6,  110.10,  and  1001.2(c)(19). 


50 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


Table  3.14.3(a)     Horizontal  Clearances 


Clearances  Between 


Maximum, 
in. 


Minimum, 
in. 


Rqmt. 
No. 


Car  platform  and  landing  sill 
Side-post  construction 
Corner-post  construction 

Car  and  hoistway  enclosure  (except  sides  used 
for  loading  and  unloading) 

Car  platform  sill  and  hoistway  enclosure  for  full 
width  of  hoistway  opening 
Vertically  sliding  hoistway  doors 
Other  than  vertically  sliding  hoistway  doors 

Car  and  counterweight 

Two  adjacent  cars 

Counterweight  and  counterweight  screen 

Counterweight  and  hoistway  enclosure 


1V2 
iy3 


v2 


2.5.1.4 
2.5.1.4 


2.5.1.1 


7V2 
5 

2.5.1.5 
2.5.1.5 

1 

2.5.1.2 

2 

2.5.1.3 

3A 

2.5.1.2 

3A 

2.5.1.2 

GENERAL  NOTE:      1  in.  =  25.4  mm 


A17.1-2000/B44-00      and      later     editions     — 
Requirements  2.1.5,  2.1.6,  2.11.10,  and  8.11.2.1.3(s). 
A17.3  —  Paragraphs  2.1.2  and  2.1.3. 

3.13.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  100.5  and  100.6  {300.1},  110.10 
{300.11},  and  1004.2(c)(14). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.1.5  and  2.1.6  {3.1},  2.11.10  {3.11},  and 
8.11.3.1.3(n). 

A17.3  —  Paragraphs  2.1.2  and  2.1,3  {Section  4.1}. 

ITEM  3.14 
HOISTWAY  CLEARANCES 

3.14.1  Periodic  Inspections 

3.14.1.1  Electric  Elevators.  Observe  the  clearances 
between  car  and  hoistway  enclosures,  between  car  and 
counterweight  or  counterweight  screen,  between  the 
counterweight  and  hoistway  enclosure,  and  between 
adjacent  cars. 

3.14.1.2  Hydraulic  Elevators:  Car  Horizontal 
Clearances.  Observe  the  clearances  between  car  and 
hoistway  enclosures,  and  between  adjacent  cars. 

3.14.2  Periodic  Test 

3.14.3  Acceptance 

Measure  and  record  horizontal  hoistway  dimensions 
and  clearances.  See  Tables  3.14.3(a)  and  3.14.3(b). 

3.14.4  References 

3.14.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Sections  107  and  108  and  Rule  1001.2(c)(20). 


A17.1-2000/B44-00     and     later 
Requirements  2.4,  2.5,  and  8.11.2.1.3(t). 
A17.3  —  Section  2.4. 


editions     — 


3.14.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Sections  108  {Rule  300.9}  and  110  (Rule 
300.11};  and  Rule  1004.2(c)(15). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.5  {3.5}  and  2.11  {3.11},  and  8.11.3.1.3(o). 

A17.3  —  Section  2.4  {4.1}. 

ITEM  3.15 
MULTIPLE  HOISTWAYS 

3.15.1  Periodic  Inspections 

Observe  the  clearances  between  cars  in  a  multiple 
hoistway.  See  Table  3.14.3(a). 

3.15.2  Periodic  Test 

3.15.3  Acceptance 

Verify  multiple  hoistways  are  constructed  in  compli- 
ance with  the  building  code.  Measure  the  running  clear- 
ances between  cars  including  equipment  attached  to 
the  car. 

3.15.4  References 

3.15.4.1  Electric  Elevators.  Al 7. ld-2000  and  earlier 
editions  —  Rules  lOO.ld  and  1001.2(c)(21). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.1.1.4  and  8.11.2.1.3(u). 

3.15.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  lOO.ld  {300.1}  and  1004.2(c)(16). 


51 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers.  X^  . 

No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME.     ^ 


ASME  A17.2-2010 


Table  3.14.3(b)    Horizontal  Distances 


Distance  Between  Horizontally  Sliding  and  Swinging  Maximum,  Minimum,  Rqmt. 

Hoistway  Door  and  Edge  of  Landing  Sill  in.  in.  No. 


Elevators  that  can  be  opened  from  car  only 
New  installations 

New  or  altered  elevators  in  existing  multiple 
hoistways 
Swinging  doors 
Sliding  doors 

Automatic  or  continuous  pressure  operation 
Sliding  hoistway  doors 
Swinging  hoistway  doors 
Swinging  hoistway  doors  on  freight  elevators  not 

accessible  to  general  public  and  located  in 

industrial-type  buildings 


2% 


2.11.4 


2.11.4 
2.11.4 


2.11.4 
2.11.4 


2.11.4 


GENERAL  NOTE:     1  in.  =  25.4  mm 


A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.1.1.4  {3.1}  and  8.11.3.1.3(p). 

ITEM  3.16 
TRAVELING  CABLES  AND  JUNCTION  BOXES 

3.16.1  Periodic  Inspections 

(a)  Junction  Boxes  and  Traveling  Cable  Supporting  Means. 
Hoistway  and  car  junction  boxes  should  be  securely 
fastened  with  covers  in  place.  Examine  the  supporting 
means  of  the  cable  at  the  connection  points.  Where  a 
steel  member  is  used  to  support  the  traveling  cable, 
examine  its  attachment  to  the  hoistway  or  car  connection 
point  and  verify  that  it  is  securely  fastened.  The  live  load 
on  steel  supporting  fillers  should  hang  in  the  direction 
of  tightening  of  the  supporting  bolt  or  other  means  of 
fastening  and  the  dead  end  taped  or  clamped  to  the  live 
end.  Examine  for  any  evidence  of  wear  or  breaks  in  the 
steel  supporting  fillers,  which  may  damage  the  insula- 
tion of  the  conductors  or  cause  the  traveling  cable  to 
release,  causing  strain  or  breakage  to  the  conductors  at 
the  terminal  lugs. 

(b)  Flexible  Wire  Mesh  Automatic  Tightening  Devices. 
Where  a  flexible  wire  mesh  automatic  tightening  device 
is  used,  examine  the  grip  to  be  sure  that  it  is  securely 
fastened  to  its  support  at  the  hoistway  or  car  connection 
point.  Examine  the  eye  of  the  grip  attached  to  the  sup- 
porting member.  When  a  double  eye  attachment  is  used, 
the  eyes  should  be  attached  so  they  share  the  load 
equally  and  do  not  exceed  15  deg  from  the  axis  of  the 
vertical  cable. 

There  are  basically  three  types  of  flexible  wire  mesh 
automatic  tightening  devices  (see  Fig.  3.16.1): 

(1)  closed  type 

(2)  split-laced  type 

(3)  split-rod  type 


Examine  the  grip  where  the  eye  is  attached  to  the 
wire  mesh  section  for  any  visible  signs  of  wear  or  break- 
age. This  point  is  subject  to  damage  because  of  flexing 
of  the  cable.  It  is  recommended  that  the  lower  section 
of  the  grip  be  secured  to  the  traveling  cable  to  prevent 
triggering  (total  or  partial  relaxing  of  the  grip)  and  cul- 
minate in  milking  of  the  grip  (slight  movement  of  grip 
on  the  outer  section  of  the  traveling  cable).  Examine  for 
damage  caused  by  the  securing  means.  The  triggering 
of  the  grip  may  cause  the  cable  to  release,  thereby  placing 
strain  or  breakage  on  the  individual  conductors.  Milking 
of  the  grip  may  cause  wear  to  the  insulation  of  travel- 
ing cable. 

(c)  Traveling  Cables.  Examine  the  traveling  cables  for 

(1)  excessive  twists  or  kinks 

(2)  damage  due  to  chafing 

(3)  intertwining  of  multiple  cables 

(4)  clearance  from  hoistway  equipment  such  as 
buffers,  plungers,  brackets,  beams,  etc. 

3.16.2  Periodic  Test 

3.16.3  Acceptance 

Check  that  traveling  cables  are  properly  installed,  sup- 
ported, and  protected  against  damage.  Traveling  cables 
should  be  supported  by  one  of  the  following  means: 

(a)  by  internal  steel  supporting  member 

(b)  by  looping  the  cables  around  supports  for  unsup- 
ported lengths  of  less  than  100  ft  (30.5  m) 

(c)  by  suspending  from  the  supports  by  a  means  that 
automatically  tightens  around  the  cable  when  tension 
is  increased  for  unsupported  lengths  of  up  to  200  ft 
(61  m) 

3.16.4  References 

3.16.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  102.1  and  1001.2(c)(22). 


52 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Fig.  3.16.1     Self-Tightening  Grips 


Closed 


Split-Laced 


Split-Rod 


A17.1-2000/B44-00     and     later     editions     — 
Requirements  2.8.1  and  8.11.2.1.3(v). 
NFPA  70  or  CSA  C22.1,  as  applicable. 

3.16.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  102.1  (300.3}  and  1004.2(c)(17). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.8.1  {3.8}  and  8.11.3.1.3(q). 

NFPA  70  or  CSA  C22.1,  as  applicable. 

ITEM  3,17 
DOOR  AND  GATE  EQUIPMENT 

(io)    3.17.1  Periodic  Inspections 

(a)  Car  and  Hoistway  Door  and  Gate  Operating,  Locking 
and  Contact  Devices,  and  Interlocking  Retiring  Cams 

(1)  Examine  all  hoistway  and  car  door  or  gate 
operating  motors  and  cams.  Check  locking  and  contact 
devices,  switches,  or  other  operating  mechanisms 
located  on  top  of  the  car  or  in  the  hoistway.  Determine 
whether  they  are  in  proper  working  order,  securely  fas- 
tened in  place,  and  properly  lubricated.  Check  hydraulic 
door  operators  for  any  oil  leakage. 

(2)  Examine  any  stationary  or  retiring  cams, 
operating  interlocks,  interlock  contacts,  or  door  opera- 
tors. Determine  whether  they  are  in  correct  alignment 
with  the  roller  arm  of  the  interlock  or  door  operating 
mechanism.  Check  whether  their  travel  is  sufficient  to 
ensure  proper  operation  of  the  interlocks  or  door 
operators. 

(3)  Examine  relating  chains,  sprockets,  and  wire 
cables  for  proper  tension  and  note  any  excessive  wear. 

(4)  Test  hoistway  door  operators  actuated  by  mag- 
netic controls  to  determine  the  car  is  within  the  landing 
zone,  or  within  the  limits  of  the  leveling  zone  where  an 


automatic  leveling  device  is  provided,  before  the  control 
causes  the  door  operator  to  open  to  the  hoistway  door. 
Check  that  the  car  is  at  rest  or  substantially  level  with 
the  landing  before  the  door  is  in  the  fully  open  position. 
Air-  (pneumatic)  operated  doors  must  meet  similar 
requirements,  provided  they  are  manually  controlled. 
The  car  must  be  within  the  landing  zone  or  within  the 
leveling  zone  before  the  door  operating  device  is  in  a 
position  to  engage  the  door  operating  cam. 

(5)  Examine  the  name  plates  on  hoistway  door  or 
gate  interlocks,  combination  mechanical  locks  and  elec- 
tric contacts,  and  car  door  or  gate  electric  contacts.  Verify 
that  they  are  of  a  type  approved  by  the  authority  having 
jurisdiction.  For  elevators  installed  under  A 17. 1-1 987 
and  later  editions,  check  that  mercury  tube  switches 
have  not  been  used  for  electric  contacts. 

(6)  Combination  mechanical  locks  and  electric  con- 
tacts of  the  hoistway  unit  system  are  permitted  by 
A17.1-1955  and  later  editions,  on  freight  elevators  under 
restricted  conditions. 

(a)  Inspect  mechanical  locks  operated  manually 
from  top  of  car,  where  used,  with  hoistway  door  or  gate 
electric  contacts.  With  the  door  or  gate  in  the  fully  closed 
position,  pull  on  the  door  or  gate,  which  should  be 
held  closed  by  the  lock.  Determine  whether  the  locking 
member  is  in  a  position  to  lock  the  door  when  or  before 
the  contact  is  closed  by  the  door  or  gate. 

(b)  Where  the  locking  members  of  such  devices 
are  operated  by  car  cams,  place  the  door  or  gate  in 
the  fully  closed  position  and  move  the  car  a  sufficient 
distance  away  from  the  floor  to  permit  the  locking  mem- 
ber to  lock  the  door  or  gate.  With  the  car  in  this  position, 
pull  or  push  on  the  door,  which  should  be  held  closed 
by  the  lock.  Release  the  lock  manually  and  open  the 
door  or  gate.  Then  slowly  close  it  to  the  position  where 


53 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


the  electric  contact  just  closes  and  note  whether  the 
locking  member  is  in  a  position  to  lock  the  door. 
(b)  Car  and  Hoistway  Door,  Gate  Hangers,  and  Equipment 

(1)  Examine  the  condition  of  hoistway  and  car  door 
or  gate  hangers,  tracks,  and  guides  to  determine  they 
are  securely  fastened  in  place,  engaged  and  not  worn, 
so  that  the  doors  will  not  come  out  of  their  guideway 
at  any  point  in  their  travel,  and  are  lubricated.  If  the 
guides  are  not  made  out  of  fire-resistive  materials,  check 
that  tabs  (this  is  not  the  hoistway  door  safety  retainer) 
to  retain  the  door  in  place  during  a  fire  are  engaged  in 
the  guideway.  Check  that  the  door  frames  are  securely 
fastened  to  the  building  structure.  Hoistway  door  safety 
retainers  are  required  on  elevators  installed  under 
A17.1-1993/B44-1985  and  later  editions. 

NOTE:  The  requirement  that  hoistway  door  panels  and  guides 
meet  certain  fire-resistive  criteria  was  specifically  stated  in  Part  1 
for  horizontally  sliding  doors  until  A17.1c-1986  and  for  vertically 
sliding  doors  until  A17.1-1984.  However,  where  required  by 
requirement  2.1.1,  the  entire  entrance  assembly  is  still  required  to 
meet  the  fire-resistive  criteria,  but  is  now  specified  in  require- 
ment 8.3.4. 

(2)  When  multipanel  entrances  are  provided,  check 
that  they  are  interconnected  or  equipped  with  interlocks 
on  each  driven  panel  for  elevators  installed  under 
A17.1-1990  and  later  editions.  A17.1b-1989  and  earlier 
editions  require  the  panels  to  be  interconnected.  Exam- 
ine interconnections  of  the  panels  of  multisection  doors. 
Determine  if  they  are  in  proper  condition  and  are 
securely  fastened  to  the  door  panels.  Examine  intercon- 
nections, whether  in  hanger  chains,  ropes,  or  other  parts, 
or  in  the  door  closer  arms  and  pins.  Check  for  any  wear, 
which  might  cause  the  panels  to  become  disconnected 
from  each  other  and  permit  the  car  to  operate  with  one 
or  more  of  the  panels  open.  On  two-speed  entrances  for 
elevators  installed  under  A17.1-1990  and  later  editions, 
check  that  the  slow  and  fast  panels  are  provided  with 
a  secondary  mechanical  interconnecting  means.  On  cen- 
ter-opening doors  with  a  single  interlock,  check  that 
the  interlock  is  operated  by  the  nondriven  panel  for 
elevators  installed  under  A17.1-1990  and  later  editions. 

(3)  Horizontally  sliding  or  single  section  swinging 
doors  of  automatic  elevators  must  be  provided  with  door 
closers  arranged  to  close  an  open  door  automatically  if 
the  car  leaves  the  landing  zone  for  any  reason.  Check 
the  door  closers  by  manually  opening  the  doors  to  the 
fully  open  position,  then  release  the  doors.  As  they  are 
returning  to  the  closed  position,  manually  stop  and 
release  the  doors  at  approximately  the  halfway  point 
and  at  approximately  2  in.  (51  mm)  from  the  strike  jamb. 
Verify  that  the  doors  return  to  the  fully  closed  and  locked 
position. 

(4)  Examine  hoistway  and  car  door  or  gate  counter- 
weights to  determine  they  are  properly  guided  or  boxed 
to  retain  the  counterweight  if  the  suspension  means 
breaks. 


(5)  Examine  car  and  hoistway  door  or  gate  suspen- 
sion members  together  with  their  connections,  pulleys, 
and  pulley  supports. 

(c)  Restricted  Opening  of  Hoistway  Doors  and/or  Car 
Doors  on  Passenger  Elevators.  For  elevators  required  to 
comply  with  the  restricted  opening  requirements  (Item 
1.18),  check  that  the  car  doors  can  be  opened  from  the 
top  of  the  car  within  specified  zones,  without  the  use 
of  special  tools. 

(d)  Landings  Locked  Out  of  Service.  Determine  that  the 
following  landings  are  not  locked  out  of  service: 

(1)  top  and  bottom  landings 

(2)  for  elevators  installed  under  A17.1b-1989  and 
later  editions,  the  designated  and  alternate  landings  for 
Phase  I  Firefighters'  Service  and  all  Phase  II  landings 

(3)  check  that  automatic  fire  doors  can  be  opened 
manually  from  the  hoistway  side  and  that  they  do  not 
lock  any  doors  that  lead  to  building  exits 

(e)  Hoistway  Door  Interlocks:  Auxiliary  Lock.  A  4  in. 
(102  mm)  locking  range  is  permitted  on  elevators  oper- 
ated from  inside  the  car  only.  An  auxiliary  lock  is 
required;  it  is  incorporated  either  in  the  door  closing 
mechanism  or  consists  of  a  rack  attached  to  the  landing 
sill  or  top  track  and  an  engaging  pawl  on  the  door.  When 
the  doors  are  power  closing,  the  auxiliary  lock  is  usually 
placed  on  the  closing  mechanism  to  prevent  damage. 

3.17.2  Periodic  Test 

3.17.3  Acceptance 

Check  that  entrance  panel(s),  frame  hardware,  and 
transoms  are  labeled  by  a  certifying  agency  acceptable 
to  the  authority  having  jurisdiction,  when  installed  in 
fire-resistive  construction.  A  single  label  may  be  pro- 
vided for  the  complete  entrance  assembly.  Check  that 
interlocks  or  combination  mechanical  locks  and  electric 
contacts  and  car  door  or  gate  electric  contacts  are  labeled 
by  a  certifying  agency  acceptable  to  the  authority  having 
jurisdiction. 

When  gasketing  material  is  applied  to  entrances  with 
a  fire-protection  rating,  check  that  it  has  been  tested  and 
labeled  by  a  certifying  agency  acceptable  to  the  authority 
having  jurisdiction. 

Check  that  center-opening  doors  are  mechanically 
interconnected  or  there  is  an  interlock  on  each  driven 
panel.  On  horizontally  sliding  doors  provided  with  a 
single  interlock,  check  that  the  door  closer  is  attached 
to  the  leading  panel  that  moves  in  the  opposite  direction. 
Check  the  secondary  mechanical  interconnecting  means 
on  multispeed  doors. 

3.17.4  References 

3.17.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Sections  110  and  111  and  Rules  210.1e  and 
1001.2(c)(23). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.11,  2.12,  2.26.1.6,  and  8.11.2.1.3(w). 


54 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


A17.3  —  Sections  2.6  and  2.7. 
A17.1  —  Inquiry  96-71. 

3.17.4.2  Hydraulic  Elevators.  A 1 7. ld-2000  and  ear- 
lier editions  —  Sections  110  {Rule  300.11}  and  111  {Rule 
300.12};  and  Rules  210.1e  {306.3}  and  1004.2(c)(18). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.11  {3.11},  2.12  {3.12},  2.26.1.6  {3.26.3},  and 
8.11.3.1.3(r). 

A17.3  —  Sections  2.6  and  2.7  {4.1}. 

A17.1  —  Inquiry  96-71. 

ITEM  3.18 
CAR  FRAME  AND  STILES 

3.18.1  Periodic  Inspections 

Failure  of  the  older  car  frame  stiles  (upright  structural 
members)  has  occurred  sufficiently  for  these  members 
to  receive  special  attention.  Make  a  careful  examination 
of  the  stiles  at  the  lowest  bolt  of  the  car  frame  crosshead 
gusset  plate.  Note  any  evidence  of  cracks  on  the  stiles, 
especially  directly  in  line  with  the  bottom  gusset  bolts. 
If  any  blistering  of  paint  is  noted,  scrape  to  expose  the 
metal  and  determine  its  condition.  If  a  crack  appears, 
it  is  probable  that  it  will  be  found  to  have  started  from 
the  outer  edge  of  the  stile  flange.  Check  that  welded 
repairs  and  required  written  certification  are  in  compli- 
ance with  the  Code.  Wood  car  frames  are  prohibited  by 
A17.1-1955  and  later  editions. 

3.18.2  Periodic  Test 

3.18.3  Acceptance 

3.18.4  References 

3.18.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Sections  203  and  213  and  Rules  1001.2(c)(24), 
1200.4,  and  1202.4a. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.15,  8.8;  8.11.2.1.3(x),  8.6.2,  and  8.7.2.15.1. 

3.18.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Section  213  {Rule  302.5)  and  Rules  301.6 
and  1004.2(c)(19). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  8.8  {3.18.5},  3.15,  and  8.11.3.1.3(s). 

ITEM  3.19 
GUIDE  RAILS  FASTENING  AND  EQUIPMENT 

3.19.1   Periodic  Inspections 

For  car  and  counterweight  guide  rails,  rail  fastenings, 
car  crossheads,  and  car  guiding  members,  the  following 
requirements  shall  be  met: 

(a)  Examine  the  guide  rails,  paying  particular  atten- 
tion to  the  condition  of  the  surfaces  and  the  correct 
alignment  of  the  joints.  Repeated  operation  of  the  car 
safety  or  improperly  adjusted  or  loose  car  guide  shoes 


that  permit  the  safety  jaws  to  run  against  the  rail  surfaces 
frequently  cause  serious  wear  or  scoring  of  the  rails  and 
the  safety  jaws. 

Where  sliding-type  guide  shoes  are  used,  determine 
that  rails  are  free  of  lint  and  dirt,  and  are  adequately 
but  not  excessively  lubricated  and  that  the  proper  lubri- 
cant, as  indicated  on  the  crosshead  data  plate  has  been 
used.  Where  roller  guides  are  used,  rails  should  be  clean 
and  dry  without  lubricant. 

(b)  Check  the  following  fastenings  to  determine 
whether  they  are  sound  and  tight,  and  that  there  are  no 
missing  bolts  or  guide  clips: 

(1)  rails  to  brackets 

(2)  brackets  to  building  construction 

(3)  fishplate  bolts 

(4)  crosshead  connection  bolts 

(5)  car  guide  shoe  bolts 

3.19.1.1  Electric  Elevators:  Alignment  of  Guide 
Rails.  If  any  excessive  or  irregular  motion  of  the  car 
was  noted  during  the  in  the  car  inspection,  examine 
guide  rail  alignment.  Examine  the  counterweight  guide 
rails  for  distance  between  guides. 

3.19.1.2  Hydraulic  Elevators:  Alignment  of  Guide 
Rails.  If  any  excessive  or  irregular  motion  of  the  car 
was  noted  during  the  in-the-car  inspection,  examine 
guide  rail  alignment.  Examine  the  sheave  guide  rails  as 
outlined  above  and  for  distance  between  guides.  On 
roped-hydraulic  elevators,  inspect  the  sheave  guide  rails 
as  specified  above. 

3.19.2  Periodic  Test 

3.19.3  Acceptance 

3.19.3.1  Electric  Elevators.  For  elevators  installed 
with  guide  shoes,  check  that  a  metal  lubrication  marking 
plate  has  been  securely  attached  to  the  car  crosshead, 
readily  visible,  and  legibly  and  permanently  marked. 

3.19.3.2  Hydraulic  Elevators.  Verify  that  a  metal 
lubrication  marking  plate  has  been  securely  attached 
to  the  car  crosshead,  readily  visible,  and  legibly  and 
permanently  marked. 

3.19.4  References 

3.19.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  205.16,  1001.2(c)(25),  and  1206.1d. 

A17.1-2000/B44-00      and      later     editions     — 
Requirements  2.17.16,  8.11.2.1.3(y),  and  8.6.4.3. 
A17.3  —  Paragraph  3.5.6. 

3.19.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Sections  200  {Rule  301.1b}  and  308;  and 
Rules  301.1,  301.6,  and  1004.2(c)(20). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.23  {3.23.2),  3.28,  3.23,  3.15.1.1.2,  and 
8.11.3.1.3(t). 

A17.3  —  Paragraph  4.9.8. 


55 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


ITEM  3.20 
GOVERNOR  ROPE 

3.20.1  Periodic  Inspections 

Inspect  the  governor  rope  for  evidence  of  lubricant 
being  added  after  installation  as  the  additional  lubricant 
may  interfere  with  the  ability  of  the  governor  to  retard 
the  governor  rope  and  apply  the  safety.  Check  the  gover- 
nor rope  data  tag  and  verify  that  the  rope  complies  with 
the  specification  on  the  governor  marking  plate.  Inspect 
the  governor  rope  as  outlined  in  Item  3.23  for  suspension 
ropes. 

3.20.2  Periodic  Test 

3.20.3  Acceptance 

Verify  the  governor  rope  that  has  been  installed  is  the 
correct  type,  size,  and  construction  as  indicated  on  the 
speed  governor  data  plate.  See  Item  2.12.  Check  for 
installation  of  the  required  governor  rope  data  tag. 

3.20.4  References 

3.20.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  — Rules  206.5, 1001.2(c)(26)/ 1202.7,  and  1206.1c. 

A17.1-2000/B44-00     and     later     editions     — 
Requirements  2.18.5,  8.11.2.1.3(z),  8.7.2.19,  and  8.6.4.2. 
A17.3  —  Paragraph  3.6.2. 

3.20.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  206.5, 301.8, 1001.2(c),  1004.2(c)  (23), 
1202.7,  and  1206.1c. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.18.5,  3.17.1,  8.11.2.1.3(z),  8.11.3.1.3(w), 
8.7.2.19,  and  8.6.4.2. 

A17.3  —  Section  3.6  and  para.  4.9.7. 


ITEM  3.21 
GOVERNOR  RELEASING  CARRIER 

3.21.1  Periodic  Inspections 

3.21.1.1  Electric  Elevators.  Examine  the  governor- 
rope  releasing  carrier  on  top  of  the  car.  Note  whether 
parts  are  rusted  or  caked  with  dirt  and  whether  springs 
are  broken. 

3.21.1.2  Hydraulic  Elevators.  For  roped-hydraulic 
elevators  installed  under  A17.1b-1989  and  later  editions, 
examine  the  governor-rope  releasing  carrier,  if  provided. 
Note  whether  parts  are  rusted  or  caked  with  dirt  or 
paint  and  whether  springs  are  broken. 

3.21.2  Periodic  Test:  5-Year  Test  (for  A17.1d-2000 
and  Earlier  Editions);  Category  5  Test  (for 
A17.1-2000/B44-00  and  Later  Editions) 

Test  the  governor  releasing  carrier  as  outlined  in  Item 
2.13.2(b). 


3.21.3  Acceptance 

3.21.4  References 

3.21.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  205.15  and  1001.2(c)(27). 

A17.1-2000/B44-00     and     later     editions     — 
Requirements  2.17.15,  8.6.2.4,  and  8.11.2.1.3(aa). 
A17.3  —  Section  3.5. 

3.21.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  205.15,  301,8,  1004.2(c)(22),  and 
1005.4. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.17.15,  3.17.1,  8.11.3.1.3(v),  and  8.11.3.4. 

ITEM  3.22 
WIRE  ROPE  FASTENING  AND  HITCH  PLATE 

3.22.1  Periodic  Inspections 

3.22.1.1  Electric  Elevators  and  Roped-Hydraulic 
Elevators 

(a)  Wire  Rope  Fastenings  and  Sheaves.  Check  that  ropes 
conform  to  the  specifications  on  the  crosshead  data  plate 
and  rope  data  tag.  Determine  that  rope  fastenings  at 
both  the  car  and  the  counterweight  or  dead-ends  of  the 
ropes  have  been  properly  made  up. 

(b)  Auxiliary  Rope  Fastening  Devices.  Where  an  auxil- 
iary rope  fastening  device  is  provided,  determine  that 
the  auxiliary  device  is  not  carrying  the  load  because  of 
rope  stretch  or  failure  at  the  regular  rope  fastening. 
Check  that  an  electric  switch  is  provided  to  open  motor 
and  control  circuits  when  the  auxiliary  rope  fastening 
device  operates.  Determine  that  it  is  properly  adjusted 
and  operational. 

(c)  Shackle  Rods.  Where  the  shackle  rod  and  rope 
socket  are  separate  pieces,  determine  that  the  fastening 
between  the  two  parts  is  positive  to  prevent  their 
separation. 

(d)  Tapered  Rope  Sockets.  Determine  whether  there  are 
any  broken  wires  at  the  point  where  the  rope  enters  the 
socket.  This  is  especially  important  in  the  case  of  the 
car  suspension  ropes  of  drum  machines.  Such  breaks 
usually  occur  at  rope  fastenings  just  inside  the  small 
end  of  the  socket  and  can,  in  many  cases,  be  detected 
by  prying  the  individual  wires  in  the  strand  with  a  sharp 
instrument,  such  as  the  blade  of  a  knife.  Also,  determine 
that  the  rope,  where  it  enters  the  socket,  has  not  had 
wire  or  strand  lays  disturbed  or  changed  and  no  strands 
bulge  out. 

(1)  Where  babbitted  metal  sockets  are  used,  note 
any  change  in  color  of  steel  wires  caused  by  overheating 
when  the  socket  was  made  up. 

(2)  Where  thermosetting  resin  composition  is  used, 
note  the  manufacturers  directions  must  be  strictly  fol- 
lowed in  handling,  mixing,  pouring,  and  curing  the  resin 
material. 


56 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


Fig.  3.22.1     Cross-Section  Through  Tapered  Rope 

Socket  Showing  Maximum  and  Minimum  Projection 

of  Loops  Above  Embedment  Medium 


d+V 


V2^rnin. 


Rope  strand 
diameter, 
d,  in. 


Tapered  rope  socket  per 
Requirement  2.20.9.4 
(Rule212.9d) 


GENERAL  NOTE:     1  in.  =  25.4  mm. 


(3)  When  the  embedment  medium  has  cooled  or 
cured,  and  the  seizing  at  the  small  end  has  been 
removed,  make  a  visual  inspection.  See  Fig.  3.22.1  and 
Table  3.22.1.  Check  for  retention  of  the  rope  lay  where 
it  leaves  the  small  end  of  the  socket,  full  penetration  of 
filler  material  as  evidenced  by  it  being  visible  around 
the  circumference  of  the  small  end  of  the  socket,  and 
correct  seating  of  the  strain  loops  in  the  filler  material. 

(e)  Other  Rope  Fastenings.  U-bolt  type  rope  clips 
(clamps)  are  prohibited  for  suspension  ropes.  Where 
nontapered  rope  fastenings  are  used,  and  approved  by 
the  authority  having  jurisdiction,  review  the  certification 
and  verify  that  the  socket  used  is  marked  and  identical 
to  the  one  on  the  certification.  Also,  verify  that  the  socket 
is  installed  in  accordance  with  the  manufacturer's/ 
supplier's  instructions.  Inspect  the  socket  for  secure  seat- 
ing of  the  wedge  and  damage  to  the  rope. 

(f)  Roping  Arrangement 


Table  3.22.1     Projection  of  Rope  Strands  Above 
Embedment  Medium  for  6-  and  8-Strand  Ropes 

Projection  Above  Embedment,  in. 


Rope 
Diameter,  in. 


Maximum 


Minimum 


% 
7/16 

y2 

9/l6 

% 
"AS 

% 
13/16 


0.17 
0.20 
0.21 
0.23 
0.25 
0.27 
0.29 
0.31 
0.32 
0.34 
0.36 


0.06 
0.07 
0.08 
0.09 
0.09 
0.10 
0.11 
0.12 
0.13 
0.14 
0.15 


GENERAL  NOTE:     1  in.  =  25.4  mm 

(1)  Where  1:1  roping  is  used,  determine  that  any 
steel  plates  used  to  support  the  rope  shackle  rods  are 
attached  to  the  underside  or  to  the  webs  of  the  car  frame 
members  in  such  a  manner  that  the  fastening  bolts  or 
rivets  are  not  in  tension.  Where  rope  equalizing  springs 
are  used,  determine  that  shackle  rods  are  not  worn  at 
the  point  where  they  pass  through  the  steel  supporting 
plate.  Note  any  collapsed  springs. 

(2)  Where  2:1  roping  is  used,  examine  dead-end 
rope  hitches.  Determine  that  steel  plates  for  supporting 
rope  shackle  rods  are  placed  on  top  of  the  supporting 
beams  or  are  located  in  such  a  manner  that  the  bolts 
supporting  the  suspension  plates  are  not  in  tension. 
Determine  that  suspension  members  are  securely  fas- 
tened and  that  no  bending  of  the  supporting  members 
has  occurred. 

(g)  Rope  Equalizers.  For  elevators  installed  under 
A17.1-1955  through  A17.1-1987,  suspension  rope  equal- 
izers, if  provided,  must  be  of  the  individual  compression 
spring  type.  Other  types  of  rope  equalizers  were  permit- 
ted subject  to  the  approval  of  the  enforcing  authority  on 
the  basis  of  adequate  tensile  and  fatigue  tests  made  by 
a  qualified  laboratory. 

For  elevators  installed  under  A17.1a-1988  and  later 
editions,  single  bar-type  equalizers  may  be  used  on 
winding  drum  machines  subject  to  limitations.  Other 
types  of  rope  equalizers  are  required  to  be  tested  by  an 
independent  laboratory  for  Code  compliance. 

Examine  rope  equalizers  and  determine  the  range  of 
their  motion  with  the  car  in  each  of  the  following 
positions: 

(1)  midpoint  of  hoistway 

(2)  at  top  terminal  landing 

(3)  at  bottom  terminal  landing 

If  properly  adjusted,  the  equalizer  arms  should  be  at 
the  center  of  their  range  of  motion  at  the  midpoint  of 
the  hoistway  and  not  be  at  either  limit  of  their  range  of 
motion  at  the  top  or  bottom  terminal  landing. 


57 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers.  ^,  . 

No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME.     ^ 


ASME  A17.2-2010 


(h)  Antirotation  Device.  For  suspension  ropes  installed 
or  replaced  under  ASME  A17.1-1993  through 
A17.1-1996,  check  the  antirotation  device  for  proper 
installation.  The  wire  rope  used  should  be  a  continuous 
loop  through  the  eye  of  each  shackle  and  connected  with 
at  least  two  wire  rope  clips.  Verify  that  the  loop  is  only 
hand-tight  so  that  it  does  not  restrict  the  lateral  motion 
of  the  shackle  rods.  For  elevators  installed  under 
A17.1a-1997,  verify  that  there  is  a  means  provided  to 
prevent  rotation  of  suspension  ropes  without  restricting 
their  movement. 

3.22.1.2  Electric  Elevators.  On  winding  drum 
machines,  hoisting  ropes  must  be  refastened  every 
12  months  for  machines  located  above  the  hoistway  and 
24  months  for  machines  located  below  or  beside  the 
hoistway  At  least  one  turn  of  rope  must  remain  on  the 
drum  when  the  car  is  resting  on  its  fully  compressed 
buffer. 

3.22.2  Periodic  Test 

3.22.3  Acceptance 
(10)    3.22.4  References 

3.22.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Section  212  and  Rules  105.3c,  203.13, 
1001.2(c)(28),  1200.5,  and  1206.3. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.20,  2.9.3.3,  2.15.13,  8.1L2.1.3(bb),  8.6.3, 
8.6.4.10,  c8. 6. 12. 4. 1.1,  c8. 6. 12.4.3,  c8. 6. 12.4.4,  and 
C8.6.12.4.5. 

A17.3  —  Paragraphs  3.12.5,  3.12.8,  and  3.12.9. 

3.22.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Section  212;  and  Rules  105.3c,  203.13, 
302.1b,  1004.2(c)(24),  and  1200.5. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.20,  2.9.3.3,  2.15.13,  3.18.1.2,  8.11.3.1.3(x), 
8.6.3,  C8.6.12.4.1.1,  c8.6.12.4.3,  c8.6.12.4.4,  and  c8.6.12.4,5. 

A17.3  —  Paragraph  4.9.10. 

ITEM  3.23 
SUSPENSION  ROPE 

(10)    3.23.1   Periodic  Inspections 

(a)  Wire  Rope  Inspection.  Examine  suspension  ropes 
and  note  if  they  conform  to  the  Code  requirements. 
Always  place  the  stop  switch  in  the  stop  position  while 
inspecting  the  rope. 

(1)  Internal  breakage  of  wire  ropes  is  difficult  to 
detect  and,  consequently,  may  be  a  greater  hazard  than 
surface  wear.  The  surface  of  the  rope  may  show  little  or 
no  wear,  but  if  the  rope  is  bent  over  a  short  radius, 
individual  wires  will  snap  and  in  extreme  cases  the  rope 
may  be  broken  by  hand.  Such  failures  are  more  likely 
to  occur  in  governor  and  compensating  ropes  where  the 
ropes  are  lightly  loaded  and  the  ratio  of  sheave  diameter 
to  rope  diameter  is  smaller. 


(2)  When  replacing  suspension  ropes,  all  ropes  in 
a  set  must  be  replaced.  The  ropes  in  the  set  must  all  be 
from  the  same  manufacturer  and  of  the  same  material, 
grade,  construction,  and  diameter. 

(3)  The  lengths  of  all  wire  ropes  in  a  set  of  suspen- 
sion ropes,  and  consequently  the  rope  tensions,  should 
be  substantially  equal  if  maximum  rope  life  and  effi- 
ciency are  to  be  obtained.  If  the  tensions  do  not  appear 
to  be  substantially  the  same,  equalization  of  the  rope 
lengths  is  recommended. 

(4)  If  ropes  are  dirty  or  overlubricated,  a  proper 
inspection  may  not  be  possible  unless  the  dirt  or  excess 
lubricant  is  removed. 

(b)  Wire  Rope  Inspection  Procedure.  Note  that  it  is  not 
possible  to  describe  the  inspection  procedure  for  every 
single  type  of  wire  rope  installation  nor  to  outline  every 
detail  of  the  inspection  procedure.  Select  the  location 
from  which  a  proper  examination  of  the  rope  can  best  be 
made.  For  example,  the  suspension  ropes  of  an  overhead 
drum  machine  cannot  be  examined  from  the  top  of  the 
car.  See  Item  2.27.1. 

(1)  For  suspension  ropes  on  traction  machines  with 
1:1  roping,  examination  of  the  ropes  should  preferably 
start  with  the  car  located  at  the  top  of  the  hoistway  and 
made  from  the  top  of  the  car,  examining  the  ropes  on 
the  counterweight  side. 

(2)  For  traction  machine  ropes  with  2:1  roping, 
examination  of  the  ropes  should  preferably  start  with 
the  car  located  at  the  top  of  the  hoistway  and  made  from 
the  top  of  the  car.  Examine  both  the  dead-end  side  and 
the  traveling-end  side  of  the  counterweight  ropes,  and 
dead-end  side  of  the  car  ropes.  The  remainder  of  the 
ropes  can  be  examined  at  the  traction  sheave  by  moving 
the  car  up  the  hoistway. 

(3)  For  overhead  winding  drum  machines  with  1:1 
roping,  the  hoisting  ropes  must  be  examined  from  the 
overhead  machinery  space.  Where  the  driving  machine 
is  located  below,  those  portions  of  the  ropes  leading 
from  the  driving-machine  drum  or  sheave  and  from  the 
counterweight  to  the  overhead  sheaves  can  be  examined 
from  the  car  top  as  the  car  descends,  except  for  a  small 
portion  which  must  be  examined  from  the  pit. 

(4)  On  all  elevators,  mark  the  ropes  with  chalk  to 
indicate  the  location  of  the  unexamined  section  of  ropes 
and  examine  them  later  from  the  machine  room  or  over- 
head machinery  space,  or  from  the  pit. 

(c)  Wire  Rope  Inspection  Criteria 

(1)  The  following  method  based  on  field  experience 
is  recommended  as  a  guide  for  the  inspection  and  evalu- 
ation of  wire  ropes.  Give  particular  attention  to  where 
the  wire  rope  passes  over  sheaves  with  the  car  at  terminal 
landings. 

(a)  Move  the  car  2  ft  (610  mm)  or  3  ft  (914  mm) 
at  a  time  and  examine  each  rope  at  each  of  these  stops. 
Note  when  broken  wires  begin  to  appear.  Thereafter 
check  at  frequent  intervals  to  determine  the  rate  of 


58 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Fig.  3.23.1     Types  of  Lay 

Regular  Lay  [Note  (1)]  /<^^y 

Strand  ^  1-J 


Rope 


(10) 


Lang  Lay  [Note  (2)] 


Strand 


Rope 


NOTES: 

(1)  Regular  lay:  stranded  rope  in  which  the  direction  of  the  lay  of  the  wires  in  the  outer  strand  is  in  the  opposite  direction  to  the  lay  of  the 
outer  strands  in  the  rope.  For  example,  the  wires  in  the  strand  will  be  spiraled  to  the  left  and  the  strands  will  be  spiraled  around  the 
core  to  the  right  (right  regular  lay  shown). 

(2)  Lang  lay:  stranded  rope  in  which  the  direction  of  the  lay  of  the  wires  in  the  outer  strand  is  in  the  same  direction  as  the  lay  of  the 
outer  strands  in  the  rope.  For  example,  the  wires  in  the  strand  will  be  spiraled  to  the  right  and  the  strands  will  be  spiraled  around  the 
core,  also  to  the  right  (right  lang  lay  shown). 


increase  in  the  number  of  broken  wires.  Any  rapid 
increase  in  the  number  of  broken  wires  is  significant. 

(b)  Count  the  number  of  broken  crown  wires  in 
a  rope  lay  (see  Figs.  3.23.1  and  3.23.2)  measured  along 
the  length  of  a  rope  within  which  the  spiral  strands 
complete  one  turn  about  the  axis.  A  lay  may  be  consid- 
ered as  a  section  of  rope  approximately  6%.  times  the 
diameter  of  the  rope,  that  is,  3\  in.  (83  mm)  for  \  in. 
(13  mm)  rope  and  4V16  in.  (103  mm)  for  %  in.  (16  mm) 
rope  (applies  only  to  6-  and  8-strand  configuration). 

(c)  Measure  for  minimum  diameter  at  various 
points  along  each  rope.  The  measurement  shall  be  taken 
across  the  top  of  two  opposing  lays,  not  in  the  valleys. 

Refer  to  the  A17.1  Code  for  rope  replacement  criteria. 
See  Table  8.11.2.1.3(cc)(l)  and  Table  8.11.2.1.3(cc)(3). 

(2)  Breaks  in  the  valleys  of  the  ropes,  while  infre- 
quent, may  be  an  indication  of  internal  breaks.  This  is 
not  to  be  confused  with  a  broken  outside  wire  when  the 
original  break  occurred  at  a  worn  crown  and  a  secondary 
fracture  has  occurred  near  the  point  where  two  adjacent 
strands  make  contact.  In  this  case,  a  piece  of  wire  has 
broken  out  and  is  missing,  and  generally  both  ends  of 
the  broken  wire  remaining  are  visible. 

(3)  Note  that  where  preformed  rope  is  used,  greater 
care  is  required  to  detect  broken  wires  that  do  not  pro- 
trude from  the  surface  of  the  rope. 

(d)  Governor  Ropes.  Governor  ropes  should  be 
inspected  and  replaced  as  outlined  for  suspension  and 


compensating  ropes  of  traction  machines.  Check  gover- 
nor rope  and  data  tag.  The  Code  also  requires  the  gover- 
nor rope  data  to  be  shown  on  a  metal  plate  attached  to 
the  speed  governor. 

(1)  If  a  governor  rope  has  been  replaced  since  the 
last  inspection,  determine  that  the  new  rope  is  of  the 
same  material,  diameter,  and  construction  as  that  speci- 
fied on  the  governor  marking  plate.  If  not,  a  test  of  the 
car  safety  and  governor  is  required. 

(2)  Ensure  wire  ropes  that  have  been  previously 
installed  have  not  been  used. 

3.23.2  Periodic  Test 

3.23.3  Acceptance 

3.23.4  References 

3.23.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Section  212;  and  Rules  206.7, 1001.2(c)(29)(a), 
1200.5,  1202.14,  1203.9,  and  1004.2(c). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.20,  and  requirements  2.18.7, 
8.11.2.1.3(cc)(l),  8.6.3,  8.7.2.21,  8.7.3.25,  and  8.11.3.1.3(y). 

3.23.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Sections  212  and  1307;  and  Rules 
1001.2(c)(29),  1004.2(c)(25),  1200.4d,  1202.14,  and  1203.9. 


59 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers, 
v. No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


(10) 


Fig.  3.23.2    Cross  Sections  of  Typical  Wire  Ropes 

Standard  Hoist  Ropes 


(a)8x  19Seale 
[Note  (1)] 

Compensation  Ropes 

(d)  8  x  25  Filler  Wire 
[Note  (2)] 


•S£* 


(b)  8x21  Filler  Wire  Type  U 

Governor  Ropes 


(c)  6  x  25  Filler  Wire 


*A^ 


*V« 


«8& 


m 


iipl 


£?• 


(e)  8  x  25  Filler  Wire 
[Note  (2)] 


(f)  8  x  19  Warrington 
[Note  (2)] 


Sample  Hoist  Rope-Designs  Used  in  North  America 


(g)  Dual-Strand  Rope 


(h)  8-Strand  Steel  Core 
For  Illustration  Only 


(i)  9-Strand  Steel  Core 


(j)  Tiller-Rope  Construction 
[Note  (3)] 

GENERAL  NOTE:     Both  traction  and  iron  grade  are  used  for  compensation  and  governor  ropes. 
NOTES: 

(1)  These  ropes  can  be  compacted  for  high  fatigue  usage. 

(2)  Use  8  x  19  Warrington  for  3/8-in.  and  7/i6-in.  diameter  ropes.  Use  8  x  25  filler  wire  for  Vrin.  and  larger  ropes. 

(3)  Typically  phosphor  bronze  material;  used  for  hand-operating  ropes.  Not  permitted  for  suspension  rope  or  governor  rope,  except  for 
replacement  on  old  elevators  with  governors  designed  for  it.  This  type  of  rope  is  also  prohibited  to  connect  the  safety  to  the  governor 
rope  (Requirement  2.17.12). 


60 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.20  and  8.2.7;  and  requirements 
8.11.2.1.3(00),  8.11.3.1.3(y)/  8.6.2.5,  8.7.2.21,  and  8.7.3.25. 

A17.3  -  Paragraphs  4.8,  and  4.9.10. 


ITEM  3.24 
TOP  COUNTERWEIGHT  CLEARANCE 

3.24.1  Periodic  Inspections 

3.24.1.1  Electric  Elevators.  With  the  car  at  the  bot- 
tom terminal  landing,  check  the  top  counterweight 
clearance. 

In  many  cases  the  measurement  is  taken  from  the  rope 
shackles  to  the  deflection  sheave  since  this  would  be  the 
first  obstruction.  With  the  car  located  near  the  top  of  the 
hoistway,  look  at  the  counterweight  rails  and  determine 
how  high  the  guides  have  been  running  on  the  rails. 
From  that  point,  place  some  calibration  chalk  or  other 
identifying- type  marks  either  on  the  rail  or  the  adjacent 
wall  level  where  the  guides  travel  in  order  to  measure 
where  the  exact  position  of  the  counterweight  is  with 
the  car  level  at  the  lowest  landing. 

Run  the  car  to  the  lowest  landing. 

If  possible  from  an  adjacent  car,  look  at  the  marks 
relative  to  the  position  of  the  counterweights  and  deter- 
mine from  the  marks  placed  on  the  wall  or  rail  the  exact 
position  of  the  counterweights.  In  a  single  car  hoistway, 
exercise  caution  and  open  the  hoistway  doors  only 
enough  to  shine  a  flashlight  in  the  hoistway  looking  at 
the  marks  placed  on  the  wall  or  rail  to  determine  the 
exact  position  of  the  counterweights. 

Add  the  car  runby,  buffer  stroke,  jump,  and  6  in. 
(150  mm)  together.  This  will  determine  the  minimum 
required  top  counterweight  clearance.  Jump  is  based  on 
115%  of  rated  speed  where  oil  buffers  are  used  and 
the  actual  governor- tripping  speed  where  spring  buffers 
are  used. 

NOTE:  The  projection  of  rope  fastenings  or  guide  shoes  above 
the  counterweight  structure  may  not  always  be  an  encroachment 
on  the  top  counterweight  clearance.  However,  excessive  projection 
should  not  be  permitted  if  interference  with  sheaves  or  other  equip- 
ment would  be  encountered  upon  maximum  overtravel. 

3.24.2  Periodic  Test 

3.24.3  Acceptance 

3.24.3.1  Electric  Elevators.  Measure  and  record  the 
top  counterweight  clearance. 

3.24.4  References 

3.24.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  107.1h  and  1001.2(c)(5). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.4.9  and  8.11.2.1.3(e). 


ITEM  3.25 
CAR,  OVERHEAD,  AND  DEFLECTOR  SHEAVES 

3.25.1  Periodic  Inspections 

3.25.1.1  Electric  Elevators 

(a)  Car  Sheaves.  Inspect  car  sheave  and  sheave  bear- 
ings for  condition  and  adequacy  of  lubrication.  Verify 
that  sheave  bearings  are  securely  fastened  to  the  frame 
members.  Hammer  test  rim  and  spokes  of  sheaves  as 
outlined  in  Item  2.26.  Verify  that  required  sheave  guards 
are  in  place. 

(b)  Overhead  and  Deflector  Sheaves.  Inspect  overhead 
and  deflector  sheaves  where  inspection  cannot  be  made 
from  the  overhead  as  outlined  in  Item  2.26. 

3.25.2  Periodic  Test 

3.25.3  Acceptance 

3.25.3.1  Electric  Elevators.  Record  and  check  for 
compliance  with  drawings  and  specifications  the  diame- 
ter of  drums,  overhead  sheaves,  and  deflector  sheaves. 

3.25.4  References 

3.25.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Section  208. 

A17.1-2000/B44-00  and  later  editions  — 
Requirement  2.24. 

A17.3  —  Paragraph  3.8.1. 

ITEM  3.26 
BROKEN  ROPE,  CHAIN,  OR  TAPE  SWITCH 

3.26.1  Periodic  Inspections  (10) 

(a)  Check  the  device  by  manually  opening  the  switch, 
and  attempt  to  move  the  car.  The  car  should  not  move. 

(b)  Verify  that  the  linkage  attached  to  the  switch  per- 
mits free  operation  of  the  switch. 

3.26.2  Periodic  Test 

3.26.3  Acceptance 

3.26.4  References 

3.26.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  209.2c(2),  210.2(f),  1001.2(c)(9),  and 
1002.21. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.25.2.3.2,  2.26.2.6,  8.11.2.1.3(1),  and 
8.11.2.2.9. 

A17.3  —  Paragraph  3.10.4(d). 

ITEM  3.27 

CROSSHEAD  DATA  PLATE  AND  ROPE  DATA 

TAGS 

3.27.1  Periodic  Inspections 

3.27.2  Periodic  Test 

3.27.3  Acceptance 

3.27.3.1  Electric  Elevators.  Check  and  verify  the 
information  on  the  crosshead  data  plate. 


61 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ews) 


ASME  A17.2-2010 


3.27.3.2  Electric  and  Roped-Hydraulic  Elevators. 

Check  and  verify  the  information  on  the  hoist  rope  data 
tag  and  the  governor-rope  data  tag. 

3.27.4  References 

3.27.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  207.3,  212.2, 1001.2(c)(ll),  and  1202.14. 

A17.1-2000/B44-00      and     later     editions     — 
Requirements  2.16.3,  2.20.2,  8.11.2.1.3(k),  and  8.7.2.21. 
A17.3  —  Paragraph  3.12.2. 

3.27.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  207.3,  212.2,  1001.2(c)(ll),  and 
1202.14. 

A17.1-2000/B44-00     and     later     editions     — 
Requirements  3.16,  2.20.2,  8.11.2.1.3(k),  and  8.7.2.21. 
A17.3  —  Paragraph  3.12.2. 

ITEM  3.28 
COUNTERWEIGHT  AND  COUNTERWEIGHT  BUFFER 

3.28.1  Periodic  Inspections 

(a)  Check  that  lock  nuts  and  cotter  pins  at  the  top 
and  bottom  of  the  counterweight  rods  are  in  place  and 
that  filler  weights  (subweights)  are  securely  held  in 
place. 

(b)  Check  that  the  counterweight  guide  shoes  are 
securely  fastened  to  the  frame  and  that  the  guiding 
members  are  not  worn  excessively.  Also,  determine  if 
swivel- type  or  roller- type  guide  shoes  are  free  to  move 
as  intended. 

(c)  Where  2;1  roping  is  used,  inspect  the  counter- 
weight sheave  and  bearings  for  condition  and  adequacy 
of  lubrication.  Also,  determine  that  the  sheave  bearings 
are  securely  fastened  to  the  counterweight  frame  and 
whether  required  sheave  guards  are  in  place.  Hammer- 
test  the  sheave  rim  and  spokes  as  outlined  in  Item  2.26. 

(d)  Check  fastenings  for  compensating  chains  or 
ropes  to  determine  that  they  are  securely  fastened  to  the 
counterweight.  For  elevators  installed  under  Al 7. 1-1 960 
and  later  editions,  compensating  chains  are  required  to 
be  fastened  directly  to  steel  counterweight  frames  or  to 
a  bracket,  but  not  to  tie  rods.  Determine  that  compensat- 
ing chains  are  suspended  so  that  they  will  not  catch  on 
beams  or  other  projections  in  the  hoistway. 

(e)  Verify  the  top  counterweight  clearance  and  bottom 
counterweight  runby. 

(f)  If  a  counterweight  is  provided  and  the  space  below 
the  hoistway  is  not  permanently  secured  against  access, 
determine  that  a  counterweight  safety  is  provided. 

(g)  Verify  that  a  counterweight  guard  is  in  place. 

3.28.1.1   Electric  Elevators.    Where  the  counter- 
weight buffer  is  attached  to  the  counterweight,  deter- 
mine that  the  buffer  fastening  bolts  are  tight.  Determine 
that  the  oil  buffers  are  filled  with  oil  to  the  proper  level. 
Refer  to  Item  5.9  for  buffer  inspection  information. 


Verify  that  a  counter- 


3.28.1.2  Hydraulic  Elevators. 

weight  buffer  is  not  provided. 

3.28.2  Periodic  Test 

3.28.3  Acceptance 

3.28.3.1  Electric  Elevators.  Counterweights  with- 
out either  mechanical  compensation  or  counterweight 
safeties  may  be  located  in  a  remote  hoistway.  See 
Item  4.11. 

3.28.4  References 

3.28.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Sections  201  and  202  and  Rule  1001.2(c)(13). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.3,  2.4.9,  2.21,  2.22,  8.11.2.1.3(m), 
8.11.2.1.5(c),  8.11.2.3.3,  and  c8.11.2.3.3(d). 

A17.3  —  Sections  2.1.5,  2.4.3,  3.1,  3.2,  and  4.9. 

3.28.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  300.8f,  301.4,  301.9,  and  1308. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  3.3,  3.4.6,  3.22.3,  8.11.3.2.3(d),  and 
c8.11.2.3.3(d). 

A17.3  —  Paragraphs  4.9.2  and  4.9.6. 

ITEM  3.29 
COUNTERWEIGHT  SAFETIES 

3.29.1  Periodic  Inspections 

If  a  counterweight  safety  is  provided,  determine  that 
all  moving  parts  of  the  safety  are  lubricated,  free  from 
corrosion,  free  to  operate,  and  that  under  ordinary 
operating  conditions  the  clearance  between  the  guide 
rail  and  each  rail  gripping  face  of  the  safety  components 
is  correct.  Examine  the  car  and  counterweight  guide 
shoes  and  their  fastenings  to  determine  that  they  are 
properly  secured,  aligned,  and  adjusted.  Check  the  gibs 
or  rollers  for  excessive  wear.  Check  that  rope  is  free  of 
corrosion  and  that  rope  fastenings  are  secure.  Where 
provided,  inspect  the  safety  drum  rope  and  its  deflecting 
sheaves  and  their  fastenings  to  determine  that  they  are 
not  worn  excessively  or  corroded  and  that  they  are  in 
operating  condition.  Safety  rope  must  be  made  from  a 
corrosion-resistant  material  (if  not  a  continuation  of  the 
governor  rope).  Use  of  Tiller  rope  is  prohibited. 

Check  the  buffer  portion  of  Type  C  safeties  to  deter- 
mine that  the  oil  level  is  within  allowable  limits.  Also, 
test  the  buffer  compression  switch  and  the  oil  level 
device  for  proper  functioning. 

3.29.2  Periodic  Test 

(a)  Yearly  Test  (for  A17.1d-2000  and  Earlier  Editions); 
Category  1  Test  (for  A17.1-2000/B44-00  and  Later  Editions). 
Check  governor-operated  counterweight  safeties,  if  pro- 
vided, as  outlined  in  Item  2.29  and  safeties  that  operate 


do) 


62 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


by  breaking  or  slackening  of  the  counterweight  suspen- 
sion means  as  outlined  in  Item  5.8.2. 

(b)  5-Year  Test  (for  A17.1d-2000  and  Earlier  Editions); 
Category  5  Test  (for  A17. 1-2000 /B44-00  and  Later  Editions). 
Check  governor-operated  counterweight  safeties,  if  pro- 
vided, as  outlined  in  Item  2.29  and  safeties  that  operate 
by  breaking  or  slackening  of  the  counterweight  suspen- 
sion means  as  outlined  in  Item  5.8.2. 

3.29.3  Acceptance 

(a)  Check  that  a  metal  marking  plate  has  been 
securely  attached  to  the  safety  plank,  readily  visible, 
and  legibly  and  permanently  marked.  Check  that  the 
date  is  accurate  and  complies  with  the  Code. 

(b)  If  a  counterweight  is  provided  and  the  space  below 
the  hoistway  is  not  permanently  secured  against  access, 
verify  that  a  counterweight  safety  is  provided.  A  coun- 
terweight safety  may  be  provided  for  ascending  car 
overspeed  protection. 

(c)  Test  the  counterweight  safeties  as  outlined  in 
Item  2.29  for  governor-operated  safeties  or  Item  5.8.2 
for  safeties  that  operate  by  breaking  or  slackening  of 
the  counterweight  suspension  means. 

Counterweight  safeties,  if  provided,  must  be  operated 
by  a  slackening  or  breaking  of  the  counterweight  suspen- 
sion means  for  hydraulic  elevators  irrespective  of  the 
rated  speed,  and  may  be  operated  by  a  slackening  or 
breaking  of  the  counterweight  suspension  means  for 
electric  elevators  with  rated  speeds  not  over  150  fpm 
(0.75  m/s).  Counterweights  are  seldom  used  on  hydrau- 
lic elevators  and  counterweight  safeties  would  be  even 
less  frequent. 

3.29.4  References 

3.29.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Section  205;  and  Rules  206.5(e),  1001.2(b), 
1001.2(c)(14),  1001.2(c),  1002.3(a),  1003.2,  and  1002.3. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.17.12.4,  2.18.5.3,  8.11.2.1.2(y), 
8.11.2.1.3(k),  8.11.2.1.3(z),  8.10.2.2.2(z),  8.11.2. 1.3(n), 
8.11.2.3.1,  8.10.2.2,  and  8.11.2.3. 

A17.3  —  Paragraphs  3.5.2,  3.6.2,  and  3.12.2. 

3.29.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  301.9, 300.10.,  1006.2, 1005.2(c),  and 
1005.4. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  3.17.2, 3.6, 8.10.3.2, 8.11.3.2.3,  and  8.11.3.4. 

ITEM  3.30 
SPEED  TEST 

3.30.1  Periodic  Inspections 

3.30.2  Periodic  Test 

3.30.3  Acceptance 

3.30.3.2  Hydraulic  Elevators.  Check  and  verify  the 
information  on  the  crosshead  data  plate.  Have  the  rated 


load  placed  in  the  car  and  use  a  tachometer  to  verify 
the  rated  speed  going  up  and  the  operating  speed  in 
the  down  direction.  The  following  procedure  is 
recommended: 

(a)  After  the  top-of-car  refuge  area,  top-of-car  run-by, 
and  operation  of  top-of-car  operating  device  have  been 
verified,  have  the  rated  load  placed  in  the  car  and  run 
it  to  the  top  with  the  top-of-car  operating  device  while 
occupying  the  refuge  area.  Be  sure  to  include  the  weight 
of  the  person  in  and  on  top-of-car  in  the  load. 

(b)  Have  an  assistant  inside  the  car  place  the  car  on 
independent  service,  if  available,  and  place  a  call  to  the 
lowest  landing. 

(c)  Hold  a  tachometer  against  the  rail  and  determine 
the  operating  speed  in  the  down  direction. 

(d)  Have  the  person  inside  the  car  place  a  call  to  a 
midlevel  landing. 

Hold  the  tachometer  against  the  rail  and  determine 
the  rated  speed. 

For  roped-hydraulic  elevators,  also  verify  the  informa- 
tion on  the  hoist  rope  data  tag,  the  governor-rope  data 
tag,  and  the  rail  lubrication  marking  plate. 

3.30.4  References 

3.30.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  205.16,  300.8,  301,  1004.2(c)(8), 
1006.2g,  and  Section  3. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.17.16,  3.4  (NR  301),  8.11.3.1.3(h), 
8.10.3.2.3(cc),  and  1.3. 

A17.3  —  Section  4.9. 

ITEM  3.31 

SLACK  ROPE  DEVICE  - 

ROPED-HYDRAULIC  ELEVATORS 

INSTALLED  UNDER  A17.1b-1989 

AND  LATER  EDITIONS 

3.31.1  Periodic  Inspections 

3.31.1.2  Hydraulic  Elevators.  Visually  inspect  the 
slack  rope  device  to  verify  that  there  is  no  damage  or 
interference  with  its  movement. 

3.31.2  Periodic  Test 

3.31.2.2  Hydraulic  Elevators:  Yearly  Test  (for 
A17.1d-2000  and  Earlier  Editions);  Category  1  Test  (for 
A17.1-2000/B44-00  and  Later  Editions).  Have  the  car 
lowered  on  the  safety  or  supports  in  the  pit  to  prevent 
the  car  from  reaching  the  first  floor.  The  device  should 
cause  power  to  be  removed  from  the  lowering  valve. 
Then  attempt  to  run  the  car  up.  The  device  should  not 
allow  power  to  the  pump.  Jump  the  device,  move  the 
car  up.  Then  remove  the  jumper  and  attempt  to  run  the 
car  by  normal  means.  The  car  should  not  operate  in 
either  direction  until  the  slack  rope  device  is  manu- 
ally reset. 


63 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


3.31.3  Acceptance 

3.31.3.2  Hydraulic  Elevators.  Inspect  the  device  and 
verify  it  will  operate  if  any  one  of  the  ropes  becomes 
slack. 

3.31.4  References 

(10)  3.31.4.2  Hydraulic  Elevators.    Al 7. ld-2000  and  ear- 

lier editions  —  Rules  302.1b,  306.4,  1004.2(c)(26), 
(NR  8.6.5.14.7),  and  1005.2f. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  3.18.1.2, 3.26.4, 8.11.3.1.3(z),  8.6.5.14.7,  and 
(NR  1005.2f). 

A17.3  —  Paragraph  4.9.9. 

ITEM  3.32 

TRAVELING  SHEAVE  -  ROPED- 

HYDRAULIC  ELEVATORS  INSTALLED 

UNDER  A17.1b-1989  AND  LATER 

EDITIONS 

3.32.1  Periodic  Inspections 

3.32.1.2  Hydraulic  Elevators.  Inspect  the  sheave  for 
the  following: 

(a)  secure  tight  fastening  to  plunger  or  cylinder. 

(b)  means  to  prevent  slack  ropes  from  leaving  the 
sheave  securely  in  place. 

(c)  guide  shoes  seated  in  guide  rails  and  condition  of 
guides  and  rails. 

(d)  rope  changes.  Where  the  material,  grade,  number, 
or  diameter  of  ropes  have  changed  and  the  existing 
sheave  has  been  retained,  check  for  approval  by  a 
licensed  professional  engineer  of  the  original  equipment 
manufacturer. 

3.32.2  Periodic  Test 

3.32.3  Acceptance 

3.32.3.2  Hydraulic  Elevators.    Verify  the  following: 

(a)  sheaves  exceed  the  minimum  allowable  pitch 
diameter 

(b)  sheaves  are  marked  with  the  minimum  permissi- 
ble groove  bottom  diameter 

(c)  finished  grooves  or  lining  for  ropes 

(d)  fillet  are  provided  for  points  of  changes  in 
diameter 

(e)  sheave  in  guide  rails  and  condition  of  rails  and 
guides 

3.32.4  References 

3.32.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Section  212;  and  Rules  208.2,  208.3, 208.5, 
301.1b,  302.1b,  307,  1004.2(c)(27),  and  1203.9. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.20,  2.24.2,  2.24.3,  2.24.5,  3.23.2,  3.18.1.2, 
(NR  307),  8.11.3.1.3(aa),  and  8.7.3.25. 

A17.3  —  Paragraph  4.9.8. 


ITEM  3.33 

COMPENSATING  ROPES  AND 

CHAINS 

3.33.1  Periodic  Inspections 

3.33.1.1  Electric  Elevators.  Examine  compensating 
chains  and  fastenings  for  excessive  wear,  damage,  or 
deterioration.  Sash  cord  wear  is  no  indication  of  chain 
damage.  See  Item  3.23  for  inspection  of  compensating 
ropes. 

3.33.2  Periodic  Test 

3.33.4  Acceptance 

3.33.4  References 

3.33.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  202.4,  1001.2(c)(30),  and  1003.2g. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.21.4,  8.11.2.1.3(dd),  8.10.2.2.3(dd),  and 
8.10.2.2.5(h). 

ITEM  3.34 

EARTHQUAKE  INSPECTION  AND  TESTS  (SEISMIC 

RISK  ZONE  2  OR  GREATER) 

3.34.1  Periodic  Inspection 

(a)  Verify  that  the  clearances  between  the  car  and  the 
counterweight  assembly,  the  counterweight  assembly 
and  hoistway  enclosure,  and  the  counterweight  assem- 
bly and  the  nearest  obstruction,  including  the  counter- 
weight screens,  complies  with  requirement.  These 
clearances  supersede  those  specified  in  A17.1a~2002, 
2.5.1.2. 

(b)  Verify  that  all  beams  and  supports  are  properly 
anchored  and  all  fastening  devices  are  in  place. 

(c)  Verify  that  all  rope  retainer  guards  or  rope 
restraints  are  in  place. 

(d)  Verify  that  snag  guards,  where  required,  are  in 
place. 

(e)  Verify  that  upper  and  lower  position  restraints  are 
provided  on  the  car  or  its  guiding  member. 

(f)  Measure  the  clearance  between  the  counterweight 
frame  and  the  face  of  the  counterweights  and  verify  that 
it  complies  with  the  requirements. 

(g)  Verify  that  the  upper  and  lower  position  restraints 
that  are  attached  to  the  counterweight  frame  are  in  place. 
Verify  that  the  clearance  between  the  upper  and  lower 
position  restraints  and  the  guide  rail  comply  with 
requirement. 

(h)  Verify  that  the  car  and  counterweight  guide  rail 
system,  including  the  bracket  spacing,  fastenings,  sup- 
ports, and  joints,  comply  with  requirement. 

(i)  Verify  that  the  emergency  exit  can  be  opened  from 
the  top  of  the  car  without  the  use  of  a  key. 


(10) 


64 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


3.34.2  Periodic  Test 

3.34.3  Acceptance 

(a)  Measure  the  horizontal  car  and  counterweight 
clearances  and  verify  that  they  comply  with  the 
requirements. 

(b)  Verify  that  rope  retainers  are  continuous  over  not 
less  than  %  of  the  arc  of  contact  between  the  rope  and 
its  sheave  or  drum,  and  located  so  not  more  than  \  of 
the  arc  of  contact  is  exposed.  Rope  restraints  may  be 
used,  and  if  they  are  used,  there  must  be  one  for  each 
30  deg  or  less  of  arc  contact. 

(c)  Verify  that  snag  guards  are  provided  for  snag 
points  created  by  rail  brackets,  rail  clip  bolts,  fishplates, 
vanes,  and  similar  devices,  where 

(1)  governor  ropes  are  located  20  in.  (500  mm)  or 
less  from  a  snag  point 

(2)  the  loop  of  traveling  cables  below  the  midpoint 
of  the  elevator  travel  is  located  36  in.  (915  mm)  or  less, 
horizontally  from  a  snag  point 

(d)  Verify  that  the  rail  system  is  installed  per  design, 
including  bracket  spacing. 

(e)  Verify  that  snag  points  less  than  12  in.  (300  mm) 
from  the  suspension  ropes  are  properly  guarded. 


3.34.3.1  Electric  Elevators.  Verify  that  snag  guards 
are  provided  for  snag  points  created  by  rail  brackets, 
rail  clip  bolts,  fishplates,  vanes,  and  similar  devices, 
where  the  counterweight  end  of  compensating  ropes  or 
chains  is  located  30  in.  (760  mm)  or  less  from  a  counter- 
weight rail  bracket,  the  loop  of  compensating  chains 
below  the  midpoint  of  the  elevator  travel  is  within  36  in. 
(915  mm)  of  a  snag  point. 

3.34.4  References 

3.34.4.1  Electric  Elevators.  A17.1-1993  through 
A17.1d-2000  editions  —  Rules  2402,  2401,  2400,  2405, 
2407,  2404,  and  2403. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  8.4.1,  8.4.2,  8.4.3,  8.4.5,  8.4.6,  8.4.7,  and 
8.4.8. 

3.34.4.2  Hydraulic  Elevators.  A17.1-1993  through 
A17.1d-2000  editions  —  Rules  2402,  2401,  2400.1(a), 
2400.1(b),  2400.1(d),  2400.2,  2405,  2404,  and  2403. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  8.4.1,  8.4.2,  8.4.3.1.1,  8.4.3.1.2,  8.4.3.1.4, 
8.4.3.2,  8.4.5,  8.4.7,  and  8.4.8. 


65 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Part  4 
Elevator  —  Outside  Hoistway 


(10) 


ITEM  4.1 
CAR  PLATFORM  GUARD 

4.1.1  Periodic  Inspections 

Place  the  car  2  ft  (610  mm)  or  3  ft  (914  mm)  above 
one  of  the  landings  with  the  hoistway  door  open  and 
inspect  the  guard  to  determine  that  it  is  in  place  and 
securely  fastened.  In  some  cases,  the  guard  can  be 
inspected  from  the  pit  with  the  car  at  the  bottom  terminal 
landing. 

On  truck  loading  elevators  with  collapsible  gates, 
check  that  a  head  guard,  which  extends  the  full  width 
of  the  hoistway  door,  is  provided  when  the  vertical 
hoistway  door  opening  is  greater  than  the  distance  from 
the  car  platform  to  the  car  top. 

4.1.2  Periodic  Test 

4.1.3  Acceptance 

For  all  elevators  where  a  car  leveling  or  truck  zoning 
device  is  provided,  check  that  there  is  a  smooth  metal 
guard  extending  a  distance  below  the  platform  floor 
equal  to  the  depth  of  the  leveling  or  truck  zone  plus 
3  in.  (76  mm),  but  not  less  than  21  in.  (533  mm)  on  the 
entrance  side  of  the  platform.  This  apron  must  have  a 
width  equal  to  or  greater  than  the  widest  hoistway  door 
opening. 

4.1.4  References 

4.1.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  203.9  and  1001.2(d)(1). 

A17.1-2000/B44-00      and      later     editions     — 
Requirements  2.15.9  and  8.11.2.1.4(a). 
A17.3  —  Section  3.3  and  para.  3.2.2. 

4.1.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  301.6  and  1004.2(d)(1). 

A17.1-2000/B44-00     and     later     editions     — 
Requirements  3.15  and  8.11.3.1.4(a). 
A17.3  —  Paragraph  3.3.2  {4.2.2}. 

ITEM  4.2 
HOISTWAY  DOORS 

4.2.1  Periodic  Inspections 

(a)  Manually  Operated  Hoistway  Door.  Open  and  close 
each  manually  operated  hoistway  door,  examine  each, 
including  any  hand-operated  latches,  and  note  any  bro- 
ken glass  panels  in  the  doors  or  any  structural  defects 


in  the  frames.  Try  to  open  the  door  by  pulling  on  it,  and 
also  by  lifting  it  without  touching  the  lock  or  latch.  If 
it  can  be  opened  in  this  manner,  the  lock  or  latch  is 
defective,  or  the  door  has  sagged  so  that  the  lock  or 
latch  is  not  engaging  properly.  Check  that  pull  straps 
are  in  good  condition  and  properly  secured  on  the  upper 
panel  of  vertical  slide  biparting  doors. 

(b)  Closed  Position  of  Hoistway  Door  or  Gate.  With  the 
car  door  or  gate  in  the  closed  position  and  with  the 
hoistway  door  or  gate  fully  open,  close  the  hoistway 
door  or  gate  slowly  from  the  landing  side  until  the  maxi- 
mum clear  opening  is  reached  at  which  the  actuation 
of  the  elevator  operating  device  will  cause  the  car  to 
start.  Measure  the  distance  from  the  nearest  face  of  the 
door  jamb  or  gate  sill  to  the  nearest  edge  of  the  door  or 
gate,  or  between  the  meeting  edges  of  biparting  doors. 
Verify  that  from  this  position  the  door  cannot  be 
reopened  from  the  landing  side. 

The  measured  distance  should  not  exceed  the  dimen- 
sions indicated  in  the  following  paragraphs: 

(1)  Horizontally  sliding  or  swinging  doors  or  verti- 
cally sliding  counterweighted  doors  or  gates,  %  in. 
(10  mm),  except  for  elevators  installed  under  A17. 1-1955 
through  1990,  horizontally  sliding  doors,  4  in.  (102  mm), 
where  the  conditions  set  forth  below  are  met. 

(a)  Car  is  operated  from  inside  only. 

(b)  The  doors  are  power  closing  or  equipped  with 
door  closers  that  will  normally  close  the  door  to  %  in. 
(10  mm)  of  the  closed  position  and  lock  it. 

(c)  Hoistway  doors  are  equipped  with  auxiliary 
locks  (Item  3.17.1). 

id)  Where  hoistway  doors  are  equipped  with 
mechanical  locks  and  electric  contacts,  2  in.  (51  mm). 

(2)  Vertically  sliding  biparting  counterbalanced 
doors,  when  the  astragal  of  the  upper  panel  is  within 
%  in.  (19  mm)  of  the  lower  panel.  For  elevators  installed 
under  A17.1-1955  through  A17.1a-1991,  this  distance 
was  when  the  door  was  not  more  than  %  in.  (19  mm) 
from  their  stopped  position  when  provided  with  inter- 
locks or  when  provided  with  mechanical  locks  and  elec- 
trical contacts  within  2  in.  (51  mm)  of  contact  with  each 
other.  The  Code  prohibits  overlapping  rigid  astragals 
and  center  latches. 

(3)  Check  the  condition  of  the  leading  edges  of  the 
entrance  panels.  Verify  that  horizontally  sliding  doors 
are  in  the  closed  position  when  the  car  is  waiting  at  a 
landing. 


66 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


(c)  Hoistway  Door  Clearance  and  Integrity.  Verify  that 
door  panels  will  not  appreciably  deflect,  deform,  or 
come  out  of  the  guides  or  tracks.  For  horizontally  sliding 
doors  installed  under  A17.1b-1992  and  later  editions, 
check  that  safety  retainers  are  provided  at  the  top  and 
bottom  of  the  panels.  Verify  that  the  clearances  between 
door  panels  with  each  other,  their  frames,  and  their  sills 
have  not  become  excessive.  The  requirements  became 
effective: 


Maximum 
Clearance,  in. 


Door  Type 

Horizontal  slide 
Vertical  slide 
Swing 


GENERAL  NOTE:     1  in.  =  25.4  mm 


Code  Edition 

1955  and  later 
1971  and  later 
1971  and  later 


(d)  Opening  of  Locked  Hoistway  Door  Panel(s).  On  ele- 
vators installed  under  A17. 1-1990  and  later  editions 
with  horizontally  sliding  and  vertically  sliding  hoistway 
doors  in  the  closed  and  locked  position,  apply  30  lbf 
(133  N)  using  a  door  test  scale  to  the  leading  edge  of 
the  door  at  the  furthest  point  from  the  interlock.  Measure 
the  gap  at  the  furthest  point  from  the  interlock.  The 
difference  shall  not  exceed  the  1  in.  (25  mm)  maximum 
per  panel. 

4*2.2  Periodic  Test 

4.2.3  Acceptance 

Examine  hoistway  doors,  interlocks,  and  mechanical 
locks  and  electric  contacts  (see  Item  4.4).  Determine 
whether  doors  meet  the  requirements  for  passenger  or 
for  freight  elevators.  Measure  the  height  and  width  of 
the  entrance.  Measure  the  distances  between  the 
hoistway  face  of  horizontally  sliding  or  swinging  doors 
and  the  hoistway  edge  of  the  landing  sill  [see 
Table  3.14.3(b)].  Also,  measure  the  distances  between 
the  hoistway  face  of  the  hoistway  doors  and  the  car  door 
or  gate  (see  Item  1.7.1).  Check  that  the  doors,  door  frame, 
and  entrance  hardware  are  labeled.  See  Item  3.17.3. 

4.2.4  References 

4.2.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Section  110;  and  Rules  111.7,  210.2,  and 
1001.2(d)(2). 

A17.1-2000/B44-00     and     later     editions     — 
Requirements  2.11,  2.12.7,  2.26.2,  and  8.11.2.1.4(b). 
A17.3  —  Paragraph  3.10.4. 

4.2.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Section  110  (Rule  300.11};  Rules  111.2b 
and  111.3b  {300.12};  and  306.4, 1004.2(d)(2),  and  1006.2h. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.11  {3.11};  2.12.2.2  and  2.12.3.2  {3.12};  and 
3.26.4,  8.11.3.1.4(b),  and  8.10.3.2.3(r). 

A17.3  —  Paragraph  4,7.4. 


ITEM  4.3 
VISION  PANELS 

4.3.1  Periodic  Inspections 

Where  vision  panels  are  provided,  note  that  clear 
wired  glass  is  used  and  is  secured  in  place.  For  elevators 
installed  under  A17.1-1990  and  later  editions,  check  that 
the  required  vision  panel  grill  is  in  place. 

4.3.2  Periodic  Test 

4.3.3  Acceptance 

Check  that  elevators  with  automatic  or  continuous 
pressure  operation,  with  manually  operated  or  self- 
closing  hoistway  doors  of  the  vertically  or  horizontally 
sliding  type,  have  a  vision  panel  at  all  landings  except 
at  landings  of  automatic  operating  elevators  where  a 
hall  position  indicator  is  provided. 

Check  that  all  horizontally  swinging  doors  have  vision 
panels. 

When  a  glass  door  is  provided,  check  the  type  of  glass, 
thickness,  minimum  surface  area,  and  edging. 

4.3.4  References 

4.3.4.1  Electric  Elevators.    A17.1d-2000  and  earlier 
editions  —  Rules  110.7  and  1001.2(d)(3). 

A17.1-2000/B44-00      and     later     editions     — 
Requirements  2.11.7  and  8.11.2.1.4(c). 
A17.3  —  Paragraph  2.6.3. 

4.3.4.2  Hydraulic  Elevators.    A17.1d-2000  and  ear- 
lier editions  —  Rules  110.7  {300.11}  and  1004.2(d)(3). 

A17.1-2000/B44-00     and     later     editions     — 
Requirements  2.11.7  {3.11}  and  8.11.3.1.4(c). 
A17.3  —  Paragraph  2.6.3  {Section  4.1}. 

ITEM  4.4 

HOISTWAY  DOOR  LOCKING 

DEVICES 

4.4.1  Periodic  Inspections 

On  doors  or  gates  equipped  with  interlocks,  which 
are  unlocked  automatically  by  retiring  cams  or  similar 
devices,  when  the  car  is  in  the  unlocking  zone  place  the 
car  near  each  landing  outside  this  zone  above  and  below 
the  landing  so  that  the  automatic  unlocking  device  on 
the  car  cannot  release  the  interlock.  With  the  car  away 
from  the  landing,  try  to  manually  open  the  hoistway 
door.  It  should  not  be  possible  to  open  the  door.  For 
sliding  doors  on  elevators  installed  under  A17.1a-1991 
and  later  editions,  check  that  a  force  of  30  lbf  (133  N) 
applied  at  the  farthest  point  from  the  interlock  will  not 
open  the  doors  more  than  1  in.  (25  mm)  per  panel. 
Observe  the  door  operation  and  note  that  on  closing  the 
doors  do  not  bounce  open  beyond  the  closed  position. 

On  vertical  sliding  biparting  doors  with  retiring  cams, 
check  the  alignment  of  the  cam  and  interlock  rollers  as 


67 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


follows:  With  the  doors  open  and  the  car  level  with  the 
landing,  observe  the  alignment  of  the  interlock  roller 
with  the  retiring  cam  and  note  as  well  that  the  interlock 
roller  is  near  the  vertical  center  of  the  retiring  cam  so 
that  the  retiring  cam  cannot  operate  the  interlock  when 
the  car  is  outside  the  landing  zone. 

4.4.2  Periodic  Test 

4.4.3  Acceptance 

Determine  whether  interlocks  or  mechanical  locks  and 
electric  contacts  are  provided  [see  Item  3.17.1(a)(6)]. 
Note  that  they  are  inaccessible  from  the  landing  side. 

Verify  that  the  interlocks,  or  the  mechanical  locks  and 
electric  contacts,  are  of  a  type  that  have  been  tested 
and  approved,  and  are  marked  for  identification  [see 
Item  3.17.1(a)(5)]. 

Check  the  retiring  cam  and  note  that  it  is  permanently 
marked  with  its  horizontal  force  and  horizontal  move- 
ment. Verify  that  the  horizontal  force  and  movement 
comply  with  minimum  Code  requirements.  Where  a 
modernization  did  not  replace  a  retiring  cam,  which 
was  installed  under  A17. 1-1960  or  earlier  editions,  the 
marking  would  not  be  present.  See  also  Item  3.17.3. 

4.4.4  References 

4.4.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Section  111  and  Rule  1001.2(d)(4). 

A17.1-2000/B44-00     and     later     editions     — 
Requirements  2.12  and  8.11.2.1.4(d). 
A17.3  —  Paragraph  2.7.1. 

4.4.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Section  111  {Rule  300.12}  and  Rule 
1004.2(d)(4). 

A17.1-2000/B44-00     and     later     editions     — 
Requirements  2.12  {3.12)  and  8.11.3.1.4(d). 
A17.3  —  Paragraph  2.7.1  {Section  4.1). 

ITEM  4.5 
ACCESS  TO  HOISTWAY 

4.5.1  Periodic  Inspections 

(a)  Unlocking  Devices.  Check  any  escutcheons  on 
doors  and  verify  that  they  are  intact,  securely  fastened 
in  place,  and  not  deformed.  The  unlocking  device  key 
is  to  be  kept  on  the  premises  by  a  person  responsible 
for  the  maintenance  of  the  elevators  and  only  accessible 
to  qualified  persons  in  case  of  emergency.  For  the  eleva- 
tors installed  under  A17.1-1978  and  later  editions,  the 
keyway  should  be  located  at  a  height  not  greater  than 
6  ft  11  in.  (2.11  m)  above  the  floor. 

For  elevators  installed  under  A17.1a-1997  and  later 
editions,  check  that  there  is  a  hoistway  door  unlocking 
device  at  each  landing  where  there  is  an  entrance. 

(b)  Hoistway  Access  Switches.  Hoistway  access 
switches  were  required  for  all  elevators  installed  under 


A17. 1-1955  edition.  Hoistway  access  switches  are 
required  under  certain  conditions  for  elevators  installed 
under  A17.1-1960  and  later  editions.  For  elevators 
installed  under  A17.1b-1983  and  later  editions  and 
A17.3,  the  movement  of  the  car  by  upper  access  switch  is 
limited  in  the  down  direction  to  the  height  of  crosshead 
above  the  platform  and  in  the  up  direction  to  the  length 
of  the  platform  guard.  Check  for  proper  operation.  Verify 
that  the  switch  key  is  kept  in  a  location  where  it  is 
available  only  to  authorized  persons. 

4.5.2  Periodic  Test 

4.5.3  Acceptance 

4.5.4  References 

4.5.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  111.6,  111.7,  and  1001.2(d)(5). 

A17.1-2000/B44-00     and     later     editions     — 
Requirements  2.12.6,  2.12.7,  and  8.11.2.1.4(e). 
A17.3  —  Paragraph  2.7.3. 

4.5.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  111.6  and  111.7  {300.12},  and 
1004.2(d)(5). 

A17.1-2000/B44-00     and     later     editions     — 
Requirements  2.12.6  and  2.12.7  {3.12},  and  8.11.3.1.4(e). 
A17.3  —  Paragraph  2.7.3  {Section  4.1}. 

ITEM  4.6 

POWER  CLOSING  OF  HOISTWAY 

DOORS 

4.6.1  Periodic  Inspections 

4.6.2  Periodic  Test 

4.6.3  Acceptance 

Where  both  a  hoistway  door  and  a  car  door  or  gate  are 
opened  and/or  closed  by  power,  check  that  the  hoistway 
door  and  the  car  door  or  gate  are 

(a)  both  of  the  horizontally  sliding  type;  or 

(b)  both  of  the  vertically  sliding  type. 

4.6.4  References 

4.6.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  -  Section  112  and  Rule  1001.2(d)(6). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.13  and  8.11.2.1.4(f). 

4.6.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  112.3  through  112.6  {300.13},  and 
1004.2(d)(6). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.13.3  through  2.13.6  {3.13},  and 
8.11.3.1.4(f). 

A17.3  —  Section  2.8  {4.1}. 


68 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


(10) 


ITEM  4.7 
SEQUENCE  OPERATION 

4.7.1  Periodic  Inspections 

Check  the  door  sequence  operation  on  elevators  with 
vertical  biparting  power-operated  hoistway  doors  and 
power-operated  car  doors  or  gates. 

(a)  During  opening  operation,  hoistway  door  should 
be  opened  two-thirds  or  more  of  its  travel  before  car 
door  or  gate  starts  to  open. 

(b)  During  closing  operation,  the  car  door  or  gate 
should  be  closed  two-thirds  or  more  of  its  travel  before 
the  hoistway  door  starts  to  close. 

4.7.2  Periodic  Test 

4.7.3  Acceptance 

4.7.4  References 

4.7.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  112.6,  1123d,  and  1001.2(d)(7). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.13.6,  2.13.3.4,  and  8.11.2.1.4(g). 

4.7.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  112.6  and  112.3d  {300.13},  and 
1004.2(d)(7). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.13.6  and  2.13.3.4  {3.13},  and  8.11.3.1.4(g). 

ITEM  4.8 
HOISTWAY  ENCLOSURE 

4.8.1  Periodic  Inspections 

(a)  Hoistway  Enclosures.  Where  openwork-type  enclo- 
sures and  doors  are  permitted  and  used,  check  enclosure 
panels  at  all  floors  and  note  whether  they  are  securely 
fastened  in  place.  Also,  verify  that  wire  netting  or  mesh 
required  by  the  applicable  regulations  is  in  place  and 
securely  fastened. 

(b)  Glass  Hoistways  (Curtain  Walls).  Al 7. 1-1978  and 
later  editions  require  laminated  glass,  where  used  for 
elevator  hoistways  in  nonfire-resistant  enclosures. 
A17.1b-1983  required  the  laminated  glass  to  comply 
with  ANSI  Z97.1.  ASME  A17.1-1993  recognized  both 
ANSI  Z97.1  and  16  CFR  Part  1201  and  required  that 
each  panel  be  marked  as  specified  in  ANSI  Z97.1,  and 
that  the  marking  be  visible  after  installation. 
ASME  A17.1-2000/B44-00  added  the  Canadian  stan- 
dard CAN  CGSB-12.1,  where  applicable,  and  required 
marking  as  specified  in  the  applicable  standard  be  visi- 
ble on  each  panel  after  installation. 

4.8.2  Periodic  Test 

4.8.3  Acceptance 

Determine  whether  the  hoistway  enclosure  conforms 
to  building  code  requirements  for  fire-resistive 
construction. 


Verify  that  means  to  prevent  accumulation  of  smoke 
and  hot  gases,  such  as  venting  or  pressurization,  are 
provided  as  required  by  the  applicable  building  code. 
See  Item  3.11. 

4.8.4  References 

4.8.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  -  Rules  100.1,  100.4,  100.5,  and  1001.2(d)(8). 

A17.1-2000/B44-00     and     later     editions     — 
Requirements  2.1.1,  2.1.4,  2.1.5,  and  8.11.2.1.4(h). 
A17.3  —  Paragraphs  2.1.1  and  2.1.2. 
ANSI  Z97.1  or  CFR  Part  1201. 

4.8.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  100.1, 100.4,  and  100.5  {300.1};  and 
1004.2(d)(8). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.1.1,  2.1.4,  and  2.1.5  {3.1);  and 
8.11.3.1.4(h). 

A17.3  —  Paragraphs  2.1.1  and  2.1.2  (Section  4.1}. 

ITEM  4.9 
ELEVATOR  PARKING  DEVICES 

4.9.1  Periodic  Inspections 

Check  operation  of  parking  (service  key)  device  and 
verify  that  all  parts  of  the  device  are  free  to  operate  and 
that  the  door  cannot  be  opened  unless  the  car  is  at  the 
landing.  For  elevators  installed  under  A17. 1-1978  and 
later  editions,  the  device  should  be  located  at  a  height 
not  greater  than  6  ft  11  in.  (2.11  m)  above  the  floor. 

4.9.2  Periodic  Test 

4.9.3  Acceptance 

See  Item  4.4.3. 

4.9.4  References 

4.9.4.1  Electric  Elevators.    A17.1d-2000  and  earlier 

editions  —  Rule  1001.2(d)(9). 

A17.1-2000/B44-00  and  later  editions  — 
Requirement  8.11.2.1.4(i). 

A17.3  —  Paragraph  2.7.2. 

4.9.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rule  1004.2(d)(9). 

A17.1-2000/B44-00  and  later  editions  — 
Requirement  8.11.3.1.4(i). 

A17.3  —  Paragraph  2.7.2  (Section  4.1}. 

ITEM  4.10 

EMERGENCY  DOORS  IN  BLIND 

HOISTWAYS 

4.10.1  Periodic  Inspections 

For  elevators  installed  under  A17. 1-1955,  check  that 
emergency  doors  are  closed,  locked,  and  free  from  fixed 


69 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


obstructions.  Check  the  operation  of  the  door  electric 
contact.  For  elevators  installed  under  A17.1-1960  and 
later  editions,  check  for  the  above  and  that  the  emer- 
gency doors  are  self-closing  and  self-locking.  Verify  that 
a  cylinder-type  lock  with  a  minimum  of  five-pin  or  five- 
disc  combination  is  provided,  that  the  key  is  removable 
only  in  the  locked  position,  and  that  the  lock  can  be 
unlocked  from  the  landing  side  only.  Verify  that  the  key 
for  this  lock  is  accessible  only  to  elevator  personnel. 
Check  that  a  sign  indicating  "DANGER,  ELEVATOR 
HOISTWAY"  has  been  provided  on  the  landing  side  of 
each  emergency  door. 

4.10.2  Periodic  Test 

4.10.3  Acceptance 

Check  the  operation  of  the  self-closing  device  and 
functioning  of  the  self-locking  device,  and  that  a  door 
electric  contact  is  provided.  Check  that  it  can  be 
unlocked  from  the  landing  side  only  through  the  use  of 
the  cylinder-type  lock,  with  a  key  that  will  not  unlock 
any  other  door  or  device  in  the  building. 

Check  that  the  key  is  kept  where  it  is  available  only 
to  elevator  personnel. 

Verify  that  cylinder-type  lock  with  a  minimum  of 
either  a  five-pin  or  five-disc  combination  has  been  pro- 
vided on  the  landing  side  of  the  door,  that  the  key  is 
removable  only  in  the  locked  position,  and  that  the  door 
can  be  unlocked  from  the  landing  side. 

NOTE:  Emergency  doors  in  blind  hoistways  are  required  on 
hydraulic  elevators  only  where  car  safeties  are  used. 

4.10.4  References 

4.10.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  110.1  and  1001.2(d)(10). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.11.1.1,  2.11.1.2,  8.1,  and  8.11.2.1.4Q). 

4.10.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  110.1  and  1004,2. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.11.1.1,  2.11.1.2,  8.1,  and  (NR  1004.2). 

ITEM  4.11 

SEPARATE  COUNTERWEIGHT 

HOISTWAY 

4.11.1   Periodic  Inspections 

Where  the  counterweight  runs  within  a  separate 
enclosure  outside  the  hoistway,  each  rope  and  its  fasten- 
ing should  be  inspected  at  the  door  in  such  enclosure 
nearest  to  the  top  of  the  hoistway.  Determine  that  inspec- 
tion doors  in  the  counterweight  enclosure  meet  the 


requirements  of  the  Code.  Instruct  the  operator  to  move 
the  car  a  short  distance  at  a  time  and  inspect  the  ropes. 

The  Code  prohibits  the  location  of  counterweights 
outside  the  elevator  hoistway,  except  for  elevators  with- 
out mechanical  compensation  or  counterweight  safeties 
installed  under  the  A17.1f-1975  and  later  editions. 
A17.1f-1975  through  A17.1b-1983,  limited  separate 
counterweight  hoistways  to  observation-type  elevators. 

Elevators  installed  under  A17.1-2000/B44-00  and 
later  editions,  confirm  that  the  enclosed  stop  switch,  the 
permanent  light  switch,  outlet,  and  light  are  provided 
in  the  hoistway  immediately  inside  the  entry  door  and 
that  all  function  properly. 

4.11.2  Periodic  Test 
4.11.4  References 

4.11.3.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  103.1,  103.3,  110.1,  and  1001.2(d)(ll). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.3.1, 2.3.3, 2.11.1.1, 2.11.1.2,  2.26.2.27,  and 
8.11.2.1.4(k). 

ITEM  4.12 
STANDBY  POWER  SELECTION  SWITCH 

4.12.1  Periodic  Inspections 

Check  that  the  standby  power  selection  key  is  kept 
in  a  location  where  it  is  available  only  to  authorized 
persons. 

4.12.2  Periodic  Test:  Yearly  Test  (for  A17.1d-2000 
and  Earlier  Editions);  Category  1  Test  (for 
A17.1-2000/B44-00  and  Later  Editions) 

See  Item  1.17.2. 

4.12.3  Acceptance 

4.12.4  References 

4.12.4.1  Electric  Elevators.  A17,ld-2000  and  earlier 
editions  —  Rules  211.2, 211.8, 1001.2(d)(13),  and  1002.2g. 

A17.1-2000/B44-00     and     later     editions     — 
Requirements  2.27.2,  2.27.8,  8.11.2.1.4(1),  and  8.11.2.2.7. 
A17.3  —  Paragraph  3.11.2. 

4.12.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  207.8  {301.10},  211.2  and  211.8 
{306.11},  1002.2g,  1004.2(d)(ll),  and  1005.2c. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.16.8  {3.16},  2.27.2  and  2.27.8  {3.27}, 
8.11.2.2.7,  8.11.3.1.4(k),  and  8.11.3.2.3. 

A17.3  —  Paragraph  3.11.2  {4.7.8}. 


70 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Parts 
Elevator  —  Pit 


ITEM  5.1 

PIT  ACCESS,  LIGHTING,  STOP  SWITCH,  AND 

CONDITION 

5.1.1  Periodic  Inspections 

(a)  Check  that  the  means  of  access  is  safe,  convenient, 
and  accessible  only  to  authorized  persons, 

(1)  If  a  pit  access  door  is  provided,  check  that  it  is 
locked  and  is  self-closing  and  can  be  opened  from  inside 
the  pit  without  a  key.  A17.3  also  requires  that  this  door 
be  kept  closed  and  locked. 

(2)  If  access  is  through  the  lowest  landing,  check 
that  the  hoistway  door  unlocking  device  or  access  switch 
operates  properly. 

(b)  If  access  is  through  the  lower  landing  and  the  pit 
floor  is  more  than  4  ft  (1  219  mm)  below  the  access  sill, 
check  the  required  pit  ladder  for  compliance  and  secure 
fastening  to  the  wall.  If  the  ladder  is  not  secure,  do  not 
use  it.  A17. 1-1978  and  later  editions  required  a  pit  ladder 
for  pit  extending  more  than  3  ft  (914  mm)  below  the 
access  sill. 

(c)  Check  that  the  stop  switch  can  be  reached  from 
the  access  entrance  and  that  it  will  prevent  the  car  from 
operating  by  placing  it  in  the  stop  position  and  having 
a  person  in  the  car  attempt  to  move  it.  In  addition  to 
the  other  requirements  in  A17.1-1971  and  later  editions, 
require  the  stop  and  run  positions  to  be  marked  on  the 
switch.  For  elevators  installed  under  A17. 1-1978 
through  A17.1b-1992,  two-pit  switches  are  required 
when  the  pit  access  is  from  the  lowest  landing  and  the 
pit  depth  is  more  than  6  ft  7  in.  (2  007  mm).  For  elevators 
installed  under  Al 7.1-1993  and  later  editions,  two-pit 
switches  are  required  when  the  depth  exceeds  66  in. 
(1  676  mm).  Verify  that  either  switch  will  stop  the  car. 

(d)  The  pit  light  switch  must  be  accessible  from  the  pit 
access  door.  Turn  this  switch  on  and  verify  that  lighting 
meets  Code  requirements.  A17.1a-1988  and  later  edi- 
tions require  the  bulb  to  be  guarded  externally  to  reduce 
accidental  breakage.  This  edition  also  requires  that  a 
duplex  receptacle  be  provided  in  the  pit. 

(e)  From  a  safe  position  on  the  landing  or  pit  access 
door,  use  a  light  to  visually  inspect  the  pit  for  the  pres- 
ence of  water,  accumulation  of  combustible  materials, 
oil  or  other  materials,  or  equipment  not  related  to  the 
elevator  operation.  Carefully  note  the  location  of  all 
equipment  in  the  pit  and  under  the  car,  and  identify  a 
refuge  area  to  use  in  case  the  car  runs  down  unexpect- 
edly. Note  the  location  of  cars  and  equipment  in  adjacent 


hoistways.  Sump  covers  level  with  the  pit  floor  are 
required  by  A17.1a-1985  and  later  editions.  On  entering 
the  pit  examine  for  cleanliness  especially  in  trenches  and 
depressions  allowed  for  buffers,  vertically  sliding  doors, 
or  structural  members. 

Check  the  pit  area  for  the  installation  of  any  pipes  or 
ducts  not  related  to  the  operation  of  the  elevator.  For 
elevators  installed  under  A17.1-1993  and  later  editions, 
a  permanent  means  of  preventing  the  accumulation  of 
water  is  required. 

(f)  For  elevators  installed  under  A17.1a-1988  and 
later  editions,  check  that  a  duplex  receptacle  has  been 
provided  in  the  pit.  For  elevators  installed  under 
ANSI/NFPA  70-1993,  check  the  receptacle  is  provided 
with  ground-fault  circuit-interrupter  protection. 

For  elevators  installed  under  ANSI/NFPA  70-1996 
and  later  editions,  check  that  the  receptacle  is  of  the 
ground-fault  circuit-interrupter  type.  A  single  receptacle 
supplying  a  permanently  installed  sump  pump  does  not 
require  ground-fault  circuit-interrupter  protection. 

5.1.2  Periodic  Test 

5.1.3  Acceptance 

Examine  the  pit  construction  for  Code  compliance  and 
note  that  the  pit  floor  is  approximately  level.  If  the  pit 
has  a  drain,  verify  that  it  is  not  directly  connected  to  a 
sewer. 

5.1.4  References 

5.1.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  102, 103.2, 106.1, 210.2(g),  1001.2(e)(1), 
and  1206.2a. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.8, 2.3.2,  (NR  106.1),  2.26.2.7, 8.11.2.1.5(a), 
and  8.6.4.7. 

A17.3  —  Paragraphs  2.3.1,  2.3.2,  and  2.7.3. 

NFPA  70  or  CSA  C22.1,  as  applicable. 

5.1.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Section  102  {Rule  300.3};  and  Rules  106.1 
{300.7},  300.10,  306.4,  1004.2(e)(1),  and  1206.2a. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.8  {3.8};  (NR  106.1)  {3.2),  3.6,  3.26.4, 
8.11.3.1.5(a),  and  8.6.4.7. 

A17.3  —  Paragraphs  2.3.1,  2.3.2,  and  2.7.3  {Section 
4.1};  and  3.10.4. 

NFPA  70  or  CSA  C22.1,  as  applicable. 


71 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


ITEM  5.2 

BOTTOM  CLEARANCE,  RUNBY,  AND  MINIMUM 

REFUGE  SPACE 

5.2.1  Periodic  Inspections 

If  there  has  been  an  obvious  change  such  as  a  new 
buffer,  buffer  mounting,  or  rope  fastenings,  check  the 
car  and  counterweight  bottom  clearances  and  runbys 
(see  Item  5.2.3). 

(10)  5.2.1.1   Electric  Elevators.    The  car  and  counter- 

weight runby  may  be  less  than  provided  upon  installa- 
tion, provided  the  car  and  counterweight  does  not  strike 
the  buffer,  the  top  car  clearances  have  not  been  reduced 
below  that  required  at  the  time  of  installation  or  alter- 
ation (Item  3.4),  and  the  final  terminal  stopping  devices 
remain  operational  (Items  2.26,  3.8,  and  5.4).  For  spring- 
return-type  oil  buffers,  where  compression  is  permitted, 
check  that  any  compression  of  the  car  and  counterweight 
buffers  does  not  exceed  25%  of  the  buffer  stroke. 

Where  required,  examine  the  counterweight  guard  for 
secure  fastening  and  placement.  In  some  cases,  remov- 
able blocking  is  furnished  in  connection  with  the  coun- 
terweight buffer  to  provide  adjustment  following  rope 
stretch  in  order  to  secure  proper  counterweight  runby 
without  shortening  the  ropes.  If  smooth  metal  plates  are 
used  for  blocking,  examine  for  evidence  of  the  plates 
being  coated  with  oil  and  picked  up  by  the 
counterweight. 

Check  the  available  refuge  space  for  elevators  installed 
under  A17.1b-1992  and  later  editions. 

5.2.1.2  Hydraulic  Elevators.  Check  the  available  ref- 
uge space  for  elevators  installed  under  A17.1e-1987  and 
later  editions. 

If  a  counterweight  is  provided,  the  minimum  counter- 
weight runby  must  not  be  reduced  below  the  sum  of 
the  distance  the  car  can  travel  above  the  top  terminal 
landing  until  the  plunger  strikes  its  mechanical  stop 
plus  6  in.  (150  mm). 

5.2.2  Periodic  Test 

5.2.3  Acceptance 

5.2.3.1  Electric  Elevators.  Check  the  bottom  car  and 
counterweight  clearance  and  runby  for  compliance  with 
the  Code  requirements.  Position  the  car  above  the  lower 
landing  to  allow  access  to  the  pit.  These  may  be  deter- 
mined as  follows: 

(a)  Bottom  Car  Runby.  See  Fig.  5.2.3. 

(1)  Measure  the  distance  from  the  landing  sill  to 
the  car  floor  sill  dimension  a. 

(2)  Without  moving  the  car,  measure  distance  from 
the  buffer  to  the  buffer  strike  plate  on  the  bottom  of  the 
car,  dimension  b.  Subtract  a  from  b;  this  will  be  the 
bottom  car  runby.  Note  that  a  negative  number  indicates 
that  the  car  will  strike  the  buffer  when  level  with  the 
bottom  landing. 


(3)  For  spring-return-type  oil  buffers,  where  com- 
pression is  permitted,  check  that  any  compression  of  the 
car  and  counterweight  buffers  does  not  exceed  25%  of 
the  buffer  stroke. 

(b)  Bottom  Car  Clearance.  See  Fig.  5.2.3. 

(1)  Measure  the  distance  (dimension  c)  from  the 
lowest  structure  member  beneath  the  car,  ignoring  roller 
guides,  platform  aprons,  safety  jaws,  and  other  equip- 
ment located  within  12  in.  (305  mm)  horizontally  of  the 
hoistway  wall. 

(2)  Measure  the  distance  from  the  buffer  to  the 
buffer  striking  plate  on  the  car  and  add  the  buffer  stroke 
to  this  measurement  b  plus  buffer  stroke.  Subtract  b  plus 
buffer  stroke  from  c  to  obtain  the  bottom  car  clearance. 
Do  not  consider  trenches,  depressions,  or  foundation 
encroachments  when  making  these  measurements.  Also, 
use  these  measurements  to  determine  that  no  part  of 
the  car  or  equipment  will  touch  the  floor  when  the  car 
rests  on  its  fully  compressed  buffer. 

(c)  Bottom  Counterweight  Runby,  With  the  car  level 
with  the  top  terminal  landing,  visually  check  the  dis- 
tance between  the  bottom  of  the  counterweight  and  the 
top  of  the  counterweight  buffer  in  the  pit,  or  where  a 
gravity-return  counterweight  buffer  is  used,  between  the 
buffer  plunger  and  the  striker  block  in  the  pit. 

For  spring- return- type  oil  buffers,  where  compression 
is  permitted,  check  that  any  compression  of  the  car  and 
counterweight  buffers  does  not  exceed  25%  of  the  buffer 
stroke. 

Check  the  counterweight  runby  against  the  data  plate 
shown  in  the  pit. 

5.2.3.2  Hydraulic  Elevators.  Check  the  bottom  car 
clearance  and  runby  for  compliance  with  the  Code 
requirements.  Position  the  car  above  the  lower  landing 
to  allow  access  to  the  pit.  These  may  be  determined  as 
follows: 

(a)  Bottom.  Car  Runby.  See  Fig.  5.2.3. 

(1)  Measure  the  distance  from  the  landing  sill  to 
the  car  floor  sill,  dimension  a. 

(2)  Without  moving  the  car,  measure  distance  from 
the  buffer  to  the  buffer  strike  plate  on  the  bottom  of  the 
car,  dimension  b.  Subtract  a  from  b;  this  will  be  the 
bottom  car  runby.  Note  that  a  negative  number  indicates 
that  the  car  will  strike  the  buffer  when  level  with  the 
bottom  landing. 

(b)  Bottom  Car  Clearance.  See  Fig.  5.2.3. 

(1)  Measure  the  distance  (dimension  c)  from  the 
lowest  structure  member  beneath  the  car,  ignoring  roller 
guides,  platform  aprons,  and  other  equipment  located 
within  12  in.  (305  mm)  horizontally  of  the  hoistway 
walls. 

(2)  Measure  the  distance  (dimension  b)  from  the 
buffer  to  the  buffer  striking  plate  on  the  car  and  add 
the  buffer  stroke  to  this  measurement.  Subtract  b  plus 
buffer  stroke  from  c  to  obtain  the  bottom  car  clearance. 
Do  not  consider  trenches,  depressions,  or  foundation 


72 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Fig.  5.2.3     Bottom  Car  Clearance  Hydraulic  Elevators 


Bottom  car  runby  =  b- 
Bottom  car  clearance  = 


{b+  buffer  stroke) 


Example: 

Buffer  stroke  =  10  in. 

a  =  24  in. 

6  =  30  in. 

c=  66  in. 

Bottom  car  runby  =  30  in.  -  24  in.  =  6  in. 

Bottom  car  clearance  =  66  in.  -  (30  in.  +  10  in.)  =  26  in. 


GENERAL  NOTES:     Minimum  refuge  space  not  less  than  (a)  or  (b)  below. 

(a)  24  in.  by  48  in.  by  24  in,  high;  or 

(b)  18  in.  by  36  in.  by  42  in.  high. 


encroachments  when  making  these  measurements.  Also, 
use  these  measurements  to  verify  that  no  part  of  the  car 
or  equipment  will  touch  the  floor  when  the  car  rests  on 
its  fully  compressed  buffer. 

(c)  Bottom  Plunger  Clearance.  Verify  that  with  the  car 
on  full  compressed  buffers,  the  plunger  does  not  strike 
the  bottom  of  the  casing.  To  do  this,  lower  the  car  by 
inspection  or  manual  lowering  and  fully  compress  the 
buffers.  On  spring  buffers  that  may  not  be  compressed 
easily  measure  the  distance  from  the  buffer  strike  plate 
to  the  buffer  springs  with  the  car  level  with  the  landing 
(runby).  Add  to  this  distance  the  full  stroke  of  the  buffer. 
With  the  buffer  springs  removed,  the  car  must  be  low- 
ered at  least  the  sum  of  the  two  distances. 

If  a  counterweight  is  provided,  verify  the  bottom 
counterweight  runby  and  that  no  counterweight  buffers 
are  provided. 

Check  the  counterweight  runby  against  the  data  plate 
shown  in  the  pit. 

5.2.4  References 

5.2.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  103.2,  107.1a,  107.1b,  201. 4h, 
1001.2(e)(2),  1202.14b,  and  1206.8. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.3.2,  2.4.1,  2.4.2,  2.22.4.8,  8.11.2.1.5(b), 
(NR  1202.14b),  and  8.6.4.11. 

A17.3  —  Paragraphs  2.4.2  and  2.4.3. 


5.2.4.2  Hydraulic  Elevators.  A17.1d~2000  and  ear- 
lier editions  —  Rules  300.8,  302.3c,  1004.2(e)(2),  and 
1006.2e. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  3.4, 3.18.3.3,  8.11.3.1.5(b),  and  8.10.3.2.5(c). 

A17.3  —  Paragraph  2.1.5. 

ITEM  5.3 

FINAL  AND  EMERGENCY  TERMINAL  STOPPING 

DEVICES 

53.1  Periodic  Inspections 

5.3.1.1  Electric  Elevators.  The  lower  final  terminal 
stopping  device  should  be  located  as  close  to  the  termi- 
nal landing  as  possible  without  interfering  with  the  nor- 
mal terminal  stopping  device. 

Where  spring  buffers  are  used,  the  lower  terminal 
stopping  device  must  stop  the  car  before  the  car  strikes 
the  buffer.  With  the  car  parked  as  near  the  device  as 
possible  and  the  stop  button  in  the  stop  position,  use  a 
light  to  check  alignment  of  the  device  and  the  operating 
cam.  The  roller  should  be  centered  on  the  cam  in  such 
a  position  that  the  cam  or  roller  will  not  be  damaged 
when  it  operates.  This  must  allow  free  motion  of  the 
roller  arm  and  positive  opening  of  the  switch  contact 
without  damaging  the  switch.  Have  the  car  moved  up 
and  check  that  the  device  is  securely  fastened  and  not 
loose. 


73 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


(10) 


5.3.2  Periodic  Test 

5.3.2.1  Electric  Elevators 

(a)  Yearly  Test  (for  A17.1d-2000  and  Earlier  Editions); 
Category  1  Test  (for  A17.1-2000/B44-00  and  Later  Editions). 
The  operation  of  the  final  terminal  stopping  device  (final 
limit)  and  its  relation  to  the  cam  by  jumping  out  the 
normal  terminal  stopping  device  and  running  the  car 
past  the  terminal  floor  at  slow  speed.  The  car  should 
stop  as  close  to  the  floor  as  practical. 

The  final  terminal  stopping  device  should  not  func- 
tion when  the  car  is  stopped  by  the  normal  terminal 
stopping  device.  Where  spring  buffers  are  used,  verify 
that  the  device  will  function  before  the  buffer  is  engaged. 
Measure  the  length  of  the  cam  and,  using  the  bottom 
car  runby  and  buffer  stroke,  check  that  the  device  will 
continue  to  function  until  the  car  rests  on  its  fully  com- 
pressed buffer.  After  this  test,  it  will  be  necessary  to 
jump  the  final  terminal  stopping  device  to  move  the  car 
off  of  it. 

(b)  5-Year  Test  of  Emergency  Terminal  Stopping  Means 
(for  A17.1d-2000/B44-00  and  Earlier  Editions);  Category  5 
Test  of  Emergency  Terminal  Stopping  Means  (for 
A17.1-2000/B44-00  and  Later  Editions).  For  static  control 
elevators  see  Item  2.28.2(b)  and  for  emergency  terminal 
speed  limiting  devices  see  Item  5.3.2. 

5.3.3  Acceptance 

5.3.4  References 

5.3.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  209.3,  1001.2(e)(4),  and  1003.2e. 

A17.1-2000/B44-00  and  later  editions  -  Requirements 
2.25.3,  8.11.2.1.5(d),  and  8.10.2.2.5(c)  or  c8.10.2.2.5(c)(6). 

A17.3  —  Paragraph  3.9.2. 


5.4.4.2  Hydraulic  Elevators.  A17.1d~2000  and  ear- 
lier editions  —  Rules  305.1,  1002. 2e  {1005.2c},  and 
1004.2(e)(5). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  3.25.1,  8.11.2.2.5  {8.11.3.2.3},  and 
8.11.3.1.5(e). 

A17.3  —  Paragraph  3.9.1  {Section  4.6}. 

ITEM  5.5 
TRAVELING  CABLES 

5.5.1  Periodic  Inspections 

Examine  the  lower  portion  of  the  traveling  cables  and 
their  connections  to  the  car  as  outlined  in  Item  3.11.  The 
cables  should  not  touch  the  pit  floor  or  rub  against  any 
other  equipment.  Examine  visible  portion  of  cables  for 
wear,  twist,  or  damage. 

5.5.2  Periodic  Test 

5.5.3  Acceptance 

5.5.4  References 

5.5.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rule  102.2. 

A17.1-2000/B44-00      and      later      editions     — 
Requirement  2.8.2. 
NFPA  70  or  CSA  C22.1,  as  applicable. 

5.5.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  102.2  {300.3}  and  1004.2(e)(6). 

A17.1-2000/B44-00     and     later     editions     — 
Requirements  2.8.2  {3.8}  and  8.11.3.1.5(f). 
NFPA  70  or  CSA  C22.1,  as  applicable. 


ITEM  5.4 

NORMAL  TERMINAL  STOPPING 

DEVICES 

5.4.1  Periodic  Inspections 

If  the  normal  terminal  stopping  device  is  located  in 
the  hoistway,  check  that  it  is  securely  fastened,  that  the 
roller  is  in  good  condition  and  aligned  with  the  cam. 
The  alignment  with  the  cam  may  have  to  be  checked 
from  the  top  of  the  car  as  described  in  Item  3.5.1. 

5.4.2  Periodic  Test 

See  Items  2.28  and  3.5. 

5.4.3  Acceptance 

5.4.4  References 

5.4.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  209  and  1002.2e. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.25  and  8.11.2.2.5. 

A17.3  —  Paragraph  3.9.1. 


ITEM  5.6 
GOVERNOR-ROPE  TENSION  DEVICES 

5.6.1  Periodic  Inspections 

Examine  the  governor-rope  tension  device  and  deter- 
mine whether 

(a)  there  is  sufficient  remaining  travel  of  the  sheave 
frame  to  maintain  tension  in  the  governor  rope  and  that 
the  frame  is  securely  fastened  to  the  hoistway 

(b)  the  frame  moves  freely  in  its  guides 

(c)  the  operation  of  the  sheave  while  the  car  is  in 
motion,  reveals  no  excessive  wear  of  the  sheave,  shaft, 
or  bearings,  and  that  all  parts  are  lubricated 

(d)  check  for  excess  lubricant  or  other  contaminants 
that  may  get  on  the  governor  rope 

(e)  with  the  car  operating,  listen  for  noise  caused  by 
rubbing  or  bearing  in  a  failure  mode 

Lifting  of  the  tension  weights  with  the  car  at  rest  and 
the  stop  switch  in  the  stop  position  may  also  assist  in 
detecting  defects. 


74 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


5.6.2  Periodic  Test 

5.6.3  Acceptance 

5.6.3.1   Electric  Elevators.    See  Item  2.28.3. 

5.6.4  References 

5.6.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  206.7,  1001.2(e)(7),  and  1206.1a. 

A17.1-2000/B44-00     and     later     editions     — 
Requirements  2.18.7,  8.11.2.1.5(g),  and  8.6.1.6.2. 

5.6.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  206.7,  301.8,  1004.2(e)(ll),  and 
1206.1a. 

A17.1-2000/B44-00     and     later     editions     — 
Requirements  2.18.7,  3.17.1,  8.11.3.1.5(k),  and  8.6.1.6.2. 
A17.3  —  Paragraph  4.9.7. 


ITEM  5.7 
CAR  FRAME  AND  PLATFORM 

5.7.1  Periodic  Inspections 

Examine  the  car  portion  of  the  car  frame  accessible 
from  the  pit  and  determine  whether  all  fastenings, 
including  those  between  the  car  frame  and  the  platform, 
are  securely  in  place  and  that  the  frame  is  not  distorted. 

Examine  the  buffer  strike  plates  to  determine  that  they 
have  not  been  deformed  or  removed. 

Examine  the  frame  and  platform  members  and  their 
fastenings.  Distorted  or  straightened  members,  blistered 
paint,  exuded  rust  from  between  members  or  around 
bolts  or  rivets,  and  oil  bubbles  on  members  may  all  be 
clues  to  a  cracked  or  fractured  member.  Where  examina- 
tion reveals  the  possibility  of  a  fracture,  further  investi- 
gation should  be  made  as  identified  in  Item  3.18. 

Check  any  platform  toe  guards  and  aprons  on 
entrance  sides  and  determine  whether  they  are  securely 
fastened  to  the  platform.  Check  platform  balancing 
weights  and  determine  whether  they  are  securely  fas- 
tened. Check  the  platform  guard  for  secure  fastening 
and  length.  If  a  truck  zoning  device  is  provided,  the 
guard  should  meet  Code  requirements  for  this 
application. 

If  a  wood  car  platform  is  provided,  check  the  fire 
protection  of  the  underside  of  the  car  platform  for  com- 
pliance. If  a  fire-retard  ant  paint  has  been  used,  it  should 
be  in  good  condition.  If  the  underside  is  clad  with  sheet 
metal,  it  must  be  in  place. 

5.7.2  Periodic  Test 

5.7.3  Acceptance 

If  a  wood  platform  has  been  painted  with  fire- 
retard  ant  paint,  have  the  installer  furnish  data  on  the 
paint  to  verify  Code  compliance. 


5.7.4  References 

5.7.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  203.8, 203.6, 207.2b(3),  and  1001.2(e)(9). 

A17.1-2000/B44-00      and      later     editions     — 
Requirements  2.15.8,  2.15.6,  2.16.2.2,  and  8.11.2.1.5(1). 
A17.3  —  Section  3.3. 

5.7.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Section  308;  and  Rules  301.6,  302.2c,  and 
1004.2(e)(7). 

A17.1-2000/B44-00     and     later     editions     — 
Requirements  3.28,  3.15,  3.18.2.3,  and  8.11.3.1.5(g). 
A17.3  —  Section  3.3  {para.  4.2.2}. 

ITEM  5.8 
CAR  AND  COUNTERWEIGHT  SAFETIES  AND  GUIDING 

MEMBERS  -  INCLUDING  ROPED-HYDRAULIC 

ELEVATORS  INSTALLED  UNDER  A17.1b-1989  AND 

LATER  EDITIONS 

5.8.1  Periodic  Inspections 

5.8.1.1  Guide  Rails 

(a)  Steel  Guide  Rails.  Examine  the  car  and  counter- 
weight guiding  members  and  their  fastenings  to  deter- 
mine that  they  are  properly  secured,  aligned,  and 
adjusted,  and  that  they  are  not  worn  excessively. 

Determine  that  all  moving  parts  of  the  safety  are  clean, 
lubricated,  not  corroded,  free  to  operate,  and  that  the 
clearance  between  the  guide  rail  and  each  rail  gripping 
face  of  the  safety  parts  is  in  compliance  with  the  Code 
(see  note  below). 

Check  that  the  rope  used  to  connect  the  safety  to  the 
governor  rope  is  securely  fastened  and  snugly  seated  in 
the  deflection  sheaves  without  any  kink  or  excess  slack. 
The  rope  should  not  be  corroded.  On  drum-operated 
safeties  check  that  the  safety  drum  rope  is  correctly 
wound  on  the  drum.  Where  the  safety  jaws  are  con- 
nected with  tie  rods,  such  rods  must  be  straight  and 
secure. 

If  the  safety  switch  is  located  here,  inspect  its  condi- 
tion, position,  and  fastening.  Check  to  see  that  a  metal 
marking  plate  is  securely  attached  to  the  safety  plank, 
readily  visible,  and  legibly  and  permanently  marked 
indicating  the  following: 

(1)  the  maximum  tripping  speed,  in  ft/min  (m/s), 
for  which  the  safety  may  be  used  —  A17.1-1955  and 
later  editions 

(2)  the  maximum  weight  in  pounds  that  the  safety 
as  installed  is  designed  to  stop  and  sustain  — 
A17.1-1955  and  later  editions 

(3)  the  type  of  safety  —  A17.1-1955  and  later 
editions 

(4)  the  name  or  logo /trademark  of  the  manufac- 
turer —  A17.1-2000  and  later  editions 

(5)  the  force  required  to  activate  the  safety  or 
governor-rope  releasing  carrier  —  A17.1a-1997  and  later 
editions 


75 


C 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


This  marking  plate  has  been  required  since 
A17.1-1955,  but  A17.3  does  not  require  this  marking 
plate.  Prior  to  Al 7. 1-1955  the  safety  was  required  to 
be  marked  with  load  and  speed  date,  but  no  marking 
method  was  specified. 

NOTE:  A  running  clearance  of  %2  in.  (2.4  mm)  was  permitted 
for  safeties  installed  under  the  1937  and  earlier  editions  of  the 
Code.  A  clearance  of  %4  in.  (3.6  mm)  is  required  for  elevators 
installed  under  A17. 1-1955  and  later  editions,  with  a  V]6  in. 
(1.6  mm)  minimum  between  either  side  of  the  rail  and  the  gripping 
face.  This  facilitates  adjusting  the  governor  rope  movement 
(required  to  operate  the  safety  mechanism  to  the  point  where  the 
safety  jaws  exert  pressure  on  the  rails)  to  within  the  maximum 
permitted  by  Rule  205.11.  The  closer  running  clearance,  permitted 
for  the  older  safeties,  may  result  in  wear  on  the  gripping  surface 
of  the  jaws  which  requires  careful  inspection  to  detect,  and  may 
necessitate  frequent  readjustment.  A17.3  does  not  address  safety 
jaw  running  clearance  but  does  address  the  safety  rope  pullout 
that  often  affects  the  safety  jaw  clearance.  If  sliding  guides  have 
been  replaced  with  roller  guides,  the  safety  jaws  must  not  touch  the 
guide  rail  when  the  roller  guide  is  at  its  fullest  extent  of  movement. 

(b)  Wood  Guide  Rails.  Make  an  examination  of  the  fol- 
lowing items  in  addition  to  the  governor- rope  system 
and  guide  rails. 

(1)  From  the  top  of  the  car,  examine  all  safety 
operating  parts  including  levers  and  linkage  to  be  sure 
that  all  keys  and  set  screws  are  in  place  and  tight.  There 
should  not  be  an  excessive  amount  of  lost  motion  in  the 
transmittal  of  movement  to  the  finger  rods  actuating  the 
safety  jaws. 

(2)  From  the  pit,  with  the  elevator  car  platform  at 
a  convenient  height,  the  safety  jaws  can  be  readily  exam- 
ined and  applied  against  the  guide  rails  by  pulling  the 
governor  rope.  The  safety  jaws  should  be  brought  in 
contact  with  both  guide  rails  in  such  a  manner  that  any 
downward  motion  of  the  car  would  cause  the  jaw  teeth 
to  dig  into  the  rails. 

(3)  When  a  safety  operating  switch  is  provided,  the 
motion  of  bringing  the  safety  jaws  in  contact  with  the 
rails  must  be  sufficient  to  operate  the  switch. 

(4)  The  distance  between  the  rail  gripping  surfaces 
should  not  be  less  than  the  thickness  of  the  rail  plus 
\  in.  (6.4  mm). 

5.8.2  Periodic  Test 

See  Item  2.29. 

5.8.2.2  Hydraulic  Elevators.  Test  counterweight 
safeties  that  are  operated  by  breaking  or  slacking  of  the 
counterweight  suspension  means  by  placing  an 
extended  jack  and  blocking  under  the  counterweight. 
Then  slowly  move  the  car  up  allowing  the  counterweight 
to  contact  the  blocking.  Then  lower  the  jack,  to  obtain 
slack  rope,  to  operate  the  safety  and  verify  that  the 
counterweight  safety  will  stop  and  hold  the  counter- 
weight, to  obtain  slack  rope  to  operate  the  safety.  It 
will  be  necessary  to  jump  the  slack  rope  device  when 
conducting  this  test  to  prevent  it  from  operating  before 


sufficient  slack  rope  is  obtained  to  operate  the  safety. 
After  this  test  the  elevator  should  not  operate  until  both 
the  safety  switch  and  the  slack  rope  device  are  manu- 
ally reset. 

For  roped-hydraulic  elevators,  the  car  safeties  may,  in 
addition  to  being  activated  by  the  governor,  be  activated 
by  the  slacking  or  breaking  of  the  suspension  means. 
Test  as  outlined  above  for  counterweight  safeties,  except 
place  the  jack  under  the  car, 

5.8.3  Acceptance 

Examine  the  data  on  the  safety  marking  plate. 

5.8.4  References 

5.8.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Section  203  and  Rules  205.11,  1001.2(e)(10), 
1001.2b(2)(c),  1002.3a,  1206.1g,  and  1202.4a. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.15,  2.17.11,  8.11.2.1.5(j),  8.11.2.1.2, 
8.11.2.3.1,  8.6.4.5,  and  8.7.2.15.1. 

A17.3  —  Section  3.5. 

5.8.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Sections  205  and  1306;  and  Rules  301.8, 
301.9,  1004.2(e)(10),  1005.2c,  and  1005.4. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.17  and  8.2.6;  and  3.17.1,  3.17.2, 
8.11.3.1.5(j),  8.11.3.2.3,  and  8.11.3.4. 

A17.3  —  Paragraphs  4.9.6  and  4.9.8. 

NOTE:     Items  5.9  through  5.10  apply  to  electric  elevators  only. 


ITEM  5.9 

BUFFER  AND  EMERGENCY  TERMINAL  SPEED 

LIMITING  DEVICES 

5.9.1  Periodic  Inspections 

5.9.1.1  Electric  Elevators 

(a)  Oil  Buffers,  Make  the  following  examinations: 

(1)  Check  the  bolts  holding  the  buffers  and  mount- 
ing to  determine  that  they  are  tight. 

(2)  Check  the  buffer  oil  level  by  the  means  provided 
to  determine  that  it  is  within  the  maximum  and  mini- 
mum allowable  limits. 

(3)  Test  the  plunger  for  excessive  side  play. 

(4)  Verify  that  the  plunger  is  free  of  dirt  or  rust. 

(5)  Check  the  buffer  marking  plate.  A17.1-1987  and 
later  editions  require  the  stroke  to  be  shown  on  the  buffer 
marking  plate.  Check  that  the  maximum  and  minimum 
loads,  the  maximum  striking  speed,  and  the  oil  viscosity, 
index  number,  and  pour  point  are  provided. 
A17.1-2000/B44-00  and  later  editions  also  require  that 
name,  trademark,  or  file  number  for  identification  of 
the  manufacturer  and  the  certification  markings  on  the 
buffer  data  plate. 


do) 


76 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


(b)  Spring  Buffers.  Check  car  and  counterweight 
spring  buffers  to  determine  that 

(1)  they  and  their  supports  are  securely  fastened 
in  place. 

(2)  they  are  vertical  and  in  alignment  with  striker 
plates  on  the  car  or  counterweight. 

(3)  springs  are  properly  seated  in  the  cup  or  other 
mounting  provided. 

(4)  springs  have  not  been  deformed,  obviously 
weakened,  or  damaged. 

(5)  the  buffer  marking  plate  is  in  place  and  contains 
all  of  the  required  information.  A17.1d-1986  and  later 
editions  require  the  number  of  springs  to  be  shown  on 
the  buffer  marking  plate. 

(6)  removable  springs  are  identified  and  that  the 
marking  plate  indicates  the  identification. 

(c)  Solid  Bumpers.  Check  car  and  counterweight  solid 
bumpers  to  determine  that 

(1)  they  and  their  supports  are  securely  fastened 
in  place 

(2)  no  damage  or  deterioration  exists 

(3)  they  are  vertical  and  in  alignment  with  the 
striker  plates  of  the  car  or  counterweight 

5.9.2  Periodic  Test 

5.9.2.1  Electric  Elevators 

(a)  Yearly  Tes  t  of  Oil  Buffers  (for  A17.1  d-2000  and  Earlier 
Editions);  Category  1  Test  of  Oil  Buffers  (for  A17. 1-2000/ 
B44-00  and  Eater  Editions).  Test  the  gravity  and  spring- 
re  turn- type  oil  buffers  by  fully  compressing  the  plunger 
and  verifying  that  it  will  return  to  a  full  extended  posi- 
tion in  90  s.  If  the  buffer  cannot  be  manually  depressed, 
it  will  be  necessary  to  place  blocking  between  the  car  or 
counterweight  and  operating  downward  at  slow  speed. 
This  can  be  done  by  suspending  a  4  x  4  beneath  the 
car  or  counterweight  in  alignment  with  the  buffer.  It  is 
usually  best  to  operate  the  car  at  slow  speed  from  the 
car  top  operator  for  this  test.  If  the  4x4  cannot  be 
suspended,  it  may  be  held  in  place  with  a  1  x  4  attached 
to  it.  This  will  allow  the  person  holding  it  to  position 
themselves  in  a  safe  position  in  case  the  4x4  slips  off 
of  the  buffer  and /or  the  car  continues  to  move.  If  possi- 
ble, the  person  should  be  positioned  outside  the 
hoist  way  or  in  an  adjacent  pit  with  the  adjacent  pit  car 
out  of  service.  Test  buffers  on  Type  C  safeties  in  the 
same  manner. 

Then  place  a  50  lb  (23  kg)  weight  on  spring-return- 
type  oil  buffer  and  depress  it  2  in.  (51  mm).  This  can  be 
done  using  a  small  hydraulic  jack  between  the  car  and 
buffer.  Release  the  buffer  and  verify  that  it  will  return 
to  its  fully  extended  position  within  30  s. 

Test  the  compression  switch  on  gas  spring- return-type 
buffers  by  compressing  the  buffer  l/2  in.  (13  mm)  and 
using  a  ohmmeter  to  determine  that  the  switch  opens. 
Then  move  the  car  up,  take  one  lead  off  of  the  switch,  and 
verify  that  the  car  cannot  operate  with  the  switch  open. 


Test  the  buffer  compression  switch  on  Type  C  safety 
buffers  by  having  the  buffer  compressed  10%  of  its  stroke 
and  use  an  ohmmeter  to  verify  that  the  switch  opens. 
Then  move  the  car  allowing  the  buffer  to  return  to  a 
fully  extended  position.  Remove  one  of  the  leads  from 
the  switch  and  attempt  to  operate  the  car.  The  car  must 
not  operate  with  the  lead  removed.  Restore  the  lead  and 
remove  one  lead  from  the  oil  level  switch.  Again  attempt 
to  operate  the  car.  This  should  also  prevent  operation 
of  the  car. 

(b)  5-Year  Test  of  Oil  Buffers  (for  A17 .1  d-2000  and  Earlier 
Editions);  Category  5  Test  of  Oil  Buffers  (for  A17. 1-2000/ 
B44-00  and  Eater  Editions) 

(1)  For  car  buffers,  if  the  elevator  is  equipped  with 
counterweight  safeties,  tie  down  the  counterweight 
safety  lift  lever  with  four  wraps  of  No.  16  gage  copper 
wire  or  equivalent.  This  will  avoid  an  accidental  setting 
of  the  counterweight  safety  by  inertia.  Do  not  block  the 
counterweight  safety;  it  must  remain  workable.  Reverse 
the  procedure  for  testing  the  counterweight  buffer.  Place 
the  rated  load  in  the  car.  Jump  out  the  terminal  slow 
downs  and  directional  switches.  The  final  terminal  stop- 
ping device  must  remain  operative  but  temporarily  relo- 
cated to  permit  full  compression  of  the  buffer.  Take  the 
cars  in  adjacent  hoistways  out  of  service. 

(a)  Full-Stroke  Buffer.  Move  the  car  up  sufficient 
to  obtain  rated  speed  and  run  the  car  into  the  buffer. 

(b)  Reduced  Stroke  Buffer.  Temporarily  reduce  the 
speed  of  the  car  to  the  speed  on  the  buffer  marking 
plate.  Then  run  the  car  into  the  buffer  at  this  speed. 

(c)  Emergency  Terminal  Speed  Eimiting  Device. 
Where  such  a  device  is  provided,  determine  that  it  is 
operational.  Then  run  the  car  into  the  terminal  at  rated 
speed.  The  device  should  slow  the  car  down  so  that  the 
stop  is  no  more  severe  than  that  produced  by  running 
the  car  into  the  buffer  at  the  buffer  design  speed. 

(2)  After  the  test 

(a)  remove  any  jumpers  that  were  installed 

(b)  examine  the  buffer  for  damage,  excess  oil  loss 
and  determine  that  the  plunger  returns  to  full  extended 
position  in  90  s 

(c)  examine  the  car  (including  car  interior)  for 
damage 

(d)  restore  the  final  terminal  stopping  device  to 
the  proper  position  and  test  it  as  outlined  in  Item  5.4 

(e)  remove  any  tie-down  that  was  wrapped  on 
the  car  or  counterweight  lift  lever 

(f)  have  the  required  test  tags  installed 

(3)  For  counterweight  buffer,  remove  the  rated  load 
from  the  car  and  test  the  counterweight  buffer  as  out- 
lined for  car  buffers. 

NOTE:  This  test  is  not  required  where  Type  C  safeties  are  used. 
However,  where  Type  C  safeties  are  applied,  check  the  buffer  por- 
tion of  Type  C  safeties  to  determine  that  the  oil  level  is  within 
allowable  limits.  Also,  test  the  buffer  compression  switch  and  the 
oil  level  device  for  proper  functioning. 


77 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers.  X| 

No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME.       ^s 


ASME  A17.2-2010 


5.9.3  Acceptance 

5.9.3.1  Electric  Elevators.  Compare  the  data  on  the 
buffer  marking  plate  with  the  data  on  the  elevator  layout 
drawings  and  the  actual  installed  conditions  of  the  ele- 
vator and  verify  that  it  meets  Code  requirements,  espe- 
cially for  load  rating,  stroke,  and  speed,  or  number  of 
springs. 

5.9.4  References 

(10)  5.9.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  — Section 201  and  Rules  109.1, 210.2(w),  1002.3f, 
1003.2e,  1206.1f,  and  1308.2. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.22  and  2.6,  2.26.2.22,  8.11.2.3.6, 
8.10.2.2.5(c),  c8.10.2.2.5(c)(6),  8.6.1.6.3,  c8.6.12,2.6,  8.2.3, 
and  8.3.1.3. 

A17.3  —  Section  3.1  and  para.  3.10.4(m). 


ITEM  5.10 

COMPENSATING  CHAINS,  ROPES, 

AND  SHEAVES 

5.10.1  Periodic  Inspections 

5.10.1.1  Electric  Elevators.  Where  compensating 
ropes  or  chains  are  used,  determine  that 

(a)  there  is  sufficient  remaining  travel  of  the  sheave 
frame  to  maintain  tension  in  the  compensating  ropes 
and  to  operate  the  compensating  sheave  switch.  Ropes 
should  have  sufficient  tension  to  remain  within  the 
sheave  grooves. 

(b)  the  sheave  frame  moves  freely  in  the  guides  while 
the  car  is  in  motion. 

(c)  there  is  no  evidence  of  excessive  wear  of  the 
sheave,  shaft,  or  bearings  and  all  parts  are  lubricated. 

(d)  the  car  stops  when  the  switch  or  switches  operated 
by  the  compensating  sheave  frame  are  opened.  Manu- 
ally open  these  switches  while  the  car  is  in  motion  at 
lowest  operating  speed. 

(e)  the  ropes  or  chains  are  properly  hung  and  securely 
fastened  to  the  underside  of  car  and  counterweight  (see 
Items  3.22,  3.23,  3,28,  and  3.34). 

(f)  inspect  the  portion  of  the  compensating  chains  or 
ropes  and  their  fastenings  that  could  not  be  inspected 
from  the  car  top.  Where  chains  are  used,  examine  for 
wear  at  mating  links. 

(g)  if  a  tie-down  is  provided  for  holding  the  compen- 
sating-rope  sheave  during  the  operation  of  the  safety  or 
buffer,  it  should  be  visually  examined  for  condition  and 
damage. 

(h)  check  the  compensating  sheave  switch.  Check  the 
compensating  rope  tie-down,  which  was  required  for 
speeds  exceeding  800  ft/min  (4.06  m/s)  in  A17.1d-1970, 
and  700  ft/min  (3.56  m/s)  in  A17.1-1971  to  the  present. 


5.10.2  Periodic  Test 

5.10.3  Acceptance 

5.10.3.1  Electric  Elevators.  Check  the  compensating 
rope  tie-down  if  the  rated  speed  is  greater  than 
700  ft/min  (3.56  m/s). 

5.10.4  References 

5.10.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions)  —  Rules  202.4,  205.17,  210.2c,  and  1001.2(e)(8). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.21.4,  2.17.17,  2.26.2.3,  and  8.11.2.1.5(h). 

NOTE:     Items  5.11  through  5.14  apply  to  hydraulic  elevators  only. 

ITEM  5.11 
PLUNGER  AND  CYLINDER 

5.11.1  Periodic  Inspections 

5.11.1.2  Hydraulic  Elevators.  Examine  the  plunger 
for  pitting,  scoring,  or  corrosion  that  may  cause  excess 
leakage  and  create  a  safety  hazard.  Check  that  the  means 
to  collect  leakage  is  in  compliance  with  the  Code  and 
properly  maintained. 

Examine  the  plunger  fastening  to  the  car  frame  to 
verify  that  it  is  secure  and  adequately  fastened  to  the  car. 

5.11.2  Periodic  Test 

5.11.3  Acceptance 

5.11.4  References 

5.11.4.2  Hydraulic  Elevators.  A 1 7. ld-2000  and  ear- 
lier editions  —  Section  302  and  Rules  1004.2(e)(3)  and 
1206.5b. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  3.18,  8.11.3.1.5(c),  8.6.5.1,  8.6.5.2,  8.6.5.5, 
and  8.6.5.6. 

A17.3  —  Paragraphs  4.3.1  and  4.3.2. 

ITEM  5.12 
CAR  BUFFER 

5.12.1  Periodic  Inspections 

5.12.1.1  Hydraulic  Elevators 

(a)  Spring  Buffers.  Check  car  spring  buffers  to  verify 
that 

(1)  they  and  their  supports  are  securely  fastened 
in  place. 

(2)  they  are  vertical  and  in  alignment  with  striker 
plates  on  the  car. 

(3)  springs  are  properly  seated  in  the  cup  or  other 
mounting  provided. 

(4)  springs  have  not  been  deformed,  obviously 
weakened,  or  damaged. 

(5)  the  buffer  marking  plate  is  in  place  and  contains 
all  of  the  required  information.  A17.1d-1986  and  later 


(10) 


78 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


editions  require  that  the  number  of  springs  be  indicated 
on  the  marking  plate  in  addition  to  the  other  data. 

(6)  removable  springs  are  identified  and  that  the 
marking  plate  indicates  the  identification. 

(b)  Oil  Buffers.  When  they  are  used  refer  to  Item  5.3 
for  the  required  inspection  and  test. 

(c)  Solid  Bumpers.  Prior  to  the  A17.1-1978  edition 
solid  bumpers  were  allowed  on  passenger  elevators  with 
rated  speed  not  exceeding  50  ft/min  (0.25  m/s)  and 
freight  elevators  with  rated  speed  not  exceeding 
75  ft/min  (0.38  m/s).  A17.1-1978  did  not  allow  the  use 
of  solid  bumpers  (except  with  Type  C  safeties). 
A17.1a-1982  and  later  editions  allow  solid  bumpers  on 
hydraulic  elevators  that  have  an  operating  speed  in  the 
down  direction  of  less  than  50  ft/min  (0.25  m/s).  Check 
solid  bumpers  to  verify  that 

(1)  they  and  their  supports  are  securely  fastened 
in  place 

(2)  no  damage  or  deterioration  exists 

(3)  they  are  vertical  and  in  alignment  with  the 
striker  plates  of  the  car 

(4)  removable  springs  are  identified  and  that  the 
marking  plate  indicates  the  identification 

5.12.2  Periodic  Test 

5.12.3  Acceptance 

5.12.3.2  Hydraulic  Elevators.  Compare  the  data  on 
the  buffer  marking  plate  with  the  data  on  the  elevator 
layout  drawings  and  the  actual  installed  conditions  of 
the  elevator  and  verify  that  it  meets  Code  requirements, 
especially  for  load  rating,  stroke,  and  speed,  or  number 
of  springs. 

5.12.4  References 

5.12.4.2  Hydraulic  Elevators.  A 1 7. ld-2000  and  ear- 
lier editions  —  Rules  301.3,  306.4,  1004.2(e)(4),  1206.1e, 
and  1308.2. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  3.22.1,  3.26.4,  8.11.3.1.5(d),  8.6.4.4,  and 
8.2.3.2. 

A17.3  —  Paragraph  4.2.1. 


ITEM  5.13 
GUIDING  MEMBERS 

5.13.1  Periodic  Inspections 

5.13.1.2  Hydraulic  Elevators.  Examine  the  car  guid- 
ing members  and  their  fastenings  to  verify  that  they  are 
properly  secured,  aligned,  and  adjusted,  and  that  they 
are  not  worn  excessively.  Examine  for  wear  and  proper 
lubrication.  See  also  Item  3.18. 

5.13.2  Periodic  Test 

5.13.3  Acceptance 


5.13.4  References 

5.13.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Section  308;  and  Rules  301.1, 1004.2(e)(8), 
and  1206.1d. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  3.28,  3.23,  8.11.3.1.5(h),  and  8.6.4.3. 

ITEM  5.14 
SUPPLY  PIPING 

5.14.1  Periodic  Inspections 

5.14.1.2  Hydraulic  Elevators.  Inspect  supply  piping 
as  described  in  Item  2.18,  giving  special  attention  to 
fitting  and  condition  of  piping.  Piping  supports  are  very 
important  in  pits  since  the  pipe  is  subject  to  being 
stepped  on.  This  can  cause  leaks  and  damage  to  connec- 
tions. If  a  shutoff  valve  is  in  the  pit,  verify  that  it  is  in 
good  condition  and  has  an  adequate  pressure  rating 
since  failure  of  a  pit  valve  could  create  a  very  hazardous 
condition. 

5.14.2  Periodic  Test 

5.14.3  Acceptance 

5.14.3.2  Hydraulic  Elevators.  Inspect  as  outlined  in 
Item  2.35.4. 

5.14.4  References 

5.14.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Section  208  and  Rules  1004.2(e)(9)  and 
1006.2f. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.24,  8.11.3.1.5(0,  and  8.10.3.2.2(r). 

A17.3  —  Paragraph  4.4.4. 

ITEM  5.15 
OVERSPEED  VALVE 

5.15.1  Periodic  Inspections 

5.15.2  Category  5  Periodic  Test 

5.15.2.2  Hydraulic  Elevators:  Category  5  Test  for 
Al  7.1-2000  and  Later  Editions.  Demonstrate  that  the 
overspeed  valve,  when  supplied,  will  stop  the  car  run- 
ning in  the  down  direction  with  rated  load  in  accordance 
with  the  written  procedure  provided  by  the  valve  manu- 
facturer or  the  person  or  firm  maintaining  the  equip- 
ment. Verify  that  the  valve  is  sealed. 

5.15.3  Acceptance 

5.15.3.2  Hydraulic  Elevators 

(a)  Verify  that  the  overspeed  valve,  if  provided,  is 
properly  marked.  Witness  the  testing  of  the  overspeed 
valve  to  ensure  proper  operation.  For  single  jack 
arrangements,  verify  that  the  valve  is  located  in  the 
pressure  piping  within  12  in.  (300  mm)  of  the  hydraulic 


(10) 


79 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


jack.  If  multiple  valves  are  used,  verify  that  they  are 
located  so  as  to  minimize  the  distance  from  the  valves 
to  the  hydraulic  jack.  For  multiple  jack  arrangements, 
verify  that  one  of  the  following  installations  is  used. 

(1)  Verify  that  an  overspeed  valve  is  located  in  the 
pressure  piping  on  the  hydraulic  machine  side  of,  and 
immediately  before,  the  tee  junction,  wye  junction,  or 
branch  junction  that  connects  the  branch  pressure  pipes 
to  the  jacks. 

(2)  Verify  that  for  dual  hydraulic  jack  systems,  the 
total  length  of  branch  pressure  pipe  between  the  tee  or 
wye  junction  and  the  jacks  does  not  exceed  the  distance 
between  the  jacks,  measured  horizontally,  plus  39  in. 
(1  m).  In  these  multiple  jack  systems,  the  length  of  the 
branch  pressure  piping  shall  be  minimized. 

(3)  If  the  elevator  is  equipped  with  a  plunger  grip- 
per,  review  its  marking  plate  and  verify  application  for 
the  application. 

(b)  Verify  that  pipe  supports  are  provided  near 
changes  in  pipe  direction  and  particularly  near  valves 
and  joints.  Verify  that  horizontal  spans  are  supported 
at  intervals  per  Table  8.4.11.3. 

5.15.4  References 

5.15.4.2  Hydraulic  Elevators.  A17.1d -2000  and  ear- 
lier editions  —  Rules  303.3c(l)(d)  (Line  Rupture  Valve) 
and  2410.6  (Safety  Valve),  and  (NR  3.19.4.7.2), 
(NR  3.19.4.7.3),  [NR  3.19.4.7.5(a)],  (NR  3.19.4.7.6), 
[NR  8.10.3.2.5(i)]  and  (NR  8.11.3.4.4). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  3.19.3.3  and  8.4.11.2  and  3.19.4.7.2, 
3.19.4.7.3,  3.19.4.7.5(a),  3.19.4.7.6,  8.10.3.2.5(1),  and 
8.11.3.4.4. 

(io)  ITEM  5.16 

EARTHQUAKE  INSPECTION  AND  TESTS  (SEISMIC 
RISK  ZONE  2  OR  GREATER) 

5.16.1  Periodic  Inspections 

(a)  Verify  that  rope  retainers  or  rope  restraints  are  in 
place  on  governor  tension  sheaves  located  in  the  pit. 

(b)  Verify  that  the  snag  guards,  where  required,  that 
cannot  be  observed  from  the  top  of  car,  are  in  place. 

(c)  Observe  the  part  of  the  car  and  counterweight  rail 
system  that  cannot  be  seen  from  the  top  of  car. 

5.16.1.1  Electric  Elevators 

(a)  Verify  that  all  rope  retainer  guards  or  rope 
restraints  are  in  place  on  compensating  sheaves. 

(b)  Verify  that  the  means  to  prevent  the  tension  sheave 
assembly,  used  with  compensating  ropes,  from  being 
dislocated  from  its  normal  operation  position  is 
provided. 

5.16.1.2  Hydraulic  Elevators 

(a)  For  elevators  not  equipped  with  car  safeties,  verify 
that  they  are  equipped  with  either  an  overspeed  valve 


or  plunger  gripper  and  that  they  have  been  tested  and 
sealed. 

(b)  Verify  that  the  pipe  supports  are  in  place. 

5.16.2  Periodic  Test 

For  seismic  risk  zones,  test  the  overspeed  valve 
(Requirement  8.11.3.4.5). 

5.16.3  Acceptance 

(a)  Verify  that  rope  retainers  on  governor  tension 
sheaves  located  in  the  pit  are  continuous  over  not  less 
than  %  of  the  arc  of  contact  between  the  rope  and  its 
sheave  or  drum  and  located  so  not  more  than  \  of  the 
arc  of  contact  is  exposed.  Rope  restraints  may  be  used, 
and  if  they  are  used,  there  must  be  one  for  each  30  deg 
or  less  of  arc  contact. 

(b)  Verify  that  snag  guards  are  provided  for  snag 
points  created  by  rail  brackets,  rail  clip  bolts,  fishplates, 
vanes,  and  similar  devices,  where 

(1)  governor  ropes  are  located  20  in.  (500  mm)  or 
less  from  a  snag  point 

(2)  the  loop  of  traveling  cables  below  the  mid-point 
of  the  elevator  travel  is  located  36  in.  (915  mm)  or  less 
horizontally  from  a  snag  point 

(c)  Verify  that  the  rail  system  that  cannot  be  observed 
from  the  top  of  car  is  installed  per  design,  recording 
bracket  spacing. 

(d)  Verify  that  the  proper  information  is  contained  on 
the  elevator  layout  drawings. 

5.16.3.1  Electric  Elevators 

(a)  Verify  that  rope  retainers  on  compensating 
sheaves  are  continuous  over  not  less  than  %  of  the  arc 
of  contact  between  the  rope  and  its  sheave  or  drum  and 
located  so  not  more  than  V6  of  the  arc  of  contact  is 
exposed.  Rope  restraints  may  be  used,  and  if  they  are 
used,  there  must  be  one  for  each  30  deg  or  less  of  arc 
contact. 

(b)  Verify  that  snag  guards  are  provided  for  snag 
points  created  by  rail  brackets,  rail  clip  bolts,  fishplates, 
vanes,  and  similar  devices,  where  the  loop  of  compensat- 
ing chains  below  the  midpoint  of  the  elevator  travel  is 
within  36  in.  (915  mm)  of  a  snag  point. 

5.16.4  References 

5.16.4.1  Electric  Elevators.  A17.1-1993  through 
A17.1d-2000  editions  —  Rules  2400,  2407,  and  2403. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  8.4.3,  8.4.6,  and  8.4.8. 

5.16.4.2  Hydraulic  Elevators.  A17.1-1993  through 
A17.1d-2000  and  earlier  editions  —  Rules  2400,  2410.6, 
2410.5,  2410.2,  and  2410.3. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  8.4.3,  8.4.11.2,  8.4.11.3,  8.4.11.5,  and 
8.4.11.7. 


80 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


Part  6 
Elevator  —  Firefighters*  Service 


A17.1b-1973  and  later  editions  and  A17.3  require  ele- 
vators to  be  provided  with  firefighters'  service.  This  ser- 
vice was  referred  to  previously  as  operation  of  elevators 
under  fire  or  other  emergency  conditions. 

ITEM  6.1 

OPERATION  OF  ELEVATORS  UNDER  FIRE  AND 

OTHER  EMERGENCY  CONDITIONS 

(A17.1b»1973  THROUGH  Al7.1b-1980) 

6.1.1  Periodic  Inspections 

On  all  elevators  provided  with  firefighters'  service, 
check  that  the  monthly  operation  log  is  maintained. 

6.1.2  Periodic  Test:  Yearly  Test  (for  A17.1d-2000 
and  Earlier  Editions);  Category  1  Test  (for 
A17.1-2000/B44-00  and  Later  Editions) 

(a)  General 

(1)  All  automatic  operating  elevators  serving  three 
or  more  landings  or  having  a  travel  of  25  ft  (7.62  m)  or 
more  are  required  to  return  to  the  main  floor,  which  is 
the  floor  providing  egress  from  the  building,  or  elevators 
without  a  landing  at  the  main  floor  are  required  to  return 
to  the  landing  closest  to  the  main  floor  or  other  approved 
landing.  This  is  commonly  referred  to  as  Phase  I 
Emergency  Recall  Operation. 

(2)  All  automatic  operating  elevators  having  a 
travel  of  70  ft  (21 .33  m)  or  more  above  the  lowest  grade 
elevation  surrounding  the  building  are  required  to  have 
provisions  to  allow  firefighters  or  other  authorized  per- 
sonnel to  operate  the  elevator  on  emergency  in-car  oper- 
ation. This  is  commonly  referred  to  as  Phase  II 
Emergency  In-Car  Operation. 

(b)  Phase  I  Emergency  Recall  Operation:  Automatic 
Elevators 

(1)  A  three-position  ("ON/7  "OFF,"  and  "BYPASS") 
key-operated  switch  must  be  provided  at  the  main  floor. 
When  the  main  floor  three-position  key-operated  switch 
is  turned  to  the  "ON"  position,  all  cars  must  return  to 
the  main  floor  and  park  with  the  doors  open.  Elevators 
without  a  landing  at  the  main  floor  must  return  to  the 
landing  closest  to  the  main  floor  or  other  approved 
landing. 

(2)  The  key  is  only  permitted  to  be  removable  in 
the  "ON"  or  ''OFF"  position. 

NOTE:     In  order  to  cause  as  little  inconvenience  as  possible  with 
multiple  elevator  systems,  it  is  suggested  that  the  elevators  be  put 


back  in  service  immediately  and  one  elevator  at  a  time  be  isolated 
for  individual  testing. 

(3)  With  the  main  floor  key-operated  switch  in  the 
"OFF"  position  and  the  car  at  the  main  floor,  register 
several  calls.  With  the  inspector  in  the  car,  allow  the  car 
to  run.  As  the  car  leaves  the  floor,  have  the  main  floor 
key  switch  turned  to  the  "ON"  position.  The  car  must 
stop  and  reverse  at  or  below  the  next  available  floor 
without  opening  the  door(s)  and  return  to  the  main  floor 
where  it  is  required  to  park  with  the  door(s)  open.  As 
the  car  descends,  operate  the  emergency  stop  switch  to 
see  that  it  has  been  rendered  inoperative.  Check  that 
the  car  buttons  have  been  rendered  inoperative  and  that 
the  car  will  not  respond  to  any  car  calls.  Also,  determine 
that  all  call-registered  lights  and  lanterns  are  extin- 
guished and  remain  inoperative. 

(4)  With  the  main  floor  key-operated  switch  in  the 
"OFF"  position,  run  the  car  to  any  floor.  Then  with  the 
doors  open,  have  the  main  floor  key-operated  switch 
turned  to  the  "ON"  position.  Check  to  see  that  the  door 
reopening  devices  for  power-operated  doors  which  are 
sensitive  to  smoke,  heat,  or  flame  are  rendered  inopera- 
tive. Check  to  see  that  the  mechanical  safety  edge  is  still 
operative.  With  the  doors  open,  actuate  the  emergency 
stop  switch  to  see  that  it  is  operative.  The  doors  may 
or  may  not  close  but  the  car  must  not  move. 

(5)  Return  the  emergency  stop  switch  to  the  "RUN" 
position.  The  automatic  power-operated  doors  should 
close  without  delay  and  the  car  proceed  to  the  main 
floor  and  park  with  the  doors  open. 

(6)  Check  all  call  buttons  to  see  that  they  are  inoper- 
ative and  call-registered  lights  and  directional  lanterns 
are  extinguished  when  the  main  floor  key-operated 
switch  is  in  the  "ON"  position. 

(7)  Check  to  see  that  no  stop  switches  other  than 
those  inside  the  car  (i.e.,  pit,  car  top,  etc.)  and  no  safety 
circuits  other  than  the  door  reopening  devices  which 
are  sensitive  to  smoke,  heat,  or  flame,  as  previously 
mentioned,  are  rendered  inoperative  when  the  main 
floor  key-operated  switch  is  in  the  "ON"  position. 

(S)  With  the  main  floor  key-operated  switch  in  the 
"OFF"  position,  activate  the  sensing  device.  A  sensing 
device  is  required  to  be  located  in  every  elevator  lobby 
except  the  main  floor  lobby,  which  when  activated,  will 
perform  the  same  functions  as  previously  described 
when  the  main  floor  key-operated  switch  is  in  the  "ON" 
position.  Sensing  devices  must  be  of  the  manually  reset- 
ting type. 


81 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers.  X^  . 

No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME.     ^ 


ASME  A17.2-2010 


NOTES: 

(1)  If  the  sensing  system  is  connected  to  a  central  fire  alarm  system, 
notify  proper  authorities  before  activating. 

(2)  Sensing  devices  can  be  activated  by  using  a  test  button  if 
supplied,  or  by  simulating  smoke  or  heat  and  smoke  condi- 
tions. Manufacturer's  recommended  test  procedures  should  be 
followed.  Use  of  chemical  smoke  may  oversensitize  smoke 
detectors. 

(9)  With  the  smoke  sensor  activated,  turn  the  main 
floor  key-operated  switch  to  the  "BYPASS"  position.  The 
elevator  must  return  to  normal  service. 

(c)  Phase  I  Emergency  Recall  Operation:  Attendant- 
Operated  Elevators.  Elevators  operable  only  by  a  desig- 
nated attendant  in  the  car  must  be  provided  with  both 
visual  and  audible  signals. 

(d)  Phase  I  and  Phase  II  Automatic  Operating  Elevators 
With  Dual  Operation.  Elevators  arranged  for  dual  opera- 
tion must,  when  on  automatic  operation,  conform  to 
Items  6.1.2(b)  and  (e),  and  when  on  attendant  operation, 
conform  to  Item  6.1.2(c). 

(e)  Phase  II  In-Car  Emergency  Operation.  Where  Phase 
II  operation  is  required,  a  three-position  key-operated 
switch  must  be  provided  in  or  adjacent  to  the  operating 
panel  in  each  car.  A17.1b-1973  through  A17.1f-1975 
required  a  three-position  ("OFF,"  "ON,"  and  "BYPASS") 
key-operated  switch,  the  third  position  being  used  to 
bypass  the  interlocks.  A17.1g-1976  removed  the  require- 
ment for  "BYPASS"  position.  The  key  must  be  removable 
in  the  "OFF"  position  only.  With  Phase  I  Service  acti- 
vated, turn  the  in-car  key-operated  switch  to  the  "ON" 
position. 

NOTE:  The  inspector  is  cautioned  to  check  the  position  of  the 
various  key  switches  relative  to  the  installation  date  of  the  elevator 
to  be  tested. 

(1)  Check  that  the  elevator  is  operable  only  by  the 
car  buttons  and  does  not  respond  to  corridor  calls. 

(2)  Check  that  the  doors  will  not  open  automati- 
cally at  any  floor  except  the  main  floor. 

(3)  Check  that  the  opening  of  the  door  is  controlled 
by  a  continuous  pressure  button  or  switch  and  that  when 
the  button  or  switch  is  released  prior  to  the  door  reaching 
its  fully  open  position,  the  door  will  automatically 
reclose. 

(4)  Check  that  fully  opened  doors  can  be  closed 
only  by  registering  a  car  call  or  by  the  use  of  an  in-car 
door  close  button  or  switch. 

(5)  Check  to  see  that  Phase  II  operation  once  acti- 
vated cannot  be  deactivated  until  the  car  has  returned 
to  the  main  floor.  To  do  this,  with  the  main  floor 
key-operated  switch  in  the  "ON"  position,  take  the  car 
to  any  floor.  Then  turn  the  main  floor  key-operated 
switch  to  the  "OFF"  position,  or  if  a  smoke  detector  is 
activated,  to  the  "BYPASS"  position,  and  make  sure  the 
Phase  II  operation  is  maintained  until  the  car  is  returned 
to  the  main  floor. 


(6)  Turn  the  main  floor  key-operated  switch  to  the 
"OFF"  position  or,  if  a  smoke  detector  is  activated,  to 
the  "BYPASS"  position.  Take  the  elevator  to  a  floor  above 
the  main  floor  and  turn  the  in-car  key-operated  switch 
to  the  "ON"  position.  Check  to  see  that  the  Phase  II 
operation  does  not  operate  unless  the  main  floor 
key-operated  switch  is  in  the  "ON"  position  or  a  smoke 
detector  has  been  activated. 

(f)  Multideck  Elevators.  Multideck  elevators  should  be 
inpsected  as  outlined  in  Items  6.1.2(b)  through  (e)  as 
well  as  the  following: 

(1)  The  main  floor  key-operated  switch  for  Phase  I 
operation  may  be  at  either  of  the  main  floors. 

(2)  The  in-car  key-operated  switch  for  Phase  II 
operation  must  be  located  in  the  top  deck.  Check  the 
operation  of  the  in-car  key-operated  switch.  The  lower 
deck  must  be  rendered  out  of  service  before  the  Phase  II 
can  be  effective.  Means  for  placing  lower  deck  out  of 
service  must  be  located  in  that  deck  or  adjacent  to  the 
entrance  in  the  corridor. 

(g)  Operating  Instructions  and  Keys 

(1)  Operating  instructions  for  Phase  I  and  Phase  II 
service  must  be  posted  adjacent  to  the  main  floor 
key-operated  switch.  Instructions  must  be  in  letters  not 
less  than  V4  in.  (6.4  mm)  in  height,  be  permanently 
installed,  and  protected  against  removal  and 
defacement. 

(2)  All  switches  must  be  keyed  alike  for  Phase  I 
and  Phase  II  operation  and  not  be  a  part  of  building 
master  key  system.  Keys  must  be  kept  on  premises  for 
the  main  floor  switch  plus  a  key  for  each  in-car 
key-operated  switch  in  a  location  readily  accessible  to 
authorized  persons  but  not  readily  available  to  the 
public. 

6.1.3  Acceptance 

6.1.4  References 

6.1.4.1  Electric  Elevators.    A17.1b-1973  through 
A17.1b-1980  —  Rule  211.3. 

A17.1d-2000  and  earlier  editions  —  Rules  112.3d, 
112.5,  1001.2(d)(12),  1002.2f,  and  1206.7. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.13.3.4, 2.13.5,  8.11.2.1.4(1),  8.11.2.2.6,  and 
8.6.10.1. 

6.1.4.2  Hydraulic  Elevators.    A17.1b-1973  through 
A17.1b-1980  —  Rule  211.3. 

A17.1d-2000  and  earlier  editions  —  Rules  112.3d  and 

112.5  (306.11);  and  1001.2(d)(12),  1002.2f,  1004.2(d)(12), 
and  1206.7. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.13.3.4  and  2.13.5  {3.27};  and  8.11.2.1.4(1), 
8.11.2.2.6,  [NR  1004.2(d)(12)],  and  8.6.10.1. 


82 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


ITEM  6.2 

OPERATION  OF  ELEVATORS  UNDER  FIRE  AND 

OTHER  EMERGENCY  CONDITIONS  (A17.1-1981 

THROUGH  A17.1b-1983) 

6.2.1  Periodic  Inspections 

On  all  elevators  provided  with  firefighters'  service, 
check  that  the  monthly  operation  log  is  maintained. 

6.2.2  Periodic  Test:  Yearly  Test  (for  A17.1d-2000 
and  Earlier  Editions);  Category  1  Test  (for 
A17.1-2000/B44-00  and  Later  Editions) 

(a)  General 

(1)  All  automatic  operating  elevators  serving  three 
or  more  landings  or  having  a  travel  of  25  ft  (7.62  m)  or 
more  will  return  to  the  main  floor,  which  is  the  floor 
providing  egress  from  the  building,  or  elevators  without 
a  landing  at  the  main  floor  must  return  to  the  landing 
closest  to  the  main  floor  or  other  approved  landing.  This 
is  commonly  referred  to  as  Phase  I  Emergency  Recall 
Operation. 

(2)  All  automatic  operating  elevators  having 
Phase  I  must  have  provisions  to  allow  firefighters  or 
other  authorized  personnel  to  operate  the  elevator  on 
emergency  in-car  operation.  This  is  commonly  referred 
to  as  Phase  II  Emergency  In-Car  Operation. 

(b)  Phase  I  Emergency  Recall  Operation:  Automatic 
Elevators 

(1)  A  three-position  ("ON,"  "OFF/'  and  "BYPASS") 
key-operated  switch  must  be  provided  at  the  designated 
level.  When  the  designated  level  three-position 
key-operated  switch  is  turned  to  the  "ON"  position,  all 
cars  are  required  to  return  nonstop  to  the  designated 
level  and  park  with  the  doors  open. 

(2)  The  keys  are  only  permitted  to  be  removable  in 
the  "ON"  and  "OFF"  positions. 

NOTE:  In  order  to  cause  as  little  inconvenience  as  possible  with 
multiple  elevator  systems,  it  is  suggested  that  the  elevators  be  put 
back  in  service  immediately  and  one  elevator  at  a  time  be  isolated 
for  individual  testing. 

(3)  With  the  designated  level  key-operated  switch 
in  the  "OFF"  position  and  the  car  at  the  main  floor, 
register  several  calls.  With  the  inspector  in  the  car,  allow 
the  car  to  run.  As  the  car  leaves  the  floor,  have  the 
designated  level  key-operated  switch  turned  to  the 
"ON"  position.  The  car  should  stop  and  reverse  at  or 
below  the  next  available  floor  without  opening  the 
door(s)  and  return  to  the  designated  level  and  park 
with  the  door(s)  open.  As  the  car  descends,  operate  the 
emergency  stop  switch  to  see  that  it  has  been  rendered 
inoperative.  Check  that  the  car  buttons  have  been  ren- 
dered inoperative  and  that  the  car  will  not  respond  to 
any  car  calls.  Also,  determine  that  all  call-registered 
lights  and  in-car  lanterns  are  extinguished  and  remain 
inoperative. 


(4)  With  the  main  floor  key-operated  switch  in  the 
"OFF"  position,  run  the  car  to  any  floor.  Then  with  the 
doors  open,  have  the  main  floor  key-operated  switch 
turned  to  the  "ON"  position.  Check  to  see  that  the  door 
reopening  devices  for  power-operated  doors  that  are 
sensitive  to  smoke,  heat,  or  flame  are  rendered  inopera- 
tive. Check  to  see  that  the  mechanical  safety  edge  and 
door  operating  buttons  are  still  operative.  With  the  doors 
open,  actuate  the  emergency  stop  switch  to  see  that  it 
is  operative.  The  doors  may  or  may  not  close  but  the 
car  must  not  move. 

(5)  Return  the  emergency  stop  switch  to  the  "RUN" 
position.  The  automatic  power-operated  doors  must 
close  without  delay  and  the  car  proceed  to  the  main 
floor  and  park  with  the  doors  open.  If  the  elevator  is 
equipped  with  vertically  sliding  doors  with  automatic 
or  momentary  pressure  closing,  the  closing  sequence 
should  initiate  and  the  car  proceed  to  the  designated 
level.  If  the  elevator  is  equipped  with  manual  doors  or 
power-operated  continuous  pressure  closing,  the  visual 
and  audible  signals  should  operate  and  when  the  doors 
close,  the  car  should  return  to  the  designated  level. 

(6)  Check  all  call  buttons  to  see  that  they  are  inoper- 
ative and  call-registered  lights  and  directional  lanterns 
are  extinguished  when  the  designated  level 
key-operated  switch  is  in  the  "ON"  position. 

(7)  Check  to  see  that  no  stop  switches  other  than 
those  inside  the  car  (i.e.,  pit,  car  top,  etc.)  and  no  safety 
circuits  other  than  the  door  reopening  devices  that  are 
sensitive  to  smoke,  heat,  or  flame,  as  previously  men- 
tioned, are  rendered  inoperative  when  the  main  floor 
key-operated  switch  is  in  the  "ON"  position. 

(8)  Check  that  the  visual  and  audible  signal  device 
is  activated. 

(9)  With  the  main  floor  key-operated  switch  in  the 
"OFF"  position,  activate  the  smoke  detector.  A  smoke 
detector  is  required  to  be  located  in  every  elevator  lobby 
including  designated  level,  and  associated  machine 
room,  which,  when  activated,  performs  the  same  func- 
tions as  previously  described  when  the  designated  level 
key-operated  switch  is  in  the  "ON"  position.  If  the 
smoke  detector  at  the  designated  level  is  activated,  the 
elevators  must  return  to  an  alternate  level  designated 
by  the  enforcing  authority.  Smoke  detectors  must  not 
be  self-resetting. 

NOTES: 

(1)  If  the  sensing  system  is  connected  to  a  central  fire  alarm  system, 
notify  proper  authorities  before  activating. 

(2)  Smoke  detectors  can  be  activated  by  using  a  test  button  if 
supplied,  or  by  simulating  smoke  conditions.  Manufacturer's 
recommended  test  procedures  should  be  followed.  Use  of 
chemical  smoke  may  oversensitize  smoke  detectors. 

(10)  With  the  smoke  sensor  activated,  turn  the  des- 
ignated level  key-operated  switch  to  the  "BYPASS"  posi- 
tion. The  elevator  must  return  to  normal  service. 


83 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


(11)  Check  to  see  that  there  are  no  other  devices 
other  than  the  Phase  I  switch(es)  or  smoke  detectors  in 
the  elevator  lobbies,  machine  room,  or  hoistway  that 
could  initiate  Phase  I  operation. 

(c)  Phase  I  Emergency  Recall  Operation:  Attendant.  Ele- 
vators operable  only  by  a  designated  attendant  in  the  car 
must  be  provided  with  both  visual  and  audible  signals. 

(d)  Phase  I  and  Phase  II  Automatic  Operating  Elevators 
With  Dual  Operation.  Elevators  arranged  for  dual  opera- 
tion must  when  on  automatic  operation,  conform  to 
Items  6.2.2(b)  and  (e),  and  when  on  attendant  operation, 
conform  to  Item  6.2.2(c). 

(e)  Phase  II  In-Car  Emergency  Operation.  Phase  II  oper- 
ation requires  that  a  two-position  ("OFF/'  "ON") 
key-operated  switch  be  provided  in  or  adjacent  to  the 
operating  panel  in  each  car.  The  key  must  be  removable 
in  the  "OFF"  position  only.  With  Phase  I  service  activated 
and  after  the  car  has  returned  to  the  designated  or  alter- 
nate level,  turn  the  in-car  key-operated  switch  to  the 
"ON"  position. 

(1)  Check  that  the  elevator  is  operable  only  by  the 
car  buttons  and  does  not  respond  to  corridor  calls. 

(2)  Check  that  all  corridor  call  buttons  and  direc- 
tional lanterns  are  inoperative. 

(3)  Check  that  the  opening  of  the  door  is  controlled 
by  a  continuous  pressure  button  or  switch  and  that  when 
the  button  or  switch  is  released  prior  to  the  door  reaching 
its  fully  open  position,  the  door  will  automatically 
reclose. 

(4)  Check  that  fully  opened  doors  can  be  closed 
only  by  registering  a  car  call  or  by  the  use  of  an  in-car 
door  close  button  or  switch. 

(5)  Check  to  see  that  door  reopening  devices  sensi- 
tive to  smoke  or  flame  are  inoperative. 

(6)  Check  to  see  that  means  provided  to  cancel  car 
calls  is  operative  by  registering  calls  and  cancelling 
them. 

(7)  Check  to  see  that  Phase  II  operation  once  acti- 
vated cannot  be  deactivated  until  the  car  has  returned 
to  the  designated  or  alternate  level.  To  do  this,  with 
the  designated  level  key-operated  switch  in  the  "ON" 
position  and  the  in-car  key-operated  switch  in  the  "ON" 
position,  take  the  car  to  any  floor  except  the  designated 
floor.  Then  turn  the  designated  level  key-operated 
switch  to  the  "OFF"  position,  or  if  a  smoke  detector  is 
activated,  to  the  "BYPASS"  position,  and  make  sure  the 
Phase  II  operation  is  maintained  until  the  car  is  returned 
to  the  designated  or  alternate  level. 

(8)  Turn  the  designated  level  key-operated  switch 
to  the  "OFF"  position  or,  if  a  smoke  detector  is  activated, 
to  the  "BYPASS"  position.  Take  the  elevator  to  a  floor 
other  than  the  designated  level  and  turn  the  in-car 
key-operated  switch  to  the  "ON"  position.  Check  to  see 
that  the  Phase  II  operation  does  not  operate  even  if  the 
designated  key-operated  switch  is  turned  to  the  "ON" 
position  or  a  smoke  detector  has  been  activated. 


(f)  Multideck  Elevators.  Multideck  elevators  should  be 
inspected  as  outlined  in  Items  6.2.2(b)  through  (e)  as 
well  as  the  following: 

(1)  The  designated  level  key-operated  switch  for 
Phase  I  operation  must  be  at  the  designated  level  served 
by  the  upper  compartment. 

(2)  The  in-car  key-operated  switch  for  Phase  II 
operation  must  be  located  in  the  upper  compartment. 
Check  the  operation  of  the  in-car  key-operated  switch 
in  accordance  with  Item  6.2.2(e). 

(3)  Check  to  see  that  means  is  provided  for  locking 
the  lower  deck  out  of  service. 

(g)  Operating  Instructions  and  Keys 

(1)  Operating  instructions  for  Phase  I  service  must 
be  posted  adjacent  to  the  designated  level  key-operated 
switch.  Instructions  should  be  in  letters  not  less  than 
\  in.  (3.2  mm)  in  height,  be  permanently  installed,  and 
protected  against  removal  and  defacement. 

(2)  All  switches  must  be  keyed  alike  for  Phase  I 
and  Phase  II  operation  and  shall  not  be  a  part  of  building 
master  key  system.  Keys  should  be  kept  on  premises 
for  the  main  floor  switch  plus  a  key  for  each  in-car 
key-operated  switch  in  a  location  readily  accessible  to 
authorized  persons  but  not  readily  available  to  the 
public. 

(h)  Inspection  Operation.  Place  the  car  on  inspection 
operation  and  operate  from  top  of  car.  Check  that  an 
audible  signal  sounds  and  that  the  elevator  remains 
under  control  of  the  top-of-car  operating  device  when 
the  Phase  I  key  switch  is  in  the  "ON"  position  or  a 
smoke  detector  is  actuated. 

(i)  Firefighters'  Service  When  on  Standby  (Emergency 
Power).  Elevators  installed  under  A17.1b-1983  and  later 
editions  are  required  to  have  a  manual  selection  switch 
to  override  an  automatic  sequencing  of  standby  power. 
With  the  elevator  at  an  upper  floor,  switch  the  power 
to  the  elevators  to  standby  power  and  place  the  Phase  I 
key-operated  switch  in  the  "ON"  position.  Activate  the 
manual  selection  switch  to  select  a  car  other  than  that 
selected  by  the  automatic  sequencing.  If  the  manual 
selection  switch  is  key  operated,  it  must  use  the  same 
key  as  the  firefighters'  service  key. 

6.2.3  Acceptance 

6.2.4  References 

6.2.4.1  Electric  Elevators.  A17.1-1981  through 
A17.1b~1983  —  Rule  211.3. 

A17.1d-2000  and  earlier  editions  —  Rules  112.3d, 
112.5,  1001.2(d)(12),  1002.2f,  and  1206.7. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.13.3.4, 2.13.5, 8.11.2.1.4(1),  8.11.2.2.6,  and 
8.6.10.1. 

6.2.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions— Rules  112.3d,  112.5, 1001.2(d)(12),  1002.2f, 
and  1206.7. 


C 


84 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME, 


ASME  A17.2-2010 


A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.13.3.4,  2.13.5,  8.11.2.1.4(1),  8.11.2.2.6,  and 
8.6.10.1. 

ITEM  6.3 

FIREFIGHTERS*  SERVICE 

(A17.1-1984  THROUGH  A17.1a-1988  and  A17.3) 

6.3.1  Periodic  Inspections 

On  all  elevators  provided  with  firefighters'  service, 
check  that  the  monthly  operation  log  is  maintained. 

6.3.2  Periodic  Test:  Yearly  Test  (for  A17.1d-2000 
and  Earlier  Editions);  Category  1  Test  (for 
A17.1-2000/B44-00  and  Later  Editions) 

Elevators  required  to  comply  with  A17.3  must  comply 
with  A17.1-1987  or  later  editions. 

(a)  General  All  elevators  that  have  a  travel  of  25  ft 
(7.62  m)  or  more  above  or  below  the  designated  level 
(see  definition)  are  required  to  conform  to  Rules  211.3 
through  211.8. 

(b)  Phase  I  Emergency  Recall  Operation:  Automatic 
Elevators 

(1)  A  three-position  ("ON/7  "OFF/7  and  "BYPASS") 
key-operated  switch  must  be  provided  at  the  designated 
level.  When  the  designated  level  key-operated  switch 
is  turned  to  the  "ON"  position,  all  cars  must  return  to 
the  designated  level  and  park  with  the  doors  open. 

(2)  The  keys  are  only  permitted  to  be  removable  in 
the  "ON"  or  "OFF"  position. 

NOTE:  In  order  to  cause  as  little  inconvenience  as  possible  with 
multiple  elevator  systems,  it  is  suggested  that  the  elevators  be  put 
back  in  service  immediately,  and  one  elevator  at  a  time  be  isolated 
for  individual  testing. 

(3)  With  the  designated  level  key-operated  switch 
in  the  "OFF"  position  and  the  car  at  the  designated  level, 
register  several  calls.  With  the  inspector  in  the  car,  allow 
the  car  to  run.  As  the  car  leaves  the  floor,  have  someone 
turn  the  designated  level  key-operated  switch  to  the 
"ON"  position.  The  car  should  stop  and  reverse  at  or 
below  the  next  available  floor  without  opening  the 
doors(s)  and  return  to  the  designated  level  where  it 
should  park  with  the  door(s)  open.  As  the  car  descends, 
operate  the  emergency  stop  switch  to  see  that  it  has 
been  rendered  inoperative.  Check  that  the  car  buttons 
have  been  rendered  inoperative  and  that  the  car  will 
not  respond  to  any  car  calls.  Also,  determine  that  all 
call-registered  lights  and  in-car  lanterns  are  extin- 
guished and  remain  inoperative. 

(4)  With  the  designated  level  key-operated  switch 
in  the  "OFF"  position,  run  the  car  to  any  floor.  Then  with 
the  doors  open,  have  the  designated  level  key-operated 
switch  turned  to  the  "ON"  position.  Check  to  see  that 
the  door  reopening  devices  for  power-operated  doors, 
which  are  sensitive  to  smoke  or  flame,  are  rendered 
inoperative.  Check  to  see  that  the  mechanical  safety  edge 


and  "DOOR  OPEN"  buttons  are  still  operative  and  that 
door  closing  conforms  to  Rule  112.5.  With  the  doors 
open,  actuate  the  emergency  stop  switch  to  see  that  it 
is  operative.  The  doors  may  or  may  not  close  but  the 
car  must  not  move. 

(5)  Return  the  emergency  stop  switch  to  the  "RUN" 
position.  The  automatic  power-operated  doors  should 
close  without  delay  and  the  car  proceed  to  the  desig- 
nated level  and  park  with  the  doors  open.  If  the  elevator 
is  equipped  with  vertically  sliding  doors  with  automatic 
or  momentary  pressure  closing,  the  closing  sequence 
should  initiate  and  the  car  proceed  to  the  designated 
level.  If  the  elevator  is  equipped  with  manual  doors  or 
power-operated  continuous  pressure  closing,  the  visual 
and  audible  signals  required  by  Rule  211.3a(7)  must 
operate  and  when  the  doors  are  closed,  the  car  should 
return  to  the  designated  level. 

(6)  Check  all  call  buttons  to  see  that  they  are  inoper- 
ative and  call-registered  lights  and  directional  lanterns 
are  extinguished  when  the  designated  level 
key-operated  switch  is  in  the  "ON"  position. 

(7)  Check  to  see  that  no  stop  switches  other  than 
emergency  stop  switch  inside  the  car  (i.e.,  pit,  car  top, 
etc.)  and  no  safety  circuits  other  than  the  door  reopening 
devices,  which  are  sensitive  to  smoke  or  flame,  as  pre- 
viously mentioned,  are  rendered  inoperative  when  the 
designated  level  key-operated  switch  is  in  the  "ON" 
position. 

(8)  Check  that  the  visual  and  audible  signal  device 
is  activated. 

(9)  With  the  designated  level  key-operated  switch 
in  the  "OFF"  position,  activate  the  smoke  detector.  A 
smoke  detector  must  be  located  in  every  elevator  lobby, 
including  designated  level  and  associated  machine 
room,  which,  when  activated,  performs  the  same  func- 
tions as  previously  described  when  the  designated  level 
key-operated  switch  is  in  the  "ON"  position.  If  the 
smoke  detector  at  the  designated  level  is  activated,  the 
elevator  should  return  to  an  alternate  level  designated 
by  the  enforcing  authorities  unless  the  Phase  I  switch 
is  activated.  Smoke  detectors  must  not  be  self-resetting. 

NOTES: 

(1)  If  the  sensing  system  is  connected  to  a  central  fire  alarm  system, 
notify  proper  authorities  before  activating. 

(2)  See  Rule  211.3b  for  locations  when  sensing  devices  are  not 
required.  Smoke  detectors  can  be  activated  by  using  a  test 
button  if  supplied,  or  by  simulating  smoke  conditions.  Manu- 
facturer's recommended  test  procedures  should  be  followed. 
Use  of  chemical  smoke  may  oversensitize  smoke  detectors. 

(10)  With  the  smoke  detector  activated,  turn  the 
designated  level  key-operated  switch  to  the  "BYPASS" 
position.  The  elevator  must  return  to  normal  service. 

(c)  Phase  I  Emergency  Recall  Operation:  Attendant- 
Operated  Elevators.  Elevators  operable  only  by  a  desig- 
nated attendant  in  the  car  must  be  provided  with  both 
visual  and  audible  signals. 


85 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


(d)  Phase  I  and  Phase  II  Automatic  Operating  Elevators 
With  Dual  Operation.  Elevators  arranged  for  dual  opera- 
tion, except  hospital  service,  must,  when  on  automatic 
operation,  conform  to  Items  6.3.2(b)  and  (e),  and  when 
on  attendant  operation,  conform  to  Item  6.3.2(c).  The 
elevator  must  revert  to  automatic  operation  not  less  than 
15  s  nor  more  than  60  s  after  Phase  I  activation. 

(e)  Phase  II  In-Car  Emergency  Operation:  Automatic 
Elevators.  Phase  II  operation  requires  that  a  three- 
position  key-operated  switch  must  be  provided  in  or 
adjacent  to  the  operating  panel  in  each  car.  The  key  must 
be  removable  in  the  "OFF,"  "HOLD,"  or  "ON"  positions. 
With  Phase  I  service  activated  and  after  the  car  has 
returned  to  the  designated  or  alternate  level,  turn  the 
in-car  operated  switch  to  the  "ON"  position. 

(1)  Check  that  the  elevator  is  operable  only  by  the 
car  buttons  and  does  not  respond  to  corridor  calls. 

(2)  Check  that  all  corridor  call  buttons  and  direc- 
tional lanterns  are  inoperative. 

(3)  Check  that  the  opening  of  the  door  is  controlled 
by  a  continuous  pressure  button  or  switch  and  that  when 
the  button  or  switch  is  released  prior  to  the  door  reaching 
its  fully  open  position,  the  door  will  automatically 
reclose. 

(4)  Check  that  fully  opened  doors  can  be  closed 
only  by  continuous  pressure  on  a  door  close  button. 

(5)  Check  to  see  that  the  door  reopening  devices 
sensitive  to  smoke  or  flame  are  inoperative. 

(6)  Check  that  the  means  provided  to  cancel  car 
calls  is  operative  by  registering  calls  and  cancelling 
them.  All  elevators  installed  under  A17.1a-1985  or  later 
editions  require  a  separate  car  "CALL  CANCEL"  button. 

(7)  Check  to  see  that  Phase  II  operation  once  acti- 
vated cannot  be  deactivated  until  the  car  has  returned 
to  the  designated  or  alternate  level.  To  do  this,  with 
the  designated  level  key-operated  switch  in  the  "ON" 
position,  and  the  in-car  key-operated  switch  in  the  "ON" 
position,  take  the  car  to  any  floor  except  the  designated 
floor.  Then  turn  the  designated  level  key-operated 
switch  to  the  "OFF"  position,  or  if  a  smoke  detector  is 
activated,  to  the  "BYPASS"  position,  and  make  sure  the 
Phase  II  operation  is  maintained  until  the  car  is  returned 
to  the  designated  or  alternate  level. 

(8)  Turn  the  designated  level  key-operated  switch 
to  the  "OFF"  position  or,  if  a  smoke  detector  is  activated, 
to  the  "BYPASS"  position.  Take  the  elevator  to  a  floor 
other  than  the  designated  level  and  turn  the  in-car 
key-operated  switch  to  the  "ON"  position.  Check  to  see 
that  the  Phase  II  operation  does  not  operate  even  if  the 
designated  level  key-operated  switch  is  turned  to  the 
"ON"  position  or  a  smoke  detector  has  been  activated. 

(9)  Take  the  car  to  an  upper  floor  and  with  the  door 
closed,  turn  the  in-car  key-operated  switch  to  the  "OFF" 
and  "HOLD"  position.  It  should  have  no  effect  on  the 
Phase  II  operation. 


(10)  Take  the  car  to  an  upper  floor  and  with  the 
doors  open,  place  the  in-car  key-operated  switch  in  the 
"HOLD"  position.  The  car  should  remain  at  the  floor 
and  the  door  close  button  should  be  inoperative.  Take 
the  car  to  an  upper  floor,  and  with  the  doors  open,  place 
the  in-car  key-operated  switch  in  the  "OFF"  position. 
The  car  should  respond  as  specified  in  Item  6.3.2(e)(7) 
and  return  nonstop  to  the  designated  level. 

(f)  Multideck  Elevators.  Multideck  elevators  should  be 
inspected  as  outlined  in  Items  6.3.2(b)  through  (e)  in 
addition  to  the  following: 

(1)  The  designated  level  key-operated  switch  for 
Phase  I  operation  should  be  at  the  designated  level 
served  by  the  upper  compartment. 

(2)  The  in-car  key-operated  switch  for  Phase  II 
operation  must  be  located  in  the  upper  compartment. 
Check  the  operation  of  the  in-car  key-operated  switch 
in  accordance  with  Item  6.3.2(e). 

(3)  Check  to  see  that  means  is  provided  for  locking 
the  lower  deck  out  of  service. 

(g)  Operating  Instructions  and  Keys 

(1)  Operating  instructions  for  Phase  I  service 
should  be  posted  adjacent  to  the  designated  level 
key-operated  switch.  Instructions  for  operating  under 
Phase  II  operation  should  be  incorporated  with  or  adja- 
cent to  the  in-car  key-operated  switch.  Instructions 
should  be  in  letters  not  less  than  \  in.  (3,2  mm)  in  height, 
be  permanently  installed,  and  protected  against  removal 
and  defacement. 

(2)  All  switches  should  be  keyed  alike  for  Phase  I 
and  Phase  II  operation  and  not  be  a  part  of  building 
master  key  system.  Keys  should  be  kept  on  premises 
for  the  designated  level  switch  plus  a  key  for  each  in- 
car  key-operated  switch  in  a  location  readily  accessible 
to  authorized  persons  but  not  readily  available  to  the 
public. 

(h)  Inspection  Operation.  Place  the  car  on  inspection 
operation  and  operate  from  top  of  car.  Check  that  an 
audible  signal  sounds  and  that  the  elevator  remains 
under  control  of  the  top-of-car  operating  device  when 
the  Phase  I  key  switch  is  in  the  "ON"  position  or  a 
smoke  detector  is  actuated. 

(i)  Firefighters'  Service  When  on  Standby  (Emergency 
Power).  Elevators  are  required  to  have  a  manual  selec- 
tion switch  to  override  an  automatic  sequencing  of 
standby  power.  With  the  elevator  at  an  upper  floor, 
switch  the  power  to  the  elevators  to  standby  power 
and  place  the  Phase  I  key-operated  switch  in  the  "ON" 
position.  Activate  the  manual  selection  switch  to  select 
a  car  other  than  that  selected  by  the  automatic  sequenc- 
ing. If  the  manual  selection  switch  is  key  operated,  it 
must  use  the  same  key  as  the  firefighters'  service  key. 

6.3.3  Acceptance 

6.3.4  References 

6.3.4.1   Electric  Elevators.    A17.1-1984  through 
A17.1a-1988/  Rules  211.3  through  211.8. 


86 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


A17.1d-2000  and  earlier  editions  —  Rules  112.3d, 
112.5,  1001.2(d)(12)/  1002.2f,  and  1206.7. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.13.3.4,  2.13.5, 8.11.2.1.4(1),  8.11.2.2.6,  and 
8.6.10.1. 

A17.3  —  Paragraph  3.11.3. 

6.3.4.2  Hydraulic  Elevators.  A17.1-1984  through 
A17.1a-1988  —  Rules  211.3  through  211.8. 

A17.1d-2000  and  earlier  editions  —  Rules  112.3d, 
112.5,  1001.2(d)(12)/  1002.2f,  and  1206.7. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.13.3.4, 2.13.5,  8.11.2.1.4(1),  8.11.2.2.6,  and 
8.6.10.1. 

A17.3  —  Paragraph  3.11.3. 

ITEM  6.4 

FIREFIGHTERS*  SERVICE 

(A17.1b-1989  THROUGH  A17.1d-2000) 

6.4.1  Periodic  Inspections 

Check  that  the  monthly  operation  log  is  maintained. 

6.4.2  Periodic  Test:  Yearly  Test  (for  A17.1d-2000 
and  Earlier  Editions);  Category  1  Test  (for 
A17.1-2000/B44-00  and  Later  Editions) 

(a)  General  All  elevators  that  have  a  travel  of  25  ft 
(7.62  m)  or  more  are  required  to  conform  to  Rules  211.3 
through  211.8. 

(b)  Phase  I  Emergency  Recall  Operation:  Automatic 
Elevators.  A  three-position  ("ON,"  "OFF,"  and 
"BYPASS")  key-operated  switch  should  be  located  in 
the  elevator  lobby  in  site  of  the  elevator.  It  should  not 
be  behind  a  locked  door  or  cover.  An  additional  two- 
position  "OFF"  and  "ON"  key-operated  switch  may  be 
provided  at  any  location. 

(1)  When  the  designated  level  three-position  key- 
operated  switch  is  turned  to  the  "ON"  position,  all  cars 
should  return  to  the  designated  level  and  park  with  the 
doors  open.  For  elevators  installed  under  A17. 1-1993 
and  later  editions  with  two  entrances  at  the  designated 
level,  verify  that  the  entrance  to  the  lobby  with  the 
Phase  I  key-switch  opens. 

(2)  The  key  is  only  permitted  to  be  removable  in 
the  "ON"  or  "OFF"  position. 

NOTE:  In  order  to  cause  as  little  inconvenience  as  possible  with 
multiple  elevator  systems,  it  is  suggested  that  the  elevators  be  put 
back  in  service  immediately  and  one  elevator  at  a  time  be  isolated 
for  individual  testing. 

(3)  With  the  designated  level  key-operated  switch 
in  the  "OFF"  position  and  the  car  at  the  designated  level, 
register  several  calls.  With  the  inspector  in  the  car,  allow 
the  car  to  run.  As  the  car  leaves  the  floor,  turn  the  desig- 
nated level  key-operated  switch  to  the  "ON"  position. 
The  car  should  stop  and  reverse  at  or  below  the  next 
available  floor  without  opening  the  door(s)  and  return 


to  the  designated  level  where  it  should  park  with  the 
door(s)  open.  As  the  car  descends,  operate  the  in-car 
stop  switch  or  emergency  stop  switch  to  see  that  it  has 
been  rendered  inoperative.  Check  that  the  car  buttons 
have  been  rendered  inoperative  and  that  the  car  will 
not  respond  to  any  car  calls.  Also,  determine  that  all 
call-registered  lights  and  in-car  lanterns  are  extin- 
guished and  remain  inoperative. 

(4)  With  the  designated  level  key-operated  switch 
in  the  "OFF"  position,  run  the  car  to  any  floor.  Then  with 
the  doors  open,  have  the  designated  level  key-operated 
switch  turned  to  the  "ON"  position. 

Check  to  see  that  the  door  reopening  devices  for 
power-operated  doors,  which  are  sensitive  to  smoke  or 
flame,  are  rendered  inoperative.  Check  to  see  that  the 
mechanical  safety  edge  and  "DOOR  OPEN"  buttons 
are  still  operative  and  that  door  closing  conforms  to 
Rule  112.5.  With  the  doors  open,  actuate  the  emergency 
stop  switch  to  see  that  it  is  operative.  The  doors  may 
or  may  not  close  but  the  car  must  not  move. 

(5)  Return  the  emergency  stop  switch  to  the  "RUN" 
position.  The  automatic  power-operated  doors  must 
close  without  delay  and  the  car  should  proceed  to  the 
designated  level  and  park  with  the  doors  open.  If  the 
elevator  is  equipped  with  vertically  sliding  doors  with 
automatic  or  momentary  pressure  closing,  the  closing 
sequence  should  initiate  and  the  car  proceed  to  the  des- 
ignated level.  If  the  elevator  is  equipped  with  manual 
doors  or  power-operated  continuous  pressure  closing, 
the  visual  and  audible  signals  required  by 
Rule  211.3a(4)(c)  should  operate  and  when  the  doors 
are  closed,  the  car  return  to  the  designated  level. 

(6)  Check  all  call  buttons  to  see  that  they  are  inoper- 
ative and  call-registered  lights  and  directional  lanterns 
are  extinguished  when  the  designated  level 
key-operated  switch  is  in  the  "ON"  position.  Position 
indicators,  where  provided,  must  remain  in  service. 

(7)  Check  to  see  that  no  emergency  stop  switches 
other  than  those  inside  the  car  (i.e.,  pit,  car  top,  etc.)  and 
no  safety  circuits  other  than  the  door  reopening  devices, 
which  are  sensitive  to  smoke  or  flame,  as  previously 
mentioned,  are  rendered  inoperative  when  the  desig- 
nated level  key-operated  switch  is  in  the  "ON"  position. 

(8)  Check  installations  with  vertical  slide  doors  that 
corridor  "DOOR  OPEN"  and  "DOOR  CLOSE"  buttons 
remain  operative. 

(9)  Check  that  the  visual  and  audible  signal  device 
is  activated.  For  elevators  installed  under  A17. 1-1990, 
verify  that  the  visual  signal  graphic  is  as  shown  in 
Fig.  6.4.2(b)(9). 

(10)  With  the  designated  level  key-operated  switch 
in  the  "OFF"  position,  activate  the  smoke  detector.  A 
smoke  detector  should  be  located  in  every  elevator 
lobby,  including  designated  level  and  associated 
machine  room,  which,  when  activated,  performs  the 


87 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Fig.  6.4.2(b)(9)    Visual  Signal 


oc 

^» 

^s 

K 

/ 

mr 

s 

h 

/ 

\ 

\ 

s 

I 

J 

V 

c 

,,*** 

— 

'V 

^ 

^s 

_»■ 

1  in. 

(25  mm) 

min. 


■  1  in.  (25  mm)  min. 


same  functions  as  previously  described  when  the  desig- 
nated level  key-operated  switch  is  in  the  "ON"  position. 
If  the  smoke  detector  at  the  designated  level  is  activated, 
the  elevator  should  return  to  an  alternate  level  desig- 
nated by  the  enforcing  authorities.  Smoke  detectors  may 
be  installed  in  any  hoistway  and  must  be  installed  in 
hoistways  that  are  sprinklered.  For  elevators  installed 
under  A17.1-1993  and  later  editions,  activate  any  smoke 
detectors  in  the  hoistway  at  or  below  the  lowest  landing 
of  recall  Check  the  elevator  returns  to  the  upper  recall 
level.  No  smoke  detectors,  other  than  those  referenced, 
or  other  devices  are  permitted  to  activate  automatic 
Phase  I  recall.  Smoke  detectors  must  not  be  self-resetting. 

NOTES: 

(1)  If  the  sensing  system  is  connected  to  a  central  fire  alarm  system, 
notify  proper  authorities  before  activating. 

(2)  See  Rule  211.3b  for  locations  when  sensing  devices  are  not 
required.  Smoke  detectors  can  be  activated  by  using  a  test 
button  if  supplied,  or  by  simulating  smoke  conditions.  Manu- 
facturer's recommended  test  procedures  should  be  followed. 
Use  of  chemical  smoke  may  oversensitize  smoke  detectors. 

(11)  With  the  smoke  detector  activated,  turn  the 
designated  level  key-operated  switch  to  the  "BYPASS" 
position.  The  elevator  must  return  to  normal  service. 
With  the  designated  level  smoke  detector  activated  and 
the  designated  level  key-operated  switch  in  the  ''OFF" 
position,  turn  the  additional  Phase  I  switch,  if  provided, 
to  the  "ON"  position.  The  car  must  remain  at  the  alter- 
nate level. 

(12)  If  the  car  is  provided  with  an  in-car  "DOOR 
OPEN"  button,  take  the  car  to  an  upper  floor.  With 
the  door  open,  have  the  designated  level  key-operated 
switch  turned  to  the  "ON"  position.  The  in-car  "DOOR 
OPEN"  button  should  remain  operative  until  the  car 
moves  away  from  the  landing. 

(13)  Turn  the  additional  two-position  Phase  I 
switch,  if  provided,  to  the  "ON"  position;  turn  the  three- 
position  Phase  I  switch  to  the  "BYPASS"  position.  The 
elevator  must  remain  on  Phase  I  and  not  return  to  normal 
service. 


(c)  Phase  I  Emergency  Recall  Operation:  Attendant- 
Operated  Elevators.  Elevators  operable  only  by  a  desig- 
nated attendant  in  the  car  must  be  provided  with  both 
visual  and  audible  signals. 

(d)  Phase  I  and  Phase  II  Automatic  Operating  Elevators 
With  Dual  Operation.  Elevators  arranged  for  dual  opera- 
tion must,  when  on  automatic  operation,  conform  to 
Items  6.4.2(b)  and  (e),  and  when  on  attendant  operation, 
conform  to  Item  6.4.2(c).  The  elevator  must  revert  to 
automatic  operation  not  less  than  15  s  nor  more  than 
60  s  after  Phase  I  activation. 

(e)  Phase  II  In-Car  Emergency  Operation:  Automatic 
Elevators.  Phase  II  operation  requires  that  a 
three-position  key-operated  switch  ("OFF,"  "HOLD," 
and  "ON,"  in  that  order)  be  provided  in  the  operating 
panel  in  each  car.  The  key  should  be  removable  in  the 
"OFF,"  "HOLD,"  or  "ON"  position.  With  Phase  I  service 
activated  and  after  the  car  has  returned  to  the  designated 
or  alternate  level,  turn  the  in-car  key-operated  switch 
to  the  "ON"  position. 

(1)  Check  that  the  elevator  is  operable  only  by  the 
car  buttons  and  does  not  respond  to  corridor  calls. 

(2)  Check  that  all  corridor  call  buttons  and  direc- 
tional lanterns  are  inoperative. 

(3)  Check  that  the  opening  of  the  door  is  controlled 
by  a  continuous  pressure  button  and  that  when  the  but- 
ton is  released  prior  to  the  door  reaching  its  fully  open 
position,  the  door  will  automatically  reclose.  On  cars 
with  two  entrances,  if  both  entrances  can  be  opened  at 
the  same  landing,  separate  "DOOR  OPEN"  and  "DOOR 
CLOSE"  buttons  must  be  provided  for  each  entrance. 

(4)  Check  that  automatic  car  doors  or  gates,  oppo- 
site manual  hoistway  doors,  operate  as  specified  in 
Item  6.4.2(e)(3). 

(5)  Check  to  see  that  the  door  reopening  devices 
are  inoperative. 

(6)  Check  that  corridor  door  open  and  close  but- 
tons, if  provided,  are  inoperative. 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


(7)  Check  that  the  means  provided  in  the  car 
operating  panel  to  cancel  car  calls  is  operative  by  regis- 
tering calls  and  cancelling  them.  A  traveling  car  should 
stop  at  or  before  the  next  available  landing. 

(8)  Check  that  floor  selection  buttons  are  provided 
in  the  car  to  permit  travel  to  all  landings  serviced  by 
the  car.  These  buttons  must  be  operational,  by  passing 
all  security  during  Phase  II  operation. 

(9)  With  the  car  on  Phase  II  operation,  register  two 
or  more  car  calls  and  proceed  to  close  the  door.  The  car 
should  proceed  to  the  next  available  landing  for  the 
registered  call.  Once  the  car  stops  at  that  landing,  all 
registered  calls  must  be  cancelled. 

(10)  Check  to  see  that  Phase  II  operation  once  acti- 
vated cannot  be  deactivated  until  the  car  has  returned 
to  the  designated  or  alternate  level.  To  do  this,  with 
the  designated  level  key-operated  switch  in  the  "ON" 
position,  and  the  in-car  key-operated  switch  in  the  "ON" 
position,  take  the  car  to  any  floor  except  the  designated 
floor.  Then  turn  the  designated  level  key-operated 
switch  to  the  "OFF"  position,  or  if  a  smoke  detector  is 
activated,  to  the  "BYPASS"  position,  and  make  sure  the 
Phase  II  operation  is  maintained  until  the  car  is  returned 
to  the  designated  level. 

(11)  Turn  the  designated  level  key-operated  switch 
to  the  "OFF"  position  or,  if  a  smoke  detector  is  activated, 
to  the  "BYPASS"  position.  Take  the  elevator  to  a  floor 
other  than  the  designated  level  and  turn  the  in-car  key- 
operated  switch  to  the  "ON"  position.  Check  to  see 
that  the  Phase  II  operation  does  not  operate  even  if  the 
designated  level  key-operated  switch  is  turned  to  the 
"ON"  position  or  a  smoke  detector  has  been  activated. 

(12)  Take  the  car  to  an  upper  floor  and  with  the 
door  closed,  turn  the  in-car  key-operated  switch  to  the 
"OFF"  and  "HOLD"  position.  It  should  have  no  effect 
on  the  Phase  II  operation, 

(13)  With  the  Phase  I  key-operated  switch  in  the 
"ON"  position,  take  the  car  to  an  upper  floor  and,  with 
the  doors  open,  place  the  in-car  key-operated  switch  in 
the  "HOLD"  position.  The  car  should  remain  at  the  floor. 

(14)  Take  the  car  to  an  upper  floor,  and,  with  the 
doors  open,  place  the  in-car  key-operated  switch  in  the 
"OFF"  position.  Upon  completion  of  the  door  closing 
the  car  should  revert  to  Phase  I  operation  and  return 
nonstop  to  the  designated  or  alternate  level.  For  eleva- 
tors installed  under  A17. 1-1993  and  later  editions 

(a)  check  that  the  door  reopening  device  is 
inoperative. 

(b)  check  that  in-car  "DOOR  OPEN"  and  "DOOR 
CLOSE"  buttons  remain  operative  regardless  of  the  type 
of  doors.  For  vertically  sliding  doors,  the  corridor 
"DOOR  OPEN"  and  "DOOR  CLOSE"  buttons  are 
operative. 

(c)  check  that  the  door  reopens  when  in-car 
key-operated  switch  is  placed  in  the  "ON"  or  "HOLD" 
position  before  door  closes  completely. 


Fig.  6.4.2(g)(1)    Phase  I  Instructions 


FIREFIGHTERS'  OPERATION 

To  recall  elevators 
Insert  fire  key  and  turn  to  "ON" 


(f)  Multideck  Elevators.  Multideck  elevators  should  be 
inspected  as  outlined  in  Items  6.4.2(b)  through  (e)  in 
addition  to  the  following: 

(1)  The  designated  level  key-operated  switch  for 
Phase  I  operation  should  be  at  the  designated  level 
served  by  the  upper  compartment. 

(2)  The  in-car  key-operated  switch  for  Phase  II 
operation  must  be  located  in  the  upper  compartment. 
Check  the  operation  of  the  in-car  key-operated  switch 
in  accordance  with  Item  6.4.2(e). 

(3)  Check  to  see  that  means  is  provided  for  locking 
the  lower  deck  out  of  service. 

(g)  Operating  Instructions  and  Keys 

(1)  Operating  instructions  for  Phase  I  service 
should  be  posted  adjacent  to  the  designated  level  key- 
operated  switch.  Instructions  for  operating  under 
Phase  II  operation  should  be  incorporated  with  or  adja- 
cent to  the  in-car  key-operated  switch.  Instructions 
should  be  in  letters  not  less  than  %  in.  (3,2  mm)  in  height, 
permanently  installed,  and  protected  against  removal 
and  defacement.  The  instructions  must  be  exactly  as 
shown  in  Figs.  6.4.2(g)(1)  and  6.4.2(g)(2)  or  6.4.2(g)(3). 

All  switches  must  be  keyed  alike  for  Phase  I  and 
Phase  II  operation  and  not  be  a  part  of  building  master 
key  system.  For  elevators  installed  under  A17.1b-1992 
and  later  editions,  check  that  all  elevators  in  the  building 
are  keyed  alike.  Keys  should  be  kept  on  premises  for 
the  designated  level  key-operated  switch  plus  a  key  for 
each  in-car  key-operated  switch  in  a  location  readily 
accessible  to  authorized  persons  but  not  readily  available 
to  the  public. 

(h)  Inspection  Operation.  Place  the  car  on  inspection 
operation  and  operate  from  top  of  car.  Check  that  an 
audible  signal  sounds  and  that  the  elevator  remains 
under  control  of  the  top-of-car  operating  device  when 
the  Phase  I  key-operated  switch  is  in  the  "ON"  position 
or  a  smoke  detector  is  actuated. 

(i)  Interruption  of  Power.  Place  the  car  on  Phase  II  and 
go  to  a  floor  other  than  the  designated  or  alternate  level. 
Open  the  main  line  switch,  then  close  the  main  line 
switch.  The  elevator  should  remain  on  Phase  II 
operation. 

(j)  Firefighters'  Service  When  on  Standby  (Emergency) 
Power.  Elevators  are  required  to  have  a  manual  selection 
switch  to  override  an  automatic  sequencing  of  standby 


89 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


(10) 


Fig.  6.4.2(g)(2)    Phase  II  Instructions  (A17.1b-1989  Through  A17.1b-1995) 


FIREFIGHTERS'  OPERATION 

To  operate  car 

Insert  fire  key  and  turn  to  "ON" 
Press  desired  floor  button 

To  cancel 
floor  selection 

Press  "CALL  CANCEL"  button 

To  close  door 

Press  and  hold  "DOOR  CLOSE"  button 

To  open  door 

Press  and  hold  "DOOR  OPEN"  button 

To  hold  car 
at  floor 

With  doors  open,  turn  key  to  "HOLD" 

To  return  car 
to  recall  floor 

With  doors  open,  turn  key  to  "OFF" 

Fig.  6.4.2(g)(3)     Phase  II  Instructions  (A17.1-1996  Through  A17.1d-2000) 


FIREFIGHTERS'  OPERATION 

cCk 

When  flashing,  exit  elevator 

To  operate  car 

Insert  fire  key  and  turn  to  "ON'* 
Press  desired  floor  button 

To  cancel 
floor  selection 

Press  "CALL  CANCEL"  button 

To  close  power- 
operated  door 

Press  and  hold  "DOOR  CLOSE"  button 

To  open  power- 
operated  door 

Press  and  hold  "DOOR  OPEN"  button 

To  hold  car 
at  floor 

With  doors  open,  turn  key  to  "HOLD" 

To  automatically  send 
car  to  recall  floor 

With  doors  open,  turn  key  to  "OFF" 

90 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers.  & 

No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME.    ^^ 


ASMEA17.2-2010 


power.  With  the  elevator  at  an  upper  floor,  switch  the 
power  to  the  elevators  to  standby  power  and  place  the 
Phase  I  key-operated  switch  in  the  "ON"  position.  Acti- 
vate the  manual  selection  switch  to  select  a  car  other 
than  that  selected  by  the  automatic  sequencing.  Check 
that  power  will  be  transferred  to  the  manually  selected 
car  only  after  the  automatically  selected  car  has  stopped, 
normally  after  Phase  I  recall  has  been  completed.  If  the 
manual  selection  switch  is  key  operated,  it  must  use  the 
same  key  as  the  firefighters'  service  key. 

6.4.3  Acceptance 

6.4.4  References 

6.4.4.1  Electric  Elevators.  A17.1d-2000  and  earlier 
editions  —  Rules  112.3d,  112.5,  211.2  through  211.8, 
1001.2(d)(12),  1002.2f,  and  1206.7. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.13.3.4,  2.13.5,  2.27.2  through  2.27.8, 
8.11.2.1.4(1),  8.11.2.2.6,  and  8.6.10.1. 

6.4.4.2  Hydraulic  Elevators.  A17.1d-2000  and  ear- 
lier editions  —  Rules  112.3d,  112.5,  211.2  through  211.8 
{306.11},  1001.2(d)(12),  1002.2f,  and  1206.7. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.13.3.4, 2.13.5, 2.27.2  through  2.27.8  (3.27), 
8.11.2.1.4(1),  8.11.2.2.6,  and  8.6.10.1. 

ITEM  6.5 

ACCEPTANCE  CHECKLIST  FOR  FIREFIGHTERS' 

SERVICE  (ASME  A17.1-2000  and  CSA  B44-00): 

AUTOMATIC  ELEVATORS 

NOTE:  The  acceptance  checklist  is  more  detailed  than  the  ''rou- 
tine inspection"  checklist.  The  routine  inspection  will  confirm  that 
the  operation  has  been  maintained  in  working  order.  See  Nonman- 
datory  Appendix  B  for  the  acceptance  checklist. 

6.5.1  Emergency  Signaling  Devices 

6.5.1.1  "ALARM"  must  sound  and  illuminate 
when  pressed.  If  rise  is  over  100  ft  (30  m),  a  second 
device  is  required. 

6.5.1.2  In-car  emergency  stop  button  (if  present) 
must  sound  alarm. 

6.5.1.3  If  rise  is  more  than  60  ft  (18  m),  check  for 
two-way  communication  between  cab  and  point  outside 
hoist  way. 

6.5.1.4  Ensure  that  audible  alarms  and  communi- 
cations are  functional  with  loss  of  normal  power. 

6.5.1.5  Check  for  means  to  communicate  with 
machine  room  when  required  by  A17.1,  requirement 
2.26.1.5.10(c). 

6.5.2  Phase  I  Key  Switch  and  Instructions 

6.5.2.1  Operating  instructions. 

6.5.2.2  Group  3  security  keys. 


6.5.2.3  Labeled  'TIRE RECALL"  marked  "RESET/7 
"OFF/'  and  "ON,"  in  that  order. 

6.5.2.4  Provide  at  designated  level  for  group. 

6.5.2.5  Located  in  the  lobby,  visible  and  readily 
accessible. 

6.5.2.6  The  key  cannot  be  removed  in  the  "RESET" 
position.  But  it  can  be  removed  in  the  other  positions. 

6.5.2.7  Second  switch,  if  present,  must  be  at  central 
alarm  and  control  facility  labeled  'TIRE  RECALL"  only 
be  two-position  switch  marked  "OFF"  and  "ON,"  in 
that  order. 

6.5.3  Phase  II  In-Car  Switch  and  Instruction 

6.5.3.1  Ensure  that  there  is  a  key  for  each  Phase  I, 
each  Phase  II,  and  each  standby  power  selection  switch 
in  the  building. 

6.5.3.2  The  same  key  is  used  for  Phase  I  and 
Phase  II  and  standby  power  for  all  elevators  in  the 
building. 

6.5.3.3  Keys  are  available  only  to  authorized  emer- 
gency and  firefighting  personnel. 

6.5.3.4  The  key  can  only  be  removed  in  the  "OFF" 
and  "HOLD"  positions. 

6.5.3.5  The  keys  shall  be  Group  3  security  (see 
Item  8.1). 

6.5.3.6  Labeled  "FIRE  OPERATION,"  marked 
"OFF,"  "HOLD,"  and  "ON,"  in  that  order. 

6.5.4  Monthly  Test 

6.5.4.1      Monthly  test  log  is  completed. 

6.5.5  Phase  I  Operation  While  Running 

Place  several  floor  calls  in  the  car.  While  going  up, 
have  the  person  at  the  designated  level  place  the  Phase  I 
switch  in  the  "ON"  position.  Where  a  duplicate  switch 
is  provided,  verify  that  Phase  I  is  initiated  by  placing  the 
switch  to  the  "ON"  position.  Determine  the  following: 

(a)  The  car  stops  and  reverses  without  opening  the 
doors. 

(b)  The  in-car  stop  switch  or  emergency  stop  switch 
is  inoperative. 

(c)  Call-registered  lights  and  directional  lanterns  are 
extinguished  and  inoperative. 

(d)  Position  indicators,  where  provided,  are  inopera- 
tive, except  in  car,  designated  level,  and  central  control 
station. 

(e)  The  in-car  door  open  button  is  rendered  inopera- 
tive as  soon  as  car  moves  away  from  the  landing. 

(f)  Car  call  buttons  and  corridor  call  buttons  are 
inoperative. 

(g)  The  car  returns  to  the  designated  level  and  parks 
with  power-operated  doors  open.  If  there  is  more  than 


91 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


one  entrance  at  the  designated  landing,  only  the  doors 
serving  the  lobby  with  the  fire  recall  switch  open. 

(h)  The  visual  and  audible  signals  operate  and  stay 
on  until  car  is  at  the  designated  level. 

6.5.6  Phase  I  Operation  With  Doors  Open 

Place  the  Phase  I  switch  to  the  "OFF"  position  and 
run  the  car  to  any  floor.  With  the  doors  open,  have  the 
Phase  I  switch  turned  to  the  "ON"  position  and  check 
the  following: 

(a)  Door  reopening  devices  sensitive  to  smoke  or 
flame  are  inoperative  immediately. 

(b)  If  door  reopening  devices  are  rendered  inopera- 
tive, the  closing  speed  is  reduced  so  that  the  kinetic 
energy  is  reduced  to  2l/2  ft-lb  (3.5  J). 

(c)  The  emergency  stop  switch  or  in-car  stop  switch 
is  rendered  inoperative  as  soon  as  the  car  moves  away 
from  the  landing. 

(d)  The  in-car  door  open  button  is  rendered  inopera- 
tive as  soon  as  the  car  moves  away  from  the  landing. 

6.5.7  Emergency  Stop  Switch  and/or  In-Car  Stop 
Switch  and  Doors  Closing 

Place  the  Phase  I  switch  to  the  "OFF"  position  and 
run  the  car  to  any  floor.  Activate  the  emergency  stop 
switch  or  the  in-car  stop  switch.  With  the  doors  open, 
have  the  Phase  I  switch  turned  to  the  "ON"  position. 
Return  the  emergency  stop  switch,  or  in-car  stop  switch 
to  the  "RUN"  position. 

6.5.7.1  Verify  that  the  automatic  power-operated 
horizontal  sliding  doors  close  promptly,  that  other  types 
of  doors  can  be  closed  and  once  closed  the  car  moves 
to  the  designated  level. 

6.5.8  Stop  Switches  and  Door  Buttons 

While  on  Phase  1  verify  that 

(a)  stop  switches  other  than  those  inside  the  car 
remain  operative 

(b)  for  vertical  sliding  doors,  the  corridor  door  open 
and  door  close  buttons  remain  operative 

6.5.9  Fire  Alarm  Initiating  Device  and  Operation 

6.5.9.1  Verify  that  there  is  a  fire  alarm  initiating 
device  in  each  elevator  lobby,  the  elevator  machine  room, 
and  sprinklered  hoistway. 

In  jurisdictions  enforcing  the  NBCC,  verify  that  there 
is  a  fire  alarm  initiating  device  in  each  elevator  lobby, 
at  the  designated  level  if  not  sprinklered  throughout 
and  in  the  machine  room  if  sprinklered. 

6.5.9.2  With  the  car(s)  on  normal,  have  the  input 
for  main  return  activated  and  verify  that  the  elevator 
commences  Phase  I  operation  and  all  cars  return  to  the 
designated  level. 

6.5.9.3  To  reset  operation  initiated  from  fire  alarm 
system,  the  fire  alarm  signal  must  be  reset,  then  the 


Phase  I  switch  must  be  cycled  to  "RESET"  momentarily 
then  to  "OFF" 

6.5.9.4  With  the  car(s)  on  normal,  have  the  input 
for  alternate  level  return  activated  and  verify  that  the 
elevator  commences  Phase  I  operation  and  all  cars  return 
to  the  alternate  level. 

6.5.9.5  Car(s)  should  only  respond  to  the  first  fire 
alarm  input. 

6.5.9.6  Activate  the  machine  room  fire  alarm  ini- 
tiating device  input  and  verify  Phase  I  and  all  cars  return 
to  the  designated  level. 

6.5.9.7  Activate  the  designated  level  machine 
room  fire  alarm  initiating  device  and  verify  Phase  I  and 
all  cars  return  to  the  alternate  floor. 

6.5.9.8  With  the  car(s)  on  normal,  have  the  input 
for  machine  room  return  activated  and  verify  the  visual 
signal  in  the  car  illuminates  intermittently. 

6.5.9.9  In  jurisdictions  not  enforcing  the  NBCC, 
where  the  fire  alarm  initiating  device  is  required  in  the 
hoistway,  activate  the  input  and  verify  all  cars  return  to 
the  designated  landing,  except  that  fire  alarm  initiating 
devices  installed  at  or  below  the  lowest  landing  of  recall 
shall  cause  the  cars  to  return  to  the  upper  recall  level. 

6.5.10  Fire  Alarm  Initiating  Device  and  Phase  I 
Switch 

6.5.10.1  Activate  the  alternate  landing  return 
input  and  observe  that  the  elevator  returns  to  the  alter- 
nate landing. 

6.5.10.2  If  a  two-position  key  switch  is  provided, 
place  it  in  the  "ON"  position  and  verify  that  the  elevator 
remains  at  the  alternate  landing. 

6.5.10.3  Turn  both  the  Phase  I  switch  and  the 
additional  Phase  I  switch  (when  provided)  to  the  "ON" 
position  and  verify  that  the  car  returns  to  the  desig- 
nated level. 

6.5.11  Phase  I!  Key  Switch  and  Sign 

With  Phase  I  activated  and  the  car  at  the  designated 
or  alternate  landing,  place  the  Phase  II  key  switch  in  the 
"ON"  position.  Operate  the  car  and  check  the  following: 

(a)  The  elevator  can  be  operated  only  from  the  car 
buttons  and  will  not  respond  to  corridor  calls. 

(b)  All  corridor  call  buttons,  door  open  and  close  but- 
tons, and  directional  lanterns  are  inoperative.  All  land- 
ing position  indicators,  except  at  the  designated  landing 
and  central  alarm  and  control  facility,  are  inoperative. 
Car  position  indicators  are  operative. 

(c)  Power-operated  doors  can  only  be  opened  by  con- 
tinuous pressure  on  the  door  open  button  and  if  released 
before  the  doors  are  in  the  normal  "OPEN"  position, 
the  door  will  close  without  delay. 


92 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


(d)  Open  power-operated  doors  can  be  closed  only 
by  continuous  pressure  means.  If  the  means  is  released 
before  the  door  is  fully  closed,  horizontal  sliding  doors 
will  reopen  and  vertical  sliding  doors  will  stop,  or  stop 
and  reopen. 

(e)  If  two  entrances  can  be  opened  and  closed  at  the 
same  landing,  separate  door  open  and  close  buttons  are 
provided  for  each  entrance. 

(/)  All  door  reopening  devices  are  inoperative  (except 
the  door  open  button).  Full  speed  closing  is  permitted. 

(g)  "CALL  CANCEL"  button  is  labeled  and  when 
activated,  will  cancel  all  calls  and  cause  the  car  to  stop 
at  or  before  the  next  available  landing. 

(h)  Floor  selection  buttons  are  provided  and  func- 
tional for  all  landings  without  restrictions. 

(i)  Moving  car  will  stop  at  the  next  landing  with  a 
car  call  registered  and  remaining  car  calls  canceled. 

6.5.12  Phase  II  Switch  in  "HOLD"  Position 

6.5.12.1  Place  the  Phase  II  switch  in  the  "HOLD" 
position  and  remove  key.  Verify  that  the  car  remains  at 
the  landing  and  the  door  close  button  is  inoperative. 

6.5.12.2  Verify  that  the  car  call  buttons  are  inoper- 
ative. 

6.5.13  Phase  II  Switch  in  "OFF"  Position  and  Doors 
Closing:  Power-Operated  Horizontally  and 
Vertically  Sliding  Doors 

With  the  elevator  away  from  the  designated  level, 
Phase  I  in  effect,  place  the  Phase  II  switch  in  the  "OFF" 
position  and  verify  that 

(a)  horizontally  sliding  doors  close  automatically  and 
continuous  pressure  on  the  door  close  button  will  close 
vertically  sliding  doors 

(b)  car  reverts  to  a  Phase  I-type  return  on  completion 
of  door  closing  and  reverts  to  Phase  I  when  the  doors 
open  at  the  designated  landing 

(c)  door  reopening  device  inoperative  and  full  speed 
closing  permitted 

(d)  door  open  button  operative 

(e)  if  Phase  II  switch  turned  to  "ON"  or  "HOLD" 
before  door  is  closed,  it  will  reopen 

6.5.14  Removal  From  Phase  II 

Verify  that  the  elevator  can  be  removed  from  Phase  II 
only  when 

(a)  Phase  II  switch  is  in  "OFF"  position  at  designated 
level  and  doors  open 

(b)  Phase  II  switch  is  in  "OFF"  position  and  Phase  I 
is  in  effect 

6.5.15  Power  Disconnects  Open 

6.5.15.1  With  the  elevator  on  Phase  I,  have  the 
main  line  power  interrupted  and  restored  to  verify  that 
the  elevator  will  remain  on  Phase  I. 


6.5.15.2  With  the  elevator  on  Phase  II,  have  the 
main  line  power  interrupted  and  restored  to  verify  that 
the  elevator  will  remain  on  Phase  II. 

6.5.15.3  The  car  is  allowed  to  move  to  a  position 
in  the  hoistway  to  reestablish  position  once  movement 
is  attempted. 


6.5.16  Top-of-Car  Operating  Device 

While  operating  from  top  of  car,  have  the  Phase  I  key 
switch  placed  in  the  "ON"  position  and  verify  that 

(a)  an  audible  signal  sounds 

(b)  the  elevator  remains  under  control  of  the  top-of- 
car  operating  device 

(c)  the  elevator  remains  under  the  control  of  the 
hoistway  access  switch 


6.5.17  Automatic  Elevators  With  Attendant 
Operation 

With  elevator  on  attendant  operation,  stop  at  a  floor 
and  have  the  Phase  I  switch  placed  in  the  "ON"  position. 
Verify  that 

(a)  the  audible  and  visual  signal  operates  and  that  a 
parked  elevator  will  automatically  go  on  Phase  I  after 
a  time  delay  between  10  sec  and  30  sec. 

(b)  a  moving  car  on  attendant  operation  will  com- 
mence Phase  I  operation  without  delay. 

(c)  if  car  is  on  hospital  emergency  service,  it  will 
remain  on  that  operation  until  removed  by  the  operator 
and  at  that  point  revert  to  Phase  I  operation.  The  audible 
and  visual  signals  in  the  car  shall  be  activated  immedi- 
ately and  remain  activated  until  the  car  is  returned  to 
the  designated  landing.  With  the  car  on  firefighter  emer- 
gency operation,  the  elevator  cannot  be  placed  on  hospi- 
tal service. 


6.5.18  Elevators  on  Phase  I  and  Phase  II,  Prevention 
of  Operation  and  Disabling  Not  Allowed 

With  elevator  on  normal  operation,  verify  the 
following: 

(a)  Activate  means  other  than  those  specified  in  this 
Code  to  remove  elevators  from  normal  operation,  and 
verify  that  Phase  I  Emergency  Recall  Operation  is  not 
prevented. 

(b)  Activate  input  for  devices  that  measure  loads  and 
verify  that  the  elevator  is  not  prevented  from  operating 
at  or  below  the  capacity  that  is  required. 

(c)  Verify  that  an  accidental  ground  or  short  circuit 
in  equipment  on  landing  side  will  not  disable  Phase  II 
operation. 


93 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Part  7 
Escalator  —  External 


ITEM  7.1 
GENERAL  FIRE  PROTECTION 

7.1.1  Periodic  Inspections 

Examine  the  sides  and  undersides  of  the  escalator 
trusses  and  machinery  spaces  enclosure  for  damage  to 
fire-resistive  materials.  A17.1a-1994  and  later  editions 
permit  the  use  of  noncombustible  and  limited  combusti- 
ble materials  as  defined  by  the  building  code  or 
ANSI/NFPA  101. 

Check  that  guards  are  in  place  for  openings  provided 
for  ventilation  of  the  driving  machine  and  control  equip- 
ment spaces.  Enclosure  in  fire- resistive  ceiling  does  not 
constitute  adequate  fire  protection. 

Verify  that  provisions  to  protect  floor  openings  from 
the  passage  of  flame,  heat,  and/or  smoke  that  are 
required  by  the  building  code  have  not  been  damaged, 
removed,  or  defeated.  Escalators  installed  under 
A17. 1-1981  and  later  editions  require  protection  in  com- 
pliance with  ANSI/NFPA  101  or  local  codes.  Prior  to 
Al 7. 1-1981,  A17.1  gave  requirements  for  protection  of 
floor  opening  for  escalators  that  were  not  accredited  as  a 
means  of  egress.  However,  since  escalators  are  no  longer 
accredited  as  a  means  of  egress,  the  inspector  must  refer 
to  the  local  code  or  the  Life  Safety  Code  NFPA-101  for 
the  protection  requirement  at  each  location. 

7.1.2  Periodic  Test 

7.1.3  Acceptance 

Verify  that  floor  openings  are  protected  against  the 
passage  of  flame,  heat,  and /or  smoke  in  accordance  with 
the  requirements  of  the  building  code. 

7.1.4  References 

A17.1d-2000  and  earlier  editions  —  Sections  800  and 
801;  and  Rule  1009.2a. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.1.1  and  6.1.2;  and  8.10.4.1.1(a). 

ITEM  7.2 
GEOMETRY 

7.2.1  Periodic  Inspections 

Inspect  for  evidence  of  change  to  the  geometry  of  the 
balustrades  and  if  change  has  been  made,  inspect  as 
outlined  in  Item  7.2.3. 

If  an  escalator  is  relocated  or  a  new  escalator  is 
installed  in  existing  trusses,  it  must  comply  with  the 


current  Code  requirements.  See  Figs.  7.2.1(a),  7.2.1(b), 
and  7.2.1(c)  for  dimension  requirements  of  existing 
escalators. 

Verify  that  the  overhead  clearance  is  in  compliance 
with  local  codes. 

7.2.2  Periodic  Test 

The  width  of  the  balustrades  must  be  the  width  of 
the  step  tread  to  the  next  whole  inch  and  should  not 
decrease  in  the  direction  of  travel.  For  escalators 
installed  under  A17.1-1955  to  A17.1-1981  editions,  the 
width  should  not  change  abruptly  nor  more  than  8%  of 
the  greatest  width,  and  the  maximum  angle  of  change 
should  not  be  more  than  15%  in  the  line  of  travel. 

7.2.3  Acceptance 

(a)  Verify  that  the  angle  of  inclination  does  not  exceed 
31  deg.  If  in  doubt,  a  30  deg/60  deg  triangle,  a  level, 
and  a  straight  edge  may  be  used  to  check  the  incline. 
The  straight  edge  may  be  placed  on  the  front  of  several 
steps  as  shown  in  Fig.  7.2.3.  The  bubble  on  the  level 
should  be  in  the  center  or  slightly  to  the  left  when  placed 
as  shown  in  the  figure.  If  the  bubble  is  to  the  right,  a 
protractor  or  angle  finder  will  be  needed  to  verify  that 
the  incline  does  not  exceed  31  deg. 

(b)  Measure  the  width  of  the  step  at  a  right  angle 
transverse  to  the  direction  of  travel. 

(c)  Measure  and  mark  the  centerline  of  each  handrail 
and  use  a  plumb  line  to  find  the  distance  from  the  hand- 
rail centerline  to  the  width  of  the  escalator  or  step  edge. 

(d)  For  an  interior  low  deck  escalator,  measure  the 
distance  from  the  vertical  face  of  the  interior  panels  to 
the  vertical  face  of  the  skirt  panels  using  a  machinist 
level  and  ruler  [see  Fig.  7.2.1(c)].  Measure  the  slope  of  the 
deck  perpendicular  to  the  line  of  travel  using  a  machinist 
level  and  protractor. 

(e)  Drop  a  plumb  line  to  the  edges  of  the  steps  and 
measure  the  distance  between  the  centerline  of  the  hand- 
rails to  the  edge  of  the  steps. 

7.2.4  References 

A17.1d-2000  and  earlier  editions  —  Rules  802.1, 802.2, 
802.3d,  1009.2b,  1009.2g,  and  1207.5;  and  Appendix  D. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.1.3.1,  6.1.3.2,  6.1.3.3.4,  8.10.4.1.1(b), 
8.10.4.1.1(n),  and  8.7.6.1.5;  and  (NR  Appendix  D). 


94 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


Fig.  7.2.1(a)    Dimensions  for  Existing  Escalators  (for  Escalators  Installed  Under  A17.1-1955  and 

A17.1-1960  Editions) 


CD 

Width  between  balustrades 

CD 

\ 

| 

i      I             27  in.  above  nose 
|       \                 line  of  step 

!  \ 

Step  tread 

/  | 

1                                                       ! 

i                       16  in.  mm.                       i 

i<                                                          >\ 
i                                                              i 

Maximum  allowed  width 
step  tread  width  plus  13  in. 

Not  less  than  22  in. 
Not  more  than  48  in. 


GENERAL  NOTE:      1  in.  -  25.4  mm. 


ITEM  73 
HANDRAILS 

7.3.1  Periodic  Inspections 

(a)  Mark  one  location  on  each  handrail  with  chalk, 
then  operate  the  unit  and  inspect  each  handrail  through 
a  complete  revolution.  The  handrails,  including  splices 
and  joints,  should  be  free  of  any  cuts,  cracks,  gouges, 
pinch  points,  or  any  other  condition  that  would  be  a 
hazard  to  passengers.  Any  rust  or  rubber  filings  present 
on  the  balustrade  deck  indicates  that  an  internal  inspec- 
tion of  the  handrail  system  may  be  warranted. 

(b)  Verify  that  the  hand  or  finger  guards  are  present 
at  the  newel  base.  Check  that  the  guards  are  in  good 
condition  and  properly  sized  to  prevent  fingers  or  hands 
from  being  drawn  into  the  newel.  Finger  guards  are 
required  under  A17.1-1965  and  later  editions  and  A17.3. 
Al 7. 1-1 955  required  that  the  balustrade  be  designed  or 
guarded  to  prevent  fingers  and  hands  from  being  drawn 
into  the  balustrade  where  the  handrail  enters.  There  are 
several  types  of  guards  in  use  including  resilient  boots, 
brushes,  and  trap  doors.  Each  may  function  differently 


to  provide  the  protection.  Trap  doors  do  allow  entry  but 
prevent  entrapment. 

(c)  Ride  the  escalator  holding  the  handrails  through 
the  entire  travel.  The  handrails  should  move  smoothly 
without  jerking,  at  substantially  the  same  speed  as  the 
steps.  The  need  to  change  grip  on  the  handrail  more 
than  once  during  a  single  level  rise  would  indicate  a 
need  for  adjustment.  At  several  points  in  the  ride  firmly 
grip  the  handrail  and  verify  that  it  does  not  stall  under 
moderate  force. 

(d)  During  this  ride  observe  any  unusual  noise  that 
may  indicate  the  need  for  further  inspection.  Listen  for 
noise  that  may  indicate  wear  of  the  turn  around  rollers, 
or  other  parts. 

(e)  Check  the  horizontal  clearance  between  both  lips 
of  the  handrail  and  the  handrail  stand  (guide). 

7.3.2  Periodic  Test 

For  escalators  installed  to  A17. 1-2000  and  later  edi- 
tions, the  person  or  firm  maintaining  the  equipment 
must  provide  a  written  checkout  procedure  and  demon- 
strate that  the  handrail  speed  does  not  change  when  a 


95 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Fig.  7.2.1(b)    Dimensions  for  Existing  Escalators  (for  Escalators  Installed  Under  A17.1-1965 

Through  A17.1-1981) 


-4  in.  min.,  A17.1-1981 


61/2in.  max. 


6V2  in-  rnax. 


10  in.  max.,  A17. 1-1981 


GENERAL  NOTE:     1  in.  =  25.4  mm. 


retarding  force,  up  to  the  maximum  required  by  Code, 
is  applied  opposite  to  the  direction  of  travel.  Note  that 
it  may  be  easier  to  retard  the  handrail  motion  when 
the  handrail  is  traveling  in  the  down  direction  (i.e.,  the 
retarding  force  will  oppose  the  handrail  drive  system). 

7.3.3  Acceptance 

Check  whether  each  handrail  extends  at  normal 
height  not  less  than  12  in.  (305  mm)  beyond  the  escalator 
combplates,  and  verify  that  required  clearances  are 
present. 

Check  the  vertical  height  from  the  step  noseline  to 
the  top  of  the  handrail. 

7.3.4  References 

A17.1d-2000  and  earlier  editions  —  Rules  802.2, 802.4, 
and  1009.2c;  and  Appendix  D. 


A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.1.3.2,  6.1.3.4,  8.11.4.2.13,  8.6.8.12,  and 
8.10.4.1.1(c);  and  (NR  Appendix  D). 

A17.3  —  Paragraphs  5.1.5  and  5.1.6. 

ITEM  7.4 
ENTRANCE  AND  EGRESS  ENDS 

7.4.1  Periodic  Inspections 

(a)  The  floor  surfaces  adjacent  to  the  landing  plates 
must  be  continuous  with  the  top  of  the  landing  plate, 
with  no  abrupt  changes  in  elevation  of  more  than  \  in. 
(6.4  mm).  Access  to  an  egress  from  the  escalator  should 
be  free  of  obstacles  and  tripping  hazards.  Check  that 
the  pit  covers  are  present  and  in  good  condition. 

(b)  For  escalators  installed  under  the  A17.1a-1988  and 
later  editions  and  A17.3,  a  safety  zone  should  be  main- 
tained free  of  obstacles  (see  Fig.  7.4.1).  These  Code 


96 


C 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 

Fig.  7.2.1(c)     Relationship  of  Escalator  Parts  (A17.1a-1982  and  Later  Editions) 

4  in.  min. 


(10) 


1  in.  min 


10  in.  max.,  A17.1a-1982-A17.1-1987. 
9V2  in.  max.,  A17.1a-1988  and  later 


6  in.  max.- 


1  in.  min. 


Step  tread  width  plus  19  in.  max., 
A17.1(a)-1982  through  A17. 1-1987 


Angle: 
20  deg  min. 
30  deg  max. 


Interior  High  Deck 
Balustrade 


22  in.  min. 
40  in.  max. 


S 


D£ 


1  in.  min. 


IV4  in.  max. 


Interior  Low  Deck 
Balustrade 


Width  of  the  escalator  is  the  width  of  the  step  to  the 
next  whole  inch  Requirement  6.1.3.2  (Rule  802.2) 


GENERAL  NOTE:      1  in.  =  25.4  mm. 


Fig.  7.2.3    Checking  Incline 

Straight  edge- 
Level - 


30  deg/60  deg 
triangle 


97 


C 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers.  X^s) 

No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME.     ^ 


ASMEA17.2-2010 


Fig.  7.4.1     Safety  Zone 


(io) 


2W 


■  Handrail 
-  Newel 


-w- 


Safety  Zone 


W+8in. 


dimensions  are  minimums  and  traffic  patterns  may 
require  larger  distances. 

(c)  While  standing  on  the  unit,  verify  that  the  landing 
and  combplates  provide  a  secure  foothold  and  outdoor 
units  should  provide  a  secure  foothold  when  wet. 

7.4.2  Periodic  Test 

7.4.3  Acceptance 

Verify  that  vertical  headroom  clearance  of  7  ft  (2.13  m) 
is  provided  and  that  the  required  safety  zone  is  present. 

Check  that  floor  openings  adjacent  to  the  entire  length 
of  the  wellway  are  protected  in  accordance  with  the 
applicable  building  code. 

7.4.4  References 

A17.1d~2000  and  earlier  editions  —  Rules  802.6  and 
802.12. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.1.3.6,  8.6.8.15,  and  6.1.3.12. 

A17.3  —  Paragraphs  5.5.3  and  5.5.4. 

ITEM  7.5 
LIGHTING 

7.5.1  Periodic  Inspections 

Check  whether  the  lighting  at  the  landing  plates  and 
steps  is  in  compliance  with  the  applicable  code  by  using 
a  light  meter  while  the  escalator  is  operating.  Take  care 
not  to  cast  a  body  shadow  on  the  meter.  Note  any  lamps 
that  are  not  operating  and  their  affect  on  the  escalator 
lighting.  For  escalators  installed  under  A17.1-1987  and 
later  editions  and  A17.3,  lighting  must  be  of  uniform 
intensity  and  not  contrast  materially  with  the  sur- 
rounding area. 

For  escalators  installed  under  A17. 1-1955  through 
1971,  the  minimum  intensity  was  2   fc   (22   lx). 


A17.1a-1979  required  step  tread  lighting  to  be  uniform 
throughout  the  run  and  the  lighting  intensity  to  be  in 
accordance  with  local  codes  and  ordinances  for  stair- 
ways. For  escalators  installed  under  A17. 1-1987  and 
later  editions  and  A17.3,  the  minimum  intensity  of  5  fc 
(54  lx)  is  required.  For  escalators  installed  under  the 
A17.1-1978  to  A17.1a-2005  editions,  verify  that  green 
demarcation  lights  are  present  below  the  steps  at  both 
landings  and  are  on  when  the  escalator  is  in  operation. 

7.5.2  Periodic  Test 

7.5.3  Acceptance 

7.5.4  References 

A17.1d-2000  and  earlier  editions  —  Rules  806.2, 805.7, 
and  1009.2d. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.1.7.2,  6.1.6.7,  and  8.10.4.1.1(e), 

A17.3  —  Paragraphs  2.2.3  and  5.4. 

ITEM  7.6 
CAUTION  SIGNS 

7.6.1  Periodic  Inspections 

For  escalators  installed  under  A17. 1-1981  and  later 
editions  and  escalators  that  are  required  to  comply  with 
A17.3,  verify  that  the  required  caution  signs  are  located 
at  both  landings  readily  visible  to  boarding  passengers. 

For  escalators  installed  under  A17. 1-1993  and  later 
editions,  verify  that  any  additional  signs  are  located  at 
least  10  ft  (3.05  m)  horizontally  from  the  end  of  the 
newels  and  that  they  do  not  impede  traffic  or  otherwise 
cause  persons  to  stop. 

7.6.2  Periodic  Test 

7.6.3  Acceptance 

7.6.4  References 

A17.1d-2000  and  earlier  editions  —  Rule  805.9;  and 
Fig.  805.9a. 

A17.1-2000/B44-00  and  later  editions  — 
Requirement  6.1.6.9;  and  Fig.  6.1.6.9.1. 

A17.3  —  Paragraph  5.3.11. 

ITEM  7.7 
COMBPLATE  AND  COMB  STEP  IMPACT  DEVICE 

7.7.1  Periodic  Inspections 

Inspect  the  comb  for  missing  teeth  and  proper  mesh 
with  each  step  tread  (see  Fig.  7.7.1).  Verify  proper  mesh 
with  each  step  tread  by  holding  a  sheet  of  stiff  paper 
or  a  business  card  where  the  teeth  mesh  with  the  step 
tread,  while  standing  well  back  from  the  plate  to  prevent 
forcing  the  plate  down.  Use  of  an  extension  with  an 
alligator  clip  to  hold  the  card  is  recommended. 


(io) 


98 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


Fig.  7.7.1     Checking  Step/Combplate  Mesh 


Cleated  risers  required 
by  A17. 1-1971  and 
later  editions 


and  mesh  of  vertical  cleats 
with  slots  in  adjacent  step  riser 


Use  business  card  to  verify 
mesh  of  step  tread  and  combplate. 
The  points  of  the  combplate  teeth 
must  be  below  the  upper  surface 
of  the  treads 


Combplate 


Upper  surface  of  tread 


Alligator  clip  holding 
card  on  extension  rod 


/ 


Point  of  combplate 
teeth  below  tread 


NOTE:  Telescoping  pointers  with  alligator  clips  that  are  used  to 
ignite  water  heater  pilot  lights  are  available  in  hardware /plumbing 
supply  stores. 

The  comb  teeth  should  mesh  with  and  set  into  the 
tread  surface  so  that  the  teeth  are  always  below  the 
upper  surface  of  the  treads.  Any  section  with  one  or 
more  missing  or  broken  teeth  should  be  replaced.  For 
escalators  installed  under  A17.1c-1986  and  later  edi- 
tions, the  comb  surfaces  must  contrast  visibly  by  color, 
pattern,  or  texture. 

7.7.2  Periodic  Test 

For  units  installed  under  A17.1b-1992  and  later  edi- 
tions, have  the  operation  of  combplate  impact  devices 
tested  as  follows: 

(a)  Have  a  vertical  force  applied  to  the  center  front 
edge  of  the  combplate  until  the  device  trips.  Record  the 
force  required  to  trip  the  device  and  verify  the  unit  will 
not  start  until  manually  reset. 

(b)  Have  a  force  applied  in  the  direction  of  travel  at 
the  front  center  of  the  combplate,  increasing  the  force 


until  the  device  trips.  Record  the  force  required  to  trip 
the  device  and  verify  the  unit  will  not  start  until  manu- 
ally reset. 

(c)  Have  a  force  applied  in  the  direction  of  travel  on 
one  side  of  the  front  of  the  combplate,  increasing  the 
force  until  the  device  trips.  Record  the  force  required  to 
trip  the  device  and  verify  the  unit  will  not  start  until 
manually  reset.  Repeat  this  test  for  the  opposite  side. 

Note  that  while  the  maximum  horizontal  forces  were 
112  lbf  (500  N)  at  each  side  and  225  Ibf  (1  000  N)  at 
the  center  of  the  combplate  for  escalators  installed  to 
A17.1b-1992  through  A17.1-1996,  it  is  permitted  to  have 
the  maximum  horizontal  forces  at  higher  values  permit- 
ted by  A17.1a-1997  and  later  editions. 


7.7.3  Acceptance 

(a)  Visually  verify  that  the  combplates  are  vertically 
adjustable  and  that  the  sections  forming  the  comb  teeth 
are  replaceable. 


99 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Fig.  7.7.3    Test  of  Combplate/Landing  Plate  Assembly 


Steps 


Test  plate 


350  lb  (159  kg) 


Comb  section 
combplate  and 
landing  plate 
assembly 


77/8in. 


Comb 


117/8in. 


Move  test  plate  and 
weight  to  several 
locations  on  the 
combplate/landing 
plate  along  the 
escalator  centerline 


GENERAL  NOTE:      1  in.  =  25.4  mm. 


(b)  Place  weight  on  the  combplate  and  landing  plate 
assembly  to  verify  that  the  combplate  and  landing  plate 
will  not  contact  the  step  (see  Fig.  7.7.3). 

(io)    7JA  References 

A17.1d-2000  and  earlier  editions  —  Rules  802.6, 
805.3n,  807.3, 1206.6,  (NR  8.6.9.2.3),  1008.2r,  and  1009.2e. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.1.3.6,  6.1.6.3.13,  6.1.8.3,  8.6.8,  8.6.9.2.3, 
8.11.4.2.13,  and  8.10.4.1.1(g). 

A17.3  —  Paragraph  5.1.9. 

ITEM  7.8 
DECK  BARRICADES  AND  ANTISLIDE  DEVICES 

7.8.1  Periodic  Inspections 

For  low  deck  escalators  installed  under  the 
A17.1c-1986  and  later  editions,  check  to  see  that  deck 
barricades  are  firmly  in  place  and  in  good  condition 
at  each  end  when  the  outer  deck  width  exceeds  5  in. 
(127  mm).  The  barrier  must  extend  to  4  in.  (102  mm) 


below  the  handrail  top.  See  Fig.  7.8.1(a).  If  the  escalator 
is  not  located  at  the  edge  of  a  floor  surface,  check  that 
the  barricade(s)  is  in  place,  properly  located,  and  firmly 
secured  on  the  outer  deck  for  escalators  installed  to 
A17.1b-1995  and  later  editions. 

On  high  deck  escalators  installed  under  A17.1-1981 
and  later  editions  and  A17.3,  check  that  antislide 
devices,  where  required,  are  in  place  and  secure.  See 
Fig.  7.8.1(b). 

7.8.2  Periodic  Test 

For  escalators  installed  under  A17.1a-1988  and  later 
editions,  verify  that  glass  and  plastic  replacement  panels 
meet  the  requirements  of  ANSI  Z97.1  or  16  CFR 
Part  1201. 

7.8.3  Acceptance 

All  glass  or  plastic  (glazing  material)  must  be  legibly 
and  permanently  marked  16  CFR  Part  1201,  "American 
National  Standard  Z97.1"  or  the  characters  "ANSI 
Z97.1"  and  shall  be  marked  also  with  the  manufacturer's 
distinctive  mark  or  designation. 


100 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Fig.  7.8.1(a)     Deck  Barricade 


/ 


Wall 

Barrier  between 
escalator  and 
wall 


Barrier  between 
parallel  adjacent 
units 


~X~?  C7~~ 


Typical  Design 
(Other  Designs  Acceptable) 


Fig.  7.8.1(b)    High  Deck  Balustrade  Antislide  Devices 


I      Greater  than  12  in.     I 

h< *i 


101 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Check  that  all  exposed  fastener  heads  are  the  tamper- 
resistant  type. 

7.8.4  References 

A17.1d-2000  and  earlier  editions  —  Rules  802.3i  and 
1009.2f. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.1.3.3.10,  6.1.3.3.11,  8,6.8.11,  and 
8.10.4.1.1(h). 

ITEM  7.9 
STEPS  AND  UPTHRUST  DEVICE 

7.9.1   Periodic  Inspections 

(a)  Mark  one  of  the  steps  with  chalk,  then  run  the 
escalator  through  one  complete  revolution.  Check  that 
each  step  is  present,  clean,  free  of  debris,  and  that  the 
step  treads  and  risers  are  in  good  condition. 

(b)  Check  at  least  every  tenth  step,  by  riding  on  it,  to 
verify  that  the  following  requirements  are  met: 

(1 )  There  is  no  excessive  movement  or  play  in  the 
direction  of  travel,  at  right  angles  to  the  direction  of 
travel  and  vertically.  While  standing  on  the  step,  a  lateral 
shift  of  weight  should  not  cause  the  step  to  strike  the 
skirt  panels. 

(2)  For  escalators  installed  prior  to  A17. 1-1971,  ver- 
ify that  the  clearance  between  step  treads  on  the  hori- 
zontal run  (between  the  step  and  riser)  is  not  more  than 
%2  in.  (4  mm).  A  thickness  gauge  or  a  rule  may  be  used 
for  this  purpose.  With  the  escalator  moving  in  the  up 
direction  lay  the  rule  on  the  step  and  read  the  clearance. 
At  least  every  tenth  step  should  be  checked.  Cleated 
step  risers  are  required  for  all  escalators  installed  under 
A17.1-1971  and  later  editions,  and  they  must  mesh  with 
the  slots  of  adjacent  step  treads.  Mesh  can  be  verified 
by  trying  to  fit  a  thin  piece  of  stiff  paper,  or  business  card, 
between  steps  and  riser  while  the  escalator  is  moving  in 
the  up  direction.  The  check  should  be  made  across  the 
entire  width.  [See  Figs.  7.9.1(a)  and  7.9.1(b).] 

For  escalators  installed  under  A17.1-2000/B44-00  and 
later  editions,  check  that  the  clearance  between  the  steps 
on  the  horizontal  run  does  not  exceed  0.25  in.  (6  mm). 
[See  Fig.  7.9.1(c).] 

(3)  Use  a  level  to  check  if  the  steps  are  horizontal. 

(4)  The  tread  surface  should  be  slotted  in  the  direc- 
tion parallel  to  the  travel  so  that  they  mesh  with  the 
combplate  teeth.  Verify  that  a  cleat  is  formed  adjacent  to 
the  skirt  panel  on  each  side  of  the  step  [see  Fig.  7.9.1(d)]. 

(5)  Check  risers,  cleats,  and  step  tread  surfaces.  Spe- 
cial consideration  should  be  given  to  excessive  clearance 
and  sharp  edges.  While  standing  on  the  step  tread,  verify 
that  it  provides  a  secure  foothold. 

(6)  A  jerking  motion  on  the  steps  and  excessive 
noise  in  the  machinery  space  indicates  that  the  drive 
and  support  system  should  be  examined  to  discover  the 
source  or  cause. 


7.9.2  Periodic  Test  (10) 

For  escalators  installed  under  A17.1b-1980  and  later 
editions  and  those  required  to  comply  with  A  17.3,  have 
the  operation  of  the  step  upthrust  device  tested  as 
follows: 

(a)  With  the  escalator  running  down,  apply  an 
upthrust  force  to  a  step  to  resist  leveling  as  it  enters  the 
lower  curve.  This  should  stop  the  escalator. 

(b)  If  this  will  not  operate  the  upthrust  device,  it 
should  be  checked  more  closely  during  the  internal 
inspection  described  in  Item  8.9.2  and  a  meter  should 
be  used  to  verify  that  the  safety  circuit  is  opened  when 
the  upthrust  device  operates. 

For  escalators  required  to  comply  with  A17.3  that  have 
smooth  risers,  test  the  operation  of  the  upthrust  at  both 
the  upper  and  lower  curves.  Test  the  lower  curve  with 
the  escalator  running  down  and  the  upper  curve  with 
the  escalator  running  up.  This  may  require  two  pair  of 
pliers  gripping  on  both  sides  at  the  front  of  the  step 
tread. 

7.9.3  Acceptance 

Review  fatigue  test  and  certification  for  Code 
compliance. 

Verify  that  there  are  at  least  two  and  no  more  than 
four  flat  steps  at  each  end  of  the  escalator.  Refer  to 
Fig.  7.9.3  for  flat  step  configuration  identification. 

Check  that  the  materials  for  step  frames,  treads,  and 
risers,  including  any  attachments  or  inserts,  meet  Code 
requirements. 

Check  that  all  steps  have  yellow  demarcation  lines  on 
each  side  and  along  the  back.  Check  the  step  dimensions 
for  Code  compliance. 

7.9.4  References 

A17.1d-2000  and  earlier  editions  —  Section  3;  and 
Rules  802.5,  802.6e,  802.9d,  805.3i,  1008.21,  and  1105.1. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  1.3,  6.1.3.5,  6.1.3.6.5,  6.1.3.9.4,  6.1.6.3.9, 
8.11.4.2.9,  8.6.8.6,  8.3.11.1,  and  Fig.  18. 

A17.3  —  Paragraphs  5.1.7  and  5.1.8. 

ITEM  7.10 
OPERATING  AND  SAFETY  DEVICES 

7.10.1  Periodic  Inspections  (10) 

(a)  Starting  Switches.  Verify  that  a  record  of  personnel 
that  were  trained  in  the  proper  procedure  to  start  up  the 
escalator  is  available  on  site.  Verify  that  a  key-operated 
switch,  located  so  that  the  steps  are  within  sight,  is  the 
only  means  of  starting  the  escalator.  Verify  that  the  key 
is  only  accessible  to  authorized  personnel.  A17. 1-1937 
and  later  editions  require  the  use  of  a  key  to  start  an 
escalator.  However,  A17.1a-1988  and  later  editions  and 
A17.3  specifically  prohibit  the  starting  by  automatic 
means.  Start  the  escalator  using  the  key-operated  switch. 


102 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Fig.  7.9.1(a)     Smooth  Riser 


// 


Measurement  of  clearance 
between  skirt  panel  and  step 


/ 


Measurement  of  clearance 
between  vertical  riser  and 
f  /    step  treads  is  5/32  in- 


Skirt  panel 


Vertical  riser 


Step  treads 


Step 


Escalators  Installed  Prior  to  the 
1971  Code  Edition 


When  operating  the  switch,  verify  that  the  escalator 
steps  are  within  sight  and  that  no  one  is  on  the  step. 
Where  the  escalator  can  be  operated  in  both  directions, 
check  the  switch  operation  in  both  directions.  Where 
there  is  more  than  one  key-operated  starting  switch,  the 
function  and  location  of  all  switches  shall  be  checked. 

For  units  installed  under  Al 7. 1-1996  and  later  edi- 
tions, verify  that  the  start  switch  operating  positions  are 
properly  marked.  Check  that  the  key  is  only  removable 
in  the  "RUN"  position.  Turn  the  switch  from  "RUN"  to 
either  "UP"  or  "DOWN"  and  quickly  let  go  of  the  key. 
The  switch  must  return  to  the  "RUN"  position.  Repeat 
for  the  other  direction  of  travel.  Next  turn  the  switch  to 
either  "UP"  or  "DOWN"  position.  Stop  the  unit  with 
the  emergency  stop  button  and  keep  the  switch  in  the 
"UP"  or  "DOWN"  position.  The  unit  must  not  restart. 
Repeat  for  the  other  direction  of  travel. 

(b)  Emergency  Stop  Switches.  Operate  the  emergency 
stop  switches/buttons  and  verify  that  the  escalator 
stops.  Also,  verify  that  the  stop  switch  cannot  start  the 
escalator.  If  automatic  starting  devices  are  provided  (pre- 
A17.1a-1988),  check  that  they  will  not  function  after  the 
stop  switch  is  operated.  Verify  proper  labeling  and  signal 


where  required.  The  requirements  for  emergency  stop 
switches  in  prior  editions  of  the  Code  are  as  follows: 

(1)  A17.1-1955:  An  emergency  stop  button  or  other 
type  of  manually  operated  switch,  marked  "STOP  BUT- 
TON" or  "STOP  SWITCH"  shall  be  conspicuously  and 
accessibly  located  at  or  near  the  top  and  bottom  landing 
of  each  escalator  and  shall  be  protected  from  accidental 
contact. 

(2)  A17. 1-1960:  Emergency  stop  button  or  other 
type  of  manually  operated  switches  having  a  red  button 
or  handle  shall  be  accessibly  located  at  or  near  the  top 
and  bottom  landing  of  each  escalator,  and  shall  be  pro- 
tected against  accidental  operation. 

(3)  A17.1-1965  added:  An  escalator  stop  button 
with  an  unlocked  cover  over  it  that  can  be  readily  lifted 
or  pushed  aside  shall  be  considered  accessible. 

(4)  A17.1a-1979  required  that  the  stop  button  be 
located  in  the  right-hand  newel  base  facing  the  escalator 
at  both  landings.  Handles  were  no  longer  allowed. 

(5)  A17.1b-1983  and  later  editions  required  a 
readily  moveable  self-closing  transparent  cover  and  an 
80  dBA  signal  when  the  cover  is  moved.  The  cover 
should  be  marked  "Emergency  Stop."  The  button  should 


103 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Fig.  7.9.1(b)    Cleated  Riser 


Measurement  of  clearance 
between  skirt  panel  and  step 


Check  the  space  in 
these  positions 

// 

Step  treads  and 
//  vertical  cleats 
must  be  in  mesh 
all  the  time 


Vertical  cleats 


Step  treads 


Step 


(10) 


Fig.  7.9.1(c)    Escalator  Step  Riser 


Cleated  riser  must  mesh 
with  the  adjacent  step 
wherever  the  steps  are  exposed, 
(SeeA17.1/B44  — 6.1.3.5.3.). 


Escalator 
panel 


104 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


Fig.  7.9.1(d)     Escalator  Step  Tread  [A17.1-1955  Through  A17.1-1990,  Rule  802.5  (Requirement  6.13.5)] 


Cleat  required  on  each 
side  of  step  adjacent 
to  skirt 


_  153/4  in. 
min.  run 


V4in.  max. 
slot  width h     H- 


fJMJLllMI 


3/8  in.  max.  slot 
center  to  center 


8V2in. 
max.  rise 


3/8in.  min. 
slot  depth 


GENERAL  NOTE:     1  in.  =  25.4  mm. 


Combplate 


Fig.  7.9.3     Example  of  Two  Flat  Steps 


-  Intersection  of  comb  teeth 
with  step  tread 


105 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers.  ^s| 

No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME.     ^ 


ASME  A17.2-2010 


(10) 


(10) 


be  in  the  upper  right  quadrant  when  facing  the  escalator 
for  high  deck  balustrades,  and  for  low  deck  balustrades 
it  must  be  below  the  handrail  height.  Remote  stop 
switches  were  prohibited  under  A17.1b-1983  and  later 
editions. 

(6)  A17.3:  An  accessible  red  stop  button  marked 
"EMERGENCY  STOP"  must  be  on  the  right-hand  side 
of  each  entrance.  Remote  stop  switches  are  prohibited. 
(c)  Tandem  Operation.  For  escalators  operated  in  tan- 
dem, A17.1-1981  and  later  editions  and  A17.3,  where  a 
common  landing  is  shared  by  two  units,  verify  that  the 
units  are  electrically  interlocked.  The  interlocks  must 
stop  the  unit  carrying  passengers  into  the  common  inter- 
mediate landing,  where  bunching  will  occur,  when  the 
unit  carrying  passengers  away  from  the  landing  stops. 
Also,  verify  that  the  interlocks  assure  that  the  units  run 
in  the  same  direction. 

7.10.2  Periodic  Test 
7.103  Acceptance 

Check  that  the  starting  switches  are  within  reach  of 
an  emergency  stop  button.  Start  the  unit  and  hold  the 
start  switch  in  the  "UP"  position,  then  actuate  the  emer- 
gency stop  button.  The  unit  must  not  restart  until  the 
start  switch  is  placed  in  the  "RUN"  position  and  the 
starting  sequence  is  repeated.  Repeat  this  for  the  down 
direction  and  for  the  other  start  switch. 

For  low  deck  escalators,  check  the  clearances  between 
the  handrail  and  the  stop  switch  enclosure  and  the  dis- 
tance from  the  button  to  the  handrail. 

7.10.4  References 

A17.1d-2000  and  earlier  editions  —  Rules  805.2, 
805.3a,  805.6,  and  (NR  8.6.10.5). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.1.6.2.1,  6.1.6.3.1,  c6.1.6.3.1(a),  6.1.6.6, 
8.6.10.2,  and  8.6.10.5. 

A17.3  —  Paragraphs  5.3.1,  5.3.2,  and  5.3.10. 

ITEM  7.11 
SKIRT  OBSTRUCTION  DEVICE 

7.11.1   Periodic  Inspections 

Test  the  skirt  obstruction  device  for  escalators 
installed  under  A17.1-1971  and  later  editions  and  A17.3, 
by  having  the  person  performing  the  test  manually  trip 
the  skirt  obstruction  device  switches  on  each  side  of 
steps  at  each  landing  while  the  escalator  is  running.  This 
can  be  done  by  placing  an  object  such  as  a  wooden  stick 
between  the  steps  and  the  skirt  as  the  step  moves  by  the 
switch  (see  Fig.  7.11.1).  If  the  switch  activation  requires 
displacement  of  the  skirt  panel,  a  soft  hand-held  rubber 
eraser  can  be  used  to  displace  the  panel  by  holding  it 
so  that  it  will  be  drawn  between  the  step  and  skirt  panel. 
A  rubber  kitchen  spatula  may  also  be  used  for  this.  A 
soft  material  should  always  be  used  to  prevent  damage 


to  the  equipment.  Kicking  the  panel  does  not  verify 
proper  operation  of  the  skirt  switch.  All  four  switches 
should  be  tested. 

For  escalators  installed  under  A17.1b-1983  and  later 
editions,  the  maximum  stopping  distance  should  not 
exceed  the  distance  from  the  location  of  the  switch  to 
the  combplate  for  any  load  up  to  the  rated  load. 

Escalators  installed  under  A17.1-1971  through  1978 
editions  required  skirt  obstruction  devices  only  at  the 
lower  landing.  Prior  to  A17.1-1971  skirt  obstruction 
devices  were  not  required  but  were  sometimes  installed. 
If  they  are  installed,  they  should  be  tested. 

7.11.2  Periodic  Test 

7.11.3  Acceptance 

7.11.4  References 

A17.1d-2000  and  earlier  editions  —  Rule  805.3f. 
A17.1-2000/B44-00     and     later     editions     — 
Requirement  6.1.6.3.6. 
A17.3  —  Paragraph  5.3.7. 

ITEM  7.12 
(RESERVED) 

ITEM  7.13 
EGRESS  RESTRICTION  (ROLLING  SHUTTER)  DEVICE 

7.13.1  Periodic  Inspections 

Where  rolling  shutters  are  provided  to  protect  floor 
openings,  check  that  when  the  shutters  begin  to  close 
power  is  removed  from  the  driving  machine  and  brake, 
and  remains  off  until  the  shutter  is  fully  retracted.  If  the 
shutter  is  power  operated,  the  building  code  may  require 
a  pressure  sensitive  leading  edge  to  reverse  direction 
and  /or  stop  it  when  it  strikes  an  object. 

7.13.2  Periodic  Test 

7.13.3  Acceptance 

7.13.4  References 

A17.1d-2000  and  earlier  editions  —  Rule  805.3g. 
A17.1-2000/B44-00      and      later     editions     — 
Requirement  6.1.6.3.7. 
A17.3  —  Paragraph  5.3.8. 

ITEM  7.14 
SPEED 

7.14.1  Periodic  Inspections 

For  escalators  with  DC  motors  or  variable  frequency 
drive  motor  controls,  perform  a  speed  test.  The  maxi- 
mum permitted  speed  was  125  ft/min  (0.64  m/s)  for 
escalators  installed  under  A17.1d-2000  and  earlier  edi- 
tions, and  100  ft/min  (0.5  m/s)  for  escalators  installed 
under  Al 7. 1-2000 /B44-00  and  later  editions. 


106 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Fig.  7.11.1     Typical  Skirt  Obstruction  Device 


Switch 
plunger 


7.14.2  Periodic  Test 

7.14.3  Acceptance 

Verify  that  the  speed  of  the  escalator  cannot  be 
changed  without  first  stopping  it. 

Verify  that  the  no-load  speed  of  the  escalator  does  not 
exceed  the  maximum  permitted  speed  as  follows: 

(a)  Run  a  tachometer  wheel  along  the  deck,  skirt,  or 
other  stationary  flat  object  when  riding  the  escalator. 

(b)  Use  a  stopwatch  to  time  the  travel  from  one  landing 
to  the  other.  Divide  the  travel  in  feet  (meters)  by  the  time 
in  minutes  (seconds)  to  obtain  the  speed  in  ft/min  (m/s). 


7.14.4  References 

A17.1d-2000  and  earlier  editions  —  Rules  803. 1, 
805.3b,  1008.2O/  and  1009.2o. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.1.4.1,  6.1.6.3.2,  (NR  1008. 2o),  and 
8.10.4.1.2(1). 

ITEM  7.15 
BALUSTRADES 
7.15.1  Periodic  Inspections 

Inspect  the  balustrades  and  note  any  cracked  or  bro- 
ken panels.  Panels  and  fasteners  should  be  smooth  and 


(io) 


107 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


free  of  burrs  and  snag  points.  Interior  panels  or  molding 
must  not  be  raised  or  depressed  by  more  than  \  in. 
(6.4  mm).  Check  that  the  balustrades  are  totally  enclosed 
along  both  exterior  and  interior  lengths,  except  where 
the  handrail  enters  the  newel  base.  For  escalators 
installed  under  the  A17.1a-1982  and  later  editions  and 
A17.3,  if  gaps  exist  between  interior  panels,  they  should 
not  be  wider  than  %6  in.  (4.8  mm)  and  the  edges  should 
be  beveled  or  rounded. 

7.15.2  Periodic  Test 

Check  that  glass  replacement  panels  are  tempered  for 
escalators  installed  under  A17.1-1955,  or  tempered  or 
shatterproof  for  escalators  installed  under  A17.1-1965, 
and  that  glass  or  plastic  replacement  panels  meet  the 
requirements  of  ANSI  Z97.1  or  16  CFR  Part  1201  for 
escalators  installed  under  A17.1-1971  and  later  editions. 

7.15.3  Acceptance 

Verify  that  the  balustrades  are  adequately  supported 
and  meet  the  material,  strength,  and  dimensional 
requirements. 

Glass  or  plastic  (except  plastic  bonded  to  basic  support 
panels),  if  used,  must  meet  the  requirements  of 
ANSI  Z97.1  or  16  CFR  Part  1201  and  properly  marked. 

Check  that  components  not  used  directly  in  connec- 
tion with  the  operation  of  the  escalator  are  not  installed 
on,  in,  or  through  the  escalator. 

Check  that  the  width  between  the  balustrade  interior 
panels  does  not  change  in  the  direction  of  travel. 

7.15.4  References 

A17.1d-2000  and  earlier  editions  —  Rules  802.3  and 
1009.2g;  and  Appendix  D. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.1.3.3, 6.1.3.14,  and  8.10.4.1.1(n);  and  (NR 
Appendix  D). 

A17.3  —  Paragraph  5.1.1. 

ITEM  7.16 
CEILING  INTERSECTION  GUARDS 

(10)    7.16.1   Periodic  Inspections 

Escalators  installed  under  A17.1-1978  and  later  edi- 
tions where  the  clearance  of  the  exterior  deck  and  the 
ceiling  or  soffit  is  12  in.  (305  mm)  or  less  or  where  the 
projected  intersection  of  the  exterior  deck  and  ceiling 
or  soffit  is  24  in.  (610  mm)  or  less  from  the  adjacent 
handrail  centerline,  require  ceiling  intersection  guards. 
This  requirement  was  restricted  to  high  decks  for  escala- 
tors installed  under  A17.1a-1982  and  later  editions  and 
A17.3  (see  Fig.  7.16.1). 

On  low  decks  for  escalators  installed  under 
A17.1a-1982  and  later  editions  and  A17.3,  where  the 
centerline  of  the  handrail  is  14  in.  (356  mm)  or  less  from 
the  ceiling  or  soffit,  guards  are  also  required. 

Inspect  the  guards  for  damage  and  secure  attachment. 


7.16.2  Periodic  Test 

7.16.3  Acceptance 

Verify  that  ceiling  and  soffit  guards  are  correct  size, 
in  place,  and  secure.  Check  that  glass  or  plastic  guards 
are  marked  ANSI  Z97.1  or  16  CFR  Part  1201,  or 
CAN/CGSB  12.1;  CAN/CGSB  12.11;  CAN/CGSB  12.12, 
as  applicable. 

7.16.4  References 

A17.1d-2000  and  earlier  editions  —  Rule  802.3g;  and 
Appendix  D. 

A17.1-2000/B44-00  and  later  editions  — 
Requirement  6.1.3.3.9;  and  (NR  Appendix  D). 

A17.3  —  Paragraph  5.1.3. 

ITEM  7.17 

STEP/SKIRT  CLEARANCES,  PANELS,  AND 

PERFORMANCE  INDEX 

7.17.1  Periodic  Inspections 

Verify  that  the  skirt  panels  are  smooth  for  escalators 
installed  under  A17.1-1971  and  later  editions. 

Check  the  clearance  between  the  skirt  panel  and  the 
step  using  a  thickness  gauge  or  by  laying  a  small  rule 
on  the  edge  of  the  step  to  read  the  distance.  Several 
steps  should  be  checked  through  their  entire  travel.  The 
allowable  clearances  are  as  follows  (see  Fig.  7.17.1): 

(a)  A17.1-1955  through  A17.1d-1970:  not  more  than 
3/16  in.  (4.8  mm)  with  a  total  of  both  sides  not  more  than 
%  in.  (6.4  mm),  except  where  skirt  obstruction  devices 
are  installed  at  the  lower  entrance  for  escalators  installed 
under  the  A17.1-1965  through  A17.1d-1970. 

(b)  A17.1-1971  through  A17.1a-1979  editions:  not 
more  than  %  in.  (9.5  mm)  on  each  side. 

(c)  A17.1b-1980  through  A17.1c-1999  and  A17.3:  not 
more  than  3/16  in.  (4.8  mm)  on  each  side. 

(d)  A17.1d-2000  and  later  editions,  not  more  than 
0.2  in.  (5  mm)  when  25  lbf  (110  N)  is  laterally  applied 
from  the  step  to  the  adjacent  skirt  panel.  Each  side  shall 
be  independently  tested. 

For  escalators  installed  under  A17.1a-1982  through 
A17.1c-1999,  inspect  the  exposed  surface  of  the  skirt 
panel  to  check  whether  it  is  either  made  from  a  low 
friction  material  or  treated  with  a  friction-reducing 
material.  The  skirt  panels  of  escalators  installed  prior 
to  A17.1a-1982  should  also  be  treated  with  a  friction- 
reducing  material.  The  panel  should  be  tested  at  several 
places  during  the  run  and  especially  near  the  transition 
entrance  and  exit.  If  examination  of  the  panels  raises 
a  question  about  the  friction  of  the  skirt  panels,  the 
manufacturer's  recommendation  should  be  requested 
and  compared  to  the  treatment  schedule  if  available.  If 
skirts  are  treated,  examine  the  steps  to  verify  that  fric- 
tion-reducing treatment  has  not  been  applied  on  them. 

Skirt  deflectors,  when  provided,  shall  be  checked  to 
ensure  that  all  fasteners  are  flush  and  tamper  resistant, 


do) 


108 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
I    No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


Fig.  7.16.1     Ceiling  or  Soffit  Guard  [Requirements  6.1.3.3.9  and  6.2.3.3.7  (Rules  802.3g  and  902.3g)] 


Ceiling  soffet,  or 
adjacent  deck 


Handrail 


Guard 


Balustrade 


Moving  Walks,  A17.1-1965      | 
through  A17.1d-1986f 
7  in.  min. 

A17.M987and  later 
editions,  8  in.  min. 


Escalators,  A1 7. 1a-1982 
and  later  editions  and 
A17.3,  8  in.  min. 


Escalators, 
A17.1-1955  through 
A17. 1-1981,  14  in.  min. 


Fig.  7.17.1     Measuring  Gap  Between  Step  and  Skirt 

Skirt 


Use  gauge  to 
measure  gap 
between  skirt 
and  step 


Steps 


109 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


that  rigid  elements  are  smooth,  and  that  exposed  sur- 
faces have  their  low  friction  material  treatment  intact 
and  the  dimensional,  strength,  and  deflection  require- 
ments are  met. 

7.17.2  Periodic  Test 

Visually  inspect  the  condition  of  step/skirt  panel  gap 
while  the  escalator  is  stationary.  Mark  a  step  and  operate 
the  escalator  to  bring  other  steps  into  view  as  required 
until  every  step  on  the  escalator  has  been  examined. 
Document  any  outstanding  conditions,  such  as  step/ 
skirt  gaps,  damaged  steps,  damaged  step  treads,  dam- 
aged skirt  panels,  mismatched  skirt  panel  joints,  or  sharp 
edges  on  the  edge  of  the  step  or  skirt  panel.  Pay  particu- 
lar attention  to  the  gaps  between  the  riser  portion  of 
the  step  and  the  skirt  panel. 

Run  the  escalator  in  its  normal  direction  of  travel  for 
at  least  two  cycles  of  steps.  If  the  escalator  is  operated 
in  both  directions,  run  the  escalator  for  at  least  two 
cycles  of  steps  in  both  the  up  and  down  directions. 
Visually  examine  the  step /skirt  gaps  along  the  entire 
length  of  the  escalator.  Pay  particular  attention  to  the 
gaps  at  the  transitions.  Note  any  abnormal  operation 
of  the  escalator  such  as  jumping  steps,  irregular  step 
movement,  step /skirt  panel  interference,  or  skirt  panel 
misalignments. 

(a)  Step/Skirt  Performance  Index  Test  (Moving  Step). 
Select  two  steps  to  conduct  this  test.  One  step  should 
be  selected  as  a  representative  step.  It  should  appear 
similar  to  the  majority  of  the  other  steps  on  the  escalator. 
A  second  step  should  be  chosen  to  represent  any  unusual 
step  or  group  of  steps.  Steps  that  appear  to  have  been 
replaced,  exhibit  wear,  show  signs  of  damage,  or  move 
in  irregular  ways  are  candidates  for  the  second  test  step. 
If  all  the  steps  appear  similar,  then  the  steps  should  be 
randomly  selected.  In  any  case,  the  test  steps  should  be 
separated  by  at  least  eight  steps. 

If  the  escalator  is  a  "DOWN"  escalator,  or  the  escalator 
is  operated  in  both  directions,  the  test  step  should  be 
moved  to  the  top  of  the  escalator  before  the  curved  skirt 
panels  prior  to  each  test  run,  and  run  down  during  the 
test.  If  the  escalator  is  normally  operated  as  an  "UP" 
escalator,  then  the  test  step  should  be  moved  to  the 
bottom  of  the  escalator  just  before  the  curved  skirt  panels 
prior  to  each  test  run,  and  run  up  during  the  test. 

(1)  Install  the  test  apparatus  on  the  step  to  be  tested. 
Install  a  polycarbonate  test  specimen  on  the  test 
apparatus. 

(2)  Orient  a  frictional  force  transducer  to  match  the 
angle  of  the  skirt  panel  as  shown  in  Fig.  7.17.2. 

(3)  Using  the  test  apparatus  apply  a  25  lbf  (110  N) 
load  between  the  step  and  skirt.  The  load  should  be 
maintained  throughout  the  test, 

(4)  Start  a  new  test  and  begin  acquiring  data  as 
soon  as  the  escalator  is  operating  at  rated  speed.  Data 
obtained  prior  to  the  escalator  operating  at  rated  speed 


Fig.  7.17.2    Angle  of  Skirt  Panel 


Step  nose 


>1  in. 
(25  mm) 


<4  in 
{100  mm) 


<10  in. 
(250  mm) 


is  to  be  discarded.  A  coefficient  of  friction  and  a  loaded 
gap  measurement  should  be  recorded  every  6  in. 
(150  mm)  at  a  minimum. 

(5)  Run  the  escalator  continuously  until  the  test 
step  and  apparatus  reach  the  curved  skirt  panel  at  the 
opposite  end  of  the  escalator.  Stop  collecting  data. 

(6)  Process  the  collected  data. 

(7)  Repeat  steps  (1)  through  (6)  for  both  sides  of 
both  test  steps.  Use  a  new  polycarbonate  test  specimen 
for  each  run.  The  index  values  obtained  should  not 
exceed  the  values  specified  by  ASME  A17.1  and /or 
A17.3  Codes. 

(b)  Loaded  Gap  Test  (Stationary  Step).  This  test  will  be 
conducted  in  the  curved  portions  of  the  escalator  where 
moving  step  testing  was  not  conducted.  The  steps 
selected  for  this  test  can  be  the  same  as  those  used  for 
the  coefficient  of  friction  and  loaded  gap  moving  step 
tests.  The  escalator  should  be  stationary  while  these 
measurements  are  taken. 

(1)  Move  the  step  to  be  tested  to  the  flat  portion 
of  the  escalator  at  the  bottom  of  the  escalator.  The  edge 
of  the  combplate  should  be  approximately  6  in.  (150  mm) 
from  the  edge  of  the  test  step. 

(2)  Install  the  test  apparatus  on  the  step  to  be  tested. 
Install  a  polycarbonate  test  specimen  on  the  portion  of 
the  apparatus  that  touches  the  skirt  panel. 

(3)  Using  the  test  apparatus  apply  a  25  lbf  (110  N) 
load  between  the  step  and  the  skirt. 

(4)  Measure  and  record  the  loaded  gap. 

(5)  Remove  the  25  lbf  (110  N)  load  and  advance 
device  or  escalator  so  that  the  device  moves  approxi- 
mately 12  in.  (300  mm)  further  away  from  the  combplate. 

(6)  Repeat  steps  (3)  through  (5)  until  the  test  appa- 
ratus has  reached  the  point  where  the  coefficient  of  fric- 
tion and  loaded  gap  moving  step  test  begins. 

(7)  Repeat  steps  (1)  through  (6)  for  the  opposite 
skirt  panel. 

(S)  Repeat  the  previous  seven  steps,  but  this  time 
start  at  the  top  of  the  escalator  and  gradually  move  the 


110 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


escalator  down  until  the  apparatus  has  reached  the  area 
where  moving  step  measurements  were  made. 

The  recorded  loaded  gap  measurements  should  not 
exceed  the  values  specified  by  ASME  A17.1  and/or 
ASME  A17.3  Codes. 

7.17.3  Acceptance 

Check  that  the  skirt  panels  extend  to  a  height  of  at 
least  1  in.  (25  mm)  vertically  above  the  step  tread  nose 
line  and  that  they  meet  Code  deflection  requirements. 

7.17.4  References 

A17.1d-2000  and  earlier  editions  —  Rules  802.Se, 
802.3f,  802.3k,  1008.2s,  1008.21,  1206.6b,  and  1206.6c. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.1.3.3.5,  6.1.3.3.6,  (NR  802.3k),  (NR 
1008.2s),  (NR  1008.2t),  8.6.8.4,  and  (NR  1206.6c). 


ITEM  7.18 
OUTDOOR  PROTECTION 

7.18.1  Periodic  Inspections 

For  escalators  installed  under  A17.1a-1988  and  later 
editions,  check  that  the  required  cover  over  the  hori- 
zontal projection  of  the  unit  is  present  and  in  good  condi- 
tion. Verify  that  there  is  no  accumulation  of  snow  or 
freezing  rain  on  the  steps  or  landing  plates. 

7.18.2  Periodic  Test 

Heaters  are  required  for  escalators  installed  under 
A17.1a-1988  and  later  editions  only  if  steps  are  subject 
to  snow  or  freezing  rain.  Check  that  heaters  are  opera- 
tional. Heaters  may  be  located  inside  the  unit  (see 
Item  8.3.2). 

7.18.3  Acceptance 

Check  that  the  cover  extends  outward  from  the  center- 
line  of  the  handrail  such  that  a  line  from  the  edge  of 
the  cover  to  the  handrail  centerline  is  not  less  than  15  deg 
from  the  vertical.  Two  methods  for  checking  this  are 
shown  in  Fig.  7.18.3. 

Check  that  the  landing  plates  and  combplates  have 
provisions  to  provide  a  secure  foothold  when  wet. 

Check  that  all  electrical  components  are  weatherproof, 
that  all  wiring  is  identified  for  use  in  wet  locations,  and 
that  they  are  properly  installed  (gaskets,  seals,  etc.). 

7.18.4  References 

A17.1d-2000  and  earlier  editions  —  Section  807;  and 
Rules  1008.2p  and  1009.2L 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.1.8;  and  8.11.4.2.14  and  8.10.4.1.1(q). 


ITEM  7.19 
MAINTENANCE  RECORDS 

7.19.1  Periodic  Inspections 

Review  the  maintenance  records  and  verify  that  they 
are  available  to  elevator  personnel  and  that  they  are 
legible  and  up  to  date.  They  should  include  the 
following: 

(a)  description  of  maintenance  task  performed  and 
dates 

(b)  description  and  dates  of  examinations,  tests, 
adjustments,  repairs,  and  replacements 

(c)  description  and  dates  of  call  backs  (trouble  calls) 
or  reports  that  are  reported  to  elevator  personnel  by  any 
means,  including  corrective  action  taken 

(d)  verify  that  a  start  up  procedure  is  available  to 
authorized  personnel  (A17.1,  requirement  8.6.10.5) 

(e)  electronic  format  is  acceptable 

7.19.2  Periodic  Test 

7.19.3  Acceptance 

7.19.4  References 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  8.6.1.4,  c8.6.12.2.5,  and  8.6.10.5. 

ITEM  7.20 

EARTHQUAKE  INSPECTION  AND  TESTS  (SEISMIC 

RISK  ZONE  2  OR  GREATER) 

7.20.1  Periodic  Inspections 

7.20.2  Periodic  Test 

Check  the  operation  of  the  seismic  switch  where 
provided. 

7.20.3  Acceptance 

(a)  Verify  that  the  balustrades  are  installed  and  fas- 
tened according  to  the  manufacturer's  drawings. 

(b)  Verify  that  seismic  switch  is  installed  and  if  it  is 
used  exclusively  to  control  the  escalator,  it  is  located  in 
a  machine  room,  machinery  space  and,  where  possible, 
mounted  adjacent  to  a  vertical  load-bearing  member.  If 
there  is  no  vertical  load-bearing  member  in  close  prox- 
imity, it  may  be  located  at  the  nearest  accessible  vertical 
load-bearing  member  at  approximately  the  same  hori- 
zontal level  as  the  upper  machinery  space  or  machine 
room. 

(c)  Verify  that  the  seismic  switch,  when  actuated, 
causes  power  to  be  removed  from  the  escalator  driving 
machine  and  brake. 


(io) 


(10) 


7.20.4  References 

A17.1-2000/B44-00      and 
Requirements  8.5.1  and  8.5.4. 


later     editions     — 


111 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Fig.  7*18.3    Escalator  Cover  Overlap 


c/2/c/l  must  be  0.268  or  more 


Use  a  protractor  to 
measure  either  angle 


15  deg  or  more 


Plumb  line 


Two  Methods  for  Checking  Compiiance 

with  Requirement  6.1.8.2  (Rule  807.2) 

Cover  Requirement 


112 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Part  8 
Escalator  —  Internal 


ITEM  8.1 

MACHINERY  SPACE  ACCESS,  LIGHTING, 

RECEPTACLE,  AND  CONDITION 

8.1.1  Periodic  Inspections 

For  remote  machine  rooms,  see  Item  8.1.2. 

do)    8.1.2  Periodic  Test 

Determine  that  the  means  of  access  is  securely  fas- 
tened in  place.  A17.3b-1995  requires  that  access  plates 
be  fastened  in  place  when  no  more  than  30  lbf  (311  N) 
effort  is  required  to  open  them.  If  a  door  is  used,  verify 
that  it  is  kept  locked  and  the  key  is  available  only  to 
authorized  personnel.  Check  the  lighting  and  test  the 
receptacle.  In  remote  machine  space,  check  that  lighting 
at  floor  level  is  at  least  10  fc  (108  lx)  for  escalators 
installed  under  A17.1-1981  and  later  editions. 

Verify  that  the  space  is  clean  of  dirt  and  rubbish  and 
free  of  oil  and  combustibles.  Items  unrelated  to  escalator 
maintenance  or  operation  shall  not  be  stored  in  machine 
space.  No  lubricant  or  solvent  with  a  flashpoint  less  than 
110°F  (43°C)  shall  be  stored  in  such  space.  Water  should 
not  have  accumulated  on  the  floor  of  the  space.  Verify 
that  jumpers  are  not  stored  in  the  machine  space, 
hoistway,  or  pit.  For  escalators  installed  under 
A17.1-1978  to  A17.1a-2005,  verify  that  the  two  fluores- 
cent demarcation  lamps  are  clean,  green,  and  in  good 
condition  at  each  landing. 

Verify  that  no  penetrations  exist  through  the  sides 
and  undersides  of  the  machinery  space  and  truss  that 
compromises  its  fire  resistance  or  allows  physical  contact 
with  moving  parts. 

For  escalators  installed  under  Al 7. 1-2000 /B44-00  and 
later  editions,  check  that  a  fixed  guard  is  in  place  to 
protect  against  accidental  contact  with  the  moving  steps. 

(10)    8.1.3  Acceptance 

Check  whether  a  reasonable  means  of  access  to  the 
interior  is  provided.  Where  access  plates  are  used,  they 
should  comply  with  the  Code  weight  restrictions. 
Removal  of  the  floor  plates  over  the  landing  pit  consti- 
tutes reasonable  access  if  the  opening  uncovered  affords 
ample  space  for  the  entry  of  one  person.  When  an  access 
door  is  provided  on  the  side  of  the  enclosure,  verify  the 
proper  functioning  of  the  door  key  and  lock  and  that 
the  key  is  only  removeable  in  the  locked  position. 

If  fire  shutters  are  required  by  the  local  building  code, 
verify  that  they  are  present  at  ventilation  openings  and 


operate  correctly.  Verify  that  demarcation  lights  are 
located  within  16  in.  (406  mm)  of  the  combplate,  and 
properly  installed  (see  Item  7.5.1). 

Verify  that  the  15  A,  120  V  duplex  receptacle  is  prop- 
erly located  in  machine  rooms,  under  access  plates  and 
machine  areas  in  the  incline,  are  functional,  and  that  the 
light  control  for  remote  machine  rooms  is  within  easy 
reach  of  the  access  and  can  be  operated  without  reaching 
or  passing  over  any  machinery  components. 

Check  that  components  not  used  directly  in  connec- 
tion with  the  operation  of  the  escalator  are  not  installed 
on,  in,  or  through  the  escalator. 

8.1.4  References 

A17.1d-2000  and  earlier  editions  —  Section  806;  and 
Rules  801.1,  805.7,  1008.2a,  1009.2J,  and  1206.6a. 

A17.1-2000/R44-00  and  later  editions  — 
Requirements  6.1.7;  and  6.1.2.1,  6.1.6.7,  6.1.3.14, 
8.11.4.2.1,  8.10.4.1.2(a),  8.1,  8.6.1.6.3,  c8.6.12.2.6,  8.6.8.14, 
8.6.8.15,  and  8.6.8.13. 

A17.3  —  Paragraph  555. 

ITEM  8.2 

MACHINERY  SPACE  STOP  SWITCHES  AND 

INSPECTION  CONTROL 

8.2.1  Periodic  Inspections 

For  remote  machine  rooms,  see  Item  8.2.2. 

8.2.2  Periodic  Test 

Test  the  operation  of  machine  space  stop  switch (es) 
by  placing  them  in  the  stop  position.  Then,  make  sure 
that  everyone  is  clear  and  attempt  to  start  the  escalator 
with  the  key  switch. 

For  escalators  installed  under  A17.1-2000/B44-00  and 
later  editions,  check  the  operation  of  the  inspection  con- 
trol device  from  each  end.  The  device  only  permits 
movement  by  a  constant  pressure  means,  and  clearly 
indicates  the  direction  of  travel. 

If  a  plug  in  control  station  is  used,  verify  that  it  is 
stored  in  the  upper  landing  machinery  space. 

Have  the  unit  operated  with  the  inspection  control 
device.  Check  that  the  device  only  permits  movement 
by  a  constant  pressure  means  and  clearly  indicates  the 
direction  of  travel. 

8.2.3  Acceptance 

Check  that  stop  switches  are  properly  installed,  cor- 
rectly labeled,  and  operate  correctly  in  all  machine 


(io) 


(10) 


113 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


spaces  or  other  spaces  where  access  to  the  interior  is 
provided.  Where  the  main  line  disconnect  switch  is 
located,  a  separate  stop  switch  is  not  required. 

8.2.4  References 

A17.1d-2000  and  earlier  editions  —  Rules  210.2, 
805.Se,  (NR  6.1.6.2.2),  1008.2b,  and  1009.2k. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.26.2,  6.1.6.3.5,  6.1.6.2.2,  8.11.4.2.2,  and 
8.10.4.1.2(b). 

ITEM  8.3 
CONTROLLER  AND  WIRING 

8.3.1   Periodic  Inspections 

For  remote  machine  rooms,  inspect  as  outlined  in 
Item  8.3.2. 

(io)    8.3.2  Periodic  Test 

Examine  the  controller  visually  to  verify  that  it  is  clean 
and  that  the  switches,  contactors,  and  relays  and  their 
electrical  connections  are  in  good  condition.  Check  that 
the  fuses  are  in  place,  of  the  proper  type  and  rating, 
and  have  not  been  jumped  or  otherwise  tampered  with. 
Check  for  jumper  wires  or  other  changes  which  may 
indicate  that  safety  devices  have  been  defeated  or 
altered.  Visually  examine  wiring  for  damage  and  all 
components  for  evidence  of  overheating.  Operate  the 
main  line  circuit  breakers  or  disconnect  switch  to  verify 
that  all  power  is  removed  from  the  drive  machine. 

Verify  that  all  electrical  components  are  enclosed  to 
prevent  accidental  contact.  If  heaters  are  present  (see 
Item  7.18.2),  verify  that  they  are  operational.  For  escala- 
tors installed  under  A17.1-1965  through  A17.1a-1985, 
verify  that  the  circuit  breakers  will  not  be  automatically 
opened  by  the  fire  alarm. 

(io)    8.3.3  Acceptance 

Check  for  proper  voltage,  correct  wiring,  and  arrange- 
ment of  wiring,  controller,  and  other  components. 

Check  numbering  of  drive  machines  and  disconnects 
where  multiple  drive  machines  are  in  a  machine  room. 
Verify  that  disconnects  are  in  sight  of  machines  operated. 
Inspect  all  wiring  enclosure  raceways  conduit,  electrical 
metallic  tubing,  metal  wireways,  junction  boxes  for  con- 
dition, workmanship,  and  fastening. 

Visually  inspect  condition  of  weatherproof  electrical 
enclosure  where  required  on  outdoor  units.  Verify  that 
use  of  flexible  conduit,  armored  cable,  and  flexible  leads 
complies  with  the  applicable  code  requirements. 

The  person  or  firm  installing  the  escalator  must  pro- 
vide a  manufacturer's  written  procedure  and  demon- 
strate compliance  with  6.1.6.10  or  6.2.6.9.  Where  there 
are  no  test  or  check  requirements,  the  written  checklist 
must  state  "No  test  or  check  required/'  The  documenta- 
tion must  state  the  reason  no  test  or  check  is  required. 


This  procedure  may  also  be  part  of  the  maintenance 
control  program  (MCP)  as  required  by  8.6.1.2.1. 

The  following  shall  be  documented  or  demonstrated: 

(a)  completion  or  maintenance  of  circuit  (6.1.6.13) 

(b)  redundancy  and  its  checking  (6.1.6.10.1  and 
6.1.6.10.2) 

(c)  static  control  (6.1.6.10.3) 

(d)  electrically  powered  safety  devices  (EPD) 
(6.2.6.10) 

(e)  installation  of  devices  to  make  electrical  protective 
devices  (EPD)  ineffective  (6.2.6.11) 

(f)  contactors  and  relays  for  use  in  critical  operating 
circuits  (6.1.6.14) 

Also  include  documentation  when  required  by 
A17.7-2007/B44.7-07and  later  editions  — Requirements 
2.10.1  and  2.10.2. 

8.3.4  References 

A17.1d-2000  and  earlier  editions  —  Sections  806  and 
807.2,  805.10b,  805.12,  1101,  1206.1,  1008.2c,  1009.21, 
1009.2,  and  (NR  10.3.3). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.1.7;  6.1.8.2,  6.1.6.10,  6.1.6,13,  8.3.3, 
8.6.1.2.1,  8.11.4.2.3,  8.10.4.1.2(c),  and  10.3.3. 

A17.1a-2008  —  Requirement  8.11.4.2  redesignated  as 
8.6.8.15. 


ITEM  8.4 
DRIVE  MACHINE  AND  BRAKE 

8.4.1  Periodic  Inspections 

8.4.2  Periodic  Test 

Verify  that  the  driving  machine  is  properly  secured, 
lubricated,  clean,  and  in  good  condition.  Visually  check 
the  driving-machine  fastenings  and  bearing  caps  to  ver- 
ify that  they  are  tight. 

Verify  that  the  driving  machine  is  connected  to  the 
main  drive  shaft  by  toothed  gearing,  a  mechanical  cou- 
pling, or  a  chain  and  that  it  is  in  good  condition.  Look 
for  evidence  of  any  excessive  backlash  in  the  driving 
gears  or  chains.  If  a  chain  is  used  to  connect  the  driving 
machine  to  a  sprocket  on  the  main  drive  shaft,  visually 
examine  the  chain  and  sprockets  for  wear,  excessive 
slack,  and  proper  lubrication.  Lack  of  lubrication  for  a 
chain  may  be  indicated  by  rouge  (red  rust  deposits)  on 
the  side  plates  of  the  links. 

For  escalators  installed  under  A17.1a-1988  and  later 
editions,  verify  that  cast  iron  links  are  not  used.  If  the 
links  appear  to  be  cast  iron,  have  a  small  hole  drilled 
(in  a  low  stress  area)  and  observe  the  drill  cuttings.  If 
the  cuttings  are  a  fine  powder,  cast  iron  is  indicated.  If 
the  cuttings  are  shavings,  then  the  links  are  not  cast  iron. 

Inspect  any  drive  belts  and  sheaves  for  damage  and 
wear.  Check  for  proper  belt  tension  and  reasonable 
equality  of  tension  in  a  set  of  belts. 


(10) 


(10) 


114 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


A5MEA17.2-2010 


Visually  examine  the  components  for  signs  of  over- 
heating. Verify  that  an  electrically  released  brake  is  pres- 
ent and  automatically  applied  when  power  is 
interrupted.  It  is  to  be  located  on  the  driving  machine 
for  units  installed  under  A17. 1-1955  through 
A17.1a-1957  and  A17.1c-1986  and  later  editions.  Other 
editions  allowed  the  brake  to  be  on  the  main  drive  shaft. 

For  escalators  installed  under  A17.1b-1983  and  later 
editions,  verify  that  the  driving-machine  brake  is  located 
on  the  gear  reducer  of  main  drive  shaft  if  means  other 
than  a  continuous  shaft  mechanical  coupling  or  toothed 
gearing  is  used  to  connect  the  motor  to  the  gear  reducer. 

For  escalators  installed  under  A17.1b-1983  and  later 
editions  and  A17.3,  the  brake  may  be  magnetically 
applied  using  a  ceramic  permanent  magnet.  Prior  to 
this,  a  mechanically  applied  brake  was  required.  Visually 
inspect  the  condition  of  the  brake  pads,  drums,  and 
discs. 

For  escalators  installed  to  A17.1b-1983  and  later  edi- 
tions, this  brake  must  stop  a  down-running  escalator 
with  a  retardation  not  exceeding  3  ft/s2  (0.91  m/s2).  For 
escalators  installed  to  A17.1b-1983  through  A17.1-2000, 
this  was  a  maximum  rate.  For  escalators  installed  to 
A17.1a-2002  and  later  editions,  it  is  an  average  rate,  but 
there  is  an  additional  restriction  on  the  peak  horizontal 
retardation,  which  is  not  intended  to  be  field  verified. 

It  is  not  required  to  measure  the  actual  retardation. 
Instead,  the  brake  torque  will  provide  verification  that 
those  requirements  are  met  in  addition  to  other  brake 
requirements  (e.g.,  stopping  and  holding  the  rated  load). 

Visually  inspect  all  mechanisms  for  condition  and 
operation. 

Verify  that  escalators  installed  under  A17.1b-1983  and 
later  editions  have  a  nameplate  or  data  plate  that  speci- 
fies the  required  brake  torque.  Escalators  installed  under 
A17.1a-1988  and  later  editions  require  that  the  name- 
plate  or  data  plate  torque  be  specified  as  breakaway,  the 
maximum  torque  required  to  cause  the  brake  to  begin 
moving,  or  dynamic,  the  torque  required  to  keep  the 
shaft  moving  very  slowly  at  a  steady  rate.  The  location 
where  the  torque  is  to  be  measured  is  required  to  be 
clearly  indicated. 

For  escalators  installed  under  A17.1a-1991  and  later 
editions,  the  nameplate  or  data  plate  is  required  to  spec- 
ify the  range  of  brake  torque.  For  escalators  installed  to 
A17. 1-2000  and  later  editions,  it  must  also  indicate  the 
minimum  distance  from  the  skirt  obstruction  device  to 
the  combplate. 

For  escalators  installed  to  A17. 1-2004  and  later  edi- 
tions, it  must  also  indicate  the  type  of  brake  (fixed  or 
variable).  While  the  range  of  brake  torque  is  still  required 
to  be  indicated  for  fixed  torque  brakes,  for  variable 
torque  brakes  the  minimum  brake  torque  for  a  loaded 
escalator  and  minimum  stopping  distance  for  an 
unloaded  escalator  must  be  indicated. 


Have  the  torque  tested  to  verify  that  the  torque  com- 
plies and  check  the  minimum  stopping  distance  for  vari- 
able torque  brakes.  Note  that  temperature  can  affect  the 
brake  torque. 

The  torque  wrench  should  have  a  current  calibration 
certificate  traceable  to  the  National  Bureau  of  Standards 
and  have  a  range  of  at  least  25%  higher  than  the  required 
torque. 

If  the  driving-machine  brake  is  separated  from  the 
main  drive  shaft  by  a  chain,  check  for  the  presence  of 
a  second  brake  that  is  required  on  the  main  drive  shaft. 
The  requirements  for  this  additional  brake  on  the  main 
drive  shaft  are: 

(a)  A17.1-1960  through  A17.1a-1982  required  that  it 
be  electrically  released  if  an  electrically  released  brake 
was  not  provided  on  the  driving  machine. 

(b)  A17.1-1955  through  A17.1a-1982  required  that  it 
be  mechanically  applied,  while  A17.1b-1983  and  later 
editions  required  that  it  be  either  mechanically  or  mag- 
neticaly  (ceramic  permanent  magnet)  applied. 

(c)  A17.1b-1983  through  A17.1d-2000  required  that 
it  stop  a  down-running  escalator  with  rated  load  at  a 
rate  not  to  exceed  3  ft/ sec2  (0.91  m/s2). 

(d)  A17.3  requires  the  brake  to  be  mechanically  or 
magnetically  (permanent  magnet)  applied  and  capable 
of  stopping  a  down-running  escalator  with  rated  load. 

8.4.3  Acceptance 

Check  the  certification  for  the  driving-machine  brake. 

Check  the  stopping  distance  with  no  load.  Compare 
this  with  the  minimum  stopping  distance  and  the  mini- 
mum distance  from  the  skirt  obstruction  devices  to  the 
combplate  against  the  information  on  the  data  plate. 

Check  the  brake  certification. 

8.4.4  References 

A17.1d-2000  and  earlier  editions  —  Section  804;  and 
Rule  1008.2d. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.1.5;  and  8.11.4.2.4. 

A17.3  —  Section  5.2. 


ITEM  8.5 
SPEED  GOVERNOR 

8.5.1  Periodic  Inspections 

8.5.2  Periodic  Test 

When  a  speed  governor  is  required,  test  it  to  verify 
that  it  is  functioning.  Manually  operate  the  switch  or 
use  any  testing  mechanisms  (such  as  flywheel  weights) 
that  may  be  provided.  The  flyballs  and  all  operating 
mechanisms  must  be  present  and  in  good  operating 
condition.  When  the  switch  is  opened,  it  should  inter- 
rupt power  to  the  driving  machine.  For  escalators 
installed  under  A17.1-1990  and  later  editions,  verify 


115 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


that  the  escalator  cannot  be  started  by  the  starting  switch 
until  the  device  is  manually  reset. 

When  a  manual  reset  is  required  for  units  installed 
under  A17.1b-1995  and  later  editions,  turn  the  power 
off  and  then  back  on,  and  then  try  the  start  switch  to 
check  that  the  device  will  not  reset.  Also,  some  indication 
that  the  device  has  been  activated  needs  to  be  provided 
(fault  finder,  etc.). 

8.53  Acceptance 

When  an  overspeed  governor  is  required,  verify  that 
it  activates  at  the  proper  speed,  which  cannot  be  more 
than  40%  above  the  rated  speed.  This  can  be  done  using 
a  rubber  drive  wheel  driven  by  a  variable  speed  drill 
and  a  tachometer.  Other  methods  approved  by  the  man- 
ufacturer for  field  testing  may  be  used. 

8.5.4  References 

A17.1d-2000  and  earlier  editions  —  Rules  805.3b, 
1008.2e,  and  1009.2m. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.1.6.3.2,  8.11.4.2.5,  and  8.10.4.1.2(e). 

A17.3  —  Paragraphs  5.3.3  and  5.3.5. 

ITEM  8.6 

BROKEN  DRIVE  CHAIN  AND 

DISCONNECTED  MOTOR  SAFETY  DEVICE 

8.6.1  Periodic  Inspections 

8.6.2  Periodic  Test 

(a)  If  the  driving  machine  is  connected  to  the  main 
drive  shaft  by  a  chain,  check  the  broken  drive  chain 
device  to  verify  that  it  will  apply  the  main  shaft  brake 
and  stop  the  drive  machine  if  the  drive  chain  parts.  All 
parts  of  the  device  should  be  in  good  condition  and 
show  freedom  to  move.  Have  the  switch  manually  oper- 
ated and  verify  that  it  will  open  the  drive  motor  circuit. 
Common  devices  include  a  block  that  is  held  in  tension 
by  the  drive  chain  that  activates  the  switch  when  tension 
is  lost,  or  a  plate  that  depresses  a  switch  when  the  drive 
chain  strikes  it.  For  escalators  installed  under 
A 17. 1-1 990  and  later  editions,  verify  that  the  escalator 
cannot  be  started  by  the  starting  switch  until  the  device 
is  manually  reset. 

When  a  manual  reset  is  required  for  units  installed 
under  A17.1b-1995  and  later  editions,  turn  the  power 
off  and  then  back  on,  and  then  try  the  start  switch  to 
check  that  the  device  will  not  reset.  Also,  some  indication 
that  the  device  has  been  activated  needs  to  be  provided 
(fault  finder,  etc.). 

(b)  If  the  drive  motor  is  attached  to  a  gear  reducer 
by  means  other  than  a  continuous  shaft,  coupling,  or 
toothed  gearing,  check  that  the  device  provided  will 
apply  the  brake  if  the  motor  becomes  disconnected  from 
the  gear  reducer.  Have  the  switch  manually  operated 
and  verify  that  all  operating  mechanisms  are  present, 


clean,  lubricated,  and  in  good  condition.  For  escalators 
installed  under  Al 7. 1-1990  and  later  editions,  verify 
that  the  escalator  cannot  be  started  by  the  starting  switch 
until  the  device  is  manually  reset. 

When  a  manual  reset  is  required  for  units  installed 
under  A17.1b-1995  and  later  editions,  turn  the  power 
off  and  then  back  on,  and  then  try  the  start  switch  to 
check  that  the  device  will  not  reset.  Also,  some  indication 
that  the  device  has  been  activiated  needs  to  be  provided 
(fault  finder,  etc.). 

8.6.3  Acceptance 

8.6.4  References 

A17.1d-2000  and  earlier  editions  —  Rules  804.3b, 
805.3d,  805.3J,  and  1008.2f. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.1.5.3.2,  6.1.6.3.4,  6.1.6.3.10,  and 
8.11.4.2.6. 

A17.3  —  Paragraphs  5.3.5  and  5.3.6. 


ITEM  8.7 
REVERSAL  STOP  SWITCH 

8.7.1  Periodic  Inspections 

8.7.2  Periodic  Test 

Manually  operate  the  device  and  verify  that  all 
operating  mechanisms  are  present  and  in  good  condition 
and  that  the  device  will  open  the  circuits  to  the  driving- 
machine  motor  and  brake  to  stop  an  ascending  escalator 
from  reversing  its  direction  of  travel.  For  escalators 
installed  under  A17. 1-1990  and  later  editions,  verify  that 
the  escalator  cannot  be  started  by  the  starting  switch 
until  the  device  is  manually  reset. 

When  a  manual  reset  is  required  for  units  installed 
under  A17.1b-1995  and  later  editions,  turn  the  power 
off  and  then  back  on,  and  then  try  the  start  switch  to 
check  that  the  device  will  not  reset.  Also,  some  indication 
that  the  device  has  been  activated  needs  to  be  provided 
(fault  finder,  etc.). 

There  are  several  different  types  of  devices  that  are 
used  (friction  reversal  devices,  speed  monitoring,  etc.). 
Therefore,  the  type  of  device  will  dictate  the  testing 
procedure.  If  the  device  cannot  be  manually  operated, 
a  written  procedure  must  be  provided  by  the  person  or 
firm  performing  the  tests. 

8.7.3  Acceptance 

8.7.4  References 

A17.1d-2000  and  earlier  editions  —  Rules  805.3h  and 
1008.2g. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.1.6.3.8,  8.10.4.1.2(g),  and  8.11.4.2.7. 

A17.3  —  Paragraphs  5.3.5  and  5.3.9. 


116 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


ITEM  8.8 
BROKEN  STEP  CHAIN  DEVICE 

8.8.1  Periodic  Inspections 

8.8.2  Periodic  Test 

Manually  operate  the  broken  step  chain  devices  to 
verify  that  each  will  interrupt  power  to  the  driving 
machine  and  brake.  Visually  inspect  each  device  to  ver- 
ify that  they  are  in  position  to  operate  and  will  activate 
when  either  step  chain  breaks,  and  (where  automatic 
tensioning  is  not  provided)  when  excessive  sag  occurs 
in  either  step  chain.  For  escalators  installed  under 
A17.1-1990  and  later  editions,  verify  that  the  escalator 
cannot  be  started  by  the  starting  switch  until  the  device 
is  manually  reset. 

When  a  manual  reset  is  required  for  units  installed 
under  A17.1b-1995  and  later  editions,  turn  the  power 
off  and  then  back  on,  and  then  try  the  start  switch  to 
check  that  the  device  will  not  reset.  Also,  some  indication 
that  the  device  has  been  activated  needs  to  be  provided 
(fault  finder,  etc.). 

8.8.3  Acceptance 

8.8.4  References 

A17.1d-2000  and  earlier  editions  —  Rules  805.3c  and 
1008.2h. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6,1.6.3.3  and  8.11.4.2.8. 

A17.3  —  Paragraphs  5.3.4  and  5.3.5. 


ITEM  8.9 
STEP  UPTHRUST  DEVICE 

8.9.1  Periodic  Inspections 

(10)    8.9.2  Periodic  Test 

The  operation  of  the  upthrust  device  was  tested  dur- 
ing the  external  inspection  and  test  in  Item  7.9.2.  While 
the  steps  are  removed  (Item  8.12.2),  manually  move  the 
mechanism  and  visually  inspect  the  components  of  the 
upthrust  device.  Visually  examine  the  upthrust  tabs  on 
each  step  for  damage,  alignment,  and  attachment  (see 
Fig.  8.9.2). 

8.9.3  Acceptance 

8.9.4  References 

A17.1d-2000  and  earlier  editions  —  Rules  805.3i  and 
1008.2L 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.1.6.3.9  and  8.11.4.2.9. 

A17.3  —  Paragraph  5.1.7. 


ITEM  8.10 
MISSING  STEP  DEVICE 

8.10.1  Periodic  Inspections 

8.10.2  Periodic  Test 

For  escalators  installed  under  A17.1b-1989  and  later 
editions,  test  the  missing  step  device  by  running  the 
escalator  with  a  step  missing  on  the  underside  of  the 
escalator.  The  device  must  stop  the  escalator  before  the 
gap  resulting  from  the  missing  step  emerges  from  the 
combplate. 

For  escalators  installed  under  A17.1-1990  and  later 
editions,  verify  that  the  escalator  cannot  be  started  by 
the  starting  switch  until  the  device  is  manually  reset. 

When  a  manual  reset  is  required  for  units  installed 
under  A17.1b-1995  and  later  editions,  turn  the  power 
off  and  then  back  on,  and  then  try  the  start  switch  to 
check  that  the  device  will  not  reset.  Also,  some  indication 
that  the  device  has  been  activated  needs  to  be  provided 
(fault  finder,  etc.). 


8.10.3  Acceptance 

8.10.4  References 

A17.1d-2000  and  earlier  editions 
1008.2). 


do) 


Rules  805.5  and 


editions 


A17.1-2000/B44-00     and     later 
Requirements  6.1.6.5  and  8.11.4.2.10. 

ITEM  8.11 
STEP  LEVEL  DEVICE 

8.11.1  Periodic  Inspections 

8.11.2  Periodic  Test 

For  escalators  installed  under  A17.1-1990  and  later 
editions,  visually  inspect  the  step  level  devices  at  each 
end  and  on  both  sides  to  verify  that  it  is  in  place  and 
able  to  function.  Have  the  switch  manually  operated  to 
verify  that  it  will  open  the  safety  circuit  and  stop  the 
escalator. 

For  escalators  installed  under  A17. 1-1990  and  later 
editions,  verify  that  the  escalator  cannot  be  started  by 
the  starting  switch  until  the  device  is  manually  reset. 

When  a  manual  reset  is  required  for  units  installed 
under  A17.1b-1995  and  later  editions,  turn  the  power 
off  and  then  back  on,  and  then  try  the  start  switch  to 
check  that  the  device  will  not  reset.  Also,  some  indication 
that  the  device  has  been  activated  needs  to  be  provided 
(fault  finder,  etc.). 

8.11.3  Acceptance 

Have  the  devices  tested  (at  both  ends  and  on  each 
side)  by  mechanically  lowering  a  step  \  in.  (3.2  mm) 
and  operating  the  escalator.  A  smaller  roller  or  adjust- 
ment may  be  used  to  lower  the  step. 


117 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Fig.  8.9.2    Typical  Step  Upthrust  Device 


Pivot 


Step  hooks 


Upthrust  switch 


8.11.4  References 

A17.1d-2000  and  earlier  editions  —  Rules  805.3k, 
1008.2k,  and  1009.2n. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.1.6.3.11,  8.11.4.2.11,  and  8.10.4.1.2(k). 

ITEM  8.12 
STEPS,  STEP  CHAINS,  AND  TRUSSES 

8.12.1  Periodic  Inspections 

8.12.2  Periodic  Test 

Have  at  least  half  of  the  steps  removed,  then  move 
the  remaining  steps  to  the  upper  half  of  the  escalator 
(see  Fig.  8.12.2).  Some  escalators  use  the  steps  as  the 
side  guide  means  and  require  every  sixth  step  to  be  left 
in  to  prevent  the  chain  from  falling  off.  Using  a  good 
light  visually  inspect  the  drip  pans,  undersides  of  steps, 
trusses,  roller  tracks,  chains,  handrails,  and  the  interiors 
of  balustrades,  skirts,  and  newels.  Verify  that  they  are 
present,  in  good  condition,  clean  of  dirt  and  rubbish, 
and  free  of  oil  and  combustibles.  Visually  inspect  for 
any  damage  to  the  fire-resistive  material  on  the  escalator 
enclosure  (see  Item  8.1). 

Visually  inspect  the  chains  for  lubrication  and  buildup 
of  dirt  and  grease.  Lack  of  lubrication  may  be  indicated 
by  rouge  (red  rust  deposits)  on  the  side  plates  of  the 
links. 

Verify  that  cast  iron  links  are  not  used  on  escalators 
installed  under  A17. 1-1978  and  later  editions.  See 
Item  8.4.2  for  method  of  identifying  cast  iron. 

Check  the  operation  of  any  escalator  step-chain  ten- 
sion devices.  If  they  are  of  the  automatically  operated 
"tension-weight"-type,  verify  that  the  truss  is  provided 
with  a  positive  means  to  retain  the  weights  in  the  truss 
if  the  weights  are  released. 


Move  the  remaining  steps  to  the  lower  half  of  the 
escalator  and  inspect  the  upper  half  in  the  same  manner 
(see  Fig.  8.12.2). 

Inspect  each  of  the  steps  for  evidence  of  structural 
damage,  condition  of  the  step  rollers  and  upthrust  tabs 
and  material.  Verify  that  the  step  tread  material  is  non- 
combustible  or  that  the  undersides  are  properly  covered 
with  fire-resistive  materials.  Escalators  installed  under 
A17.1-1955  through  A17.1-1993  required  that  step 
frames  be  made  of  noncombustible  materials. 
A17.1a-1994  and  later  editions  specifically  required  that 
step  frames,  treads,  and  risers,  excluding  any  attach- 
ments or  inserts,  be  made  of  metal  (except  magnesium 
alloys)  or  meet  certain  flammability  requirements. 

8.12.3  Acceptance 

Verify  that  if  the  tracking  system  fails,  the  running 
gear  is  retained  in  its  guides  and  the  step  wheel  tracks 
will  prevent  displacement  of  the  steps  and  running  gear 
if  the  chain  breaks. 

Verify  that  foreign  material  such  as  stone  or  concrete 
is  not  in  the  truss  interior. 

If  the  step  rollers  are  not  located  directly  under  the 
step  (i.e.,  located  past  the  edges  of  the  sides  of  the  steps), 
then  check  that  provisions  (e.g.,  unistrut,  c-channel)  are 
made  to  prevent  the  step  from  falling  into  the  truss/ 
step  band  upon  the  loss  of  the  step  roller  assemblies. 

Check  that  components  not  used  directly  in  connec- 
tion with  the  operation  of  the  escalator  are  not  installed 
on,  in,  or  through  the  escalator. 

8.12.4  References 

A17.1d-2000  and  earlier  editions  —  Rules  801.1, 802.7, 
802.8,  802.11,  806.3,  1008.21,  1009.2o,  and  1206.6. 


118 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Fig.  8.12.2    Positioning  of  Steps  for  Inspection  of  Truss 


A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.1.2.1,  6.1.3.5.8,  6.1.3.7,  6.1.3.8,  6.1.3.11, 
6.1.3.1.4,  6.1.7.3,  8.11.4.2.12,  8.10.4.1.2(1),  and  8.6.8. 

ITEM  8.13 
HANDRAIL  SYSTEMS  AND  SAFETY  DEVICES 

8.13.1  Periodic  Inspections 

(10)    8.13.2  Periodic  Test 

Examine  the  handrail  drive  systems  to  ensure  that  all 
chains,  pulleys,  gears,  rollers,  and  belts  are  present  and 
in  good  condition.  The  operation  should  be  free  of  exces- 
sive noise  and  slack,  which  indicates  wear. 

(a)  For  escalators  installed  under  A17.1a-1988 
through  A17.1b-1992,  test  the  operation  of  the  stopped 
handrail  device.  Have  the  handrail  motion  sensor 
mechanically  disconnected  while  the  unit  is  off  and  then 
run  the  unit,  or  grab  the  handrail  and  stall  it  while 
the  escalator  is  running.  Verify  that  the  alarm  sounds 
immediately  and  the  escalator  stops  within  15  sec. 

(b)  For  escalators  installed  under  A17. 1-1993  and 
later  editions,  check  the  operation  of  the  handrail  speed 
monitoring  device.  An  alarm  must  sound  immediately 


if  the  speed  of  either  handrail  deviates  from  the  step 
speed  by  15%  or  more,  and  the  unit  must  shut  down  if 
the  speed  deviation  is  continuous  for  2  sec  to  6  sec.  If 
holding  the  moving  handrail  cannot  activate  the  device, 
then  it  will  be  necessary  to  activate  the  device  by  another 
means  (disconnecting  the  speed  sensor,  changing  dip 
switch  settings  on  the  controller,  etc.).  Verify  that  the 
unit  cannot  be  started  until  the  device  is  manually  reset. 
For  units  installed  under  A17.1b-1995  and  later  editions, 
turn  the  power  off  and  then  back  on  and  then  try  the 
start  switch  to  check  that  the  device  will  not  reset.  Also, 
some  indication  that  the  device  has  been  activated  needs 
to  be  provided  (fault  finder,  etc.). 

(c)  For  escalators  installed  under  A17.1b-1992  and 
later  editions,  test  the  operation  of  the  handrail  entry 
device  by  having  a  soft  object  that  will  not  damage  the 
unit  inserted  between  the  handrail  and  hand  guard. 
After  the  unit  stops,  verify  that  it  cannot  be  restarted 
with  the  key  switch  until  the  device  has  been  manually 
reset.  The  device  need  only  operate  in  the  direction  of 
the  handrail  travel,  except  for  units  installed  under 
A17.1-1996  and  later  editions,  the  device  must  operate, 
irregardless  of  the  direction  of  travel  of  the  handrail 
where  an  opening  is  created  in  the  balustrade  to  prevent 


119 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers, 
v     No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


entrapment.  When  a  manual  reset  is  required  for  units 
installed  under  A17.1b-1995  and  later  editions,  turn  the 
power  off  and  then  back  on  and  then  try  the  start  switch 
to  check  that  the  device  will  not  reset.  Also,  some  indica- 
tion that  the  device  has  been  activated  needs  to  be  pro- 
vided (fault  finder,  etc.). 

8.13.3  Acceptance 

(10)    8.13.4  References 

A17.1d-2000  and  earlier  editions  —  Rules  802.4, 
802.11, 805.4, 805.3m,  (NR  8.6.8.1),  1008.2m,  1008.2q,  and 
1009.2c. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.1.3.4,  6.1.3.11,  6.1.6.4,  6.1.6.3.12,  8.6.8.1, 
8.11.4.2.13,  8.11.4.2.18,  and  8.10.4.1.1(c). 


ITEM  8.14 
CODE  DATA  PLATE 

8.14.1  Periodic  Inspections 

Check  that  the  Code  Data  Plate  is  installed.  This  is 
the  Code  that  is  to  be  used  for  the  inspection  and  test. 

8.14.2  Periodic  Test 

8.14.3  Acceptance 

8.14.4  References 

A17.1d-2000  and  earlier  editions  —  Rules  808,  908, 
and  1200.6. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  8.9,  8.9,  and  8.7.1.8. 

ITEM  8.15 
RESPONSE  TO  SMOKE  DETECTORS 

8.15.1  Periodic  Inspections 

8.15.2  Periodic  Test 

For  units  installed  under  A17.1a-1994  and  later  edi- 
tions, when  smoke  detectors  are  provided  that  will  shut 
down  a  running  unit,  verify  that  the  emergency  stop 
button  alarm  will  sound  and  the  unit  does  not  shut  down 
for  at  least  15  s.  The  unit  may  be  tested  by  activating  the 
smoke  detector  or  by  other  means. 

CAUTION:     If  the  sensing  system  is  connected  to  a  central  fire 
alarm  system,  notify  proper  authorities  before  activating. 

8.15.3  Acceptance 

8.15.4  References 

A17.1d-2000  and  earlier  editions  —  Rule  805.8. 
A17.1-2000/B44-00      and      later      editions     — 
Requirement  6.1.6.8. 


ITEM  8.16 
STEP  LATERAL  DISPLACEMENT  DEVICE 

8.16.1  Periodic  Inspections 

8.16.2  Periodic  Test 

For  curved  escalators,  manually  actuate  the  device  on 
the  stopped  escalator.  Verify  that  the  starting  switch 
cannot  start  the  escalator  until  the  device  is  manually 
reset. 

8.16.3  Acceptance 

8.16.4  References 

A17.1d-2000  and  earlier  editions  —  Rules  805. 3p, 
1003.2b(20). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.1.6.3.14,  8.11.4.2.21,  and  8.10.4.1.2(r). 


ITEM  8.17 
INSPECTION  CONTROL 

8.17.1  Periodic  Inspections 

8.17.2  Periodic  Test 

If  provided,  check  the  operation  of  the  inspection  con- 
trol device.  Check  that  the  device  only  permits  move- 
ment by  a  constant  pressure  means,  and  clearly  indicates 
the  direction  of  travel.  If  a  plug-in  control  station  is  used, 
verify  that  it  is  stored  in  the  upper  pit. 

8.17.3  Acceptance 

Verify  that  when  the  transfer  switches  located  at  each 
landing  are  enabled,  only  the  inspection  control  device 
can  operate  the  equipment.  Verify  that  the  switches  are 
properly  located,  manually  operated,  protected  against 
accidental  contact,  and  properly  labeled.  Verify  that  if 
both  switches  are  activated,  then  all  inspection  control 
devices  are  inoperative. 

If  a  portable  control  station  is  used,  verify  that  the 
cord  does  not  exceed  the  maximum  allowed  length.  If 
a  plug-in  portable  control  station  is  used,  check  that 
either  a  transfer  switch  is  provided  or  that  when  the 
portable  control  station  is  plugged  in,  the  control  of  the 
equipment  is  automatically  transferred  to  the  control 
station. 

8.17.4  References 

A17.1-2000/B44-00  and  later  editions  — 
Requirement  6.1.6.2.2. 


120 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


(io)  ITEM  8.18 

EARTHQUAKE  INSPECTION  AND  TESTS  (SEISMIC 
RISK  ZONE  2  OR  GREATER) 

8.18.1  Periodic  Inspection 

8.18.2  Periodic  Test 

8.18.3  Acceptance 

(a)  Verify  that  the  connections  between  the  truss  and 
the  building  are  installed  according  to  the  manufactur- 
er's drawings. 


(b)  Verify  that  restraints  are  installed  and  allow  move- 
ment as  required. 


8.18.4  References 

A17.1-2000/B44-00     and 
Requirements  8.5.2  and  8.53. 


later     editions 


121 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Part  9 
Moving  Walk  —  External 


ITEM  9.1 
GENERAL  FIRE  PROTECTION 

9.1.1  Periodic  Inspections 

Examine  the  sides  and  undersides  of  the  moving  walk 
trusses  and  machinery  spaces  enclosure  for  damage  to 
fire-resistive  materials.  A17.1a-1994  and  later  editions 
permit  the  use  of  noncombustible  and  limited  combusti- 
ble materials  as  defined  by  the  building  code  or 
ANSI/NFPA  101. 

Check  that  guards  are  in  place  for  openings  provided 
for  ventilation  of  the  driving  machine  and  control  equip- 
ment spaces.  Enclosure  in  fire-resistive  ceiling  does  not 
constitute  adequate  fire  protection. 

Verify  that  provisions  to  protect  floor  openings  from 
the  passage  of  flame,  heat,  and/or  smoke  that  are 
required  by  the  building  code  have  not  been  damaged, 
removed,  or  defeated. 

Moving  walks  installed  under  Al 7. 1-1981  and  later 
editions  require  protection  in  compliance  with 
ANSI/NFPA  101  or  local  codes.  Prior  to  A17.1-1981, 
A  17.1  gave  requirements  for  protection  of  floor  opening 
for  moving  walks  that  were  not  accredited  as  a  means 
of  egress.  However,  since  moving  walks  are  no  longer 
accredited  as  a  means  of  egress,  the  inspector  must  refer 
to  the  local  code  or  the  Life  Safety  Code  NFPA-101  for 
the  protection  requirement  at  each  location. 

9.1.2  Periodic  Test 

9.1.3  Acceptance 

Verify  that  floor  openings  are  protected  against  the 
passage  of  flame,  heat,  and /or  smoke  in  accordance  with 
the  requirements  of  the  building  code. 

9.1.4  References 

A17.1d-2000  and  earlier  editions  —  Sections  900  and 
901;  and  Rule  1009.2a. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.2.1  and  6.2.2;  and  8.10.4.1.1(a). 

A17.3  —  Paragraphs  9.1.1  and  9.2.2. 

ITEM  9.2 
GEOMETRY 

9.2.1  Periodic  Inspections 

Inspect  for  evidence  of  change  to  the  geometry  of  the 
balustrades  and  if  change  has  been  made,  inspect  as 
outlined  in  Item  9.2.3. 


If  a  moving  walk  is  relocated  or  a  new  moving  walk 
is  installed  in  existing  trusses,  it  must  comply  with  the 
current  Code  requirements.  See  Figs.  9.2.1(a)  and  9.2.1(b) 
for  dimension  requirements  of  existing  moving  walks. 

Verify  that  the  overhead  clearance  is  in  compliance 
with  local  codes. 

9.2.2  Periodic  Test 

9.2.3  Acceptance 

(a)  Measure  the  slope  of  the  treadway  at  the  centerline 
using  a  level  and  protractor  or  an  angle  finder  at  each 
incline  (if  any).  See  Fig.  9.2.3. 

(b)  Measure  the  width  of  the  treadway  at  a  right  angle 
transverse  to  the  direction  of  travel.  See  Tables  9.2.3(a), 
9.2.3(b),  and  9.2.3(c)  for  existing  moving  walks  installed 
prior  to  1971.  For  moving  walks  installed  under 
A17.1-1971  and  later  editions,  refer  to  A17.1a-1991. 

(c)  Measure  and  mark  the  centerline  of  each  handrail 
and  use  a  plumb  line  to  find  the  horizontal  distance 
from  the  handrail  centerline  to  the  vertical  plane  through 
the  exposed  treadway  edge.  Measure  the  height  from 
the  top  of  the  handrail  to  the  treadway  at  several  points. 

(d)  For  an  interior  low  deck  moving  walk,  measure 
the  distance  from  the  vertical  face  of  the  interior  panels 
to  the  vertical  face  of  the  skirt  panels  using  a  machinist 
level  and  ruler  [see  Fig.  9.2.1(b)].  Measure  the  slope 
of  the  deck  perpendicular  to  the  line  of  travel  using  a 
machinist  level  and  protractor. 

9.2.4  References 

A17.1d-2000  and  earlier  editions  —  Rules  902.1, 902.2, 
902.3d,  (NR  8.6.8.12),  1009.2b,  1009.2g,  and  1208.5;  and 
Appendix  D. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.2.3.1,  6.2.3.2,  6.2.3.3.4,  8.6.8.12, 
8.10.4.1.1(b),  8.10.4.1.1(n),  and  8.7.6.2.5;  and 
(NR  Appendix  D). 

A17.3  —  Paragraphs  9.3.1,  9.3.2,  9.3.3,  and  9.3.6. 

ITEM  9.3 
HANDRAILS 

9.3.1  Periodic  Inspections 

(a)  Mark  one  location  on  each  handrail  with  chalk, 
then  operate  the  unit  and  inspect  each  handrail  through 
a  complete  revolution.  The  handrails,  including  splices 
and  joints,  should  be  free  of  any  cuts,  cracks,  gouges, 


do) 


122 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Fig.  9.2.1(a)     Moving  Walk  Geometry  (for  Moving  Walks  Installed  Under  A17.1-1965  Through  A17.1b-1980)      (10) 


C^> 


30jn_.__ 

Minimum  height 
of  balustrades 


Width  of  moving  walk 
[width  of  moving  walk  is 
exposed  width  of  treadway. 
See  Tables  9.2.3(a),  (b),  and  (c)] 


GENERAL  NOTE:     1  in.  =  25.4  mm. 


pinch  points,  or  any  other  condition  that  would  be  a 
hazard  to  passengers.  The  undersides  of  the  handrails 
should  be  close  enough  to  the  handrail  stand  to  prevent 
any  fingers  from  getting  between  the  handrail  and  the 
handrail  stand.  Any  rust  or  rubber  filings  present  on 
the  balustrade  deck  indicates  that  an  internal  inspection 
of  the  handrail  system  may  be  warranted. 

(b)  Verify  that  the  hand  or  finger  guards  are  present 
at  the  newel  base.  Check  that  the  guards  are  in  good 
condition  and  properly  sized  to  prevent  fingers  or  hands 
from  being  drawn  into  the  newel.  Finger  guards  are 
required  under  A17. 1-1965  and  later  editions. 

(c)  Ride  the  moving  walk  holding  the  handrails 
through  the  entire  travel.  The  handrails  should  move 
smoothly  without  jerking,  at  substantially  the  same 
speed  as  the  tread  ways.  The  need  to  frequently  change 
grip  on  the  handrail  indicate  a  need  for  adjustment. 
During  this  ride  observe  any  unusual  noise  that  may 
indicate  the  need  for  further  inspection.  At  several  points 
in  the  ride  firmly  grip  the  handrail  and  attempt  to  see 
if  it  stalls  under  moderate  force.  On  many  units  the 
handrails  will  normally  stall  if  it  is  firmly  gripped 
and  held. 

(d)  Listen  for  noise  that  may  indicate  wear  of  the  turn- 
around rollers,  or  other  parts. 


(e)  Moving  walks  installed  under  A17.1-1981  through 
A17.1a-1987  editions  required  only  one  moving  handrail 
if  the  slope  was  3  deg  or  less,  the  width  was  24  in. 
(610  mm)  or  less,  and  the  speed  was  70  ft/min  or  less. 
Moving  walks  installed  under  A17. 1-1965  through 
A17.1a-1979  did  not  require  a  moving  handrail  if  the 
slope  was  3  deg  or  less,  and  the  speed  was  70  ft/min 
or  less.  Only  one  handrail  was  required  (regardless  of 
speed  or  incline)  if  the  width  was  less  than  21  in. 
(533  mm).  A  balustrade  with  no  moving  handrail  should 
not  have  any  surface  that  can  be  gripped. 

(/)  Check  the  horizontal  clearance  between  both  lips 
of  the  handrail  and  the  handrail  stand  (guide). 

9.3.2  Periodic  Test 

For  moving  walks  installed  to  A17. 1-2000  and  later 
editions,  the  person  or  firm  maintaining  the  equipment 
must  provide  a  written  checkout  procedure  and  demon- 
strate that  the  handrail  speed  does  not  change  when  a 
retarding  force,  up  to  the  maximum  required  by  Code, 
is  applied  opposite  to  the  direction  of  travel.  Note  that 
it  may  be  easier  to  retard  the  handrail  motion  when 
the  handrail  is  traveling  in  the  down  direction  (i.e,  the 
retarding  force  will  oppose  the  handrail  drive  system). 


123 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 

(io)      Fig.  9.2.1(b)    Moving  Walk  Geometry  (for  A/loving  Walks  Installed  Under  A17.1-1981  Through  A17.1a-1991) 

— 4  in.  min. 

10  in.  max.,  A17.1-1981-A17. 1-1987;  "A  |\  I/ 

91/2  in.  max.,  A17.1a-1988  and  later      ^  '    X  V 


1  in.  min 


1  in.  min. 


42  in.  max. 


33  in.  min.,  A17.1-1981-A17.1-1987, 
30  in.  min.,  A17.1a-1988-1991 


Width  of  moving  walk 
(exposed  width  of  treadway) 


See  Fig.  7.2.1(c)  for  low 
deck  configuration 


GENERAL  NOTE:      1  in.  =  25.4  mm. 


(10) 


Fig.  9.2.3    Maximum  Treadway  Angle 


3  deg  max. 


12  deg  max.  at  any  point,  A17. 1-1981  and  later  editions 

andA17.3a-1994 
12  deg  max.  at  any  point,  A17.1-1965-A17.1b-1980 


3  deg  max. 


GENERAL  NOTE;     1  in.  =  25.4  mm. 


124 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


(io)         Table  9.2.3(a)    Treadway  Width  (A17.1-1965 
Through  A17.1d-1970) 


(10) 


Maximum 

Maximum  Moving  Walk  Treadway  Width,  in. 

Treadway  Slope 

Treadway  Speed, 

Treadway  Speed, 

at  any  Point  on 

Maximum, 

Above  140  ft/min  to 

Treadway,  deg 

140  ft/min 

180  ft/min 

0  to    3 

Unlimited 

40 

Above    3  to    5 

110 

40 

Above    5  to    8 

78 

40 

Above    8  to  12 

40 

Above  12  to  15 

40 

GENERAL  NOTES: 

(a)  1  deg  =  1.75  E  -  02  radian 

(b)  1  in.=  25.4  mm 


Table  9.2.3(b)    Treadway  Width  (A17.1-1971  and 
Later  Editions) 


Maximum 

Treadway  Slope 

at  any  Point, 

deg 


Maximum  Moving  Walk  Treadway  Width,  in. 

90.1  ft/min        140.1  ft/min 
Up  to  to  to 

90  ft/min         140  ft/min         180  ft/min 


0  to  4(1) 

Unrestricted 

60 

40 

4(1)  to  8 

40 

40 

40 

8  to  12(2) 

40 

40 

Not  Permitted 

GENERAL  NOTES: 

(a)  1  deg  =  1.75  E  -  02  radian 

(b)  1  in.  =  25.4  mm 
NOTES: 

(1)  5  deg  for  units  installed  under  A17. 1-1971  through  A17.1- 
1978. 

(2)  15  deg  for  units  installed  prior  to  A17. 1-1981. 


Table  9.2.3(c)    Minimum  Treadway  Width 


A17.1a-1980 
and  Prior 
Editions 


A17.1-1981  and 

Later  Editions 
and  A17.3a-1994 


16  in. 


22  in. 


GENERAL  NOTES: 

(a)  1  deg  =  1.75  E  -  02  radians 

(b)  1  in.  =  25.4  mm 


A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.2.3.2,  6.2.3.4,  8.11.4.2.13,  and 
8.10.4.1.1(c);  and  (NR  Appendix  D). 

A17.3  —  Paragraph  9.3.4. 

ITEM  9.4 
ENTRANCE  AND  EGRESS  ENDS 

9.4.1  Periodic  Inspections  (io) 

(a)  The  floor  surfaces  adjacent  to  the  landing  plates 
must  be  continuous  with  the  top  of  the  landing  plate, 
with  no  abrupt  changes  in  elevation  of  more  than  \  in. 
(6.4  mm).  Access  to  and  egress  from  the  moving  walk 
should  be  free  of  obstacles  and  tripping  hazards.  Check 
that  the  pit  covers  are  present  and  in  good  condition. 
For  moving  walks  installed  under  A17. 1-1965  through 
A17.1b-1989  editions,  the  landing  plate  should  be 
smooth  from  the  line  of  intersection  of  the  teeth  and 
the  treadway  surface  for  a  distance  not  to  exceed  4  in. 
(102  mm)  and  not  less  than  1  in.  (25  mm). 

(b)  For  moving  walks  installed  under  the  A17.1b-1989 
and  later  editions,  a  safety  zone  should  be  maintained 
free  of  obstacles  (see  Fig.  7.4.1).  These  Code  dimensions 
are  minimums  and  traffic  patterns  may  require  larger 
distances. 

(c)  While  standing  on  the  unit,  verify  that  the  landing 
and  combplates  provide  a  secure  foothold  and  that  out- 
door units  provide  a  secure  foothold  when  wet. 

9.4.2  Periodic  Test 

9.4.3  Acceptance 

Verify  that  vertical  headroom  clearance  of  7  ft  (2.13  m) 
is  provided  and  that  the  required  safety  zone  is  present. 

Check  that  floor  openings  adjacent  to  the  entire  length 
of  the  wellway  are  protected  in  accordance  with  the 
applicable  building  code. 

9.4.4  References  (io) 

A17.1d-2000  and  earlier  editions  —  Rules  902.8, 907.3, 
and  902.16. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.2.3.8,  c6.2.3.8.5,  6.2.8.3,  6.2.3.16,  and 
8.6.8.15. 

A17.3  —  Paragraph  9.4.3. 


9.3.3  Acceptance 

Check  whether  each  handrail  extends  at  normal 
height  not  less  than  12  in.  (305  mm)  beyond  the  moving 
walk  combplates,  and  verify  that  required  clearances  are 
present  (see  Fig.  9.3.3). 

9.3.4  References 

A17.1d-2000  and  earlier  editions  —  Rules  902.2, 902.4, 
1008.2m,  and  1009.2c;  and  Appendix  D. 


ITEM  9.5 
LIGHTING 

9.5.1  Periodic  Inspections 

Check  whether  the  lighting  at  the  landing  plates  and 
treadway  is  in  compliance  with  the  applicable  code  by 
using  a  light  meter  while  the  moving  walk  is  operating. 
Take  care  not  to  cast  a  body  shadow  on  the  meter.  Note 
any  lamps  that  are  not  operating  and  their  affect  on  the 
moving  walk  lighting.  For  moving  walks  installed  under 


125 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 

Fig.  9.3.3    Moving  Walk  Handrail  Extension  (A17.1-1971  and  Later  Editions) 

End  of  exposed  treadway 

^\^^    *-        -* 12  in.  min. 

Handraik 

Normal  handrail  height 


10  in.  max. 


GENERAL  NOTE:      1  in.  =  25.4  mm. 


A17.1-1965  and  later  editions,  lighting  must  be  a  mini- 
mum of  5  fc  (54  lx),  of  uniform  intensity,  and  must  not 
materially  contrast  with  the  surrounding  area. 

9.5.2  Periodic  Test 

9.5.3  Acceptance 

9.5.4  References 

A17.1d-2000  and  earlier  editions  —  Rules  906.2  and 
1009.2d. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.2.7.2  and  8.10.4.1.1(e). 

A17.3  —  Paragraph  9.7.1. 

ITEM  9.6 
CAUTION  SIGNS 

9.6.1  Periodic  Inspections 

For  moving  walks  installed  under  A17. 1-1981  and 
later  editions  and  moving  walks  required  to  conform  to 
A17.3a-1994/  verify  that  the  required  caution  signs  are 
located  at  both  entrances  readily  visible  to  boarding 
passengers.  For  moving  walks  installed  under 
A17.1-1996  through  A17.1d-2000,  verify  that  any  addi- 
tional signs  are  located  at  least  10  ft  (3.05  m)  horizontally 
from  the  end  of  the  newels  and  that  they  do  not  impede 
traffic  or  otherwise  cause  persons  to  stop. 

9.6.2  Periodic  Test 

9.6.3  Acceptance 

9.6.4  References 

A17.1d-2000  and  earlier  editions  —  Rule  905.8;  and 
Fig.  805.9a. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.2.6.8;  and  Fig.  6.1.6.9.1. 

A17.3  —  Paragraph  9.6.11. 


ITEM  9.7 
COMBPLATE  AND  COMB  STEP  IMPACT  DEVICE 

9.7.1  Periodic  Inspections 

Inspect  the  comb  for  missing  teeth  and  proper  mesh 
with  each  treadway  tread  (see  Fig.  7.7.1).  Verify  proper 
mesh  with  each  treadway  tread  by  holding  a  sheet  of 
stiff  paper  or  business  card  where  the  teeth  mesh  with 
the  treadway  tread  while  standing  well  back  from  the 
plate  to  prevent  forcing  the  plate  down.  Use  of  an  exten- 
sion with  an  alligator  clip  to  hold  the  card  is 
recommended. 

NOTE:  Telescoping  pointers  with  alligator  clips  that  are  used  to 
ignite  water  heater  pilot  lights  are  availbale  in  hardware /plumbing 
supply  stores. 

The  comb  teeth  should  mesh  with  and  set  into  the 
tread  surface  so  that  the  teeth  are  always  below  the 
upper  surface  of  the  treads.  Any  section  with  one  or 
more  missing  or  broken  teeth  should  be  replaced.  For 
moving  walks  installed  under  A17.1a-1988  and  later 
editions  and  moving  walks  required  to  conform  to 
Al 7.33-1994,  the  comb  surfaces  must  contrast  visibly  by 
color,  pattern,  or  texture. 

9.7.2  Periodic  Test 

For  units  installed  under  A17.1b-1992  and  later  edi- 
tions, have  the  combplate  impact  devices  tested  as 
follows: 

(a)  Have  a  vertical  force  applied  to  the  center  front 
edge  of  the  combplate  until  the  device  trips.  Record  the 
force  required  to  trip  the  device  and  verify  the  unit  will 
not  start  until  manually  reset. 

(b)  Have  a  force  applied  in  the  direction  of  travel  at 
the  front  center  of  the  combplate,  increasing  the  force 
until  the  device  trips.  Record  the  force  required  to  trip 
the  device  and  verify  the  unit  will  not  start  until  manu- 
ally reset. 


126 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


(c)  Have  a  force  applied  in  the  direction  of  travel  on 
one  side  of  the  front  of  the  combplate,  increasing  the 
force  until  the  device  trips.  Record  the  force  required  to 
trip  the  device  and  verify  the  unit  will  not  start  until 
manually  rest.  Repeat  this  test  for  the  opposite  side. 

Note  that  while  the  maximum  horizontal  forces  were 
112  lbf  (500  N)  at  each  side  and  225  lbf  (1  000  N)  at  the 
center  of  the  combplate  for  moving  walks  installed  to 
A17.1b-1992  through  A17.1-1996,  it  is  permitted  to  have 
maximum  horizontal  forces  at  the  higher  values  permit- 
ted by  A17.1a-1997  and  later  editions. 

9.7.3  Acceptance 

(a)  Visually  verify  that  the  combplates  are  vertically 
adjustable  and  that  the  sections  forming  the  comb  teeth 
are  replaceable. 

(b)  Place  the  required  weight  on  the  combplate  and 
landing  plate  assembly  to  verify  that  the  combplate  and 
landing  plate  will  not  contact  the  treadway  (see 
Fig.  7.7.3). 

9*7.4  References 

A17.1d-2000  and  earlier  editions  —  Rules  902.8, 
905.3k,  907.3,  1206.6,  1008.2r,  and  1009.2e. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.2.3.8  6.2.6.3.11,  6.2.8.3,  8.6.8,  8.11.4.2.13, 
and  8.10.4.1.1(g). 

A17.3  —  Section  9.4. 

ITEM  9.8 
DECK  BARRICADES 

9.8.1  Periodic  Inspections 

For  low  deck  moving  walks  installed  under 
A17.1a-1988  and  later  editions  and  moving  walks 
required  to  comply  with  A17.3a-1994,  check  to  see  that 
deck  barricades,  when  required,  are  firmly  in  place  and 
in  good  condition  when  the  outer  deck  exceeds  5  in. 
(125  mm)  and  the  deck  is  more  than  36  in.  (915  mm) 
above  any  part  of  the  floor.  The  barrier  must  extend  to 
4  in.  (102  mm)  below  the  handrail  top. 

9.8.2  Periodic  Test 

For  moving  walks  installed  under  A17.1b-1989  and 
later  editions,  verify  that  glass  or  plastic  replacement 
panels  meet  the  requirements  of  ANSI  Z97.1  or  16  CFR 
Part  1201. 

9.8.3  Acceptance 

All  glass  or  plastic  (glazing  material)  must  be  legibly 
and  permanently  marked  16  CFR  Part  1201,  " American 
National  Standard  Z97 .1"  or  with  the  characters 
"ANSI  Z97.1"  and  also  shall  be  marked  with  the  manu- 
facturer's distinctive  mark  or  designation. 

Check  that  all  exposed  fasteneer  heads  are  the  tamper- 
resistant  type. 


9.8.4  References 

A17.1d-2000  and  earlier  editions  —  Rules  902.3h  and 
1009.2f. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.2.3.3.8  and  8.10.4.1.1(h). 

A17.3  —  Paragraph  9.3.3.6. 

ITEM  9.9 
TREADWAYS 

9.9.1  Periodic  Inspections 

(a)  Mark  treadways  with  chalk,  then  run  the  moving 
walk  through  one  complete  revolution.  Check  that  each 
treadway  is  continuous,  unbroken,  clean,  free  of  debris, 
and  that  the  treads  are  in  good  condition. 

(b)  Check  at  least  everytenth  pallet  or  a  distance  of 
approximately  one-tenth  the  entire  length,  by  riding  on 
it,  to  verify  that  the  following  requirements  are  met: 

(1)  There  is  no  excessive  movement  or  play  in  the 
direction  of  travel,  at  right  angles  to  the  direction  of 
travel,  and  vertically.  While  standing  on  the  treadway, 
a  shift  of  weight  should  not  cause  the  treadway  to  strike 
the  skirt  panels. 

(a)  Belt  Type.  The  treadway  consists  of  an  integral 
belt  of  uniform  width  and  thickness,  made  or  spliced 
in  one  continuous  piece  forming  a  loop. 

(b)  Pallet  Type.  The  treadway  consists  of  closely 
coupled  meshing  pallets,  or  small  platforms.  This  is  simi- 
lar to  an  escalator  step  without  a  riser. 

(c)  Belt  Pallet  Type.  For  moving  walks  installed 
under  A17.1-1987  and  earlier  editions,  this  type  was 
permitted.  The  treadway  consists  of  a  continuous  inte- 
gral belt  supported  on  coupled  pallets.  The  pallets  may 
not  ordinarily  be  visible  when  standing  on  the  treadway. 

(2)  Alternate  cleats  on  adjacent  pallets  should  mesh 
so  that  no  continuous  transverse  gap  exist  between  pal- 
lets. Mesh  can  be  verified  by  trying  to  fit  a  thin  piece 
of  stiff  paper  or  business  card  between  treadways  while 
the  moving  walk  is  moving  in  the  up  direction.  The  check 
should  be  made  across  the  entire  width  (see  Fig.  7.7.1). 

(3)  The  tread  surface  should  be  slotted  in  the  direc- 
tion parallel  to  the  travel  so  that  they  mesh  with  the 
combplate  teeth.  Verify  that  a  cleat  is  formed  adjacent 
to  the  skirt  panel  on  each  side  of  the  treadway  (see 
Fig.  9.9.1). 

(4)  The  cleats  in  the  treadway  tread  surfaces  should 
not  be  damaged,  broken,  or  worn.  Special  consideration 
should  be  given  to  excessive  clearance  and  sharp  edges. 
While  standing  on  the  treadway  tread,  verify  that  it 
provides  a  secure  foothold. 

(5)  A  jerking  motion  on  the  treadways  and  exces- 
sive noise  in  the  machinery  space  indicates  that  the  drive 
and  support  system  should  be  examined  to  discover  the 
source  or  cause. 

(6)  Use  a  straight  edge  to  verify  that  adjacent  pallets 
do  not  vary  more  than  V16  in.  (1.6  mm)  in  elevation 


127 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers, 
t     No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


(10) 


Fig.  9.9.1     Moving  Walk  Treadway  Slots 


V4  in.  max. 
slot  width, 
A17.1-1965-A17.1a-1991 


|  3/gin.,  A17.1a-1988  and  later  editions; 


Cleat  adjacent  to 
skirt  panel 


3/8  in.,  A17. 1-1988  and  later  editions; 
3/16  in.,  A17.M965-A17.1-1987 


Minimum  slot  depth 


GENERAL  NOTE:      1  in.  =  25.4  mm 


(10) 


(vertical  displacement).  On  belt-pallet-type  treadways, 
verify  that  the  fasteners  that  attach  the  belt  to  the  pallets 
do  not  project  above  the  exposed  treadway  surfaces. 
Inspect  the  splices  in  belt-type  treadways  to  verify  that 
they  produce  a  continuous  unbroken  treadway. 

(7)  For  moving  walks  required  to  conform  to 
A17.3a-1994,  check  that  the  splices  of  belt-type 
treadways  are  continuous  and  unbroken. 

9.9.2  Periodic  Test 

9.9.3  Acceptance 

Review  fatigue  test  and  certification  for  the  Code 
compliance. 

Check  that  the  material  for  pallet  frames  and 
treadways,  including  any  attachments  or  inserts,  meet 
Code  requirements. 

9.9.4  References 

A17.1d-2000  and  earlier  editions  —  Rules  902.5, 902.6, 
902.9,  902.11,  and  1105.1. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.2.3.5,  6.2.3.6,  6.2.3.9,  6.2.3.11,  8.6.8.6,  and 
8.3.11.1. 

A17.3  —  Paragraph  9.3.5. 

ITEM  9.10 
OPERATING  AND  SAFETY  DEVICES 

9.10.1  Periodic  Inspections 

(a)  Starting  Switches.  Verify  that  a  record  of  personnel 
that  were  trained  in  the  proper  procedure  to  start  up 
the  moving  walk  is  available  on  site.  Operate  the  moving 
walk  in  both  directions  using  the  key-operated  start 
switch.  When  operating  the  switch,  the  exposed 


treadways  should  be  within  sight.  Check  the  operation 
and  location  of  this  switch.  A17.1b-1989  and  later  edi- 
tions specifically  prohibit  automatic  starting  by  any 
means.  Verify  that  the  key  is  only  accessible  to  author- 
ized personnel. 

For  units  installed  under  A17.1-1996  and  later  edi- 
tions, verify  that  the  start  switch  operating  positions  are 
properly  marked.  Check  that  the  key  is  only  removable 
in  the  "RUN"  position.  Turn  the  switch  from  "RUN"  to 
either  "UP"  or  "DOWN"  and  quickly  let  go  of  the  key. 
The  switch  must  return  to  the  "RUN"  position.  Repeat 
for  the  other  direction  of  travel.  Next  turn  the  switch  to 
either  the  "UP"  or  "DOWN"  position.  Stop  the  unit  with 
the  emergency  stop  button  and  keep  the  switch  in  the 
"UP"  or  "DOWN"  position.  The  unit  must  not  restart. 
Repeat  for  the  other  direction  of  travel. 

(b)  Emergency  Stop  Switches.  Operate  the  emergency 
stop  switches/buttons  and  observe  that  the  moving 
walk  stops.  Verify  that  this  stop  switch  will  not  start  the 
moving  walk.  If  automatic  starting  devices  are  provided 
(A17.1a-1988),  verify  that  they  will  not  function  after 
the  stop  switch  is  operated.  Verify  proper  labeling  and 
signal  where  required.  The  requirements  for  emergency 
stop  switches  in  prior  editions  of  the  Code  are  as  follows: 

(1)  A17.1-1965:  Emergency  stop  button  or  other 
type  of  manually  operated  switches  having  a  red  button 
or  handle  shall  be  accessible  located  at  or  near  the  top 
and  bottom  landing  of  each  moving  walk,  and  shall  be 
protected  against  operation  by  accident. 

(2)  A17.1a-1988  and  later  editions  required  a 
readily  moveable  self-closing  transparent  cover  and  an 
80  dBA  signal  when  the  cover  is  moved.  The  cover 
should  be  marked  "Emergency  Stop."  The  location  of 
the  button  should  be  in  the  upper  right  quadrant  when 


128 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


facing  the  moving  walk  at  each  end  for  high  deck  balus- 
trades, and  for  low  deck  balustrades  it  must  be  below 
the  handrail  height.  Remote  stop  switches  were  prohib- 
ited and  handles  were  not  allowed. 

(c)  Tandem  Operation.  For  moving  walks  operated  in 
tandem,  A17.1a-1988  and  later  editions,  where  traffic 
flow  is  such  that  bunching  will  occur  if  the  moving  walk 
carrying  passengers  away  stops,  verify  that  the  units  are 
electrically  interlocked.  The  interlocks  must  stop  the  unit 
carrying  passengers  into  the  common  intermediate  land- 
ing, if  the  unit  carrying  passengers  away  from  the  land- 
ing should  stop.  Also,  verify  that  the  interlocks  assure 
that  the  units  run  in  the  same  direction. 

9.10.2  Periodic  Test 

(10)    9.10.3  Acceptance 

Check  that  the  starting  switches  are  within  reach  of 
an  emergency  stop  button.  Start  the  unit  and  hold  the 
start  switch  in  the  "UP"  direction,  then  actuate  the  emer- 
gency stop  button.  The  unit  must  not  restart  until  the 
start  switch  is  placed  in  the  "RUN"  position  and  the 
starting  sequence  is  repeated.  Repeat  this  for  the 
"DOWN"  direction  and  for  the  other  start  switch. 

For  low  deck  moving  walks,  check  the  clearances 
between  the  handrail  and  the  stop  switch  enclosure  and 
the  distance  from  the  button  to  the  handrail.  In  jurisdic- 
tions enforcing  NBCC,  if  provided,  check  that  the  auxil- 
iary emergency  stop  is  within  view  of  the  moving  walk. 

(to)    9.10.4  References 

A17.1d-2000  and  earlier  editions  —  Rules  905.1, 905.2, 
905.3a,  905.6,  and  (NR  8.6.10.5). 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.2.6.1,  6.2.6.2.1,  6.2.6.3.1,  c6.2.6.3.1(a), 
6.2.6.6,  8.6.10.2,  and  8.6.10.5. 

A17.3  —  Paragraphs  9.3.5,  9.6.3,  and  9.6.9. 


ITEM  9.11 
(RESERVED) 

ITEM  9.12 
(RESERVED) 

ITEM  9.13 
EGRESS  RESTRICTION  (ROLLING  SHUTTER)  DEVICE 

9.13.1  Periodic  Inspections 

Where  rolling  shutters  are  provided  to  protect  floor 
openings,  check  that  when  the  shutters  begin  to  close, 
the  power  is  removed  from  the  driving  machine  and 
brake,  and  remains  off  until  the  shutter  is  fully  retracted. 
If  the  shutter  is  power  operated,  the  building  code  may 
require  a  pressure  sensitive  leading  edge  to  reverse 
direction  and /or  stop  it  when  it  strikes  an  object. 


9.13.2  Periodic  Test 

9.13.3  Acceptance 

9.13.4  References 

A17.1d-2000  and  earlier  editions  —  Rule  905.3f. 
A17.1-2000/B44-00  and  later  editions  —  Requirement 
6.2.6.3.6. 

A17.3  —  Paragraph  9.6.7. 

ITEM  9.14 
SPEED 

9.14.1  Periodic  Inspections 

For  moving  walks  with  DC  motors,  perform  a 
speed  test. 

9.14.2  Periodic  Test 

9.14.3  Acceptance 

Determine  the  no  load  speed  of  the  moving  walk  in 
both  directions  as  follows: 

(a)  Run  a  tachometer  wheel  along  the  deck,  skirt,  or 
other  stationary  flat  object  when  riding  the  moving 
walk,  or 

(b)  Use  a  stopwatch  to  time  the  travel  from  one  land- 
ing to  the  other.  Divide  the  travel  in  feet  (meters)  by  the 
time  in  minutes  (seconds)  to  obtain  the  speed  in  ft/min 
(m/s). 

Refer  to  Tables  9.14.3(a),  9.14.3(b),  and  9.14.3(c)  for 
allowable  speeds  of  existing  equipment. 

Table  9.14.3(a)    Treadway  Speed 
(A17.1-1981  and  Later  Editions) 

Maximum  Treadway  Slope 

at  any  Point  on  Treadway,  Maximum  Treadway 

deg  Speed,  ft/min 


0  to  8 
Above  8  to  12 


180 
140 


GENERAL  NOTES: 

(a)  1  deg  =  1.75  E  -  02  radian 

(b)  1  ft/min  =  5.08  E  -  03  m/s 

Table  9.14.3(b)    Treadway  Speed  (A17.1-1965 
Through  A17.1b-1980) 


(10) 


Maximum  Treadway  Slope 

at  Point  of  Entrance  or 

Maximum  Treadway 

Exit,  deg 

Speed,  ft/min 

Oto  3 

180 

Above  3  to  5 

160 

Above  5  to  8 

140 

Above  8  to  12 

130 

Above  12  to  15 

125 

GENERAL  NOTES: 

(a)  1  deg  =  1.75  E  -  02  radian 

(b)  1  ft/min  =  5.08  E  -  03  m/s 


129 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


Table  9.14.3(c)    Treadway  Speed 


Maximum  Treadway  Slope 
at  any  Point  on  Treadway,  deg 


Maximum  Treadway 
Speed,  ft/min 


0  to    8 
Above  8  to  1 5 


180 
140 


GENERAL  NOTES: 

(a)  1  deg  =  1.75  E  -  02  radian 

(b)  1  ft/min  =  5.08  E  -  03  m/s 


Verify  that  the  speed  of  the  moving  walk  cannot  be 
changed  without  first  stopping  it. 

9.14.4  References 

A17.1d-2000  and  earlier  editions  —  Rules  903.1, 
905.3b,  1008.20,  and  1009.2o. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.2.4,  6.2.6.3.2,  (NR  1008.2o),  and 
8.10.4.1.2(1). 

(io)  ITEM  9.15 

BALUSTRADES 

9.15.1  Periodic  Inspections 

Inspect  the  balustrades  and  note  any  cracked  or  bro- 
ken panels.  Panels  and  fasteners  should  be  smooth  and 
free  of  burrs  and  snag  points.  Interior  panels  or  molding 
must  not  be  raised  or  depressed  by  more  than  \  in. 
(6.4  mm).  Check  that  the  balustrades  are  totally  enclosed 
along  both  exterior  and  interior  lengths,  except  where 
the  handrail  enters  the  newel  base.  For  moving  walks 
installed  under  A17.1a-1988  and  later  editions  and  mov- 
ing walks  required  to  conform  to  A17.3a-1994,  if  gaps 
exist  between  interior  panels,  they  should  not  be  wider 
than  %6  in.  (4.8  mm)  and  the  edges  should  be  beveled 
or  rounded.  Check  that  glass  or  plastic  panels  meet  the 
treadway  and  skirt  panels  should  not  exceed  V4  in. 
(6.4  mm).  For  skirtless  balustrades  installed  under 
Al 7. 1-1965,  the  vertical  clearance  between  the  top  of 
the  treadway  and  the  underside  of  the  balustrade  should 
not  exceed  \  in.  (3.2  mm). 

For  units  installed  under  A 17. 1-1 971  and  later  edi- 
tions and  moving  walks  required  to  conform  to 
A17.3a-1994,  the  vertical  clearance  between  the  top  of 
the  treadway  and  the  underside  of  the  balustrade  should 
not  exceed  \  in.  (6.4  mm).  See  Fig.  9.17.1.  Verify  that 
skirt  panels  are  smooth  for  moving  walks  installed  under 
A17.1a-1988  and  later  editions  and  moving  walks 
required  to  conform  to  A17.3a-1994. 

9.15.2  Periodic  Test 

9.15.3  Acceptance 

Check  that  the  skirt  panels,  tions  and  A17.3a-1994. 
Verify  that  the  balustrades  meet  the  material,  strength, 
and  dimensional  requirements. 


Glass  or  plastic,  if  used,  should  meet  the  requirements 
of  the  ANSI  Z97.1,  or  16  CFR  Part  1201,  or  CAN/CGSB 
12.1;  CAN/CGSB  12.11;  CAN/CGSB  12.12,  as  applica- 
ble. The  glass  or  plastic  (glazing  material)  must  be  legi- 
bly and  permanently  marked  "16  CFR  Part  1201", 
"American  National  Standard  Z97.1"  or  the  characters 
"ANSI  7371"  and  must  also  be  marked  with  the  manu- 
facturer's distinctive  mark  or  designation.  Plastic 
bonded  to  basic  support  panels  need  not  conform  to 
ANSI  Z97.1  or  16  CFR  Part  1201. 

Check  that  components  not  used  directly  in  connec- 
tion with  the  operation  of  the  moving  walk  are  not 
installed  on,  in,  or  through  the  moving  walk. 

Check  that  the  width  between  the  balustrade  interior 
panels  does  not  change  in  the  direction  of  travel. 

9.15.4  References 

A17.1d-2000  and  earlier  editions  —  Rules  902.3  and 
1009.2g;  and  Appendix  D. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.2.3.3,  6.2.3.17,  and  8.10.4.1(n);  and  (NR 
Appendix  D). 

A17.3  —  Paragraphs  9.3.3.1  and  9.3.3.2. 

ITEM  9.16 
CEILING  INTERSECTION  GUARDS 

9.16.1  Periodic  Inspections 

Moving  walks  installed  under  A17, 1-1981  and  later 
editions  where  the  clearance  of  the  exterior  deck  and 
the  ceiling  or  soffit  is  12  in.  (305  mm)  or  less  or  where 
the  projected  intersection  of  the  exterior  deck  and  ceiling 
or  soffit  is  24  in.  (610  mm)  or  less  from  the  handrail 
centerline,  require  ceiling  intersection  guards.  This 
requirement  was  restricted  to  high  decks  for  moving 
walks  installed  under  A17. 1-1987  and  later  editions  and 
moving  walks  required  to  conform  to  A17.3a-1994.  On 
low  decks  for  moving  walks  installed  under  A17. 1-1987 
and  later  editions  and  moving  walks  required  to  con- 
form to  A17.3a-1994  where  the  centerline  of  the  handrail 
is  14  in.  (356  mm)  or  less  from  the  ceiling  or  soffit,  guards 
are  also  required. 

Inspect  the  guards  for  damage  and  secure  attachment. 

9.16.2  Periodic  Test 

9.16.3  Acceptance 

Verify  that  guards  are  correct  size,  in  place  and  secure, 
and  conform  to  dimensional  requirements  (see 
Fig.  7.16.1). 

Check  that  glass  or  plastic  guards  are  properly 
marked. 

9.16.4  References 

A17.1d-2000  and  earlier  editions  —  Rule  902.3g;  and 
Appendix  D. 


130 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
iNo  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


Fig.  9.17.1    Treadway  Clearances 


(10) 


I  V8in.  max.,  A17. 1-1965  i 

]  V4in.  max.,  A17. 1-1971  and  later  editions    i 


CD 


V4in.  max., 
A17.1d-1970 
and  later  editions 


Width  of  moving  walk 


GENERAL  NOTE:     1  in.  =  25.4  mm. 


A17.1-2000/B44-00      and     later      editions     — 
Requirement  6.2.3.3.7;  and  (NR  Appendix  D). 
A17.3  —  Paragraph  9.3.3.5. 

ITEM  9.17 
SKIRT  PANELS 

(10)    9.17.1  Periodic  Inspections 

Check  the  clearance  between  the  skirt  panel  and  the 
treadway  using  a  thickness  gauge  or  by  laying  a  small 
rule  on  the  side  of  the  treadway  to  read  the  distance. 
The  treadways  should  be  checked  at  several  points  along 
its  entire  travel. 

For  moving  walks  installed  under  A17. 1-1971  and 
later  editions  and  moving  walks  required  to  conform 
to  A17.3a-1994,  the  horizontal  clearance  between  the 
treadway  and  skirt  panels  should  not  exceed  V4  in. 
(6.4  mm).  For  skirtless  balustrades  installed  under 
A17.1-1965,  the  vertical  clearance  between  the  top  of 
the  treadway  and  the  underside  of  the  balustrade  should 
not  exceed  \  in.  (3.2  mm). 

For  units  installed  under  A17.1-1971  and  later  edi- 
tions and  moving  walks  required  to  conform  to 
A17.3a-1994,  the  vertical  clearance  between  the  top  of 
the  treadway  and  the  underside  of  the  balustrade  should 
not  exceed  \  in.  (6.4  mm).  See  Fig.  9.17.1.  Verify  that 
skirt  panels  are  smooth  for  moving  walks  installed  under 


A17.1a-1987  and  later  editions  and  moving  walks 
required  to  conform  to  A17.3a-1994. 

9.17.2  Periodic  Test 

9.17.3  Acceptance 

Check  that  the  skirt  panels,  where  provided,  extend 
to  a  height  of  at  least  1  in.  (25  mm)  vertically  above  the 
treadway  tread  nose  line.  Skirt  panels  should  not  deflect 
more  than  V16  in.  (1.6  mm)  under  a  force  of  150  lbf  (667  N). 
Inspect  the  exposed  surface  of  the  panel  adjacent  to  the 
treadway  for  smoothness. 

9.17.4  References 

A17.1d-2000  and  earlier  editions  —  Rules  902.3e  and 
902.3f. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.2.3.3.5  and  6.2.3.3.6. 

A17.3  —  Paragraphs  9.3.3.3  and  9.3.3.4. 

ITEM  9.18 
OUTDOOR  PROTECTION 

9.18.1  Periodic  Inspections 

For  moving  walks  installed  under  A17.1b-1989  and 
later  editions,  check  that  the  required  cover  over  the 
horizontal  projection  of  the  unit  is  present  and  in  good 
condition. 


131 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Verify  that  there  is  no  accumulation  of  snow  or  freez- 
ing rain  on  the  treadways  or  landing  plates. 

9-18.2  Periodic  Test 

Heaters  are  required  for  moving  walks  installed  under 
A17.1b-1989  and  later  editions  only  if  treadways  are 
subject  to  snow  or  freezing  rain.  Check  that  heaters  are 
operational.  The  heaters  may  be  located  inside  the  units 
(see  Item  10.3.2). 

9.183  Acceptance 

Check  that  the  cover  extends  outward  from  the  center- 
line  of  the  handrail  such  that  a  line  from  the  edge  of 
the  cover  to  the  handrail  centerline  is  not  less  than  15  deg 
from  the  vertical.  Two  methods  for  checking  this  are 
shown  in  Fig.  7.18.3. 

Check  that  the  landing  plates  and  combplates  have 
provisions  to  provide  a  secure  foothold  when  wet.  Check 
that  all  electrical  components  are  weatherproof,  that  all 
wiring  is  identified  for  use  in  wet  locations,  and  that 
they  are  properly  installed  (gaskets,  seals,  etc.). 

9.18.4  References 

A17.1d-2000  and  earlier  editions  —  Rules  907, 
1008.2p,  and  1009.2i. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.2.8,  8.11.4.2.14,  and  8.10.4.1. l(q). 

ITEM  9.19 
MAINTENANCE  RECORDS 

9.19.1  Periodic  Inspections 

Review  the  maintenance  records  and  verify  that  they 
are  available  to  elevator  personnel  and  that  they  are 
legible  and  up  to  date.  They  should  include  the 
following: 

(a)  description  of  maintenance  task  performed  and 
dates 

(b)  description  and  dates  of  examinations,  tests, 
adjustments,  repairs,  and  replacements 


(c)  description  and  dates  of  call  backs  (trouble  calls) 
or  reports  that  are  reported  to  elevator  personnel  by  any 
means,  including  corrective  action  taken 

(d)  verify  that  a  startup  procedure  is  available  to 
authorized  personnel  (Al 7. 1-2000/ B44-00  —  8.6.10.5) 

9.19.2  Periodic  Test 

9.19.3  Acceptance 

9.19.4  References 

A17.1-2000  and  later  editions  - 
C8.6.12.2.5,  and  8.6.10.5. 


-  Requirements  8.6.1.4, 


(10) 


ITEM  9.20  (10) 

EARTHQUAKE  INSPECTION  AND  TESTS  (SEISMIC 
RISK  ZONE  2  OR  GREATER) 

9.20.1  Periodic  Inspections 

9.20.2  Periodic  Test 

Check  the  operation  of  the  seismic  switch  where 
provided. 

9.20.3  Acceptance 

(a)  Verify  that  balustrades  are  installed  and  fastened 
according  to  manufacturer's  drawings. 

(b)  Verify  that  seismic  switch  is  installed  and  if  it  is 
used  exclusively  to  control  the  moving  walk,  it  is  located 
in  a  machine  room,  machinery  space  and,  where  possi- 
ble, mounted  adjacent  to  a  vertical  load-bearing  member. 
If  there  is  no  vertical  load-bearing  member  in  close  prox- 
imity, the  seismic  switch  may  be  located  at  the  nearest 
accessible  vertical  load-bearing  member  at  approxi- 
mately the  same  horizontal  level  as  the  upper  machinery 
space  or  machine  room. 

(c)  Verify  that  the  seismic  switch,  when  actuated, 
causes  power  to  be  removed  from  the  moving  walk 
driving  machine  and  brake. 

9.20.4  References 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  8.5.1  and  8.5.4. 


132 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


A5ME  A17.2-2010 


Part  10 
Moving  Walk  —  Internal 


ITEM  10.1 

MACHINERY  SPACE  ACCESS,  LIGHTING, 

RECEPTACLE,  AND  CONDITION 

10.1.1  Periodic  Inspections 

For  remote  machine  rooms,  see  Item  10.1.2. 

10.1.2  Periodic  Test 

Determine  that  the  means  of  access  is  securely  fas- 
tened in  place.  If  a  door  is  used,  verify  that  it  is  kept 
locked  and  the  key  is  available  only  to  authorized  per- 
sonnel. Check  the  lighting  and  test  the  receptacle.  In 
remote  machine  space,  check  that  the  lighting  is  at  least 
10  fc  (108  lx)  for  moving  walks  installed  under 
A17.1-1981  and  later  editions. 

Verify  that  the  space  is  clean  of  dirt  and  rubbish  and 
free  of  oil  and  combustibles.  Combustible  items  unre- 
lated to  moving  walk  maintenance  or  operation  with  a 
flashpoint  less  than  110°F  (43°C)  should  not  be  present. 
Water  should  not  have  accumulated  on  the  floor  of  the 
space.  Verify  that  jumpers  are  not  stored  in  the  machine 
space,  hoistway,  or  pit. 

Verify  that  no  penetrations  exist  through  the  sides 
and  undersides  of  the  machinery  space  and  truss  that 
compromises  its  fire  resistance  rating  or  allows  contact 
with  moving  parts  by  the  public. 

For  moving  walks  installed  under  A17.1-2000/B44-00 
and  later  editions,  check  that  a  guard  is  in  place  to 
protect  against  accidental  contact  with  the  moving  pal- 
lets or  treadway. 

10.1.3  Acceptance 

Determine  whether  a  reasonable  means  of  access  to 
the  interior  is  provided.  Verify  that  the  weight  of  access 
plates  is  in  compliance  with  the  Code  requirements. 
Removal  of  the  floor  plates  over  the  landing  pit  consti- 
tutes reasonable  access  if  the  opening  uncovered  affords 
ample  space  for  the  entry  of  one  person.  When  an  access 
door  is  provided  on  the  side  of  the  enclosure,  verify  that 
the  door  is  locked  and  the  key  is  removable  only  in  the 
locked  position. 

If  fire  shutters  are  required  by  the  local  building  code, 
verify  that  they  are  present  at  ventilation  openings  and 
operate  correctly  Verify  that  the  15  A,  120  V  duplex 
receptacles  located  in  the  machine  space,  under  access 
plates  and  machine  areas  located  along  the  line  of  travel 
within  the  unit,  are  functional.  Verify  that  the  light  con- 
trol for  remote  machine  rooms  is  within  easy  reach  of 


the  access  and  can  be  operated  without  reaching  or  pass- 
ing over  any  machinery  components. 

Check  that  components  not  used  directly  in  connec- 
tion with  the  operation  of  the  moving  walk  are  not 
installed  on,  in,  or  through  the  moving  walk. 

10.1.4  References  (10) 

A17.1d-2000  and  earlier  editions  —  Section  906;  and 
Rules  901.1,  907.2,  1008.2a,  and  1009.2J. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.2.7;  and  6.2.2.1,  6.2.8.2,  8.1,  8.6.1.6.3, 
c8.6.12.2.6,  8.6.14,  8.6.8.15,  8.11.4.2.1,  and  8.10.4.1.2(a). 

A17.3  —  Paragraph  9.7.2. 

ITEM  10.2  (10) 

STOP  SWITCH  AND  INSPECTION  CONTROL 

10.2.1  Periodic  Inspections 

For  remote  machine  rooms,  see  Item  10.2.2. 

10.2.2  Periodic  Test  (10) 

Test  the  operation  of  machine  space  stop  switch(es) 
by  placing  them  in  the  stop  position,  then  make  sure 
that  everyone  is  clear  and  attempt  to  start  the  moving 
walk  with  the  key  switch. 

For  moving  walks  installed  under  Al 7. 1-2000 /B44-00 
and  later  editions,  check  the  operation  of  the  inspection 
control  device  from  each  end.  The  device  only  permits 
movement  by  a  constant  pressure  means,  and  clearly 
indicates  the  direction  of  travel. 

If  a  plug  in  control  station  is  used,  verify  that  it  is 
stored  in  the  upper  landing  machinery  space. 

Have  the  unit  operated  with  the  inspection  control 
device.  Check  that  the  device  only  permits  movement 
by  a  constant  pressure  means,  and  clearly  indicates  the 
direction  of  travel. 

10.2.3  Acceptance 

Check  that  proper  stop  switches  are  installed  and 
operate  correctly  in  all  machine  spaces  or  other  space 
where  access  to  the  interior  is  provided.  Where  the  main 
line  disconnect  switch  is  located,  a  separate  stop  switch 
is  not  required. 

10.2.4  References  (10) 

A17.1d-2000  and  earlier  editions  —  Rules  905.3e, 
1008.2b,  and  1009.2k. 


133 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.2.6.3.5,  6.2.6.2.2,  8.11.4.2.2,  and 
8.10.4.1.2(b). 

ITEM  10.3 
CONTROLLER  AND  WIRING 

10.3.1  Periodic  Inspections 

Inspect  remote  machine  rooms  as  outlined  in 
Item  10.3.2. 

(io)    10.3.2  Periodic  Test 

Examine  the  controller  visually  to  verify  that  it  is  clean 
and  that  the  switches,  contactors,  and  relays  and  their 
electrical  connections  are  in  good  condition.  Check  that 
the  fuses  are  in  place,  of  the  proper  type  and  rating, 
and  have  not  been  jumped  or  otherwise  tampered  with. 
Check  for  jumper  wires  or  other  changes,  which  may 
indicate  that  safety  devices  have  been  defeated  or 
altered. 

Visually  examine  wiring  for  damage  and  all  compo- 
nents for  evidence  of  overheating.  Operate  the  main  line 
circuit  breakers  or  disconnect  switch  to  verify  that  all 
power  is  removed  from  the  drive  machine.  Verify  that  all 
electrical  components  are  enclosed  to  prevent  accidental 
contact.  If  heaters  are  present  (see  Item  9.18.2),  verify 
that  they  are  operational.  For  moving  walks  installed 
under  A17.1-1965  through  A17.1c-1986,  verify  that  the 
circuit  breakers  will  not  be  automatically  opened  by  the 
fire  alarm. 

(io)    10.3.3  Acceptance 

Check  for  proper  voltage,  correct  wiring,  and  arrange- 
ment of  wiring,  controller,  and  other  components. 

Check  numbering  of  drive  machines  and  disconnects 
where  multiple  drive  machines  are  in  a  machine  room. 
Verify  that  disconnects  are  in  sight  of  machines  operated. 
Inspect  all  wiring  enclosure  raceways  conduit,  electrical 
metallic  tubing,  metal  wireways,  junction  boxes  for  con- 
dition workmanship  and  fastening.  Visually  inspect  con- 
dition  of  weatherproof  electrical  enclosure  where 
required  on  outdoor  units.  Verify  that  use  of  flexible 
conduit,  armored  cable,  and  flexible  leads  comply  with 
the  applicable  electrical  Code  requirements. 

The  person  or  firm  installing  the  moving  walk  shall 
provide  a  manufacturer's  written  procedure  and  demon- 
strate compliance  with  6.1.6.10  or  6.2.6.9.  Where  there 
are  no  test  or  check  requirements,  the  written  checklist 
must  state  "No  test  or  check  required/'  The  documenta- 
tion must  state  the  reason  no  test  or  check  is  required. 
This  procedure  may  also  be  part  of  the  maintenance 
control  program  (MCP)  as  required  by  8.6.1.2.1. 

The  following  shall  be  documented  or  demonstrated: 

(a)  completion  or  maintenance  of  circuit  (6.1.6.13) 

(b)  redundancy  and  its  checking  (6.1.6.10.1  and 
6.1.6.10.2) 


(c)  static  control  (6.1.6.10.3) 

(d)  electrically  powered  safety  devices  (EPD) 
(6.2.6.10) 

(e)  installation  of  devices  to  make  electrical  protective 
devices  (EPD)  ineffective  (6.2.6.11) 

(f)  contactors  and  relays  for  use  in  critical  operating 
circuits  (6.1.6.14) 

Also  include  documentation  when  required  by 
A17.7-2007/B44.7-07  and  later  editions  — 
Requirements  2.10.1  and  2.10.2. 

10.3.4  References  (io) 

A17.1d-2000  and  earlier  editions  —  Section  906  and 
Rules  907.2,  905.3i,  (NR6.2.6.12),  1206.1,  1008.2c,  and 
1009.21. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.2.7;  and  6.2.8.2, 6.2.6.9,  6.2.6.12,  8.6.1.2.1, 
8.11.4.2.3,  and  8.10.4.1.2(c). 

NFPA  70  or  CSA  C22.1,  as  applicable. 

ITEM  10.4 
DRIVE  MACHINE  AND  BRAKE 


10.4.1  Periodic  Inspections 

10.4.2  Periodic  Test 

Determine  whether  the  driving  machine  is  properly 
secured,  lubricated,  clean,  and  in  good  condition.  Visu- 
ally check  the  driving-machine  fastenings  and  bearing 
caps  to  verify  that  they  are  secure  and  in  place. 

Verify  that  the  driving  machine  is  connected  to  the 
main  drive  shaft  by  toothed  gearing,  a  mechanical  cou- 
pling, or  a  chain  and  that  it  is  in  good  condition.  Look 
for  evidence  of  any  excessive  backlash  in  the  driving 
gears  or  chains.  If  a  chain  is  used  to  connect  the  driving 
machine  to  a  sprocket  on  the  main  drive  shaft,  visually 
examine  the  chain  and  sprockets  for  wear,  excessive 
slack,  and  proper  lubrication.  Lack  of  lubrication  for  a 
chain  may  be  indicated  by  rouge  (red  rust  deposits)  on 
the  side  plates  of  the  links. 

For  moving  walks  installed  under  A17.1a-1988  and 
later  editions,  verify  that  cast  iron  links  are  not  used.  If 
the  links  appear  to  be  cast  iron,  have  a  small  hole  drilled 
(in  a  low  stress  area)  and  observe  the  drill  cuttings.  If 
the  cuttings  are  a  fine  powder,  cast  iron  is  indicated.  If 
the  cuttings  are  shavings,  then  the  links  are  not  cast  iron. 

Inspect  any  drive  belts  and  sheaves  for  damage,  wear, 
belt  tension,  and  reasonable  equality  of  tension  in  a  set 
of  belts. 

Visually  examine  the  components  for  signs  of  over- 
heating. Verify  that  an  electrically  released  brake  is  pres- 
ent and  automatically  applied  when  power  is 
interrupted.  A  brake  was  not  required  for  units  installed 
under  A17.1-1987  and  earlier  editions  if  the  unit  would 
not  run  in  the  down  direction  under  rated  load  with 
the  power  off.  The  brake  is  to  be  located  on  the  driving 
machine  for  units  installed  under  A17.1a-1988  and  later 


(io) 


134 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


editions  and  moving  walks  required  to  conform  to 
A17.3a-1994.  Earlier  editions  allowed  the  brake  to  be 
on  the  drive  shaft.  For  moving  walks  installed  under 
the  A17.1-1981  through  A17.1-1987  editions  and  A17.3, 
the  brake  may  be  applied  to  specially  attached  braking 
surfaces  directly  on  the  tread  way. 

For  moving  walks  installed  under  A17.1a-1988  and 
later  editions  and  moving  walks  required  to  conform  to 
A17.3a-1994  where  means  other  than  a  continuous  shaft, 
mechanical  coupling,  or  toothed  gearing  is  used  to  con- 
nect the  motor  to  the  reduction  gear,  verify  that  the 
brake  is  located  on  the  gear  reducer  or  main  drive  shaft. 
A17.3a-1994  requires  this  brake  on  the  main  drive  shaft 
or  a  specially  attached  braking  surface  attached  directly 
to  the  tread  way. 

For  moving  walks  installed  under  A17.1a-1988  and 
later  editions,  and  moving  walks  required  to  conform 
to  A17.3a-1994,  the  brake  may  be  magnetically  applied 
using  a  ceramic  permanent  magnet.  Prior  to  this,  a 
mechanically  applied  brake  was  required.  Visually 
inspect  the  condition  of  the  brake  pads,  drums,  and 
discs. 

For  moving  walks  installed  to  A17.1a-1988  and  later 
editions,  this  brake  must  stop  a  down  or  horizontal 
running  moving  walk  with  a  retardation  not  to  exceed 
3  ft/s2  (0.91  m/s2).  For  moving  walks  installed  to 
A17.1a-1988  through  A17.1-2000,  this  was  a  maximum 
rate.  For  moving  walks  installed  to  A17.1a-2002  and 
later  editions,  it  is  an  average  rate,  but  there  is  an  addi- 
tional restriction  on  the  peak  horizontal  retardation, 
which  is  not  intended  to  be  field  verified. 

It  is  not  required  to  measure  the  actual  retardation. 
Instead  the  brake  torque  will  provide  verification  that 
those  requirements  are  met  in  addition  to  other  brake 
requirements  (e.g.  stopping  and  holding  the  rated  load). 

Verify  that  moving  walks  installed  under  A17.1a-1988 
and  later  editions  have  a  nameplate  or  data  plate  that 
specifies  the  required  brake  torque.  Moving  walks 
installed  under  A17.1b-1989  and  later  editions  require 
that  the  nameplate  or  data  plate  torque  be  specified  as 
breakaway,  the  maximum  torque  required  to  cause  the 
brake  to  begin  moving,  or  dynamic,  the  torque  required 
to  keep  the  shaft  moving  very  slowly  at  a  steady  rate.  The 
location  where  the  torque  is  to  be  measured  is  required  to 
be  clearly  indicated. 

For  moving  walks  installed  under  A17.1a-1991  and 
later  editions,  the  nameplate  or  data  plate  is  required 
to  specify  the  range  of  brake  torque.  For  moving  walks 
installed  under  Al  7. 1-2000  and  later  editions,  the  mini- 
mum stopping  distance  with  no  load  must  be  indicated. 

Have  the  torque  tested  to  verify  that  the  torque  com- 
plies and  check  the  minimum  stopping  distance.  Note 
that  temperature  can  affect  the  brake  torque.  The  torque 
wrench  should  have  a  current  calibration  certificate 
traceable  to  the  National  Bureau  of  Standards  and  have 
a  range  of  at  least  25%  higher  than  the  required  torque. 


If  the  driving-machine  brake  is  separated  from  the 
main  drive  shaft  by  a  chain  and  the  moving  walk  is 
capable  of  running  by  gravity  with  any  load,  check  for 
presence  of  a  second  brake  that  is  required  on  the  main 
drive  shaft.  The  requirements  for  this  brake  are 

(a)  A17.1-1965  through  A17.1-1987  required  this 
brake  to  be  electrically  released  unless  an  electrically 
released  brake  was  provided  on  the  driving  machine. 

(b)  A17.1a-1988  and  later  editions  required  the  brake 
to  be  mechanically  or  magnetically  applied  (ceramic  per- 
manent magnets),  and  allowed  it  to  be  located  either  on 
the  main  drive  shaft  or  a  special  braking  surface  attached 
to  the  treadway. 

(c)  For  moving  walks  installed  under  the  A17.1a-1988 
through  A17.1d-2000,  the  brake  is  required  to  stop  hori- 
zontal or  a  down-running  moving  walk  at  a  rate  not 
greater  than  3  ft/sec2  (0.91  m/s2). 

10.4.3  Acceptance 

Check  the  stopping  distance  with  no  load  against  the 
minimum  distance  information  on  the  data  plate. 

10.4.4  References 

A17.1d-2000  and  earlier  editions  —  Section  904;  and 
Rule  1008.2d. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.2.5;  and  8.11.4.2.4. 

A17.3  —  Paragraph  9.5.1. 


ITEM  10.5 
SPEED  GOVERNOR 

10.5.1  Periodic  Inspections 

10.5.2  Periodic  Test 

Test  speed  governor  when  provided  to  verify  that  it 
is  functioning.  Manually  operate  the  switch  or  use  any 
testing  mechanisms  (such  as  flywheel  weights)  that  may 
be  provided.  The  flyballs  and  all  operating  mechanisms 
must  be  present  and  in  good  operating  condition.  When 
the  switch  is  opened,  it  should  interrupt  power  to  the 
driving  machine.  For  moving  walks  installed  under 
A 17. 1-1 990  and  later  editions,  verify  that  the  moving 
walk  cannot  be  started  by  the  starting  switch  until  the 
device  is  manually  reset. 

A17.3a-1994  requires  that  the  speed  governor  activate 
when  the  speed  exceeds  20%  above  the  rated  speed. 
Al 7. 1-1965  and  later  editions  require  that  the  speed 
governor  activate  when  the  speed  exceeds  40%  above 
the  rated  speed. 

When  a  manual  reset  is  required  for  units  installed 
under  A17.1b-1995  and  later  editions,  turn  the  power 
off  and  then  back  on,  and  then  try  the  start  switch  to 
check  that  the  device  will  not  reset.  Also,  some  indication 
that  the  device  has  been  activated  needs  to  be  provided 
(fault  finder,  etc.). 


135 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


10.5.3  Acceptance 

When  a  speed  governor  is  required,  verify  that  the 
speed  governor  activates  at  the  proper  speed,  which 
cannot  be  more  than  40%  above  the  rated  speed.  This 
can  be  done  on  some  models  using  a  rubber  drive  wheel 
driven  by  a  variable  speed  drill  and  a  tachometer.  Other 
methods  approved  by  the  manufacturer  for  field  testing 
pulse  pickup  type  or  other  electronic  governors  may 
be  used. 

10.5.4  References 

A17.1d-2000/B44-00  and  earlier  editions  — 
Rules  905.3b,  1008.2e,  and  1009.21. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.2.6.3.2,  8.11.4.2.5,  and  8.10.4.1.2(c). 

A17.3  —  Paragraph  9.6.4. 

ITEM  10.6 

BROKEN  DRIVE  CHAIN 

AND  DISCONNECTED  MOTOR 

SAFETY  DEVICE 

10.6.1  Periodic  Inspections 

10.6.2  Periodic  Test 

(a)  If  the  driving  machine  is  connected  to  the  main 
drive  shaft  by  a  chain,  check  the  broken  drive  chain 
device  to  verify  that  it  will  apply  the  main  shaft  brake 
and  stop  the  drive  machine  if  the  drive  chain  parts.  All 
parts  of  the  device  should  be  in  good  condition  and 
show  freedom  to  move.  Have  the  switch  manually  oper- 
ated and  verify  that  it  will  open  the  drive  motor  circuit. 
Common  devices  include  a  block  that  is  held  in  tension 
by  the  drive  chain  that  activates  the  switch  when  tension 
is  lost,  or  a  plate  that  depresses  a  switch  when  the  drive 
chain  strikes  it.  For  moving  walks  installed  under 
A17.1-1990  and  later  editions,  verify  that  the  moving 
walk  cannot  be  started  by  the  starting  switch  until  the 
device  is  manually  reset. 

When  a  manual  reset  is  required  for  units  installed 
under  A17.1b-1995  and  later  editions,  turn  the  power 
off  and  then  back  on,  and  then  try  the  start  switch  to 
check  that  the  device  will  not  reset.  Also,  some  indication 
that  the  device  has  been  activated  needs  to  be  provided 
(fault  finder,  etc.). 

(b)  If  the  drive  motor  is  attached  to  a  gear  reducer 
by  means  other  than  a  continuous  shaft,  coupling,  or 
toothed  gearing,  check  that  the  device  provided  will 
apply  the  brake  if  the  motor  becomes  disconnected  from 
the  gear  reducer.  Have  the  switch  manually  operated 
and  verify  that  all  operating  mechanisms  are  present, 
clean,  lubricated,  and  in  good  condition.  For  moving 
walks  installed  under  A17.1-1990  and  later  editions, 
verify  that  the  moving  walk  cannot  be  started  by  the 
starting  switch  until  the  device  is  manually  reset. 

When  a  manual  reset  is  required  for  units  installed 
under  A17.1b-1995  and  later  editions,  turn  the  power 


off  and  then  back  on,  and  then  try  the  start  switch  to 
check  that  the  device  will  not  reset.  Also,  some  indication 
that  the  device  has  been  activated  needs  to  be  provided 
(fault  finder,  etc.). 

10.6.3  Acceptance 

10.6.4  References 

A17.1d-2000  and  earlier  editions  —  Rules  904.3b, 
905.3d,  905.3h,  and  1008.2f. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.2.5.3.2,  6.2.6.3.4,  6.2.6.3.8,  and  8.11.4.2.6. 

A17.3  —  Paragraphs  9.6.6  and  9.6.10. 

ITEM  10.7 
REVERSAL  STOP  SWITCH 

10.7.1  Periodic  Inspections 

10.7.2  Periodic  Test 

Manually  operate  the  reverse  stop  switch  to  verify 
that  all  operating  mechanisms  are  present  and  in  good 
condition  and  that  the  device  will  open  the  circuits  to  the 
driving-machine  motor  and  brake  to  stop  an  ascending 
moving  walk  from  reversing  its  direction  of  travel.  For 
moving  walks  installed  under  A17.1-1990  and  later  edi- 
tions, verify  that  the  moving  walk  cannot  be  started  by 
the  starting  switch  until  the  device  is  manually  reset. 

When  a  manual  reset  is  required  for  units  installed 
under  A17.1b-1995  and  later  editions,  turn  the  power 
off  and  then  back  on,  and  then  try  the  start  switch  to 
check  that  the  device  will  not  reset.  Also,  some  indication 
that  the  device  has  been  activated  needs  to  be  provided 
(fault  finder,  etc.). 

There  are  several  different  types  of  devices  that  are 
used  (friction  reversal  devices,  speed  monitoring,  etc.). 
Therefore,  the  type  of  device  will  dictate  the  testing 
procedure.  If  the  device  cannot  be  manually  operated, 
a  written  procedure  must  be  provided  by  the  person  or 
firm  performing  the  tests. 

10.7.3  Acceptance 

10.7.4  References 

A17.1d-2000  and  earlier  editions  —  Rules  905.3g  and 
1008.2g. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.2.6.3.7  and  8.11.4.2.7. 

A17.3  —  Paragraph  9.6.8. 

ITEM  10.8 
BROKEN  TREADWAY  DEVICE 

10.8.1  Periodic  Inspections 

10.8.2  Periodic  Test 

Manually  operate  the  broken  treadway  devices  to  ver- 
ify that  each  will  interrupt  power  to  the  driving  machine 


136 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


and  brake.  Visually  inspect  each  device  to  verify  that 
they  are  in  position  to  operate  and  that  either  will  acti- 
vate when  the  connecting  means  breaks  between  pallets 
or  belt. 

For  moving  walks  installed  under  A17.1-1990  and 
later  editions,  verify  that  the  moving  walk  cannot  be 
started  by  the  starting  switch  until  the  device  is  manu- 
ally reset. 

When  a  manual  reset  is  required  for  units  installed 
under  A17.1b-1995  and  later  editions,  turn  the  power 
off  and  then  back  on,  and  then  try  the  start  switch  to 
check  that  the  device  will  not  reset.  Also,  some  indication 
that  the  device  has  been  activated  needs  to  be  provided 
(fault  finder,  etc.). 

10.8.3  Acceptance 

10.8.4  References 


Rules  905.3c  and 
editions     — 


A17.1d-2000  and  earlier  editions 
1008.2h. 

A17.1-2000/B44-00     and     later 
Requirements  6.2.6.3.3  and  8.11.4.2.8. 

ITEM  10.9 
(RESERVED) 

ITEM  10.10 
MISSING  PALLET  DEVICE 

10.10.1  Periodic  Inspections 

(10)     10.10.2  Periodic  Test 

For  moving  walks  installed  under  A17.1b-1989  and 
later  editions,  test  the  missing  pallet  device  by  running 
the  moving  walk  with  a  pallet  missing  on  the  underside 
of  the  moving  walk.  The  device  must  stop  the  moving 
walk  before  the  gap  resulting  from  the  missing  pallet 
emerges  from  the  combplate. 

For  moving  walks  installed  under  A17. 1-1990  and 
later  editions,  verify  that  the  moving  walk  cannot  be 
started  by  the  starting  switch  until  the  device  is  manu- 
ally reset. 

When  a  manual  reset  is  required  for  units  installed 
under  A17.1b-1995  and  later  editions,  turn  the  power 
off  and  then  back  on,  and  then  try  the  start  switch  to 
check  that  the  device  will  not  reset.  Also,  some  indication 
that  the  device  has  been  activated  needs  to  be  provided 
(fault  finder,  etc.). 

10.10.3  Acceptance 

10.10.4  References 

A17.1d-2000  and  earlier  editions  —  Rules  905.5  and 
1008.2J. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.2.6.5  and  8.11.4.2.10. 


ITEM  10.11 
PALLET  LEVEL  DEVICE 

10.11.1  Periodic  Inspections 

10.11.2  Periodic  Test 

For  moving  walks  installed  under  A17.1-1990  and 
later  editions  that  are  equipped  with  pallets  and  trail 
wheels,  visually  inspect  the  pallet  level  devices  at  each 
end  and  on  both  sides  to  verify  that  it  is  in  place  and 
able  to  function.  Have  the  switch  manually  operated  to 
verify  that  it  will  open  the  safety  circuit  and  stop  the 
moving  walk. 

For  moving  walks  installed  under  A17.1-1990  and 
later  editions,  verify  that  the  moving  walk  cannot  be 
started  by  the  starting  switch  until  the  device  is  manu- 
ally reset. 

When  a  manual  reset  is  required  for  units  installed 
under  A17.1b-1995  and  later  editions,  turn  the  power 
off  and  then  back  on,  and  then  try  the  start  switch  to 
check  that  the  device  will  not  reset.  Also,  some  indication 
that  the  device  has  been  activated  needs  to  be  provided 
(fault  finder,  etc.). 

10.11.3  Acceptance 

Have  the  devices  tested  (at  both  ends  and  on  each 
side)  by  mechanically  lowering  a  pallet  \  in.  (3.2  mm) 
and  operating  the  moving  walk.  A  smaller  roller  or 
adjustment  may  be  used  to  lower  the  pallet. 

10.11.4  References 

A17.1d-2000  and  earlier  editions  —  Rules  905.3i, 
1008.2k,  and  1009.2n. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.2.6.3.9,  8.11.4.2.11,  and  8.10.4.1.2(k). 


ITEM  10.12 

PALLETS,  PALLET  CHAINS, 

AND  TRUSSES 

10.12.1  Periodic  Inspections 

10.12.2  Periodic  Test 

Have  at  least  half  of  the  pallets  removed,  then  move 
the  remaining  pallets  to  one  end  of  the  moving  walk 
and  using  a  good  light,  visually  inspect  the  drip  pans, 
undersides  of  pallets,  trusses,  roller  tracks,  chains,  hand- 
rails, and  the  interiors  of  balustrades,  skirts,  and  newels 
to  verify  that  they  are  present,  in  good  condition,  clean 
of  dirt  and  rubbish,  and  free  of  oil  and  combustibles. 

Visually  inspect  for  any  damage  to  the  fire- resistive 
material  on  the  moving  walk  enclosure.  See  Item  10.1. 

Visually  inspect  the  chains  for  lubrication  and  buildup 
of  dirt  and  grease.  Lack  of  lubrication  may  be  indicated 
by  rouge  (red  rust  deposits)  on  the  side  plates  of  the 
links. 


137 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Verify  that  cast  iron  links  are  not  used  on  moving 
walks  installed  under  A 17. 1-1978  and  later  editions.  See 
Item  10.4.2  for  method  of  identifying  cast  iron. 

Check  the  operation  of  any  moving  walk  pallet  chain 
tension  devices.  If  they  are  of  the  automatically  operated 
"tension-weight"  type,  verify  that  the  truss  is  provided 
with  a  positive  means  to  retain  the  weights  in  the  truss 
if  the  weights  are  released. 

Move  the  remaining  pallets  to  the  opposite  end  of  the 
moving  walk  and  inspect  the  other  half  in  the  same 
manner. 

10.123  Acceptance 

(a)  Verify  that  if  the  tracking  system  fails,  the  running 
gear  is  retained  in  its  guides  and  the  treadway  wheel 
tracks  will  prevent  displacement  of  the  treadways  and 
running  gear  if  the  chain  breaks. 

(b)  Inspect  the  treadway  support  structure  for  compli- 
ance with  the  Code  for  the  following  types  of  walks: 

(1)  Slider  Bed.  Verify  that  the  treadway  is  supported 
for  its  entire  length,  except  where  it  passes  a  pulley 
support  and  that  the  bed  is  smooth  and  noncombustible. 

(2)  Roller  Bed.  Test  the  deflection  of  the  treadway 
surface  by  placing  a  25  lb  (11.3  kg)  weight  on  a  cylinder 

2  in.  (51  mm)  long  and  1  in.  (25  mm)  in  diameter  with 
its  long  axis  across  the  belt  midway  between  rollers.  Use 
a  straight  edge  that  spans  the  rollers  and  a  feeler  gauge 
or  dial  indicator  depth  gauge  to  measure  the  deflection. 
Perform  this  test  on  5%  of  the  rollers  at  random  and 
verify  that  the  deflection  does  not  exceed  0.09  in. 
(2.29  mm)  plus  0.004  times  the  distances  in  inches 
between  the  roller  centers.  Ride  the  moving  walk  and 
observe  for  roller  concentricity  over  the  full  width  of 
the  belt. 

(3)  Edge  Support  Belt.  When  the  treadway  belt  is 
transversely  rigid  and  is  supported  by  rollers  along  the 
edges,  test  the  slope  (or  tension)  as  follows: 

(a)  The  belt  should  be  properly  tensioned  and  a 
150  lb  (68  kg)  weight  placed  on  a  rigid  plate  6  in. 
(152  mm)  by  10  in.  (254  mm)  with  the  10  in.  (254  mm) 
dimension  in  the  direction  of  travel  located  on  the 
treadway  centerline. 

(b)  Use  a  straight  edge  and  feeler  gauge  or  dial 
indicator  depth  gauge  to  measure  the  deflection  across 
the  treadway  from  the  center.  The  Code  allowance  of 

3  deg  maximum  would  result  in  deflection  of  0.576  in. 
(14.6  mm)  for  a  22  in.  (559  mm)  width,  1.048  in.  (26.6  mm) 
for  40  in.  (1  016  mm)  width,  and  1.572  in.  (39.9  mm)  for 
a  60  in.  treadway  width. 

(c)  Inspect  the  center  support  for  localized  load- 
ing for  distance  apart  [6  ft  (1.789  m)  max.]  and  distance 
from  the  underside  of  the  treadway  [2  in.  (51  mm)  max.]. 

(4)  Pallet  Type.  Inspect  the  support  and  wheels  to 
verify  that  the  pallets  cannot  be  displaced  vertically 
more  than  \  in.  (3.2  mm)  should  the  pallet  connecting 


means  break.  With  the  power  off  have  two  pallets  discon- 
nected at  the  center  of  the  moving  walk  run.  Find  the 
maximum  displacement  by  lifting  on  the  pallet  edges 
with  a  moderate  force.  The  stop  should  be  detected 
before  the  maximum  displacement  allowed  by  the  Code 
is  reached.  Verify  that  foreign  material  such  as  stone  or 
concrete  is  not  in  the  truss  interior. 

(c)  Check  that  components  not  used  directly  in  con- 
nection with  the  operation  of  the  moving  walk  are  not 
installed  on,  in,  or  through  the  moving  walk. 

10.12.4  References 

A17.1d-2000  and  earlier  editions  —  Rules  901.1, 902.9, 
902.13,  1008.21,  1009.2o,  and  1206.6. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.2.2.1,  6.2.3.9,  6.2.3.13,  6.2.3.17, 
8.11.4.2.12,  8.10.4.1.2(1),  and  8.6.8. 

ITEM  10.13 
HANDRAIL  SYSTEMS  AND  SAFETY  DEVICES 

10.13.1  Periodic  Inspections 

10.13.2  Periodic  Test 

Examine  the  handrail  drive  systems  to  ensure  that  all 
chains,  pulleys,  gears,  rollers,  and  belts  are  present  and 
in  good  condition.  The  operation  should  be  free  of  exces- 
sive noise  and  slack,  which  indicates  wear. 

(a)  For  moving  walks  installed  under  A17.1b-1989 
through  A17.1b-1992,  test  the  operation  of  the  stopped 
handrail  device.  Have  the  handrail  motion  sensor 
mechanically  disconnected  while  the  unit  is  off  and  then 
run  the  unit,  or  grab  the  handrail  and  stall  it  while  the 
moving  walk  is  running.  Verify  that  the  alarm  sounds 
immediately  and  the  moving  walk  stops  within  15  sec. 

(b)  For  moving  walks  installed  under  Al 7. 1-1 993  and 
later  editions,  check  the  operation  of  the  handrail  speed 
monitoring  device.  An  alarm  must  sound  immediately 
if  the  speed  of  either  handrail  deviates  from  the  step 
speed  by  15%  or  more,  and  the  unit  must  shut  down  if 
the  speed  deviation  is  continuous  for  2  sec  to  6  sec.  If 
holding  the  moving  handrail  cannot  activate  the  device, 
then  it  will  be  necessary  to  activate  the  device  by  another 
means  (disconnecting  the  speed  sensor,  changing  dip 
switch  settings  on  the  controller,  etc.).  Verify  that  the 
unit  cannot  be  started  until  the  device  is  manually  reset. 
For  units  installed  under  A17.1b-1995  and  later  editions, 
turn  the  power  off  and  then  back  on  and  then  try  the 
start  switch  to  check  that  the  device  will  not  reset.  Also, 
some  indication  that  the  device  has  been  activated  needs 
to  be  provided  (fault  finder,  etc.). 

(c)  For  moving  walks  installed  under  A17.1b-1992 
and  later  editions,  test  the  operation  of  the  handrail 
entry  device  by  having  a  soft  object  that  will  not  damage 
the  unit  inserted  between  the  handrail  and  hand  guard. 
After  the  unit  stops,  verify  that  it  cannot  be  restarted 
with  the  key  switch  until  the  device  has  been  manually 


(10) 


138 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


reset.  The  device  need  only  operate  in  the  direction  of 
the  handrail  travel,  except  for  units  installed  under 
A17.1a-1997  and  later  editions  the  device  must  operate 
irregardless  of  the  direction  of  travel  of  the  handrail 
where  an  opening  is  created  in  the  balustrade  to  prevent 
entrapment.  When  a  manual  reset  is  required  for  units 
installed  under  A17.1b-1995  and  later  editions,  turn  the 
power  off  and  then  back  on  and  then  try  the  start  switch 
to  check  that  the  device  will  not  reset.  Also,  some  indica- 
tion that  the  device  has  been  activated  needs  to  be  pro- 
vided (fault  finder,  etc.). 

10.13.3  Acceptance 
(10)     10.13.4  References 

A17.1d-2000  and  earlier  editions  —  Rules  902.4, 
902.13, 905.1, 905.4, 905.3J,  (NR  8.6.9.1),  1008.2m,  1008.2q, 
and  1009.2c. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  6.2.3.4,  6.2.3.13,  6.2.6.1,  6.2.6.4,  6.2.6.3.10, 
8.6.9.1,  8.11.4.2.13,  8.11.4.2.18,  and  8.10.4.1.1(c). 

ITEM  10.14 
CODE  DATA  PLATE 

10.14.1  Periodic  Inspections 

Check  that  the  Code  Data  Plate  is  installed.  This  is 
the  Code  that  is  to  be  used  for  the  inspection  and  test. 

10.14.2  Periodic  Test 

10.14.3  Acceptance 

10.14.4  References 

A17.1d-2000  and  earlier  editions  —  Rules  808,  908, 
and  1200.6. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  8.9,  8.9,  and  8.7.1.8. 

ITEM  10.15 
RESPONSE  TO  SMOKE  DETECTORS 

10.15.1  Periodic  Inspections 

10.15.2  Periodic  Test 

For  units  installed  under  A17.1a-1994  and  later  edi- 
tions, when  smoke  detectors  are  provided  that  will  shut 
down  a  running  unit,  verify  that  the  emergency  stop 
button  alarm  will  sound  and  the  unit  does  not  shut  down 
for  at  least  15  s.  The  unit  may  be  tested  by  activating  the 
smoke  detector  or  by  other  means. 

CAUTION:  If  the  sensing  system  is  connected  to  a  central  fire 
alarm  system,  notify  proper  authorities  before  activating. 

10.15.3  Acceptance 

10.15.4  References 

A17.1d-2000  and  earlier  editions  —  Rule  905.7. 
A17.1-2000/B44-00      and      later      editions     — 
Requirement  6.2.6.7. 


ITEM  10.16 
INSPECTION  CONTROL 

10.16.1  Periodic  Inspections 

10.16.2  Periodic  Test 

If  provided,  check  the  operation  of  the  inspection  con- 
trol device.  Check  that  the  device  only  permits  move- 
ment by  a  constant  pressure  means,  and  clearly  indicates 
the  direction  of  travel.  If  a  plug-in  control  station  is  used, 
verify  that  it  is  stored  in  the  upper  pit. 

10.16.3  Acceptance 

Verify  that  when  the  transfer  switches  located  at  each 
landing  are  enabled,  only  the  inspection  control  device 
can  operate  the  equipment.  Verify  that  the  switches  are 
properly  located,  manually  operated,  protected  against 
accidental  contact,  and  properly  labeled.  Verify  that  if 
both  switches  are  activated,  then  all  inspection  control 
devices  are  inoperative. 

If  a  portable  control  station  is  used,  verify  that  the 
cord  does  not  exceed  the  maximum  allowed  length.  If 
a  plug-in  portable  control  station  is  used,  check  that 
either  a  transfer  switch  is  provided  or  that  when  the 
portable  control  station  is  plugged  in,  the  control  of  the 
equipment  is  automatically  transferred  to  the  control 
station. 


10.16.4  References 

A17.1-2000/B44-00 
Requirement  6.2.6.2.2. 


and     later     editions 


ITEM  10.17 

EARTHQUAKE  INSPECTION  AND  TESTS  (SEISMIC 

RISK  ZONE  2  OR  GREATER) 

10.17.1  Periodic  Inspections 

10.17.2  Periodic  Test 

10.17.3  Acceptance 

(a)  Verify  that  the  connections  between  the  truss  and 
the  building  are  installed  according  to  the  manufactur- 
er's drawings. 

(b)  Verify  that  restraints  are  installed  and  allow  move- 
ment as  required. 


(10) 


10.17.4  References 

A17.1-2000/B44-00     and 
Requirements  8.5.2  and  8,5,3. 


later     editions 


139 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers, 
v     No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


(10) 


Part  11 
Elevator  —  Machine- Room -Less  (MRL) 


This  part  is  an  informative  guide  to  the  inspection 
and  testing  of  elevators  with  machine-room-less  (MRL) 
configurations.  In  many  cases,  the  inspections  and  tests 
in  Parts  1  through  5  are  the  same  as  conventional  config- 
urations. However,  this  part  is  intended  to  supplement 
the  procedures  in  Parts  1, 2, 3,  4,  and  5  in  order  to  account 
for  the  inspection  and  test  procedures  that  may  be  neces- 
sary for  MRL  configurations, 

CAUTION:  It  is  important  for  the  inspector  to  be  familiar  with 
the  location  of  all  components  and  manufacturer's  recommended 
procedures  prior  to  beginning  any  inspections  or  tests. 

See  the  Elevator  Industry  Field  Employee's  Safety  Handbook 
foreword  regarding  the  need  to  carefully  observe  the  safety  con- 
ditions at  each  job  site  to  make  sure  there  are  no  conditions  that 
would  require  safety  precautions  beyond  those  contained  in  the 
Handbook. 


ITEM  11.1 

ACCESS  TO  MACHINE  ROOM/MACHINERY  SPACE/ 

CONTROL  ROOM/CONTROL  SPACE 

11.1.1  Periodic  Inspections 

11.1.2  Periodic  Test 

11.1.3  Acceptance 

Check  to  ensure  that  permanent  and  unobstructed 
access  is  provided  to  machine /control  rooms,  machinery 
and  control  spaces  outside  of  the  hoistway,  and  to 
machinery  and  control  spaces  inside  the  hoistway  that 
do  not  have  a  means  of  access  specified  in  Requirement 
2.73.1.2.  For  spaces  located  in  the  hoistway,  ensure  the 
following: 

(a)  Where  machine  or  emergency  brake(s)  or  elevator 
motion  or  motor  controllers  are  located  in  the  pit,  a 
permanent  means  stored  or  installed  in  the  pit  to  provide 
access  when  required. 

(b)  Where  access  to  a  working  platform  is  in  the  line 
of  movement  with  a  car  or  counterweight  through  an 
access  panel  or  door,  verify  it  is  provided  with  an  electro- 
mechanical device  that  will  prevent  operation  of  the 
machine. 

Access  panels  for  access  through  the  car  to  machine/ 
control  spaces  in  the  hoistway  must  use  a  key  to  open 
that  is  Group  1  security.  The  access  panel  must  have  an 
electrical  switch  to  prevent  operation  when  the  panel  is 
open.  The  access  panel  must  not  be  self-closing  and  must 
be  self-locking. 


Where  required,  vertical  ladders  can  be  used  in  lieu 
of  stairs  to  overhead  machinery  spaces,  except  those 
containing  controllers  and  generators. 

11.1.4  References 

A17.1S-2005  and  later  editions  —  Requirements  2.7.3, 
2.2.4/2.7.5.2.4,  2.12.6/2.12.7,  2.7.3.1.2/2.7.5.3.5,  and 
2.7.3.1.2/2.7.5.1.4. 

ITEM  11.2 
ACCESS  DOOR  AND  OPENINGS 

11.2.1  Periodic  Inspections 

Verify  that  access  doors 

(a)  are  self-closing  and  self-locking 

(b)  have  spring  type  lock,  made  to  be  opened  from 
the  inside  without  a  key 

(c)  are  kept  closed  and  locked 

(d)  are  Group  2  security 

11.2.2  Periodic  Test 

11.2.3  Acceptance 

Check  to  see  that  doors  to  machine  and  control  rooms 
are  29.5  in.  (750  mm)  x  80  in.  (2  030  mm).  All  other 
access  doors  shall  be  a  minimum  width  and  height  of 
29.5  in.  (750  mm). 


11.2.4  References 

A17.1S-2005         and         later 
Requirements  2.7.3.4.1  and  2.7.3.4.2. 


editions         — 


ITEM  11.3 
ENCLOSURE  OF  ROOMS  AND  SPACES 

11.3.1  Periodic  Inspections 

11.3.2  Periodic  Test 

11.3.3  Acceptance 

When  the  local  building  code  requires  the  room  to 
be  of  fire-resistive  construction,  ensure  that  the  room 
containing  the  elevator  equipment  complies  with  the 
requirements  of  the  building  code. 

When  of  the  nonfire-resistive  construction,  the  follow- 
ing shall  apply: 

(a)  machine  rooms/control  rooms/control  spaces 
must  be  enclosed  a  minimum  of  79  in.  (2  000  mm) 


140 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


(b)  machinery  spaces  must  be  enclosed  to  a  height  of 
not  less  79  in.  (2  000  mm)  or  to  the  height  of  the  machin- 
ery space  if  it  is  less  than  79  in.  (2  000  mm) 

113.4  References 

A17.1S-2005  and  later  editions  — 
Requirements  2.7.1.1.1/2.7.1.1.2  and  2.7.1.2/2.7.1.2.1. 


ITEM  11.4 
MAINTENANCE  PATH  AND  CLEARANCE 

11.4.1  Periodic  Inspections 

Verify  that  a  clear  path  is  kept  at  all  times. 

11.4.2  Periodic  Test 

11.4.3  Acceptance 

A  path  for  maintenance  must  be  kept  as  follows: 

(a)  Machine  and  control  rooms:  Verify  a  clear  path  of 
18  in.  (450  mm)  to  all  maintainable  components. 

(b)  Machine  and  control  spaces:  Check  for  safe  and 
convenient  access  to  maintainable  equipment. 

However,  if  the  space  is  to  be  used  as  full  bodily  entry, 
it  shall  have  a  path  of  18  in.  (450  mm). 

11.4.4  References 

A17.1S-2005  and  later  editions  —  Requirement  2.7.2. 


ITEM  11.5 

MACHINE/CONTROL  ROOMS  CONTAINING 

OVERHEAD  DRIVE  MACHINES 

11.5.1  Periodic  Inspections 

11.5.2  Periodic  Test 

11.5.3  Acceptance 

For  machine /control  rooms,  and  machinery /control 
spaces,  verify 

(a)  permanent  lighting  is  installed  in  room  or  space 

(b)  lighting  switch  is  within  easy  reach  of  the  access 
to  such  room  or  space 

(c)  that  operating  instructions  for  safe  access  to  car 
top  working  area  are  kept  on  the  premises 

(d)  correct  lighting  intensity 

NOTE:     The  machinery  space  lighting  may  be  the  top  of  car  light- 
ing provided  it  meets  the  requirements. 

11.5.4  References 

A17.1S-2005  and  later  editions  —  Requirements  2.7.4, 
2.7.9 /2.7.632(c),  and  8.6.11.6. 


ITEM  11.6 
TEMPERATURE/HUMIDITY 

11.6.1  Periodic  Inspections 

11.6.2  Periodic  Test 

11.6.3  Acceptance 

Machine /control  room  and  machinery/ control  space 
temperature  and  humidity  allowances,  verify 

(a)  that  requirements  are  posted 

(b)  current  conditions  are  within  posted  requirements 

11.6.4  References 

A17.1S-2005  and  later  editions  —  Requirement  2.7.9.2. 

ITEM  11.7 
DISCONNECTING  MEANS 

11.7.1  Periodic  Inspections 

11.7.2  Periodic  Test 

11.7.3  Acceptance 

Verify  that  a  stop  switch  or  disconnecting  means  is 
provided  in  the  machinery  or  control  space  and  is  acces- 
sible and  visible  from  the  point  of  access. 

11.7.4  References 

A17.1S-2005  and  later  editions  —  Requirement  2.7.3.5. 

ITEM  11.8 
REMOTE  MACHINE  ROOMS  AND  CONTROL  ROOMS 

11.8.1  Periodic  Inspections 

11.8.2  Periodic  Test 

11.8.3  Acceptance 

(a)  If  the  elevator  has  a  remote  machine  and /or  con- 
trol room,  verify  the  following: 

(1)  permanent  means  of  communication  is  opera- 
tive between  car  and  room 

(2)  ropes /sheaves  are  fully  enclosed,  if  necessary 

(3)  unauthorized  persons  cannot  access  these 
enclosures  —  Group  2  security  key 

(b)  If  means  are  provided  to  access  the  equipment  for 
inspection,  verify 

(1)  a  stop  switch  is  present 

(2)  a  permanent  light  and  switch  are  present  and 
accessible  from  the  access  door  or  opening 

(3)  a  duplex  receptacle  is  present  (GFI  receptacle, 
if  CSA  C22.1  enforced) 

11.8.4  References 

A17.1S-2005  and  later  editions  — 
Requirements  2.7.8.1,  2.7.8.4,  and  2.7.8.3. 


141 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


ITEM  11.9 
INSPECTION  AND  TEST  PANELS 

11.9.1  Periodic  Inspections 

11.9.2  Periodic  Test 

11.9.3  Acceptance 

(a)  Means  necessary  for  tests  are  as  follows: 

(1)  If  the  drive  machine  or  emergency  brake,  or 
motion  or  motor  controller  are  located  in  the  hoistway 
or  pit,  verify  that  the  car  can  be  moved  from  outside  of 
the  hoistway  (see  Cautionary  Note). 

(2)  In  order  to  move  the  car,  verify  that  normal 
building  power  is  not  needed,  the  means  is  accessible  to 
only  elevator  personnel  and  requires  continuous  effort. 

(3)  If  the  drive  sheave  or  rope  cannot  be  seen  from 
the  test  location,  verify  display  devices  are  provided  for 
the  following: 

(a)  direction  of  movement 

(b)  indication  of  position  within  the  door 
unlocking  zone 

(c)  indication  of  speed 

(d)  verify  display  device  is  operable  if  loss  of 
normal  building  power 

(4)  If  display  devices  are  dependent  on  batteries, 
verify  the  following: 

(a)  monitoring  of  any  batteries  is  operative 

(b)  the  car  cannot  restart  after  a  normal  stop 
when  there  is  insufficient  power  for  the  display  devices 

(5)  Verify  that  the  means  to  move  the  car  from 
outside  of  the  hoistway 

(a)  not  be  dependent  on  normal  power 

(b)  is  accessible  only  by  Group  1  security 

(c)  needs  continuous  effort  to  move  car 

(6)  If  manual  effort  means  is  needed  to  move  the 
car,  verify 

(a)  its  presence 

(b)  it  is  suitably  marked  and,  if  portable,  is  stored 
outside  the  hoistway  and  only  accessible  by  Group  1 
security 

(c)  the  manual  device  must  not  require  more  than 
90  lbf  (400  N)  to  move  the  car  or  an  electrical  means 
shall  be  provided 

(7)  If  electrical  means  are  provided  to  move  the  car 

(a)  verify  that  it  requires  constant  pressure 

(b)  if  monitoring  system  indicates  it  is  insufficient 
of  the  electrical  operation  for  the  movement  of  the  car, 
it  must  not  be  permitted  to  restart  after  a  normal  stop 

(c)  prevents  operation  of  the  car  by  all  other 
operating  means 

(b)  Check  the  inspection  and  test  panel  where  pro- 
vided for  the  following: 

(1)  readily  accessible 

(2)  keyed  for  Group  1  Security 

(3)  has  self-locking  but  not  self-closing  doors  or 
panels 


(4)  stop  switch  is  present 

(5)  lighting  is  permanent  and  of  sufficient  lux/ foot- 
candles 

(6)  contains  car  and  hoistway  door  bypass  switches 

(7)  has  means  to  manually  reset  the  following: 

(a)  unintended  car  movement 

(b)  ascending  car  protection 

(c)  car  safety  mechanism 

(d)  car  buffer  switch 

(e)  final  terminal  stopping  devices  and  governor 
switches  (where  these  devices  are  not  accessible  from 
outside  the  hoistway) 

11.9.4  References 

A17.1S-2005  and  later  editions  — 
Requirements  2.7,6.4,  2.7.6.4.1,  2.7.6.4.3,  2.7.6.5.2, 
2.7.6.4.3(e),  and  2.7.3.5. 

ITEM  11.10 
GOVERNOR,  OVERSPEED  SWITCH 

11.10.1  Periodic  Inspections 

11.10.2  Periodic  Test 

11.10.3  Acceptance 

If  governor  can  only  be  inspected  or  serviced  within 
the  hoistway,  verify  the  following: 

(a)  secure  car  against  movement  before  servicing  the 
governor 

(b)  required  signage  is  present 

(c)  switches  are  of  manual  reset  type;  see 
Note  (2.18.6.5)  for  definition  of  what  is  considered 
manual 

id)  governor  is  arranged  to  be  manually  tripped  or 
activated;  see  Note  (2.18.6.5)  for  definition  of  what  is 
considered  manual 

(e)  a  manually  reset  pit  governor  tension  sheave 
switch  is  used  if  the  governor  is  dependent  on  the  ten- 
sion of  the  sheave  weight  to  operate 

11.10.4  References 

A17.1S-2005  and  later  editions  — 
Requirements  2.7.6.3.4,  2.18.4.4,  2.18.6.5,  and  2.18.7.2. 

ITEM  11.11 
EMERGENCY  BRAKE 

11.11.1  Periodic  Inspections 

11.11.2  Periodic  Test 

11.11.3  Acceptance 

Verify  that  if  the  design  of  the  emergency  brake  is 
such  that  field  adjustment  or  servicing  is  required,  and 
the  emergency  brake  acts  on  the  brake  drum  or  braking 
surface  of  the  driving-machine,  that  it  has  a  sign  visible 
from  the  service  area  stating  "emergency  brake." 


142 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


11.11.4  References 

A17.1S-2005         and 
Requirement  2.193.2(h). 


later 


editions         — 


ITEM  11.12 
TRACTION  SHEAVES 

11.12.1  Periodic  Inspections 

Refer  to  Cautionary  Note. 

11.12.2  Periodic  Test 

11.12.3  Acceptance 

Refer  to  Cautionary  Note. 

11.12.4  References 

ITEM  11.13 
SECONDARY  AND  DEFLECTOR  SHEAVES 

11.13.1  Periodic  Inspections 

Refer  to  Cautionary  Note. 

11.13.2  Periodic  Test 

11.13.3  Acceptance 

Refer  to  Cautionary  Note. 

11.13.4  References 

ITEM  11.14 
TERMINAL  STOPPING  DEVICES 

11.14.1  Periodic  Inspections 

11.14.2  Periodic  Test 

11.14.3  Acceptance 

For  normal  terminal  stopping  devices  (NTSDs) 
located  in  machine /control  room  or  machinery /control 
space,  verify  that  the  NTSDs  are  operated  by  movement 
of  the  car. 

If  a  switch  is  provided  to  bypass  top  final-terminal 
or  buffer  switch  when  on  top-of-car  inspection,  verify 
for  proper  operation. 

11.14.4  References 

A17.1S-2005  and  later  editions  — 
Requirements  2.25.2.2.1,  2.26.1.4.2(g),  and  2.26.1.4.4. 

ITEM  11.15 

WORKING  AREAS  INSIDE  THE  HOISTWAY  AND  IN 

THE  PIT 

11.15.1  Periodic  Inspections 

11.15.2  Periodic  Test 

11.15.3  Acceptance 

11.15.3.1  Working  Area  in  the  Car  or  on  Car  Top 

(a)  If  the  drive  machine  or  emergency  brake  or  motion 
or  motor  controller  are  inspected  or  maintained  from 
inside  the  car  or  on  the  car  top 


(1)  if  unexpected  movement  can  occur  during 
inspection  or  maintenance,  verify  means  to  prevent 
movement 

(2)  provide  a  clearance  above  the  crosshead  of  24  in. 
(600  mm)  when  the  car  has  reached  its  maximum 
upward  movement 

(3)  ensure  6  in.  (150  mm)  critical  clearance  is  main- 
tained above  the  car  top  handrails  and  car  top  equipment 
when  the  car  reaches  its  maximum  upward  movement 

(b)  When  means  provided  to  prevent  movement  is 
engaged,  verify 

(1)  car  cannot  be  operated 

(2)  that  the  electrical  device  conforms  to  2.26.2.34 

(3)  that  proper  signage  is  present 

(4)  access  and  egress  from  working  area  is  present 

(5)  that  platform  guard  completely  covers  the  dis- 
tance between  the  landing  and  car  sill 

(6)  clear  headroom  of  not  less  than  53  in. 
(1  350  mm) 

(c)  When  access  panels  are  provided  in  the  car  for 
access  to  elevator  equipment  outside  of  the  car,  verify 

(1)  it  is  self-locking  but  not  self-closing 

(2)  access  panels  are  equipped  with  an  electrical 
switch  to  prevent  movement 

(3)  Group  1  security  is  provided 

11.15.3.2  Working  Area  in  the  Pit 

(a)  If  the  drive  machine  brake  or  emergency  brake  or 
motion  or  motor  controller  are  inspected  or  maintained 
from  within  the  pit,  and  if  unexpected  movement  can 
occur  during  inspection  or  maintenance,  verify  the 
means  to  prevent  movement  by  one  of  the  following: 

(1)  When  means  provided  to  prevent  movement  is 
engaged,  verify 

(a)  car  cannot  be  operated 

(b)  that  proper  signage  is  present 

(c)  access  and  egress  from  working  area  is  present 

(d)  clear  headroom  of  not  less  than  53  in. 
(1  350  mm) 

(2)  For  mechanical  means  to  stop  vertical  move- 
ment, verify 

(a)  that  car  can  only  operate  on  inspection  when 
the  device  is  active 

(b)  that  proper  signage  is  present 

(c)  that  the  device  cannot  be  accidentally 
disengaged 

(b)  When  egress  is  through  the  landing  door,  verify 

(1 )  it  can  be  opened  from  the  hoistway  side 

(2)  required  vertical  opening  is  provided  [48  in. 
(1  220  mm)] 

(c)  When  egress  is  through  a  pit  access  door,  verify 
car  does  not  block  the  opening. 

(d)  When  access  to  machine  or  emergency  brake  or 
elevator  motion  or  motor  controllers  exceeds  the  maxi- 
mum distance  from  the  pit  floor,  verify  means  are  perma- 
nently provided  in  the  pit  to  access  the  equipment. 


143 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


11.15.3.3  Working  Platforms 

(a)  For  working  platforms,  verify  the  following: 

(1)  Ensure  working  platform  is  permanently 
installed. 

(2)  Verify  the  operation  of  the  electrical  devices  on 
any  retractable  platform  that  is  in  the  path  of  a  moving 
car  or  counterweight.  However,  if  this  electrical  device 
permits  inspection  operation,  then  an  additional  electri- 
cal device  must  be  provided  to  stop  the  car  before  it 
strikes  the  moveable  stops,  but  is  rendered  ineffective 
when  the  stops  are  retracted. 

(3)  Verify  standard  railing  when  required. 

(4)  Verify  shear  protection  is  provided  when 
required. 

(5)  When  access  to  a  platform  that  is  in  the  path  of 
moving  car  or  counterweight  is  through  an  access  door 
in  the  hoist  way,  verify  that  the  electromechanical  device 
for  the  access  door  is  operative. 

(b)  For  working  platforms  in  the  line  of  movement 
of  the  car  or  counterweight,  verify  means  to  prevent 
movement  by  one  of  the  following: 

(1 )  If  retractable  stops  are  provided  and  the  car  is 

(a)  below  the  platform,  verify  that  you  have  suffi- 
cient car  top  refuge  space 

(b)  above  the  platform,  verify  that  the  required 
vertical  clearance  is  provided 

(2)  If  unexpected  movement  can  occur  during 
inspection  or  maintenance,  verify  means  to  prevent 
movement. 

11.15.3.4  Retractable  Stops.    When  provided 

(a)  verify  operation  of  electrical  device  is  provided  to 
ensure  it  removes  the  power  from  the  elevator  driving 
machine  motor  and  brake  when  it  is  not  in  the  com- 
pletely retracted  position 

(b)  if  an  electrical  device  is  provided  to  allow  inspec- 
tion operation,  verify  that  the  car  cannot  strike  these 
stops 

(c)  verify  it  is  operable  from  outside  hoistway  or  from 
platform 

(d)  verify  that  the  device  cannot  be  accidentally 
disengaged 

11.15.4  References 

A17.1S-2005  and  later  editions  —  Requirements  2.7.5, 
2.7.5.1,  2.7.5.2,  2.7.5.3,  2.7.5.4,  2.26.2.36,  2.26.4.3,  2.7.4.2, 
and  2.4. 

ITEM  11.16 

LOCATION  OF  MACHINERY  SPACES,  MACHINE 

ROOMS,  CONTROL  SPACES,  CONTROL  ROOMS, 

AND  EQUIPMENT 

11.16.1  Periodic  Inspections 

11.16.2  Periodic  Test 

11.16.3  Acceptance 

11.16.4  References 


ITEM  11.17 

HYDRAULIC  ELEVATORS  -  SHUTOFF/MANUAL 

LOWERING  VALVES 

11.17.1  Periodic  Inspections 

11.17.2  Periodic  Test 

11.17.3  Acceptance 

(a)  If  the  hydraulic  machine  and  the  shutoff  valve  are 
located  in  the  hoistway,  verify  the  following: 

(1)  The  valve  is  accessible  from  outside  of  the 
hoistway. 

(2)  It  is  not  accessible  by  anyone  but  elevator 
personnel. 

(b)  If  the  hydraulic  machine  is  located  in  the  hoistway, 
verify  the  following: 

(1)  The  manual  lowering  valve  is  accessible  from 
outside  of  the  hoistway 

(2)  It  is  not  accessible  by  anyone  but  elevator 
personnel. 

11.17.4  References 

A17.1S-2005  and  later  editions  —  Requirements  3.19.4 
and  3.19.4.4. 

ITEM  11.18 

HYDRAULIC  ELEVATORS  -  PRESSURE  GAUGE 

FITTINGS 

11.18.1  Periodic  Inspections 

11.18.2  Periodic  Test 

11.18.3  Acceptance 

If  the  hydraulic  machine  is  located  in  the  hoistway, 
verify  the  following: 

(a)  The  fittings  are  accessible  from  outside  of  the 
hoistway. 

(b)  It  is  not  accessible  by  anyone  but  elevator 
personnel. 

11.18.4  References 

A17.1S-2005         and         later         editions         — 
Requirement  3.19.4.5. 

ITEM  11.19 

HYDRAULIC  ELEVATORS  -  ATMOSPHERE  STORAGE 

AND  DISCHARGE  TANKS 

11.19.1  Periodic  Inspections 

11.19.2  Periodic  Test 

11.19.3  Acceptance 

If  the  tank  is  located  in  the  hoistway,  verify 

(a)  it  is  vented  so  that  fumes  cannot  accumulate  in 
the  hoistway 

(b)  covers  will  resist  force  of  falling  objects 


144 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


11.19.4  References 

A17.1S-2005         and 
Requirement  3.24.3.1. 


later 


editions 


ITEM  11.20 
HYDRAULIC  ELEVATORS  -  PRESSURE  PIPING 

11.20.1  Periodic  Inspections 

11.20.2  Periodic  Test 

11.20.3  Acceptance 

If  the  hydraulic  machine  is  located  in  the  hoistway 
and  the  piping,  tubing,  or  fittings  are  located  outside  of 
the  hoistway  verify  one  of  the  following: 

(a)  These  objects  shall  be  protected  from  damage. 

(b)  If  not  protected  from  damage,  ensure  means  are 
provided  to  prevent  uncontrolled  movement. 


11.20.4  References 

A17.1S-2005         and 
Requirement  3.19.2.6. 


later         editions        — 


ITEM  11.21 

EXPLANATORY  FIGURES  FOR  DEFINITIONS  OF 
ELEVATOR  MACHINERY  SPACE,  MACHINE  ROOM, 

CONTROL  SPACE,  CONTROL  ROOM,  REMOTE 
MACHINE  ROOM,  OR  REMOTE  CONTROL  ROOM 

See  Figs.  11.21-1  through  11.21-6  and  Table  11.21. 


ITEM  11.22 

INSPECTION  OPERATION  AND  HOISTWAY  ACCESS 

SWITCH  OPERATION  HIERARCHY 


See  Table  11.22. 


Fig.  11.21-2    Configuration  B 


Hoistway 


Machinery 
space 


Machine 


Landing  doors 


Motor 
-"■""  controller 


■  Access 


Control  space 


Fig.  11.21-3     Configuration  C 


Hoistway 


Machinery 
space 


Machine 


-t-1 

Landing  doors 


Control  space, 
remote 


Access 


Fig.  11.21-1     Configuration  A 


Hoistway 

Machinery 
space                    \    J 

Machine 

—  Motor 

C 

Dntrol 
room 

controller 

ill                  1 

Landing  doors 


Access 


145 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


Fig.  11.21-4    Configuration  D 


Hoistway 


Machinery 
space 


Machine 


■r — 

Landing  doors 


Control  room 
remote 


Motor 
controller 


Fig.  11.21-5    Configuration  E 


Machine 


\ 


Machine 
room 


Motor 
controller 


-  Access 


Hoistway 
located 
below 


146 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers.  & 

No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME.    ^3 


ASMEA17.2-2010 


Fig.  11.21-6    Configuration  F 


Overhead  sheave 


/ 


Machine 


/ 


Motor  controller 


Machine  room,  remote 


Hoistway 
located 
below 


Access 


Table  11.21     Definitions  of  Elevator  Machinery  Space,  Machine  Room,  Control  Space,  Control  Room, 

Remote  Machine  Room,  or  Remote  Control  Room 


Location 

Entry  into  the 

Space,  Full  or 

Partial 

Equipment  Used  Directly 

in  Connection  With  the 

Elevator,  Dumbwaiter,  or 

Material  Lift 

Equipment  Contained  Within 

Inside  or 

Outside  the 

Hoistway 

Attached  to  or 
Within  the 
Hoistway 

Mechanical 

Other  Than 

Electric 

Driving 

Machine  or 

Hydraulic 

Machine 

Electrical 
Other  Than 

Motor 
Controller 

Electric  Driving 

Machine  or 

Hydraulic 

Machine 

Motor 
Controller 

Machinery  Space 
[Note  (1)] 

Either 

Either 

Either 

Permitted 

Permitted 

Permitted 

Permitted 

Control  Space 

Not  permitted 

Required 

Machine  Room 
[Note  (1)] 

Outside  the 
hoistway 

Attached  to 
but  not  within 

Full  bodily 
entry  required 

Required 

Permitted 

Control  Room 

Not  permitted 

Required 

Machine  Room, 
Remote 

No 

Required 

Permitted 

Control  Room, 
Remote 

Not  permitted 

Required 

Machinery  Space 
Remote 

Either 

Permitted 

Permitted 

Control  Space 
Remote 

Either 

Not  permitted 

Required 

NOTE: 

(1)  A  machinery  space  outside  the  hoistway  containing  an  electric  driving  machine  and  a  motor  controller  or  a  hydraulic  machine  and  a 
motor  controller  is  a  machine  room. 


147 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


Table  11.22     Inspection  Operation  and  Hoistway  Access  Switch  Operation  Hierarchy 


I  9 
If 

B   © 

CD      K) 
V!     O 

sr  s 

I* 

CD      ft 


3.  g5 

£*  2. 

>  CD* 

B1  o 

o  '-♦» 


8  I. 
if 

>  s 

t/3 


Operation 

Modes 
Activated 


Top-of-Car 
In-Car 


Hoistway 
Access 

Machine 
Room 

Control 
Room 

Machinery 
Space 
Outside 

Hoistway 

Control 

Space 

Outside 

Hoistway 

Landing 


Pit 


Working 
Platform 


Top -of- Car, 
2.26.1.4.2 


Hoistway 

In-Car,  Access, 

2.26.1.A.3       2.12.7.3 


Machine 

Room, 

2.26.1.4.4 


Machinery  Control 
Space  Space 

Control         Outside  Outside 

Room,        Hoistway,  Hoistway, 


Landing, 


Pit, 


Working 
Platform, 


BYPASS  Operation, 
2.26.1.5 


2.26.1.4.4     2.26.1.4.4     2.26.1.4.4     2.26.1.4.4     2.26.1.4.4     2.26.1.4.4     Top-of-Car 


In-Car 


Top- of- car 
Top-of-car 
Top-of-car 
Top-of-car 
Top-of-car 
Top-of-car 


Top-of-car     Top-of-car 
In-car  fn-car 


In-car 


In-car 


In-car 


In-car 


Hoistway 
access 

Hoistway 
access 

Hoistway 
access 

Hoistway 
access 


Top-of-car     Top-of-car     Top-of-car     Top-of-car      Top-of-car  No  No  Top-of-car     Top-of-car 

operation  operation 

In-car  In-car  In-car  In-car  In-car  No  No  Top-of-car         In-car 

operation  operation 

Hoistway       Hoistway       Hoistway       Hoistway       Hoistway  No  No  Top-of-car         In-car 

access  access  access  access  access         operation  operation 

Machine  No  No  No  No  No  No  Top-of-car         In-car 

room  operation      operation      operation      operation      operation  operation 

No  Control  No  No  No  No  No  Top-of-car         In-car 

operation  room  operation      operation      operation      operation  operation 

No  No  Machinery  No  No  No  No  Top-of-car         In-car 

operation      operation         space         operation      operation      operation  operation 


Top-of-car         In-car          Hoistway  No                 No                 No  Control              No                 No                 No           Top-of-car         In-car 

access  operation  operation  operation  space  operation  operation  operation 

Top-of-car         In-car          Hoistway  No                 No                 No  No  Landing             No                 No           Top-of-car         In-car 

access  operation  operation  operation  operation  operation  operation 


No  No  No  No  No  No  No  No 

operation       operation      operation      operation      operation      operation      operation      operation 


Pit  No  No  No 

operation      operation      operation 


No  No  No  No  No  No  No  No  No  Working  No  No 

operation       operation      operation      operation      operation      operation      operation      operation      operation       platform       operation      operation 


Operation 

Modes 
Activated 


Top-of-car 


Hoistway 

access 

Machine 

> 

Room 

5 
m 

Control 

> 

room 
Machinery 

ro 

o 
o 

space 

outside 

hoistway 

Control 

space 

outside 

hoistway 

Landing 

Pit 

Working 
platform 


ASME  A17.2-2010 


MANDATORY  APPENDIX  I 
GUIDE  FOR  INSPECTION  OF  INCLINED  ELEVATORS 


(10) 


1-1  General 

1-1.1  Foreword.  This  Mandatory  Appendix  is  to  be 
used  in  conjunction  with  Parts  1  through  6  of 
A17.2-2000,  Inspection  of  Elevators  and  Moving  Walks, 
and  later  editions.  It  covers  the  variations  in  the  recom- 
mended testing  procedures  for  electric  inclined  elevators 
required  to  conform  with  the  Code  provisions  of 
A17. 1-1980  and  later  editions. 

1-1.2  Preface 

1-1.2.1  Form  and  Arrangement.  The  inclined  eleva- 
tor appendix  to  the  Inspection  Guide  only  addresses 
variations  in  the  guidelines  and  cautionary  notes. 
Inclined  elevators  are  required  by  the  Code  to  conform 
with  the  requirements  for  electric  elevators  except  as 
modified  by  the  specific  rules  pertaining  to  this  particu- 
lar type  of  electric  elevator.  Where  no  item  is  cited, 
inspection  guides  and  procedures  shall  be  as  contained 
in  Parts  1  through  6. 

1-1.2.2  Requirements  for  Existing  Installations.    At 

the  time  of  publication,  the  only  requirements  applicable 
to  inclined  elevators  in  those  jurisdictions  that  have 
adopted  Al 7.3-2008,  Safety  Code  for  Existing  Elevators 


and  Escalators,  are  those  items  that  apply  to  electric 
elevators. 

1-1.2.3  Scope.  This  Mandatory  Appendix  only 
applies  to  inclined  elevators. 

1-1.2.4  Special  Safety  Concerns.  Inspectors  are 
cautioned  to  note  that  inclined  elevators,  due  to 
operating  at  some  degree  from  the  horizontal,  present 
some  hazards  not  expected  by  persons  familiar  with  the 
inspection  of  vertical  electric  elevators.  The  horizontal 
motion  of  the  car  and  counterweight  must  always  be 
considered,  as  well  as  the  fact  that  most  inclined  eleva- 
tors have  their  counterweight  operating  directly  below 
the  car  chassis  (frame). 

1-1.2.5  Orientation.  The  majority  of  inclined  eleva- 
tor installations  will  provide  hoistway  inspections  from 
the  uphill  emergency  exit  and,  on  end-loading  installa- 
tions, from  the  uphill  loading  door.  Use  the  same  cau- 
tions in  making  inspections  that  would  be  appropriate 
for  escalators  with  the  steps  removed.  When  inspecting 
at  the  midpoint  of  the  hoistway,  the  counterweight  will 
be  passing  below  the  car  chassis  often  on  the  same  rail 
assembly. 


Part  1-1 
Elevator  —  Inside  of  Car 


ITEM  1-1.6 
CAR  EMERGENCY  SIGNAL 

1-1.6.1.3  Inclined  Elevators.  Inclined  elevators 
installed  exterior  to  a  building  structure  must  have  spe- 
cial emergency  signaling  devices  with  backup  power 
supply. 

Check  the  operation  of  the  alarm  or  means  of  voice 
communication  and  verify  that  the  receiving  location  is 
always  manned  when  the  elevator  is  in  operation.  Where 
the  emergency  power  supply  is  provided  by  batteries, 
verify  that  they  are  in  good  condition  and  are  properly 
maintained. 


1-1.6.4.3 

earlier  editions 


Inclined  Elevators. 

-  Rule  1714.1. 


A17.1d-2000  and 


A17.1-2000/B44-00 
Requirement  5.1.21.1. 


and      later     editions     — 


ITEM  1-1.10 
POWER  OPENING  OF  DOORS 

1-1.10.2.3  Inclined  Elevators.  Verify  that  the 
doors  cannot  open  unless  the  car  is  located  within  the 
6-in.  (152-mm)  unlocking  zone  in  each  direction  of  travel. 

1-1.10.4.3  Inclined  Elevators.  A17.1a-1997 
through  A17.1d-2000  —  Rule  1709.3. 

A17.1-2000/B44-00      and      later      editions     — 
Requirement  5.1.9. 


149 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


ITEM  1-1.11 
CAR  VISION  PANELS  AND  CAR  DOORS 

1-1.11.1.3  Inclined  Elevators.  Inclined  elevators 
have  been  permitted  to  use  glass  or  plastic  in  cars  or 
doors  since  first  appearing  in  A17.1.  Prior  to 
A17.1-2000/B44-00,  glass  was  required  to  conform  to 
the  requirements  of  Rule  204. lh  and  plastics  to  the 
requirements  of  ANSI  Z97.1,  without  restrictions  as  to 
size.  A17.1-2000/B44-00  and  later  editions  require  glass 
or  plastics  to  conform  to  Z97.1  or  CFR  1201.1  or  1202.2. 

1-1.11.3.3  Inclined  Elevators.  When  a  glass  or 
plastic  window  or  door  is  provided,  check  the  type  of 
glass  or  plastic,  check  the  thickness,  minimum  surface 
area,  and  edging. 

1-1.11.4.3  Inclined  Elevators.  A17.1d-2000  and 
earlier  editions  —  Rule  1708.5. 

A17.1-2000/B44-00      and      later     editions     — 
Requirement  5.1.11.3. 


ITEM  1-1.13 
EMERGENCY  EXIT 

1-1.13.1.3  Inclined  Elevators.  Very  few  inclined 
elevators  have  car  top  emergency  exits.  Some  inclined 
elevators  can  use  the  car  door  for  an  emergency  exit, 
although  most  installations  will  require  the  uphill  end 
emergency  exit. 

For  car  top  located  emergency  exits,  follow 
Item  1.13.1.1.  For  uphill  end  emergency  exits,  check  the 
electric  contact.  The  key  for  unlocking  the  uphill  end 
emergency  exit  must  be  available  to  authorized  person- 
nel but  not  available  to  the  public. 

1-1.13.3.3  Inclined  Elevators.  Verify  that  the 
uphill  end  emergency  exit  is  so  hinged  as  to  swing  in, 
that  it  can  be  opened  from  inside  the  car  only  by  using 
a  special  shape  removable  key,  that  it  can  be  opened  from 
outside  the  car  by  means  of  a  nonremovable  handle,  and 
that  it  is  provided  with  a  properly  functioning  electric 
contact  to  interrupt  power  to  the  driving  machine  and 
the  brake  when  opened.  Check  that  the  electric  contact 
and  nonremovable  handle  are  not  accessible  from  inside 
the  car.  If  an  emergency  exit  unloading  platform  is  pro- 
vided to  assist  exiting  the  car,  verify  that  it  is  attached 
to  the  car,  that  it  is  retractable  and  only  openable  from 
the  exterior  of  the  car,  and  that  it  is  equipped  with  an 
electrical  contact  that  will  not  permit  the  car  to  start  or 
run  unless  the  platform  is  retracted. 

1-1.13.4.3  Inclined  Elevators.  A17.1d-2000  and 
earlier  editions  —  Rules  1708.3.8a,  1708.3b,  and  1708.3c. 


A17.1-2000/B44-00     and     later     editions     — 
Requirements  5.1.11.1.1,  5.1.11.1.2,  and  5.1.11.1.3. 

ITEM  1-1.16 
RATED  LOAD,  PLATFORM  AREA,  AND  DATA  PLATE 

1-1.16.3.3  Inclined  Elevators.  Follow  the  proce- 
dures in  Item  1.16.3.1  except  deduct  from  the  inside 
measurement  of  the  car  50%  of  the  area  of  a  permanently 
installed  nonfolding  bench  or  seat  prior  to  computing 
the  net  platform  area.  The  net  area  computed  now  relates 
to  the  rated  load  formula  for  electric  elevators. 

1-1.16.4.3  Inclined  Elevators.  A17.1d-2000  and 
earlier  editions  —  Rule  17.1.1.1. 

A17.1-2000/B44-00     and     later     editions     — 
Requirement  5.11.13.1. 


ITEM  1-1.18 

RESTRICTED  OPENING  OF  CAR  OR  HOISTWAY 

DOORS 

1-1.18.1.3  Inclined  Elevators.  Prior  to 
A17.1-2000/B44-00,  inclined  elevators  were  required  to 
have  a  car  door  interlock  if  the  car  was  more  than  6  ft 
(2  m)  above  grade  and  the  enclosure  was  more  than  6  in. 
(152  mm)  away  Prior  to  A17.1a-1997/  the  door  was  only 
permitted  to  be  unlocked  in  the  leveling  zone.  In 
A17.1a-1997,  leveling  zone  was  changed  to  unlocking 
zone.  The  interlock  was  required  to  be  openable  from 
outside  of  the  car.  This  special  requirement  was  in  addi- 
tion to  the  requirement  for  electric  elevators.  In 
A17.1-2000/B44-00,  inclined  elevators  now  have  the 
same  requirement  as  electric  elevators,  except  that  the 
unlocking  zone  is  limited  to  6  in.  (152  mm). 

(a)  For  inclined  elevators  installed  under  A17.1-1996 
and  earlier  editions,  check  that  the  car  door  can  be 
opened  only  within  the  leveling  zone,  except  by  the 
means  provided  on  the  car  exterior. 

(b)  For  inclined  elevators  installed  under 
A17.1d-2000  and  earlier  editions,  check  that  the  car  door 
can  be  opened  only  within  the  unlocking  zone,  except 
by  the  means  provided  on  the  car  exterior. 

(c)  For  inclined  elevators  installed  under  A17.1-2000/ 
B44-00  and  later  editions,  check  that  the  car  door  can 
be  opened  only  within  the  6  in.  (152  mm)  unlocking 
zone,  except  by  means  provided  on  the  car  exterior. 

1-1.18.4.3  Inclined  Elevators.  A17.1-1996  and 
earlier  editions  —  Rule  1709.3. 

A17.1a-1997  —  Rule  1709.3. 

A17.1d-2000  and  earlier  editions  —  Rule  1709.3. 

A17.1-2000/B44-00  and  later  editions  ■— 
Requirement  2.12.5. 


150 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Part  1-2 
Inclined  Elevators  —  Machine  Room 


ITEM  1-2.13 
GOVERNOR,  OVERSPEED  SWITCH,  AND  SEAL 

1-2.13.1.3  Inclined  Elevators.  Some  inclined  ele- 
vators will  have  the  governor  located  on  the  car,  either 
driven  by  a  static  wire  rope  drive  or  by  another  positive 
type  drive.  Rope  driven  governors  are  not  required.  If 
the  governor  is  located  on  the  car,  inspection  will  have 
to  be  performed  under  Part  5. 

Examine  per  Item  2.13.1.1.  Where  the  governor  is 
driven  by  other  than  a  wire  rope  drive,  verify  that  the 
driving  means  is  free  of  evidence  of  excessive  wear  and 
lost  motion,  and  whether  all  bearings  and  moving  com- 
ponents are  not  restricted  by  paint  or  other  foreign  sub- 
stances. Move  the  components  to  verify  that  all  parts 
will  move  freely. 

1-2.13.2.3  Inclined  Elevators.  Test  per  Item 
2.13.2.1  when  the  governor  is  located  in  machine  room 
or  machinery  space.  When  the  governor  is  located  on 
the  car  and  is  wire  rope  driven,  perform  similar  testing. 
When  the  governor  is  located  on  the  car,  testing  will 
have  to  be  performed  under  Item  5. 

1-2.13.4.3  Inclined  Elevators.  A17.1d-2000  and 
earlier  editions  —  Rule  1710.4. 

A17.1-2000/B44-00  and  later  editions  — 
Requirement  5.1.15. 


ITEM  1-2.20 

WINDING  DRUM  MACHINE  AND  SLACK  CABLE 

DEVICES 

1-2.20.1.3   Inclined  Elevators.     Inspect  per 
Item  2.20.1.1. 

(a)  Winding  Drum  Machine.  Inclined  elevators  are  per- 
mitted to  use  winding  drum  machine  without  counter- 
weights for  passenger  use  when  the  net  rated  load  does 
not  exceed  1,000  lb  (453  kg),  the  distance  of  travel  does 
not  exceed  125  ft  (38  m),  and  the  rated  speed  does  not 
exceed  100  ft/min  (0.51  m/s). 

(b)  Slack  Cable  Device.  Unlike  vertical  electric  eleva- 
tors, traction  drive  inclined  elevators  operating  at  an 
inclination  of  less  than  35  deg  must  have  slack  cable 
devices.  The  devices  must  be  located  on  both  the  car 
and  counterweight  sides  of  the  driving  machine. 

1-2.20.3.3  Inclined  Elevators.    For  winding  drum 
machines,  verify  that  the  net  rated  load,  speed,  and 


distance  of  travel  do  not  exceed  Code  limitations  and 
that  no  counterweight  is  provided. 

1-2.20.4.3  Inclined  Elevators.    A17.1d-2000  and 
earlier  editions  —  Section  1712  and  Rule  1713.2. 

A17.1-2000/B44-00      and     later     editions     — 
Requirements  5.1.19  and  5.1.20.5. 


ITEM  1-2.28 
TERMINAL  STOPPING  DEVICES 

Inclined  elevators  with  runby  can  be  inspected  as  per 
Item  2.28.  End-loading  inclined  elevators  have  no  runby 
and  must  be  inspected  with  greater  care.  In  addition 
to  normal  and  final  terminal  stopping  devices,  some 
installations  may  be  equipped  with  retractable  sills  that 
include  switchgear.  Note  that  end-loading  inclined  ele- 
vators are  limited  to  a  speed  of  100  ft/min  (0.51  m/s) 
and  will  have  precompressed  oil  buffers  at  each  terminal. 

1-2.28.1.3  Inclined  Elevators.  Inspect  per  Item 
2.28.1.1  including,  if  retractable  sills  are  provided,  exam- 
ination of  the  switchgear. 

1-2.28.2.3  Inclined  Elevators.  Test  per  Item 
2.28.2.1.  If  retractable  sills  are  provided  on  an  end- 
loading  inclined  elevator,  retract  the  sill  and  verify  that 
the  car  cannot  operate  in  the  direction  towards  that 
landing. 

1-2.28.3.3  Inclined  Elevators.  Perform  the  test  as 
indicated  in  Item  2.28.3.1. 

1-2.28.4.3  Inclined  Elevators.  A17.1d-2000  and 
earlier  editions  —  Rules  1716.4  and  1716.5. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  5.1.22.4  and  5.1.22.5. 


ITEM  1-2.29 
CAR  AND  COUNTERWEIGHT  SAFETIES 

There  are  major  differences  between  vertical  electric 
elevators  and  inclined  electric  elevators  with  regard  to 
safeties  and  the  guide  rails  to  which  they  apply.  The 
stopping  distances  are  governed  in  A17.1b-1995  and 
earlier  editions  by  a  formula  and  table  based  on  V2  £■ 
Beginning  with  A 17. 1-1996,  the  formula  and  table  are 
based  on  \  g  and  this  edition  also  includes  horizontal 


151 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


retardations  for  emergency  electrical  stopping  that 
should  be  tested  with  the  safeties.  Guide  rails  used  with 
Types  A  and  C  safeties  do  not  have  to  be  machined; 
however,  inclined  elevators  installed  under  A17. 1-1996 
and  later  editions  are  not  permitted  to  use  a  Type  A  or 
C  safeties  that  develop  horizontal  retardation  in  excess 
of  the  Code-permitted  allowance.  Inclined  elevators 
installed  under  A17.1-2000/B44-00  and  later  editions 
are  permitted  to  have  a  single  safety  guide  rail  located 
between  the  main  guide  rails.  If  the  governor  is  provided 
on  the  car,  tests  will  have  to  be  performed  under  Item  5. 

NOTE:  Inclined  elevators  must  conform  to  the  requirements  for 
occupied  space.  A17.1-2000/B44-00  clarifies  that  occupied  space 
on  inclined  elevators  is  in  line  with  the  direction  of  travel  rather 
than  underneath  the  counterweight  or  car. 

1-2.29.1.3  Inclined  Elevators 

(a)  See  Item  5.8.1.1  of  the  Guide. 

(b)  Examine  the  means  provided  to  prevent 
derailment  of  the  car  or  counterweight. 

1-2.29.2.3  Inclined  Elevators 

(a)  Perform  the  examinations  indicated  in 
Item  2.29.2.1(a)  from  the  pit  or  from  the  workspace,  if 
provided. 


(c)  Perform  the  test  indicated  in  Item  2.29.2.1(c)  with 
the  car  positioned  either  in  the  lower  portion  of  the 
hoistway  or  just  above  the  work  space,  if  provided. 

(e),(f)  Perform  the  tests  indicated  in  Items  2.29.2.1(e) 
and  2.29.2.1(f)  using  Tables  1710.2(a)  and  1710.2(b)  for 
installations  under  A17.1-1996  and  earlier  editions.  Use 
the  revised  Tables  1710.2(a)  and  1710.2(b)  for  installa- 
tions under  A17.1a-1997  and  later  editions. 

1-2.29.3.3  Inclined  Elevators.  In  addition  to  the 
inability  of  some  AC  driving  machine  motors  to  permit 
sufficient  overspeed,  some  inclined  elevators  provided 
with  DC  driving  machine  motors  and  with  shallow 
angles  of  inclination  will  not  cause  sufficient  overspeed. 
Test  as  per  Items  2.29.3.1(a)  and  2.29.3.1(b). 


A17.1b-1995  and 
and  1707.3  and 


1-2.29.4.3  Inclined  Elevators. 

earlier  editions  —  Rules  1706.3 
Section  1710  with  Table  1710.4. 

A17.1d-2000  and  earlier  editions  —  Rule  1706.3,  Rule 
1707.3,  Section  1710  with  Tables  1710.2(a)  and  1710.2(b), 
and  Rule  1713.3. 

A17.1-2000/B44-00  and  later  editions  — 
Requirement  5.1.14  with  Tables  5.1.14.2,  5.1.15,  5.1.17.3, 
5.1.18.3,  5.1.18.4,  and  5.1.20.6. 


Part  1-3 
Elevator  —  Top  Car/Uphill  Emergency  Exit/End-Loading  Top 

Car  Door 


Due  to  the  horizontal  component  of  their  travel, 
inclined  elevators  rarely  have  use  for  car  top  access  and 
such  access  normally  will  not  be  found  under  49  deg  of 
inclination  where  it  starts  to  be  possible  for  inspection, 
etc.,  of  some  components.  The  majority  of  installations 
will  have  the  uphill  emergency  exit  or  uphill  loading 
door  to  be  used  to  make  hoistway  inspections.  Car  tops 
do  not  have  to  meet  structural  requirements  unless 
access  is  provided. 

Starting  with  A17.1-2000/B44-00,  inclined  elevators 
were  specifically  permitted  to  omit  car  top  stop  switches 
when  access  was  not  provided  to  the  car  top. 

Safety  precautions  are  as  follows: 

(a)  Follow  the  safety  precautions  for  top  of  car  in 
Part  3. 

(b)  Uphill  emergency  exit 

(1)  On  cars  equipped  with  an  unloading  platform, 
move  the  platform  from  its  retracted  position. 

(2)  Without  an  unloading  platform,  remain  inside 
the  door  until  the  car  stops  to  perform  examinations. 

(3)  As  inclined  elevator  counterweights  are  most 
commonly  located  within  the  same  guide  rail  assembly 


and  below  the  car,  be  extremely  cautious  near  the  mid- 
point of  travel. 

(c)  End-loading  top  car  door:  End-loading  inclined 
elevators  have  no  runby  and  the  car  door  will  be 
extremely  close  to  the  landing  door  at  the  uphill  termi- 
nal. Keep  all  parts  of  the  body  and  any  tools  inside  the 
car  when  in  motion. 


ITEM  1-3.1 
TOP-OF-CAR  STOP  SWITCH 

1-3.1.1.3  Inclined  Elevators.  Check  the  top-of- 
car  stop  switch  if  provided,  or  the  uphill  emergency  exit 
or  end-loading  top  car  door  stop  switch  in  accordance 
with  Item  3.1.1. 

1-3.1.4.3  Inclined  Elevators.  A17.1d-2000  and 
earlier  editions  —  Rules  1708.3,  1708.4,  and  1713.1. 

A17.1-2000/B44-00     and     later     editions     — 
Requirements  5.1.11,  5.1.20.1,  5.1.20.2,  and  5.1.20.3. 


152 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


ITEM  1-3.2 

CAR  TOP/INSPECTION  LOCATION  LIGHT  AND 

OUTLET 

The  light  and  outlet  on  inclined  elevators  should  be 
located  at  the  inspection  location.  Follow  the  checks  as 
described  in  Items  3.2.1  and  3.2.3. 

1-3.2.4.3  Inclined  Elevators.    A17.1d-2000  and 
earlier  editions  —  Rules  204.7  and  1713.1. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.14.7  and  5.1.2. 


ITEM  1-3.3 
TOP-OF-CAR  EXTERIOR  OPERATING  DEVICE 

1-3.3.1.3  Inclined  Elevators.  The  operating 
device  is  located  most  commonly  at  the  uphill  end  emer- 
gency exit  of  the  uphill  loading  door  on  end-loading 
inclined  elevators;  on  very  steep  inclined  elevators  with 
access  to  the  car  top,  an  operating  device  must  be  located 
on  the  car  top  and  may  also  be  located  at  an  uphill 
emergency  exit,  if  provided. 

Check  in  accordance  with  the  directions  in  Item  3.3.1. 

1-3.3.4.3  Inclined  Elevators.  A17.1d-2000  and 
earlier  editions  —  Rules  204.1g,  210.1(1,  and  1713.1. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.14.1.7,  2.26.1.4,  and  5.1.20. 

ITEM  1-3.4 

TOP-OF-CAR/UPHILL-OF-CAR  CLEARANCE  AND 

REFUGE  SPACE 

Before  making  any  inspections  or  tests,  determine  the 
available  car  top  or  uphill  end  clearance  following  the 
procedure  provided  in  Item  3.2.1.1.  Where  the  measure- 
ment is  to  be  made  in  the  direction  of  travel,  measure 
the  distance  from  the  car  chassis  or  uphill  unloading 
platform  or  the  furthest  projecting  item  in  the  direction 
of  travel.  There  is  no  clearance  or  refuge  space  on 
end-loading  inclined  elevators. 

1-3.4.1.3  Inclined  Elevators.  Measure  as 
described  in  Item  3.4.1.1  as  modified  above. 

1-3.4.3.3  Inclined  Elevators.  Measure  as 
described  in  Item  3.4.3.1  as  modified  above. 

1-3.4.4.3  Inclined  Elevators.  A17.1d-2000  and 
earlier  editions  —  Rule  1702.2. 

A17.1-2000/B44-00  and  later  editions  — 
Requirement  5.1.5.2. 

ITEM  1-3.5 
NORMAL  TERMINAL  STOPPING  DEVICES 

In  addition  to  the  other  cautions  in  this  Guide,  use 
special  care  when  examining  or  testing  end-loading 


inclined  elevators  as  they  do  not  have  runby  or  refuge 
space. 

ITEM  1-3.6 

FINAL  AND  EMERGENCY  TERMINAL  STOPPING 

DEVICES 

In  addition  to  the  other  cautions  in  this  Guide,  use 
special  care  when  examining  or  testing  end-loading 
inclined  elevators  as  they  do  not  have  runby  or  refuge 
space. 

1-3.6.2.3  Inclined  Elevators.  Test  inclined  eleva- 
tors as  suggested  by  this  Guide,  using  extra  caution 
on  end-loading  inclined  elevators.  If  a  retractable  sill  is 
provided,  its  contact  may  have  to  be  jumped  out  to 
properly  test  the  final  terminal  stopping  device. 

1-3.6.4.3  Inclined  Elevators.  A17.1d-2000  and 
earlier  editions  —  Rules  209.3,  1716.4,  and  1716.5. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.25.3,  5.1.22.4,  and  5.1.22.5. 

ITEM  1-3.8 
TOP/UPHILL  END  EMERGENCY  EXIT 

Prior  to  Al  7. 1-2000 /B44-00,  top  emergency  exits  were 
not  required  on  inclined  elevators  unless  there  was 
equipment  installed  that  required  servicing  from  the  top 
of  the  car.  Inclined  elevators  installed  under 
A17.1-2000/B44-00  and  later  editions  require  top  emer- 
gency exits  where  the  angle  of  inclination  exceeds  49 
deg  and  where  an  uphill  emergency  exit  is  not  provided. 

1-3.8.3.3  Inclined  Elevators.  Inspect  top  emer- 
gency exits  in  accordance  with  Item  3.8.3.1.  Inspect 
uphill  emergency  exits  to  verify  that  they  open  only  into 
the  car  and  that  the  size  of  the  opening  is  as  required 
by  the  Code.  Check  that  the  locking  means  can  be 
opened  only  from  the  car  exterior  by  a  nonremovable 
handle  and  may  be  opened  from  within  the  car  by  a 
special  key.  Check  that  the  electric  contact  meets  code 
requirements. 

1-3.8.4.3  Inclined  Elevators.  A17.1d-2000  and 
earlier  editions  —  Rule  1708.3. 

A17.1-2000/B44-00  and  later  editions  — 
Requirement  5.1.11. 

ITEM  1-3.10 
HOISTWAY  CONSTRUCTION 

Inclined  elevators  installed  in  open  areas  are  not  nor- 
mally required  to  meet  fire-resistive  construction.  There 
are  special  requirements  for  these  open  installations. 

1-3.10.1.3  Inclined  Elevators.  Inspect 
fire-resistive  hoistways  as  per  Item  3.10.1.1.  Inspect 
hoistway  enclosures  on  nonfire-resistive  construction  to 


153 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


determine  if  the  enclosure  is  maintained  in  a  condition 
that  will  provide  the  intended  security. 

1-3.10.3.3  Inclined  Elevators.  For  fire-resistive 
enclosures,  inspect  per  Item  3.10.3.1.  For 
nonfire-resistive  enclosures,  measure  the  clearances  and 
heights  and  examine  the  materials  used  for  compliance 
with  the  Code.  If  structures  are  used  to  support  the 
hoist  way,  note  that  they  are  designed  to  prevent  climb- 
ing. If  acrylics,  glass,  or  wired  glass  are  used  in  the 
construction  of  the  enclosure,  verify  their  compliance 
with  the  Code. 

1-3.10.4.3  Inclined  Elevators.  A17.1d-2000  and 
earlier  editions  —  Section  1700. 

A17.1-2000/B44-00  and  later  editions  — 
Requirement  5.1.2. 

ITEM  1-3.16 

TRAVELING  CABLES,  JUNCTION  BOXES,  AND 

PROTECTIVE  MEANS 

Traveling  cables  on  inclined  elevators  must  have  addi- 
tional protection  against  abrasion  and  fouling  as  they 
pass  by  the  guide  rail  structure.  The  protective  means 
provided  may  be  in  conjunction  with  that  provided  to 
protect  the  hoist  ropes.  Corrosion  protection  is  required 
for  components  used  on  weather-exposed  installations. 

1-3.16.1.3  Inclined  Elevators.  In  addition  to  the 
examinations  called  for  in  Item  3.16.1,  examine  the 
means  provided  to  protect  the  cables  from  abrasion  and 
fouling.  Verify  that  it  is  not  excessively  worn  and  that 
moving  parts  operate  freely.  Verify  that  corrosion  is  not 
affecting  components  used  in  weather-exposed 
installations. 

1-3.16.3.3  Inclined  Elevators.  In  addition  to  the 
examinations  called  for  in  Item  3.16.3,  examine  the 
means  provided  to  protect  the  cables  from  abrasion  and 
fouling.  Note  that  the  means  provided  prevents  lateral 
motion  of  the  cables  into  an  area  where  fouling  is  possi- 
ble. Verify  that  all  moving  components  operate  freely. 
Verify  components  used  in  weather-exposed  installa- 
tions are  protected  against  corrosion. 

1-3.16.4.3  Inclined  Elevators.  A17.1d-2000  and 
earlier  editions  —  Rules  1717.1  and  1717.2. 

A17.1-2000/B44-00  and  later  editions  — 
Requirement  5.7. 

ITEM  1-3.18 
CAR  FRAME  (CHASSIS) 

Inclined  elevator  car  frames  (chassis)  are  weight  bear- 
ing and  are  usually  located  below  the  car  enclosure. 
There  are  no  styles  but  the  car  must  be  considerably 
more  structural  due  to  the  horizontal  forces  imposed  in 
a  safety  stop  or  buffer  engagement.  Cast  iron  is  not 


permitted  to  be  used  for  guiding  support  or  guide  shoes 
on  inclined  elevators. 

1-3.18.1.3  Inclined  Elevators.  In  addition  to  the 
procedures  found  in  Item  3.18.1.1,  also  take  note  of  the 
operating/ supporting  roller  guides  for  bad  bearings, 
tread  delamination,  and  cracks.  Most  installations  will 
also  have  lateral  guiding  rollers  to  be  checked. 

1-3.18.4.3  Inclined  Elevators.  A17.1d-2000  and 
earlier  editions  —  Rule  1708.1. 

A17.1-2000/B44-00  and  later  editions  — 
Requirement  5.1.12.1. 

ITEM  1-3.19 
GUIDE  RAILS  FASTENING  AND  EQUIPMENT 

Inclined  elevators  are  not  required  to  have  finished 
surfaces  when  used  with  a  Type  A  or  C  safety.  Slower 
speed  installations  often  have  H  beams  for  guide  rails 
with  the  car  chassis  operating  on  the  upper  flange  and 
the  counterweight  operating  on  the  lower  flange.  Guide 
rails  together  with  guiding  members  must  retain  the  car 
and  counterweight  from  derailment.  A  single  guide  rail 
located  between  the  main  guide  rails  permitted  to  be 
used  for  application  of  the  safety  and  side  guiding 
should  be  included  in  the  inspection  procedure. 

1-3.19.1.3  Inclined  Elevators.  Examine  in  accor- 
dance with  the  procedures  found  in  Item  3.19.1.1. 

1-3.19.3.3  Inclined  Elevators.  Verify  that  the 
design  includes  protection  against  derailment  upthrust 
or  side  thrust  forces. 

1-3.19.4.3  Inclined  Elevators.  A17.1d-2000  and 
earlier  editions  —  Section  1706. 

A17.1-2000/B44-00  and  later  editions  — 
Requirement  5.1.18. 

ITEM  1-3.20 
GOVERNOR  ROPE 

1-3.20.1.3  Inclined  Elevators.  Inclined  elevators 
are  permitted  to  use  other  than  rope  to  drive  governors. 
Such  drives  will  be  found  located  on  the  car  chassis.  In 
addition,  some  governors  located  on  the  car  will  be 
driven  by  a  static  governor  rope. 
Inspect  in  accordance  with  Item  3.20.1.1. 

1-3.20.4.3  Inclined  Elevators.  A17.1d-2000  and 
earlier  editions  —  Rule  1710.4. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  5.1.15  and  5.1.16. 

ITEM  1-3.23 
SUSPENSION  ROPE 

1-3.23.1.3  Inclined  Elevators.  In  addition  to  the 
requirements  for  electric  elevators,  suspension  ropes  on 


154 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


inclined  elevators  must  be  protected  against  abrasion  as 
the  ropes  move  over  the  supporting  structure.  The 
means  used  may  also  protect  the  governor  rope,  if  used, 
and  the  traveling  cable. 

Inspect  in  accordance  with  Item  3.23.1.1,  including  the 
protection  against  abrasion,  unless  previously  inspected 
under  Item  3.16. 

1-3.23.4.3  Inclined  Elevators.     A17.1d-2000  and 
earlier  editions  —  Section  1715. 

A17.1-2000/B44-00  and  later  editions  — 
Requirement  5.1.16. 


ITEM  1-3.27 

CROSSHEAD/UPHILL  CHASSIS  MEMBER  DATA 

PLATE 

1-3.27.1.3  Inclined  Elevators.  Inclined  elevator 
data  plates  will  be  found  on  the  uphill  chassis  member. 
Inspect  in  accordance  with  Item  3.27.3.1. 

1-3.27.4.3  Inclined  Elevators.  A17.1d-2000  and 
earlier  editions  —  Rule  1711.2. 

A17.1-2000/B44-00     and     later     editions     — 
Requirement  5.1.13.2. 


Part  1-4 
Elevator  —  Outside  Hoistway 


ITEM  1-4.1 
CAR  PLATFORM  GUARD 

Prior  to  A17.1-2000/B44-00,  inclined  elevator  plat- 
form guards  were  required  to  cover  all  of  the  vertically 
exposed  area  during  leveling  and  2  in.  (51  mm)  over 
the  leveling  zone  in  each  direction.  Inclined  elevators 
installed  under  A17.1-2000/B44-00  and  later  editions 
must  have  aprons  that  extend  at  least  the  width  of  the 
widest  hoistway  opening  plus  the  leveling  zone  in  each 
direction,  and  a  vertical  face  in  the  direction  of  travel 
as  described  +3  in.  (75  mm).  In  addition,  they  must  be 
angled  in  the  direction  of  travel  and  extend  a  minimum 
of  1  in.  (25  mm)  below  the  landing  sill  at  any  position 
to  the  extent  of  the  leveling  zone. 

1-4.1.1.3  Inclined  Elevators.  Position  the  car  at 
each  extreme  of  the  leveling  zone  with  the  hoistway 
door  open  and  inspect  the  guard  to  determine  that  it  is 
in  place  and  securely  fastened.  In  some  cases,  the  guard 
can  be  inspected  from  the  pit  or  from  the  workspace,  if 
provided,  but  the  dimensions  of  the  leveling  zone  will 
have  to  be  a  known  factor. 

1-4.1.3.3  Inclined  Elevators.  Verify  that  a  smooth 
guard  extends  beyond  the  leveling  zone  in  each  direction 
of  travel  +3  in.  (75  mm)  and  that  it  extends  a  minimum 
of  1  in.  (25  mm)  vertically  below  the  landing  sill  in  all 
positions  throughout  the  leveling  zone,  that  it  is  bent 
back  in  the  direction  of  travel,  and  that  it  is  secured 
against  the  required  forces. 

1-4.1.4.3  Inclined  Elevators.  A17.1d-2000  and 
earlier  editions  —  Rules  1708.1  and  1708.2. 

A17.1-2000/B44-00  and  later  editions  — 
Requirement  5.1.12.2. 


ITEM  1-4.5 
ACCESS  TO  HOISTWAY 

Inclined  elevators  installed  under  A17.1d-2000  and 
earlier  editions  that  are  located  exterior  to  a  building 
and  are  not  fully  enclosed  were  not  required  to  conform 
to  the  access  requirements  for  vertical  electric  elevators. 
Inclined  elevators  installed  under  Al 7. 1-2000 /B44-00 
and  later  editions  that  are  of  nonfire-resistive  construc- 
tion, due  to  their  location  exterior  to  building  structure, 
are  permitted  to  have  other  means  of  access  than  those 
required  for  electric  vertical  elevators.  The  means  used 
will  vary  considerably  at  each  location,  but  must  provide 
safety  equivalent  to  that  provided  by  vertical  elevators, 
and  if  it  includes  entrance  through  the  hoistway  guard- 
ing, it  must  be  locked  and  contacted.  Operating  device 
requirements  are  special  to  inclined  elevators  including 
speed  limitation  to  125  ft/min  (38  m/s). 

1-4.5.1.3  Inclined  Elevators.  Inspect  enclosed 
hoistway  installations  in  accordance  with  Item  4.5.1. 
Inspect  other  type  access  for  the  condition  and  security 
of  the  means  of  access. 

1-4.5.4.3  Inclined  Elevators.  A17.1d-2000  and 
earlier  editions  —  Section  1704  and  Rule  1713.1. 

A17.1-2000/B44-00  and  later  editions  — 
Requirement  5.1.10. 


ITEM  1-4.8 
HOISTWAY  ENCLOSURE 

Inclined  elevators  are  permitted  to  have  enclosures  of 
acrylics,  laminated  glass,  or  wire  glass,  subject  to  the 
provisions  of  the  building  code.  Installations  located  in 
nonfire-resistive  hoistways  have  specific  requirements 
to  protect  against  unauthorized  access. 


155 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


1-4.8.1.3  Inclined  Elevators 

(a)  Hoistway  Enclosures.  Where  nonf ire-resistive  con- 
struction is  permitted  and  used,  check  that  the  materials 
used  are  in  satisfactory  condition  and  maintained  ade- 
quately braced  to  maintain  running  clearances.  Verify 
that  the  means  used  to  prevent  climbing  any  structures 
are  in  satisfactory  condition. 

(b)  Transparent  Enclosures.  Verify  that  the  glazing 
means  are  in  good  condition  to  prevent  penetration  of 
the  enclosure. 


1-4.8.3.3  Inclined  Elevators.  Inspect  fire-resistive 
hoistways  in  accordance  with  Item  4.8.3.1.  Inspect 
nonfire-resistive  hoistways  to  verify  that  the  materials 
used  are  within  the  requirements  and  will  sustain  the 
horizontal  forces,  and  that  supporting  structures  are  pro- 
tected against  climbing  to  prevent  unauthorized  access. 

1-4.8.4.3  Inclined  Elevators.  A17.1d-2000  and 
earlier  editions  —  Rule  1700.1. 

A17.1-2000/B44-00     and     later     editions     — 
Requirements  5.1.1.1  and  5.1.2. 


Part  1-5 
Elevator  Pit 


Some  inclined  elevator  installations  are  configured  so 
that  the  area  surrounding  the  terminus  of  the  guides 
cannot  be  used  as  a  pit  in  which  work  can  be  performed. 
These  installations  must  provide  a  workspace  of  mini- 
mum size  and  provided  with  a  stop  switch,  lighting, 
and  convenience  outlet. 

Safety  precautions  are  as  follows: 

(a)  In  addition  to  all  of  the  safety  precautions  found 
in  the  Guide,  inspectors  must  be  very  aware  of  the  multi- 
directional movement  of  the  car  and  counterweight. 
Note  also  that  as  counterweights  are  normally  located 
directly  under  the  car  chassis,  sometimes  within  the 
same  rail  structure,  counterweight  pit  guards  are  not 
required.  In  some  installations,  the  pit  will  not  provide 
adequate  inspection  space  and  a  workspace  must  be 
provided. 

(b)  Before  entering  the  pit  or  workspace,  if  provided, 
observe  the  operation  and  locations  of  the  car  and  coun- 
terweight and  the  available  refuge  spaces. 

ITEM  1-5.1 

PIT  ACCESS,  LIGHTING,  STOP  SWITCH,  AND 

CONDITION 

1-5.1.1.3  Inclined  Elevators 

(a)  Inspect  either  the  pit  or  the  workspace,  if  provided, 
in  accordance  with  Item  5.1.1.1. 

(b)  For  inclined  elevators  installed  outside  a  building 
structure  under  Al 7.1-2000/ B44-00  and  later  editions, 
verify  that  the  means  provided  to  remove  weather- 
caused  water  collection  has  been  maintained. 

1-5.1.3.3  Inclined  Elevators.  Examine  the  pit  or 
workspace  as  per  Item  5.1.3.1.  On  exterior  installations, 
verify  that  electrical  devices  are  weatherproof  and  that 
provision  has  been  made  to  remove  rainwater. 

1-5.1.4.3  Inclined  Elevators.  A17.1d-2000  and 
earlier  editions  —  Section  1701  and  Rule  1702.1. 


A17.1-2000/B44-00     and     later 
Requirements  5.1.3,  5.1.4,  and  5.1.10. 


editions     — 


ITEM  1-5.2 

BOTTOM  CLEARANCE,  RUNBY,  AND  MINIMUM 

REFUGE  SPACE 

1-5.2.1.3  Inclined  Elevators.  Inclined  elevators 
must  meet  the  requirements  for  electric  elevators  or 
provide  refuge  space  to  either  side  of  the  pit  or  towards 
the  downhill  end  of  the  pit. 

Inspect  in  accordance  with  Item  5.2,1,1,  making  mea- 
surements in  the  direction  of  travel. 

1-5.2.3.3  Inclined  Elevators.  Inspect  in  accor- 
dance with  Item  5.2.3.1  in  direction  of  travel.  Verify  the 
refuge  space  for  Code  compliance. 

1-5.2.4.3  Inclined  Elevators.  A17.1d-2000  and 
earlier  editions  —  Rules  1701.2  and  1702.1. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  5.1.4  and  5.1.5.1. 

ITEM  1-5.3 

FINAL  AND  EMERGENCY  TERMINAL  STOPPING 

DEVICES 

End-loading  inclined  elevators  have  special  require- 
ments due  to  the  absence  of  runby.  The  final  terminal 
stopping  device  must  operate  within  the  extremely  short 
distance  between  the  normal  stopping  device  and  the 
landing.  Some  installations  may  be  provided  with 
retractable  sills  to  permit  a  form  of  runby.  Spring  buffers 
are  not  permitted  on  end-loading  inclined  elevators  and 
oil  buffers  with  switch  gear  are  required  at  both  terminals 
and  will  be  compressed  under  normal  stopping 
conditions. 

Perform  inspections  and  tests  in  accordance  with 
Item  5.3.1.1. 

1-5.3.4.3  Inclined  Elevators.  A17.1d-2000  and 
earlier  editions  —  Rules  209.3,  1716.4,  and  1716.5. 


156 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


A17.1-2000/B44-00  and  later  editions  — 
Requirements  2.25.3,  5.1.22.4,  and  5.1.22.5. 

ITEM  1-5.4 

NORMAL  TERMINAL  STOPPING  DEVICES  AND 

RETRACTABLE  SILLS 

End-loading  inclined  elevators  are  permitted  to  use  a 
retractable  sill  to  provide  an  extremely  short  form  of 
runby. 

1-5.4.1.3  Inclined  Elevators.  Perform  inspections 
in  accordance  with  Item  5.4.1.1.  If  retractable  sills  are 
provided  on  end-loading  inclined  elevators,  verify  that 
the  car  cannot  operate  in  the  direction  of  the  particular 
sill  unless  the  sill  has  returned  to  its  normal  location. 

1-5.4.4.3  Inclined  Elevators.  A17.1d-2000  and 
earlier  editions  —  Rule  1716.5. 

A17.1-2000/B44-00  and  later  editions  — 
Requirement  5.1.22.5. 

ITEM  1-5.5 
TRAVELING  CABLES 

1-5.5.1.3  Inclined  Elevators.  Inclined  elevators 
require  means  to  guide  and  protect  traveling  cables  from 
pinching  and  abrasion  as  they  move  over  the  guide  rail 
supporting  structure.  The  means  provided  may  also  be 
used  for  suspension  and  compensating  rope  guidance 
and  abrasion  protection. 

In  addition  to  the  procedures  in  Item  5.5.1.1,  examine 
the  means  provided  to  guide  and  protect  the  traveling 
cables  from  abrasion  and  fouling. 

1-5.5.4.3  Inclined  Elevators.  A17.1d-2000  and 
earlier  editions  —  Rules  1715.2  and  1717.1. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  5.1.7.1  and  5.1.16.1. 

ITEM  1-5.8 
CAR  SAFETIES  AND  GUIDING  MEMBERS 

There  are  several  special  conditions  to  be  observed 
on  inclined  elevators.  The  rails  used  for  Types  A  and  C 


safeties  are  not  required  to  have  machined  surfaces  and 
structural  steel  shapes  might  be  used.  The  guiding  sup- 
ports and  guide  shoes  are  not  permitted  to  be  of  cast 
iron.  When  making  safety  tests,  be  aware  that  some 
inclined  elevators  have  the  governor  located  on  the  car 
(see  Items  2.13,  2.29,  and  3.20). 


1-5.8.1.3  Inclined  Elevators. 

dance  with  Item  5.8.1.1. 


Examine  in  accor- 


1-5.8.2.3  Inclined  Elevators.    See  Item  2.29. 

1-5.8.3.3  Inclined  Elevators.  Examine  in  accor- 
dance with  Item  5.8.3.1. 

1-5.8.4.3  Inclined  Elevators.  A17.1d-2000  and 
earlier  editions  —  Rules  1706.3  and  1708.1,  and 
Section  1710. 

A17.1-2000/B44-00     and     later     editions     — 
Requirements  5.1.12.1,  5.1.14,  5.1.15,  and  5.1.18. 


ITEM  1-5.9 

BUFFER  AND  EMERGENCY  TERMINAL  SPEED 

LIMITING  DEVICES 

1-5.9.1.3  Inclined  Elevators.  Inclined  elevators 
installed  at  exterior  locations  require  corrosion  protec- 
tion. End-loading  inclined  elevators  must  use  only  oil 
buffers  located  at  each  terminal. 

Inspect  and  test  in  accordance  with  Item  5.9.1.1.  Note 
the  buffer  stroke  tables  for  inclined  elevators  are  different 
from  those  for  electric  elevators. 

1-5.9.2.3  Inclined  Elevators.  Note  that  the  buffer 
stroke  tables  for  inclined  elevators  are  different  from 
those  for  electric  elevators. 

1-5.9.4.3  Inclined  Elevators.  A17.1d-2000  and 
earlier  editions  —  Section  1707  and  Rule  1716.3. 

A17.1-2000/B44-00  and  later  editions  — 
Requirements  5.1.17  and  5.1.22.3. 


Part  1-6 
Elevator  —  Firefighters'  Service 


Until  A17.1a-1997,  there  was  no  specific  exception 
for  firefighters'  service  for  inclined  elevators  installed 
exterior  to  a  building  structure. 

Where  inclined  elevators  are  installed  within  a  build- 
ing structure,  inspect  in  accordance  with  Part  6. 

If  the  jurisdictional  authority  requires  inclined  eleva- 


provided  with  firefighters'  service,  inspect  in  accordance 
with  Part  6. 

1-6.4.4.3  Inclined  Elevators.   A17.1-1996  and  ear- 
lier editions  —  no  rule. 
A17.1a-1997  through  A17.1d-2000  —  Rule  1714.2. 
A17.1-2000/B44-00      and     later     editions     — 


tors  located  exterior  to  a  building  structure  to  be        Requirement  2.27.3. 

157 

Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Fig.  1-1.16.3    Net  Platform  Area  Measurements 


A 

8ft 

(2.5  m) 

1ft 

1ft 

<  (0.3  m)  > 

(0.3  m) 

S 
e 
a 

E 

S 
e 
a 

t 

t 

^ 

Example:  8  ft  x  4  ft  =  32  ft2,  gross  platform  area  (gpa}.  Seats:  1  ft  x  4  ft  x  2  = 
8  ft2  x  50%  =  4  ft2.  32  ft2  gpa  -  4  ft2  =  28  ft2  net  platform  area 

(1.2  m  X  2.5  m  =  3  m2,  gross  platform  area  (gpa).  Seats:  0.3  m  x  1.2  m  =  0.36  m2 
x  2  =  0.72  m2,  50%  of  seat  area  =  0.36  m2;  deducted  from  3  m2  (gpa)  =  2.64  m2  net 
platform  area.) 


Fig.  I-2.13.2-1     Static  Governor  Rope  Drive 


One  end  of  the  governor 
rope  is  weighted  or  under 
spring  tension 


The  other  end  is 
tied  off >^ 


Fig.  I-2.13.2-2    Wheel  Driven  Governor 


158 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


Fig.  1-2.28.2     Retractable  Sill 


Spring  loaded  or  power  driven  retractable  sill 


u 


^5 


u 


Switch  made  permitting  car  movement 
towards  landing 


Fig.  1-3.4     Uphill  Clearance 


This  sketch  illustrates  the  need 
for  special  caution  while  examing 
the  equipment  located  below  the 
car  platform 


159 


C 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Fig.  1-4.1    Car  Platform  Guard 


Car 


Leveling  zone 
+  3  in.  (75  mm 


Bent  portion 


Fig.  1-5.1     Pits  and  Work  Spaces 


Elevation  View 


No  pit  space 


18  in.  (450  mm)  min.  J 

r 

* 

u.                    .         /^ 

Plan  View 

Workspace 

/ 

Guide  rails 

18  in.  (450  mm)  min.  : 

7^ 

' 

* 

/ 

Running  line  of  car  or  counterweight,  whichever  is  greater 


160 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers.  ^| 

No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME.     ^ 


ASMEA17.2-2010 


Fig.  1-5.2     Refuge  Space  When  Conformance  to  Requirement  2.4.1  is  Not  Provided 

24  in.  x  24  in.  x  84  in.  high 
(610  mm  x  610  mm  x  2134  mm) 


Plan  View 


48  in.  (1220  mm)  high 
Running  line  of  car  or  counterweight,  whichever  is  greater 


48  in.  (1220  mm)  high 
24  in.  (610  mm) 


161 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers.  ^L  . 

No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME.      ^ 


ASME  A17.2-2010 


Additional  Checklist  for  Inclined  Elevators 


Item 


Check 


A17.1-1996 
Section/Rule 


A17.1-2000 
Requirements 


Comments 


1 

Elevator  Inclined  —  Inside  of  Car 

1.6 

Special  car  emergency  signal 

1714.1 

5.1.21.1 

1.10 

Special  zoning  for  power  open 

1709.3 

5.1.9 

1.11 

Special  materials  allowed 

1708.5 

5.1.11.3 

1.13 

Emergency  exit  car  top  uphill 

1708.3a 
1708.3b 
1708.3c 

5.1.11.1.1 
5.1.11.1.2 
5.1.11.1.3 

1.16 

Special  platform  area 

1711.1 

5.1.13.1 

1.18 

Special  restricted  opening 

1709.3 

2.12.5 

Note  A17.1a-1997 

2 

Elevator  Inclined  —  Machine  Room 

2.13 

Special  governor  location/drive 

1710.4 

5.1.15 

2.20 

Special  winding  drum/slack  cable 

1712 
1713.2 

5.1.19 
5.1.20.5 

2.28 

Special  for  end-loading 

1716.4 
1716.5 

5.1.22.4 
5.1.22.5 

2.29 

Special  requirements  for  safeties 

Prior  A17.1D-1995 

1706,3 

1707.3 

1710 

Table  1710.4 

1706.3 

1707.3 

1710 

Table  1710.2(a) 

Table  1710.2(b) 

1713.3 

5.1.14 

Table  5.1.14.2 

5.1.15 

5.1.17.3 

5.1.18.3 

5.1.18.4 

5.1.20.6 

Major  change  in  stopping 
distances 

Electrical  stopping 

3 

Elevator,  Inclined  —  Top  of  Car/Uphill  Exit/End-Loading  Top  Car  Door 

3.1 

Stop  switch  at  location 

1708.3 
1708.4 
1713.1 

5.1.11 
5.1.20.1 
5.1.20.2 
5.1.20.3 

3.2 

Light  and  outlet  at  location 

204.7 
1713.1 

2.14.7 
5.1.20 

3.3 

Operating  device  at  location 

204.1g 
210.1d 
1713.1 

2.14.1.7 
2.26.1.4 
5.1.20 

3.4 

Top  of  car/directional  clearance  and  refuge  space 

1702.2 

5.1.5.2 

3.6 

Final  emergency  terminal  and  special  for  end- 
loading 

209.3 

1716.4 

1716.5 

2.25.3 

5.1.22.4 

5.1.22.5 

3.8 

Top/Uphill  end  emergency  exit 

1708.3 

5.1.11 

3.10 

Hoistway  construction 

1700 

5.1.2 

3.16 

Traveling  cables  and  junction  box 

1717.1 
1717.2 

5.1.7 

3.18 

Car  frame  (chassis) 

1708.1 

5.1.12.1 

3.19 

Guide  rails,  fastening,  and  equipment 

1706 

5.1.18 

162 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Additional  Checklist  for  Inclined  Elevators  (Cont'd) 


Item 


Check 


A17.1-1996 
Section/Rule 


A17.1-2000 
Requirements 


Comments 


3 

Elevator,  Inclined  —  Top  of  Car/Uphill  Exit/End-Loading  Top  Car  Door  (Cont'd) 

3.20 

Governor  rope 

1710.4 

5.1.15 
5.1.16 

3.23 

Suspension  rope 

1715 

5.1.16 

3.27 

Crosshead/uphill  chassis  member  data  plate 

1711.2 

5.1.13.2 

4 

Elevator,  Inclined  —  Outside  Hoistway 

4.1 

Car  platform  guard 

1708.1 
1708.2 

5.1.12.2 

4.5 

Access  to  hoistway 

1704 
1713.1 

5.1.10 

4.8 

Hoistway  enclosure 

1700.1 

5.1.1.1 
5.1.2 

5 

Elevator,  Inclined  -  Pit  or  Work  Space 

5.1 

Pit  access,  lighting,  stop  switch,  and  condition 

1701 
1702.1 

5.1.3 
5.1.4 
5.1.10 

5.2 

Bottom  clearance,  runby,  and  minimum  refuge 
space 

1701.2 
1702.1 

5.1.4 
5.1.5.1 

5.3 

Final  and  emergency  terminal  stopping  devices 

209.3 

1716.4 

1716.5 

2.25.3 

5.1.22.4 

5.1.22.5 

5.4 

Normal  terminal  stopping  devices 

1716.5 

5.1.22.5 

5.5 

Traveling  cables 

1715.2 
1717.1 

5.1.7.1 
5.1.16.1 

5.8 

Car  safeties  and  guiding  members 

1706.3 
1708.1 
1710 

5.1.12.1 
5.1.14 
5.1.15 
5.1.18 

5.9 

Buffers  and  emergency  terminal  speed  limiting 
devices 

1707 

Table  1707.2 

Table  1707.4 

5.1.17 

Table  5.1.17.2 

Table  5.1.17.4.4 

6 

6.4 


Elevator,  Inclined  —  Firefighters'  Service 


Firefighters'  service 


No  rule 

A17.1a-1997 

1714.2 


2.27.3 


163 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


(10) 


NONMANDATORY  APPENDIX  A 
INSPECTION  CHECKLISTS 


Checklist  for  Electric  Elevators 


A17.1-2000/ 

A17.1-1996 

B44-00 

A17.3 

Item 

Check 

Section/Rule 

Requirements 

Section/Para. 

Comments 

1 

ELEVATOR  -  INSIDE  OF  CAR 

1.1 

Door  reopening  device 

112, 
1001.2(a)(1) 

2.13, 
8.11.2.1.1(a) 

2.8 

1.2 

Stop  switches 

210.2(e), 

2.26.2.5, 

3.10.4(t), 

210. 2(v), 

2.26.2.21, 

3.10.4(u) 

1001.2(a)(2) 

8.11.2.1.1(b) 

1.3 

Operating  control  devices 

210.1a, 

2.26.1.1, 

3.10.1, 

210.1e, 

2.26.1.6, 

3.10.2, 

1001.2(a)(3) 

8.11.2.1.1(c) 

3.10.7 

1.4 

Sills  and  car  floor 

108.1, 

2.5.1, 

3.3.3, 

ANSI  A117.1 

llO.lOd, 

2.11.10.3, 

3.3.4 

110.11a, 

2.11.11.1, 

110.13a, 

2.11.13.1, 

203.16, 

2.15.16, 

210.12, 

8.11.2.1.1(d) 

1001.2(a)(4) 

1.5 

Car  lighting  and  receptacles 

204.7, 

2.14.7, 

3.4.5, 

1001.2(a)(5) 

8.11.2.1.1(e) 

3.4.6 

1.6 

Car  emergency  signal 

211.1, 
1001.2(a)(6) 

2.27.1, 
8.11.2.1.1(f) 

3.11.1 

1.7 

Car  door  or  gate 

112.2a, 

2.5.1.5.3, 

3.4.2, 

204.4, 

2.13.2.1, 

3.4.3, 

204.5, 

2.14.4, 

Appendix  A 

204.6, 

2.14.5, 

210.2q, 

2.14.6, 

1001.2(a)(7) 

2.26.2  (2,26,2.15), 
8.11.2.1.1(g) 

1.8 

Door  closing  force 

112.4(b), 
1001.2(a)(8), 
1002. 2h 

2.13.4.2.3, 
8.11.2.1.1(h), 
2.13.4.2.4, 
8.11.2.2.8 

2.8.1 

1.9 

Power  closing  of  doors  or 

112.3, 

2.13.3, 

2.8.2 

gates 

1001.2(a)(9) 

8.11.2.1.1(0 

1.10 

Power  opening  of  doors  or 

111.12, 

2.26.1.6, 

gates 

210.1e, 

210.9c, 

1001.2(a)(10), 

1002.3g, 

1002. 3h, 

1002.31 

2.26.9  (2.26.9.3), 
8.11.2.1. lQ), 
8.11.2.3.7, 
8.11.2.3.8, 
c8. 11. 2.3. 8, 
8.11.2.3.9 

1.11 

Car  vision  panels  and  glass 

204.2e, 

2.14.2.5, 

3.4.2, 

car  doors 

204.51, 

1001.2(a)(ll) 

2.14.5.8, 
8.11.2.1.1(k) 

3.4.3 

164 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


Checklist  for  Electric  Elevators  (Cont'd) 


Item 


Check 


A17.1-1996 
Section/Rule 


A17.1-2000/ 

B44-00 
Requirements 


A17.3 
Section/Para. 


Comments 


1 

ELEVATOR  -  INSIDE  OF  CAR 

(Cont'd) 

1.12 

Car  enclosure 

(NR  2.7.5.1.4), 

2.7.5.1.4, 

3.4.1, 

NFPA  70  or  CSA 

204, 

2.14, 

3.7.5 

C22.1,  as 

204.1b, 

2.14.1.2, 

applicable 

204.1h, 

2.14.1.8, 

(NR  2.14.2.6), 

2.14.2.6, 

207.2b, 

2.16.2.2, 

207.4, 

2.16.4, 

207.5, 

2.16.5, 

211.9, 

2.29.1, 

1104, 

8.3.7, 

1206.9 

8.6.10.3, 

1202.5, 

8.7.2.14, 

1001.2(a)(12), 

8.11.2.1.1(1), 

204.2b, 

2.14.2.2, 

(NR  2.14.2.6), 

2.14.2.6, 

(NR  8.1) 

8.1 

1.13 

Emergency  exit 

204. le, 
204.1], 
204.2d, 
1001.2(a)(13) 

2.14.1.5, 

2.14.1.10, 

2.14.2.4, 

8.1.2, 

8.6.10.2, 

8.11.2.1.1(m) 

3.4.4 

1.14 

Ventilation 

204.1(i), 

2.14.1.9.1(f), 

NFPA  70  or  CSA 

204.2c, 

2.14.2.3, 

C22.1,  as 

204.3c, 

2.14.3.3, 

applicable 

1001.2(a)(14) 

8.11. 2.1. l(n) 

1.15 

Signs  and  operating  device 

210.13, 

2.16.12, 

symbols 

1001.2(a)(15) 

8.11.2.1.1(o) 

1.16 

Rated  load,  platform  area,  and 

207, 

2.16, 

3.7 

data  plate 

1001.2(a)(16) 

8.11.2.1.1(p) 

1.17 

Standby  power  operation 

207.8, 
210.10, 
211.2, 

1001.2(a)(17), 
1002. 2g, 
1002. 3e 

2.16.8, 

2.26.10, 

2.27.2, 

8.11.2.  l.l(q), 

8.11.2.2.7, 

8.11.2.3.5 

1.18 

Restricted  opening  of  car  or 
hoistway  doors 

111.12, 
1001.2(a)(18) 

8.11.2.1.1(r) 

2.7.4 

1.19 

Car  ride 

200, 

203.2, 

1001.2(a)(19) 

2.23, 

2.15.2, 

8.11.2.1.1(s) 

1.20 

Earthquake  inspection  and 
tests  (seismic  Zone  2  or 
greater) 

2406 

8.4 

2 

ELEVATOR  -  MACHINE  ROOM 

2.1 

Access  to  machine  space 

101.1a, 

2.7.1.1, 

2.2.2 

NFPA  70  or  CSA 

101.3a, 

2.7.3.1, 

C22.1,  as 

101.3b, 

2.7.3.2, 

applicable 

101.3c, 

2.7.3.3, 

101.3d, 

2.7.3.4, 

1001.2(b)(1) 

8.11.2.1.2(a) 

165 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Checklist  for  Electric  Elevators  (Cont'd) 


Item 


Check 


A17.1-1996 
Section/Rule 


A17.1-2000/ 

B44-00 
Requirements 


A17.3 
Section/Para. 


Comments 


2 

ELEVATOR  -  MACHINE  ROOM  (Cont'd) 

2.2 

Headroom 

101.4, 
1001.2(b)(2) 

2.7.4, 
8.11.2.1.2(b) 

2.3 

Lighting  and  receptacles 

101.5a, 

2.7.5.1, 

2.2.3 

NFPA  70  orCSA 

101.5c, 

8.11.2.1.2(c) 

C22.1,  as 

1001.2(b)(3) 

applicable 

2.4 

Machine  space 

100.3c, 

2.1.3.3, 

2.2.1, 

100.3d, 

2.1.3.4, 

2.2.6 

100.5, 

2.1.5, 

101.1a, 

2.7.1.1, 

101.2, 

2.7.2.1, 

101.8, 

2.7.8, 

1001.2(b)(4) 

8.11.2.1.2(d) 

2.5 

Housekeeping 

1001.2(b)(5), 

1206.2b, 

1206.9 

8.11.2.1.2(e), 

8.6.4.8, 

8.6.10.3 

2.6 

Ventilation 

101.5b, 

102.4, 

1001.2(b)(6) 

2.7.5.2, 

2.8.4, 

8.11.2.1.2(0 

2.2.4 

2.7 

Fire  extinguisher 

1001.2(b)(7), 
1206.1h 

8.11.2.1.2(g), 
c8. 11. 2. 1.2(g), 
8.6.1.6.5 

2.8 

Pipes,  wiring,  and  ducts 

102.1, 

2.8.1, 

2.2.5 

ANSI/NFPA13;  A17.1, 

102.2, 

2.8.2, 

Inquiry  88-26 

1001.2(b)(8) 

8.11.2.1.2(h) 

2.9 

Guarding  of  exposed  auxiliary 

104.1, 

2.10.1, 

equipment 

1001.2(b)(9) 

8.11.2.1.2(0 

2.10 

Numbering  of  elevators, 

208.10, 

2.26.4, 

NFPA  70  orCSA 

machines,  controllers,  and 

210.4, 

2.29.1, 

C22.1,  as 

disconnect  switches 

211.9, 
1001.2(b)(10) 

8.11.2.1.2Q) 

applicable 

2.11 

Disconnecting  means  and 

210.4, 

2.26.4, 

3.10.5 

NFPA  70  orCSA 

control 

1001.2(b)(ll) 

8.11.2.1.2(p) 

C22.1,  as 
applicable 
A17. 5-1991 
clause  20.7 

2.12 

Controller  wiring,  fuses, 

102.1, 

2.8.2, 

3.10 

NFPA  70  or  CSA 

grounding,  etc. 

210.4, 

2.26.4, 

C22.1,  as 

1001.2(b)(12), 

8.11.2.1.2(q), 

applicable 

1206. If 

8.6.1.6.1, 
C8.6.12. 3.1.3, 
8.6.1.6.3, 
c8. 6.12. 2.6 

2.13 

Governor,  overspeed  switch, 

206, 

2,18, 

3.6.1, 

and  seal 

205.15, 

210.2Q), 

1001.2(b)(28), 

1002.2c, 

1002.3a, 

1002.3b, 

1003.2a, 

1206.1a 

2.17.15, 

2.26.2  (2.26.2.10), 

8.11.2.1. 2(bb), 

8,11.2.2.3, 

8.11.2.3.1, 

8.11.2.3.2, 

C8.ll. 2. 3.2(c) 

8.10.2.2.2(cc)(l), 

8,6.1.6.2 

3.10.4(g) 

166 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


Checklist  for  Electric  Elevators  (Cont'd) 


Item 


Check 


A17.1-1996 
Section/Rule 


A17.1-2000/ 

B44-00 
Requirements 


A17.3 
Section/Para. 


Comments 


2 

ELEVATOR  -  MACHINE  ROOM  (Cont'd) 

2.14 

Code  data  plate 

215, 
1200.6 

8.9, 
8.7.1.8 

2.15 

Static  control 

210.2, 
210.9(d), 
1001.2(b)(13), 
1003.2h 

2.26.2, 
2.26.9.5, 
8.11.2,1.2(m), 
8.10.2. 2. 2(m) 

2.16 

Overhead  beam  and  fasten- 

105.1, 

2.9.1, 

ings 

105.2, 
105.3, 
1001.2(b)(14) 

2.9.2, 
2.9.3, 
8.11.2.1.2(n) 

2.17 

Drive  machine  brake 

207.2b, 

207.8, 

(NR  2.24.8), 

210.8, 

1001.2(b)(15), 

[NR  8.11.2.3.10(a)], 

1002.3d 

2.16.2.2, 

2.16.8, 

2.24.8, 

2.26.8, 

8.11.2.1.2(0), 

8.11.2.3.10(a), 

8.11.2.3.4 

3.8.4 

2.18 

Traction  drive  machines 

208, 

100l.2(b)(16), 

1003.2, 

[NR  811.2.3.10(b)] 

2.24, 

8.11.2. 1.2(p), 
8.10.2.2.2(v)(b)(3), 
8.11.2.3.10(b) 

3.8.1 

2.19 

Gears,  bearings,  and  flexible 

208, 

2.24, 

3.8.1 

couplings 

1001.2(b)(17), 
1206.1a 

8.11.2.1.2(q), 
8.6.1.6.2 

2.20 

Winding  drum  machine  and 

208.1, 

2.24.1, 

3.8.2, 

slack  rope  device,  stop 

2093c(2), 

2.25.3.3.2, 

3.10.4, 

motion  switch  and  rope 

209.3e, 

2.25.3.5, 

3.12.6, 

fastening 

210.2, 

2.26.2, 

3.12.7, 

212.6, 

2.20.2, 

3.12.9 

212.7, 

2.20.7, 

212.10, 

2.20.10, 

1001.2(b)(18), 

8.11.2.1.2(w), 

(NR  8.6.4.19.4), 

8.6.4.19.4, 

(NR  8.6.4.19.5), 

8.6.4.19.5, 

1002.2d, 

8.11.2.2.4, 

1206.3 

8.6.4.10, 
C8.6.12.4.2 

2.21 

Belt-  or  chain-drive  machine 

208.9, 
1001.2(b)(19) 

2.24.9, 
8.11.2.1.2(s) 

3.8.3 

2.22 

Motor  generator 

210.9f, 

1001.2(b)(20), 

1003.2] 

2.26.9.7, 
8.11. 2.1. 2(t), 
8.10.2.2.2(t) 

2.23 

Absorption  of  regenerated 

210.10, 

2.26.10, 

3.10.10 

power 

1001.2(b)(21), 
1003.2k 

8.11.2. 1.2(u), 
8.10.2. 2. 2(u) 

2.24 

AC  drives  from  a  DC  source 

210.2, 
210.9(e), 
1001.2(b)(22), 
1003. 2i 

2.26.2, 
2.26.9.6, 
8.11.2.1.2(v), 
8.10.2.2.2(m)(3) 

167 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Checklist  for  Electric  Elevators  (Cont'd) 


A17.1-2000/ 

A17.1-1996 

B44-00 

A17.3 

Item 

Check 

Section/Rule 

Requirements 

Section/Para. 

Comments 

2 

ELEVATOR  -  MACHINE  ROOM  (Cont'd) 

2.25 

Traction  sheaves 

207.8, 

208.2, 

208.3, 

212, 

1001.2(b)(23), 

1202.14, 

1206.1a, 

1206.1b 

2.16.8, 

2.24.2, 

2,24.3, 

2.20, 

8.11.2. 1.2(w), 

8.7,2.21, 

8.6.1.6.2, 

8.6.4.1 

3.8.1 

2.26 

Secondary  and  deflector 

208, 

2.24, 

3.8.1 

sheaves 

1001.2(b)(24), 
1206.1a 

8.11.2. 1.200, 
8.6.1.6.2 

2.27 

Rope  fastenings 

105.3c, 

1001.2(b)(25), 

212 

2.9.3.3, 
8.11.2.1. 2(y), 
2.20 

3.12 

2.28 

Terminal  stopping  devices 

209, 

2.25, 

3.8.2, 

1001.2(b)(26), 

8.11.2.1.2(z), 

3.9.1, 

1002.3f 

8.11.2.3.6 

3.9.2, 
3.10.4 

2.29 

Car  and  counterweight  safeties 

205, 

2.17, 

3.5, 

1306, 

8.2.6, 

3.6, 

Table  205.3, 

Table  2.17.3, 

3.10.4(m) 

1001.2(b)(29), 

8.11.2.1.2(cc), 

1002.2b, 

8.11.2.2.2, 

1002.3a, 

8.11.2.3.1, 

1003.2, 

8.10.2.2, 

1202.6 

8.7.2.18 

2.40 

Maintenance  records 

8.6.1.4, 
c8. 6.12. 2. 5, 
8.6.10.1 

2.41 

Static  control 

2.42 

Earthquake  inspection  and 

2401, 

8.4.2, 

tests  (seismic  risk  Zone  2 

2400.1, 

8.4.3.1, 

or  greater) 

2408, 
2409 

8.4.9, 
8.4.10 

3 

ELEVATOR  -  TOP  OF  CAR 

3.1 

Top-of-car  stop  switch 

210.2(h), 
1001.2(c)(1) 

2.26.2.8, 
8.11.2.1.3(a) 

3.10.4(e) 

3.2 

Car  top  light  and  outlet 

204.7, 

2.14.7, 

3.4.5 

NFPA  70  or  CSA 

1001.2(c)(2) 

8.11.2.1.3(b) 

C22.1,  as  applica- 
ble 

3.3 

Top-of-car  operating  device 

204.1g, 
210.1d, 
1001.2(c)(3) 

2.14.1.7, 
2.26.1.4, 
8.11.2.1.3(c) 

3.10.3 

3.4 

Top-of-car  clearance,  refuge 

1206.8, 

8.6.4.11, 

2.4.4 

space,  and  standard  railing 

107, 
1304 

2.4, 
2.10.2, 
2.14.1.7, 
8.2.4 

168 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


Checklist  for  Electric  Elevators  (Cont'd) 


Item 


Check 


A17.1-1996 

Section/Rule 


A17.1-2000/ 

B44-00 
Requirements 


A17.3 
Section/Para. 


Comments 


3 

ELEVATOR  -  TOP  OF  CAR  (Cont'd) 

3.5 

Normal  terminal  stopping 
devices 

207.4, 

209.2, 

210.2, 

1001.2(c)(7), 

1002. 2e, 

1003.2f, 

1003. 3(k) 

2.25.1, 

2.25.2, 

2.26.2, 

8.11.2.1.3(g), 

8.11.2.2.5, 

8.10.2,2.2(z), 

8.10.2. 3. 2(k) 

3.9.1, 
3.10.4 

3.6 

Final  and  emergency  terminal 
stopping  devices 

209.3, 

1001.2(c)(8), 
1002. 2e, 
1003.3(k) 

2.25.3, 
8.11.2.1.3(h), 
8.11.2.2.5, 
8.10.2.3.2(k) 

3.9.2 

3.7 

Car  leveling  and  anticreep 
devices 

210. le, 
1001.2(c)(10) 

2.26.1.6, 
8.11.2.1.3Q) 

3.8 

Top  emergency  exit 

204. le, 
1001.2(c)(12) 

2.14.1.5, 
8.11.2.1.3(1) 

3.4.4 

3.9 

Floor  and  emergency 
identification  numbering 

100.7, 
211.9, 
1001.2(c)(15) 

2.29.2, 
2.29.1, 
8.11.2.1.3(0) 

3.10 

Hoistway  construction 

100, 
1001.2(c)(16) 

2.1, 
8.11.2.1.3(p) 

2.1 

3.11 

Hoistway  smoke  control 

100.4, 
1001.2(c)(17) 

2.1.4, 
8.11.2. 1.3(q) 

3.12 

Pipes,  wiring,  and  ducts 

102, 
1001.2(c)(18) 

2.8, 
8.11.2.1.3(r) 

2.1.4 

3.13 

Windows,  projections, 
recesses,  and  setbacks 

100.5, 
100.6, 
110.10, 
1001.2(c)(19) 

2.1.5, 
2.1.6, 
2.11.10, 
8.11.2.1.3(5) 

2.1.2, 
2.1.3 

3.14 

Hoistway  clearances 

107, 
108, 
1001.2(c)(20) 

2.4, 
2.5, 
8.11.2.1.3(0 

2.4 

3.15 

Multiple  hoistways 

100. Id, 
1001.2(c)(21) 

2.1.1.4, 
8.11. 2.1. 3(u) 

3.16 

Traveling  cables  and  junction 
boxes 

102.1, 
1001.2(c)(22) 

2.8.1, 
8.11.2.1.3(v) 

NFPA  70  or  C5A 
C22.1,  as 
applicable 

3.17 

Door  and  gate  equipment 

110, 

111, 

210. le, 

1001.2(c)(23) 

2.11, 
2.12, 
2.26.1.6, 
8.11.2.1.3(w) 

2.6, 
2.7 

A17.1  Inquiry  96-71 

3.18 

Car  frame  and  stiles 

203, 

213, 

1001.2(c)(24), 

1200.4, 

1202.4a 

2.15, 

8.8, 

8.11.2.1.3(x), 

8.6.2, 

8.7.2.15.1 

3.19 

Guide  rails  fastening  and 
equipment 

205.16, 
1001.2(c)(25), 
1206. Id 

2.17.16, 

8.11.2.1.3(y), 

8.6.4.3 

3.5.6 

169 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  niade  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Checklist  for  Electric  Elevators  (Cont'd) 


Item 


Check 


A17.1-1996 
Section/Rule 


A17.1-2000/ 

B44-00 
Requirements 


A17.3 
Section/Para. 


Comments 


3 

ELEVATOR  -  TOP  OF  CAR  (Cont'd) 

3.20 

Governor  rope 

206.5, 

1001.2(c)(26), 
1202.7, 
1206.1c 

2.18.5, 
8.11.2.1. 3(z), 
8.7.2.19, 
8.6.4.2 

3.6.2 

3.21 

Governor  releasing  carrier 

205.15, 
1001.2(c)(27) 

2.17.15, 
8.6.2.4, 
8.11.2.1.3(aa) 

3.5 

3.22 

Wire  rope  fastening  and  hitch 

212, 

2.20, 

3.12.5, 

plate 

105.3c, 

2.9.3.3, 

3.12.8, 

203.13, 

2.15.13, 

3.12.9 

1001.2(c)(28), 

8.11.2.1.3(bb), 

1200.5, 

8.6.3, 

1206.3 

8.6.4.10, 
C8.6.12.4.1.1, 
C8.6.12.4.3, 
c8. 6.12.4.4, 
c8. 6.12.4. 5 

3.23 

Suspension  rope 

212, 

206.7, 

1001.2(c)(29)(a), 

1200.5, 

1202.14, 

1203.9, 

1004.2(c) 

2.20, 

2.18.7, 

8.11.2.1.3(cc)(l), 

8.6.3, 

8.7.2.21, 

8.7.3.25, 

8.11.3.1.3(y) 

3.24 

Top  counterweight  clearance 

107.1h, 
1001.2(c)(5) 

2.4.9, 
8.11.2.1.3(e) 

3.25 

Car,  overhead,  and  deflector 
sheaves 

208 

2.24 

3.8.1 

3.26 

Broken  rope,  chain,  or  tape 

209.2c(2), 

2.25.2.3.2, 

3.10.4(d) 

switch 

210.2(f), 
1001.2(c)(9), 
1002. 2i 

2.26.2.6, 

8.11.2.1.3(0, 

8.11.2.2.9 

3.27 

Crosshead  data  plate  and  rope 

207.3, 

2.16.3, 

3.12.2 

data  tags 

212.2, 

1001.2(c)(ll), 

1202.14 

2.20.2, 
8.11.2.1. 3(k), 
8.7.2.21 

3.28 

Counterweight  and  counter- 

201, 

2.3, 

2.1.5, 

weight  buffer 

202, 

2.4.9, 

2.4.3, 

1001.2(c)(13) 

2.21, 

2.22, 

8.11,2. 1.3(m), 

8.11.2.1.5(c), 

8.11.2.3.3, 

c8.11.2.3.3(d) 

3.1, 
3.2, 
4.9 

3.29 

Counterweight  safeties 

205, 

2.17.12.4, 

3.5.2, 

206.5(e), 

2.18.5.3, 

3.6.2, 

1001.2(b), 

8.11.2.1. 2(y), 

3.12.2 

1001. 2(c)  (14), 

8.11.2.1.3(k), 

1001.2(c), 

8.11.2.1.3(z), 

1003.2, 

8.10.2.2.2(z), 

1002.3(a), 

8.11.2. 1.3(n), 

1003.2, 

8.11.2.3.1, 

1002.3 

8.10.2.2, 
8.11.2.3 

170 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


Checklist  for  Electric  Elevators  (Cont'd) 


Item 

Check 

A17.1-1996 
Section/Rule 

A17.1-2000/ 

B44-00 
Requirements 

A17.3 
Section/Para. 

Comments 

3 

ELEVATOR  -  TOP  OF  CAR  (Cont'd) 

3.33 

Compensating  ropes  and 
chains 

202.4, 

1001.2(c)(30), 
1003. 2g 

2.21.4, 

8.11.2.1.3(dd), 
8.10.2. 2.3(dd), 
8.10.2.2.5(h) 

3.34 

Earthquake  inspection  and 
tests  (seismic  risk  Zone  2 
or  greater) 

2402, 
2401, 
2400, 
2405, 
2407, 
2404, 
2403 

8.4.1, 
8.4.2, 
8.4.3, 
8.4.5, 
8.4.6, 
8.4.7, 
8.4.8 

4 

ELEVATOR  -  OUTSIDE  HOISTWAY 

4.1 

Car  platform  guard 

203.9, 
1001.2(d)(1) 

2.15.9, 
8.11.2.1.4(a) 

3.3, 
3.2.2 

4.2 

Hoistway  doors 

110, 
111.7, 
210.2, 
1001.2(d)(2) 

2.11, 
2.12.7, 
2.26.2, 
8.11.2.1.4(b) 

3.10.4 

4.3 

Vision  panels 

110.7, 
1001.2(d)(3) 

2.11.7, 
8.11.2.1.4(c) 

2.6.3 

4.4 

Hoistway  door  locking  devices 

111, 
1001.2(d)(4) 

2.12, 
8.11.2.1.4(d) 

2.7.1 

4.5 

Access  to  hoistway 

111.6, 
111.7, 
1001.2(d)(5) 

2.12.6, 
2.12.7, 
8.11.2.1.4(e) 

2.7.3 

4.6 

Power  closing  of  hoistway 
doors 

112, 
1001.2(d)(6) 

2.13, 
8.11.2.1.4(f) 

4.7 

Sequence  operation 

112.6, 

112.3d, 

1001.2(d)(7) 

2.13.6, 

2.13.3.4, 

8.11.2.1.4(g) 

4.8 

Hoistway  enclosure 

100.1, 
100.4, 
100.5, 
1001.2(d)(8) 

2.1.1, 
2.1.4, 
2.1.5, 
8.11.2.1.4(h) 

2.1.1, 
2.1.2 

ANSI  Z97.1  or  16  CFR 
Part  1201 

4.9 

Elevator  parking  devices 

1001.2(d)(9) 

8.11.2.1.4(0 

2.7.2 

4.10 

Emergency  doors  in  blind 
hoistways 

110.1, 
1001.2(d)(10) 

2.11.1.1, 
2.11.1.2, 
8.1, 
8.11.2.1.4(0 

4.11 

Separate  counterweight 

hoistway 

103.1, 
103.3, 
110.1, 
1001.2(d)(ll) 

2.3.1, 

2.3.3, 

2.11.1.1, 

2.11.1.2, 

2.26.2.27, 

8.11.2.1.4(k) 

171 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Checklist  for  Electric  Elevators  (Cont'd) 


Item 


Check 


A17.1-1996 
Section/Rule 


A17.1-2000/ 

B44-00 
Requirements 


A17.3 
Section/Para. 


Comments 


4 
4.12 


ELEVATOR  -  OUTSIDE  HOISTWAY  (Cont'd) 


Standby  power  selection 
switch 


211.2, 
211.8, 

1001.2(d)(13), 
1002.2g 


2.27.2, 
2.27.8, 
8.11.2.1.4(1), 
8.11.2,2.7 


3.11.2 


5 

ELEVATOR  -  PIT 

5.1 

Pit  access,  lighting,  stop 

102, 

2.8, 

2.3.1, 

NFPA  70  orCSA 

switch,  and  condition 

103.2, 

2.3.2, 

2.3.2, 

C22.1,as 

106.1, 

2.26.2.7, 

2.7.3 

applicable 

210.2(g), 

8.11.2.1.5(a), 

1001.2(e)(1), 

8.6.4.7 

1206.2a 

5.2 

Bottom  clearance,  runby,  and 

103.2, 

2.3.2, 

2.4.2, 

minimum  refuge  space 

107.1a, 

107.1b, 

201.4h, 

1001.2(e)(2), 

1202.14b, 

1206.8 

2.4.1, 

2.4.2, 

2.22.4.8, 

8.11.2.1.5(b), 

8.6.4.11 

2.4.3 

5.3 

Final  and  emergency  terminal 

209.3, 

2.25.3, 

3.9.2 

stopping  devices 

1001.2(e)(4), 
1003.2e 

8.11.2.1.5(d), 
8.10.2.2.5(c), 
C8.10.2.2.5(c)(6) 

5.4 

Normal  terminal  stopping 

209, 

2.25, 

3.9.1 

devices 

1002. 2e 

8.11.2.2.5 

5.5 

Traveling  cables 

102.2 

2.8.2 

NFPA  70  or  CSA 
C22.1,  as  applica- 
ble 

5.6 

Governor-rope  tension  devices 

206.7, 

1001.2(e)(7), 

1206.1a 

2.18.7, 

8.11.2.1.5(g), 

8.6.1.6.2 

5.7 

Car  frame  and  platform 

203.8, 
203.6, 
207.2b(3), 
1001.2(e)(9) 

2.15.8, 
2.15.6, 
2.16.2.2, 
8.11.2.1.5(0 

3.3 

5.8 

Car  and  counterweight  safeties 

203, 

2.15, 

3.5 

and  guiding  members 

205.11, 

1001. 2(e)  (10), 

1001.2b(2)(c), 

1002.3a, 

1206.1g, 

1202.4a 

2.17.11, 

8.11.2.1.5Q), 

8.11.2.1.2, 

8.11.2.3.1, 

8.6.4.5, 

8.7.2.15.1 

5.9 

Buffers  and  emergency  termi- 

201, 

2.22, 

3.1, 

nal  speed  limiting  devices 

109.1, 
210. 2(w), 
1002. 3f, 
1003.2e, 
1206. If, 
1308.2 

2.6, 

2.26.2.22, 

8.11.2.3.6, 

8.10.2.2.5(c), 

C8.10.2.2. 5(c)(6), 

8.6.1.6.3, 

c8. 6.12. 2. 6, 

8.2.3, 

8.3.1.3 

3.10.4(m) 

172 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


Checklist  for  Electric  Elevators  (Cont'd) 


Item 


Check 


A17. 1-1996 
Section/Rule 


A17.1-2000/ 

B44-00 
Requirements 


A17.3 

Section/Para. 


Comments 


5 

ELEVATOR  -  PIT  (Cont'd) 

5.10 

Compensating  chains,  ropes, 

202.4, 

2.21.4, 

and  sheaves 

205.17, 
210.2c, 
1001.2(e)(8) 

2.17.17, 
2.26.2.3, 
8.11.2.1.5(h) 

5.16 

Earthquake  inspection  and 

2400, 

8.4.3, 

tests  (seismic  risk  Zone  2  or 

2407, 

8.4.6, 

greater) 

2403 

8.4.8 

6 

ELEVATOR  -  FIREFIGHTERS'  ! 

SERVICE 

6.1 

Operation  of  elevators  under 

112.3d, 

2.13.3.4, 

A17.1D-1973  through 

fire  and  other  emergency 

112.5, 

2.13.5, 

A17.1D-1980,  Rule 

conditions  (A17.1D-1973 

1001.2(d)(12), 

8.11.2.1.4(1), 

211.3 

through  A17.1D-1980) 

1002. 2f, 
1206.7 

8.11.2.2.6, 
8.6.10.1 

6.2 

Operation  of  elevators  under 

112.3d, 

2.13.3.4, 

A17. 1-1981  through 

fire  and  other  emergency 

112.5, 

2.13.5, 

A17.1D-1983,  Rule 

conditions  (A17. 1-1981 

1001.2(d)(12), 

8.11.2.1.4(1), 

211.3 

through  A17.1D-1983) 

1002. 2f, 
1206.7 

8.11.2.2.6, 
8.6.10.1 

6.3 

Firefighters'  service  (A17.1- 

112.3d, 

2.13.3.4, 

3.11.3 

A17. 1-1984  through 

1984  through  A17.1a-1988 

112.5, 

2.13.5, 

A17.1a-1988,  Rules 

and  A17.3) 

1001.2(d)(12), 

8.11.2.1.4(1), 

211.3  through 

1002.2f, 

8.11.2.2.6, 

211.8 

1206.7 

8.6.10.1 

6.4 

Firefighters'  service  (A17.1b- 

112.3d, 

2.13.3.4, 

1989  through  A17.1d-2000) 

112.5, 

211.2-211.8, 
1001.2(d)(12), 
1002. 2f, 
1206.7 

2.13.5, 

2.27.2-2.27.8, 

8.11.2.1.4(1), 

8.11.2.2.6 

8.6.10.1 

6.5 

Acceptance  checklist  firefight- 
ers' service  (Al  7.1-2000 
and  B44-00):  automatic 
elevators 

173 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Checklist  for  Hydraulic  Elevators 


A17.1-2000/ 

A17.1-1996 

B44-00 

A17.3 

Item 

Check 

Section/Rule 

Requirements 

Section/Para. 

Comments 

1 

ELEVATOR  -  INSIDE  OF  CAR 

1.1 

Door  reopening  device 

112  {300.13}, 
1001.2(a)(1), 
1004.2(a)(1) 

2.13  {3.13}, 

8.11.2.1.1(a), 

8.11.3.1.1(a) 

2.8 

1.2 

Stop  switches 

306.4(b)(1), 

3.26.4.2(a), 

3.10.4(f)  {4.7,4}, 

306.4(b)(6), 

3.26.4.2(f), 

3.10.4(u)  {4.7.4} 

1004.2(a)(2) 

8.11.3.1.1(b) 

1.3 

Operating  control  devices 

210.1a  {306.1}, 

2.26.1.1  {3.26.1} 

3.10.1  {4.7}, 

306.3, 

3.26.3, 

3.10.2  {4.7}, 

1004.2(a)(3) 

8.11.3.1.1(c) 

3.10.9  {4.7.6} 

1.4 

Sills  and  car  floor 

108.1  {300.9}, 

2.5.1  {3.5}, 

3.3.3  {4.2.2}, 

ANSI  A117.1 

HO.lOd  {300.11}, 

2.11.10.3  {3.11}, 

3.3.4  {4.2.2} 

110.11a, 

2.11.11.1, 

110.13a, 

2.11,13.1, 

203.16  {301.6}, 

2.15.16  {3.15}, 

210.12, 

8.11.3.1.1(d) 

1004.2(a)(4) 

1,5 

Car  lighting  and  receptacles 

301.7, 

3.14, 

3.4.5  {4.2.3}, 

1004.2(a)(5) 

8.11.3.1.1(e) 

3.4.6  {4.2.3} 

1.6 

Car  emergency  signal 

211.1  {306.11}, 
1004.2(a)(6) 

2.27.1  {3.27}, 
8.11.3.1.1(f) 

3.11.1  {4.7.8} 

1.7 

Car  door  or  gate 

111.7(c)  {300.12}, 

2.5.1.5.3  {3.5}, 

3.4.2  {4.2.3}, 

112.2a  {300.13}, 

2.12.7.3  {3.12}, 

3.4.3  {4.2.3}, 

204.4-204.6  {301.7}, 

2.13.2.1  {3.13}, 

Appendix  A 

210.2(q)  {306.4}, 

2.14.4-2.14.6 

1004.2(a)(7) 

{3.14}, 
2.26.2  (2.26.2.15), 
{3.26.4}, 
8.11.3.1.1(g) 

1.8 

Door  closing  force 

112.4(b), 

301.7, 

1004.2(a)(8) 

2.13.4.2.3, 
3.14, 

2.13.4.2.4, 
8.11.3.1.1(h) 

2.8.1  {4.1} 

1.9 

Power  closing  of  doors  or 

112.3  {300,13}, 

2.13,3  {3.13}, 

2.8.2  {4.1} 

gates 

1004.2(a)(9) 

8.11.3.1.1(0 

1.10 

Power  opening  of  doors  or 

111.5  {300.12}, 

2.12.5  {3.12}, 

gates 

210.1e, 
210.9(c), 
306.3, 
1004.2(a)(10) 

2.26.1.6, 

2.26.9  (2.26.9.3), 

3.26.3, 

8.11.3.1.1(0 

1.11 

Car  vision  panels  and  glass 

204. 2e  {301.7}, 

2.14.2.5, 

3.4.2  {4.2.3}, 

car  doors 

204.5i  {301.7}, 
1004.2(a)(ll) 

2.14.5.8  {3.14}, 
8.11.3.1. l(k) 

3.4.3  {4.2.3} 

1.12 

Car  enclosure 

204.1b  {301.7}, 

2.14  {3.14}, 

3.4.1  {4.2.3}, 

204. lh,  {301.7}, 

8.3.7, 

3.7.5  {4.2.4} 

1104, 

2.29.1  {3.27}, 

204.2d  {301.7}, 

8.11.3.1.1(1), 

211.9  {306.11}, 

8.7.2.14, 

1004.2(a)(12), 

8.7.3.13 

1202.5, 

1203. 2e 

174 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


Checklist  for  Hydraulic  Elevators  (Cont'd) 


Item 


Check 


A17.1-1996 
Section/Rule 


A17.1-2000/ 

B44-00 
Requirements 


A17.3 
Section/Para. 


Comments 


1 

ELEVATOR  -  INSIDE  OF  CAR  (Cont'd) 

1.13 

Emergency  exit 

204.1J  {301.7}, 
1004.2(a)(13) 

2.14.1.10, 

3.14, 

8.1.2, 

8.6.10.2, 

8.11.3.1.1(m) 

3.4.4  {4.2.4} 

1.14 

Ventilation 

204.1  (i), 
204.2c  {301.7}, 
204.3c  {301.7}, 
1004.2(a)(14) 

2.14.1.9.1(f), 
2.14.2.3, 
2.14.3.3  {3.14}, 
8.11.3.1. l(n) 

NFPA  70  orCSA 
C22.1,  as 
applicable 

1.15 

Signs  and  operating  device 
symbols 

210.13  {306.12}, 
1004.2(a)(15) 

2.26,12, 
8.11.3.1.1(0) 

1.16 

Rated  load,  platform  area,  and 
data  plate 

207  {301.10}, 
1004. 2  (a)  (16) 

2.16  {3.16}, 
8.11.3.  l.l(p) 

3.7  {4.2.4} 

1.17 

Standby  power  operation 

211.2  {306.11}, 
1002.2g  {1005.2c(6)}, 
1004.2(a)(17) 

2.27.2  {3.27}, 
8.11.2.2.7 

{8.11.3.2.3(0}, 
8.11.3.1.  l(q) 

3.11.2  {4.7.8} 

1.18 

Restricted  opening  of  car  or 
hoistway  doors 

111.5  {300.12}, 
1004.2  (a)  (18) 

2.12.5  {3.12}, 
8.11.3.1.1(0 

2.7.4  {4.1} 

1.19 

Car  ride 

301.1a, 
301.6, 

1004.2(a)(19), 
1206.1a  {1206.5a} 

3.23.1, 
3.15, 

8.11.3.1.1(s), 
8.6.1.6.2  {8.6.5} 

1.20 

Earthquake  inspection  and 
tests  (seismic  Zone  2  or 
greater) 

2406 

8.4 

2 

ELEVATOR  -  MACHINE  ROOM 

2.1 

Access  to  machine  space 

300.1, 
300.2, 
1004.2(b)(1) 

3.1, 
3.7, 
8.11.3.1.2(a) 

2.2.2  {4.1} 

NFPA  70  or  CSA 
C22.1,  as 
applicable 

2.2 

Headroom 

101.4  {300.2}, 
1004.2(b)(2) 

2.4.7  {3.7}, 
8.11.3.1.2(b) 

2.3 

Lighting  and  receptacles 

101.5a  {300.2}, 
101.5C  {300.2}, 
1004.2(b)(3) 

2.7.5.1  {3.7}, 
8.11.3.1.2(c) 

2.2.3  {4.1} 

NFPA  70  or  CSA 
C22.1,  as 
applicable 

2.4 

Machine  space 

101.1a  {300.2}, 
105.2  {300.6}, 
105.4  {300.6}, 
1004.2(b)(4) 

2.7.1.1  {3.7}, 
2.9.2, 
2.9.4  {3.9}, 
8.11.3.1.2(d) 

2.2.2  {4.1}, 
2.2.6  {4.1} 

2.5 

Housekeeping 

1004.2(b)(5), 
1206.1  {1206.5a}, 
1206.2b  {1206.5a}, 
1206.9 

8.11.3.1.2(e), 
8.6.1.2, 
8.6.4.8  {8.6.5}, 
8.6.10.3 

2.6 

Ventilation 

101.5b  {300.2}, 

102.4, 

1004.2(b)(6) 

2.7.5.2  {3.7}, 

2.8.4, 

8.11.3.1.2(0 

2.2.4  {4.1} 

2.7 

Fire  extinguisher 

1004.2(b)(7), 
1206.2f  {1206.5a} 

8.11.3.1.2(g),  or 
c8. 11. 3. 1.2(g) 
{8.6.5} 

175 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Checklist  for  Hydraulic  Elevators  (Cont'd) 


Item 


Check 


A17.1-1996 
Section/Rule 


A17.1-2000/ 

B44-00 
Requirements 


A17.3 
Section/Para. 


Comments 


2 

ELEVATOR  -  MACHINE  ROOM  (Cont'd) 

2.8 

Pipes,  wiring,  and  ducts 

102.1  {300.3}, 

2.8.2, 

2.2.5  {4.1} 

ANSI/NFPA  13,  A17.1 

102.2  {300.3}, 

2.8.2  {3.8}, 

Inquiry  88-26 

1004.2(b)(8) 

8.11.3.1.2(h) 

2.9 

Guarding  of  exposed  auxiliary 

104.1  {300.5}, 

2.10.1  {3.10}, 

equipment 

1004.2(b)(9) 

8.11.3.1.2(f) 

2.10 

Numbering  of  elevators, 

210.4, 

2.26.4, 

NFPA  70  or  CSA 

machines,  controllers,  and 

211.9  {306.11}, 

2.29.1  {3.27}, 

C22.1,  as 

disconnect  switches 

306.6 

3.26 

applicable 

2.11 

Disconnecting  means  and 

306.3a(5)(b), 

3.26.3.1 

3.10.5  {4.7.5} 

NFPA  70  or  CSA 

control 

306.4, 

[3.26.3.1.4(b)], 

C22.1,  as 

306.6, 

3.26.4, 

applicable 

1004.2(b)(ll) 

3.26, 
8.11.3.1. 2(p) 

2.12 

Controller  wiring,  fuses, 

102.1  {300.3}, 

2.8.1  {3.8}, 

NFPA  70  or  CSA 

grounding,  etc. 

306.5, 

3.26.5, 

C22.1,  as 

306.6, 

3.26, 

applicable 

1004.2(b)  (12), 

8.11.3.1. 2(q), 

1206.1f, 

8.6.1.6.3, 

1206.5a 

C8.6.12.2.6, 
8.6.1.6.1, 
C8.6. 12.3.1.3, 
8.6.5 

2.13 

Governor,  overspeed  switch, 

205, 

2.17, 

4.9.7 

and  seal 

206, 

301.8, 

1002.2(b), 

1005.2c, 

1005.4, 

1202.7, 

1206.1 

2.18, 

3.17.1, 

8.11.2.2.2, 

8.11.3.2.3, 

8.11.3.4, 

8.7.2.19, 

8.6.1.2 

2.14 

Code  data  plate 

309, 
1200.6 

8.9, 
8.7.1.8 

2.17 

Drive  machine  brake 

301.10 

3.16 

4.2.4 

2.30 

Hydraulic  power  unit 

304, 

3.24, 

NFPA  70  or  CSA 

1004.2(b)(l3), 

8.11.3.1. 2(m), 

C22.1,  as 

1206.5 

8.6.5 

applicable 

2.31 

Relief  valves 

308, 

303.1, 

303.2, 

303.4b, 

1004.2(b)(13), 

1005.2a, 

1006.2b, 

Definitions 

3.28, 
3.19.1, 
3.19.2, 
3.19.4.2, 
8.11.3.1. 2(m), 
8.11.3.2.1, 
8.10.3. 2. 2(m), 
1.3  (Definitions) 

4,4.1 

2.32 

Control  valve 

303, 
1004.2(b)(15) 

3.19, 
8.11.3.1.2(0) 

4.4 

176 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


Checklist  for  Hydraulic  Elevators  (Cont'd) 


Item 

Check 

A17.1-1996 
Section/Rule 

A17.1-2000/ 

B44-00 
Requirements 

A17.3 
Section/Para. 

Comments 

2 

ELEVATOR  -  MACHINE  ROOM  (Cont'd) 

2.33 

Tanks 

304, 

1004.2(b)(16), 

1005.3b, 

1203.6, 

1206.5b 

3.24, 

8.11.3.1. 2(p), 

8.11.3.3.2, 

8.7.3.29, 

8.6.5.1, 

8.6.5.2, 

8.6.5.5, 

8.6.5.6 

4.5 

2.34 

Flexible  hydraulic  hose  and  fit- 
ting assemblies 

303.3C, 
1004.2(b)(17), 
1005. 2d 

3.19.3.3, 

8.11.3.1.2(q), 

8.11.3.2.4 

2.35 

Supply  line  and  shutoff  valve 

303 

3.19 

4.4.4 

2.36 

Hydraulic  cylinders 

302.3, 

1004.2(b)(19), 

1005.2b 

3.18.3, 

8.11.3.1.2(s), 

8.11.3.2.2 

2.37 

Pressure  switch 

306.14, 
1004.2(b)(20), 
1005. 2e 

3.26.8, 

8.11.3.1.2ft), 

8.11.3.2.5 

2.38 

Roped  water  hydraulic  ele- 
vators 

{NR} 

2.39 

Low  oil  protection 

306.15 

3.26.9 

2.40 

Maintenance  records 

8.6.1.4, 

C8.6.12.2.5, 

8.6.10.1 

2.41 

Static  control 

2.42 

Earthquake  inspection  and 
tests  (seismic  risk  Zone  2 
or  greater) 

2401, 
2400.1, 
2410.1, 
2410.7 

8.4.2, 

8.4.3.1, 

8.4.11.1, 

8.4.11.3, 

8.4.11.6 

3 

ELEVATOR  -  TOP  OF  CAR 

3.1 

Top-of-car  stop  switch 

306.4, 
1004.2(c)(1) 

3.26.1, 
3.26.4, 
8.11.3.1.3(a) 

4.7.4(a) 

3.2 

Car  top  light  and  outlet 

204.7  {301.7}, 
1004.2(c)(2) 

2.14.7  {3.14}, 
8.11.3.1.3(b) 

3.4.5  {4.2.3} 

NFPA70  orCSA 
C22.1,  as  applica- 
ble 

3.3 

Top-of-car  operating  device 

306.2, 
1004.2(c)(3) 

3.26.1, 
3.26.2, 
8.11.3.1.3(c) 

3.10.3, 
4.7.2 

3.4 

Top-of-car  clearance,  refuge 
space,  and  standard 
railing 

300.8, 

302.4, 

1004.2(c)(4), 

1006.2a, 

1006.2c 

3.4, 

2.10.2, 

2.14.1.7  {3.14}, 

3.18.4, 

8.11.3.1.3(d), 

8.10.3.2. 2(s), 

8.10.3.2.3(d) 

2.4.4  {4.1} 

177 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Checklist  for  Hydraulic  Elevators  (Cont'd) 


Item 


Check 


A17.1-1996 
Section/Rule 


A17.1-2000/ 

B44-00 
Requirements 


A17.3 
Section/Para. 


Comments 


3 

ELEVATOR  -  TOP  OF  CAR  (Cc 

nt'd) 

3.5 

Normal  terminal  stopping 
devices 

305.1a, 

1002. 2e  (1005.2c), 

1003.3(10, 

1004.2(c)(5) 

3.25.1.1, 
8,11.2.2.5 

(8.11.3.2.3), 
8.10.2.3.2(k)( 
8.11.3.1.3(e) 

3.9.1  (4.6), 
3.10.4 

3.6 

Final  and  emergency  terminal 
stopping  devices 

305.2, 

1004.2(c)(6), 

1005.2 

3.25.2, 
8.11.3.1.3(f) 

A17.1-1955,  Rule 
320.2 

3.7 

Car  leveling  and  anticreep 
devices 

306.3, 
306.4, 
1004.2(c)(7) 

3.26.3, 
3.26.4, 
8.11.3.1.3(g) 

4.7.3, 
4.7.4 

3.8 

Top  emergency  exit 

204.1e  (301.7), 
1004.2(c)(9) 

2.14.1.5  (3.14), 
8.11.3.1.3(0 

3.4.4  (4.2.3) 

3.9 

Floor  and  emergency  identifica- 
tion numbering 

100.7  (300.1), 
211.9(306.11), 
1004.2(c)  (10) 

2.29.2  (3.1), 
2.29.1  (3.27), 
8.11.3.1.3(j) 

3.10 

Hoistway  construction 

300.1, 
1004.2(c)  (11) 

3.1, 
8.11.3.1.3(k) 

2.1  (4.1) 

3.11 

Hoistway  smoke  control 

100.4  (300.1), 
1004.2(c)(12) 

2.1.4  (3.1), 
8.11.3.1.3(1) 

3.12 

Pipes,  wiring,  and  ducts 

102  (300.3), 
1004.2(c)(l3) 

2.8  (3.8), 
8. 11.3.1. 3(m) 

2.1.4  (4.1) 

3.13 

Windows,  projections, 
recesses,  and  setbacks 

100.5  (300.1), 

100.6  (300.1), 
110.10  (300.11), 
1004.2(c)(14) 

2.1.5, 
2.1.6  (3.1), 
2.11.10  (3.11), 
8.11.3.1. 3(n) 

2.1.2  (4.1), 

2.1.3  (4.1) 

3.14 

Hoistway  clearances 

108  (300.9), 
110  (300.11), 
1004.2(0(15) 

2.5  (3.5), 
2.11  (3.11), 
8.11.3.1.3(o) 

2.4  (4.1) 

3.15 

Multiple  hoistways 

lOO.ld  (300.1), 
1004.2(0(16) 

2.1.1.4  (3.1), 
8.11.3.1.3  (p) 

3.16 

Traveling  cables  and  junction 
boxes 

102.1  (300.3), 
1004.2(0(17) 

2.8.1  (3.8), 
8.11.3.1.3(q) 

NFPA70  orCSA 
C22.1,  as 
applicable 

3.17 

Door  and  gate  equipment 

110  (300.11), 

111  (300.12), 
210.1e  (306.3), 
1004.2(0(18) 

2.11  (3.11), 

2.12  (3.12), 
2.26.1.6(3.26.3), 
8.11.3.1. 3(r) 

2.6  (4.1), 

2.7  (4.1) 

A17.1  Inquiry  96-71 

3.18 

Car  frame  and  stiles 

213  (302.5), 

301.6, 

1004.2(0(19) 

8.8  (3,18.5), 
3.15, 
8.11.3. 1.3(s) 

3.19 

Guide  rails  fastenings  and 
equipment 

200  (301.1b), 

308, 

301.1, 

301.6, 

1004.2(0(20) 

2.23  (3.23.2), 

3.38, 

3.23, 

3.15.1.1.2, 

8.11.3.1.3(0 

4.9.8 

178 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Checklist  for  Hydraulic  Elevators  (Cont'd) 


Item 


Check 


A17.1-1996 
Section/Rule 


A17.1-2000/ 

B44-00 
Requirements 


A17.3 
Section/Para. 


Comments 


3 

ELEVATOR  -  TOP  OF  CAR  (Cc 

mt*d) 

3.20 

Governor  rope 

206.5, 

2.18.5, 

3.6, 

301.8, 

3.17.1, 

4.9.7 

1001.2(c), 

8.11.2. 1.3(z), 

1004.2(c)(23), 

8.11.3.1.3(w), 

1202.7, 

8.7.2.19, 

1206.1c 

8.6.4.2 

3.21 

Governor  releasing  carrier 

205.15, 
301.8, 

1004.2(c)(22), 
1005.4 

2.17.15, 
3.17.1, 
8.11.3.1.3(v), 
8.11.3.4 

3.22 

Wire  rope  fastening  and  hitch 

212, 

2.20, 

4.9.10 

plate 

105.3c, 

203.13, 

302.1b, 

1004.2(c)(24), 

1200.5 

2.9.3.3, 

2.15.13, 

3.18.1.2, 

8.11.3.1.3(x), 

8.6.3, 

C8.6.12.4.1.1, 

C8.6.12.4.3, 

C8.6.12.4.4, 

C8.6.12.4.5 

3.23 

Suspension  rope 

212, 

2.20, 

4.8, 

1307, 

8.2.7, 

4.9.10 

1001.2(c)(29), 

8.11.2. 1.3(cc), 

1004.2(c)(25), 

8,11.3.1.3(y), 

1200.4d, 

8.6.2.5, 

1202.14, 

8.7.2.21, 

1203.9 

8.7.3.25 

3.27 

Crosshead  data  plate  and  rope 

207.3, 

3.16, 

3.12.2 

data  tags 

212.2, 

1001.2(c)(ll), 

1202.14 

2.20.2, 

8.11.2.1.3(k), 

8.7.2.21 

3.28 

Counterweight  and 

300.8f, 

3.3, 

4.9.2, 

counterweight  buffer 

301.4, 
301.9, 
1308 

3.4.6, 
3.22.3, 
8.11.3.2.3(d), 
c8.11.2.3.3(d) 

4.9.6 

3.29 

Counterweight  safeties 

301.9, 

300.10, 

1006.2, 

1005.2(c), 

1005.4 

3.17.2, 

3.6, 

8.10.3.2, 

8.11.3.2.3, 

8.11.3.4 

3.30 

Speed  test 

205.16, 

300.8, 

301, 

1004.2(c)(8), 

1006.2g, 

Definitions 

2.17.16, 
3.4, 

8.11.3.1.3(h), 
8.10.3.2.3(cc), 
1.3  (Definitions) 

4.9 

3.31 

Slack  rope  device  —  roped- 

302.1b, 

3.18.1.2, 

4.9.9 

hydraulic  elevators  installed 

306.4, 

3.26.4, 

under  A17.1b-1989  and 

1004.2(c)(26), 

8.11.3.1.3(z), 

later  editions 

1005.2f, 

(NR  8.6.5.14.7) 

8.6.5.14.7 

179 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Checklist  for  Hydraulic  Elevators  (Cont'd) 


Item 


Check 


A17.1-1996 
Section/Rule 


A17.1-2000/ 

B44-00 
Requirements 


A17.3 
Section/Para. 


Comments 


3 

ELEVATOR  -  TOP  OF  CAR  (Cont'd) 

3.32 

Traveling  sheave  —  roped- 

212, 

2.20, 

4.9.8 

hydraulic  elevators  installed 

208.2, 

2.24.2, 

under  A17.1b-1989  and 

208.3, 

2.24.3, 

later  editions 

208.5, 

301.1b, 

302.1b, 

307, 

1004.2(c)  (27), 

1203.9 

2.24.5, 

3.23.2, 

3.18.1,2, 

8.11.3.1.3(aa), 

8.7.3.25 

3.34 

Earthquake  inspection  and 

2402, 

8.4.1, 

tests  (seismic  risk  Zone  2 

2401, 

8.4.2, 

or  greater) 

2400.1(a), 

2400.1(b), 

2400.1(d), 

2400.2, 

2405, 

2404, 

2403 

8.4.3.1.1, 

8.4.3.1.2, 

8.4.3.1.4, 

8.4.3.2, 

8.4.5, 

8.4.7, 

8.4.8 

ELEVATOR  -  OUTSIDE  HOISTWAY 


4.1 


Car  platform  guard 


301.6, 
1004.2(d)(1) 


3.15, 
8.11.3.1.4(a) 


3.3-2  {4.2.2} 


4.2 


Hoistway  doors 


110  {300.11}, 
111.2b  {300,12}, 
111.3b  {300.12}, 
306.4, 

1004.2(d)(2), 
1006.2h 


2.11  {3.11}, 
2.12.2.2  {3.12}, 
2.12.3.2  {3.12}, 
3.26.4, 
8.11.3.1.4(b), 
8.10.3.2.3(r) 


4.7.4 


4.3 


Vision  panels 


110.7  {300.11}, 
1004.2(d)(3) 


2.11.7  {3.11}, 
8.11.3.1.4(c) 


2,6.3  {4.1} 


4.4 
4.5 


Hoistway  door  locking  devices 


111  {300.12}, 
1004.2(d)(4) 


2.12  {3.12}, 
8.11.3.1.4(d) 


2.7.1  {4.1} 


Access  to  hoistway 


111.6  {300.12}, 

111.7  {300.12}, 
1004.2(d)(5) 


2.12.6, 

2.12.7  {3.12}, 
8.11.3.1.4(e) 


2.7.3  {4.1} 


4.6 


Power  closing  of  hoistway 
doors 


112.3-112.6  {300.13}: 
1004.2(d)(6) 


2.13.3-2.13.6 

{3.13}, 
8.11.3.1.4(f) 


2.8  {4.1} 


4.7 


Sequence  operation 


112.6  {300.13}, 
112.3d  {300.13}, 
1004.2(d)(7) 


2.13.6  {3.13}, 
2.13.3.4  {3.13}, 
8.11.3.1.4(g) 


4.8 


Hoistway  enclosure 


100.1  {300.1}, 

100.4  {300.1}, 

100.5  {300.1}, 
1004.2(d)(8) 


2.1.1, 
2.1.4, 
2.1.5  {3.1}, 
8.11.3.1.4(h) 


2.1.1  {4.1}, 

2.1.2  {4.1} 


4.9 
4.10 


Elevator  parking  device 


1004.2(d)(9) 


8.11.3.1.4(0 


2.7.2  {4.1} 


Emergency  doors  in  blind 
hoistways 


110.1, 
1004.2 


2.11.1.1, 
2.11.1.2, 
8.1 


180 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Checklist  for  Hydraulic  Elevators  (Cont'd) 


Item 


Check 


A17.1-1996 
Section/Rule 


A17.1-2000/ 

B44-00 
Requirements 


A17.3 
Section/Para. 


Comments 


4 

ELEVATOR  -  OUTSIDE  HOISTWAY  (Cont'd) 

4.12 

Standby  power  selection 

207.8  {301.10}, 

2.16.8  {3.16}, 

3.11.2  {4.7.8} 

switch 

211.2  {306.11}, 
211.8  {306.11}, 
1002. 2g, 
1004.2(d)(ll), 
1005.2c 

2.27.2  {3.27}, 
2.27.8  {3.27}, 
8.11.2.2.7, 
8.11.3.1.400, 
8.11.3.2.3 

5 

ELEVATOR  -  PIT 

5.1 

Pit  access,  lighting,  stop 

102  {300.3}, 

2.8  {3.8}, 

2.3.1  {4.1}, 

NFPA  70  or  CSA 

switch,  and  condition 

106.1  [300.7}, 

3.6, 

2.3.2  {4.1}, 

C22.1,  as 

300.10, 

3.26.4, 

2.7.3  {4.1}, 

applicable 

306.4, 

8.11.3.1.5(a), 

3.10.4 

1004.2(e)(1), 

8.6.4.7 

1206.2a 

5.2 

Bottom  clearance,  runby,  and 

300.8, 

3.4, 

2.1.5 

minimum  refuge  space 

302.3c, 

1004.2(e)(2), 

1006.2e 

3.18.3.3, 

8.11.3.1.5(b), 

8.10.3.2.5(c) 

5.4 

Normal  terminal  stopping 

305.1, 

3.25.1, 

3.9.1  {4.6} 

devices 

1002. 2e  {1005.2c}, 
1004.2(e)(5) 

8.11.2.2.5 

{8.11.3.2.3}, 
8.11.3.1.5(e) 

5.5 

Traveling  cables 

102.2  {300.3}, 

2.8.2  {3.8}, 

NFPA  70  or  CSA 

1004.2(e)(6) 

8.11.3.1.5(0 

C22.1,  as 
applicable 

5.6 

Governor  rope  tension  device 

206.7, 
301.8, 

1004.2(e)(ll), 
1206.1a 

2.18.7, 
3.17.1, 
8.11.3.1.5(k), 
8.6.1.6.2 

4.9.7 

5.7 

Car  frame  and  platform 

308, 
301.6, 
302.2c, 
1004.2(e)(7) 

3.28, 
3.15, 
3.18.2.3, 
8.11.3.1.5(g) 

3.3  {4.2.2} 

5.8 

Car  and  counterweight  safeties 

205, 

2.17, 

4.9.6, 

and  guiding  members  — 

1306, 

8.2.6, 

4.9.8 

including  roped-hydraulic 

301.8, 

3.17.1, 

elevators  installed  under 

301.9, 

3.17.2, 

A17.1b-1989  and  later 

1004.2(e)(10), 

8.11. 3.1. 5Q), 

editions 

1005.2c, 
1005.4 

8.11.3.2.3, 
8.11.3.4 

5.11 

Plunger  and  cylinder 

302, 

3.18, 

4.3.1, 

1004.2(e)(3), 

8.11.3.1.5(c), 

4.3.2 

1206.5b 

8.6.5.1, 
8.6.5.2, 
8.6.5.5, 
8.6.5.6 

5.12 

Car  buffer 

301.3, 

306.4, 

1004.2(e)(4), 

1206.1e, 

1308.2 

3.22.1, 

3.26.4, 

8.11.3.1.5(d), 

8.6.4,4, 

8.2.3.2 

4.2.1 

181 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Checklist  for  Hydraulic  Elevators  (Cont'd) 


Item 


Check 


A17.1-1996 
Section/Rule 


A17.1-2000/ 

B44-00 
Requirements 


A17.3 
Section/Para. 


Comments 


ELEVATOR  -  PIT  (Cont'd) 


5.13 


Guiding  members 


308, 
301.1, 

1004.2(e)(8), 
1206.1d 


3.28, 
3.23, 

8.11.3.1.5(h), 
8.6.4.3 


5.14 


Supply  piping 


208, 

1004.2(e)(9), 

1006.2f 


2.24, 

8.11.3.1.5(0, 
8.10.3.2. 2(r) 


4.4.4 


5.15 


Overspeed  valve 


303.3c(l)(d), 
2410.6, 

(NR  3.19.4.7.2), 
(NR  3.19.4.7.3), 
[NR  3.19.4.7.5(a)], 
(NR  3.19.4.7.6), 
[NR  8.10.3.2.5(0], 
(NR  8,11.3.4.4) 


3.19.3.3, 

8.4.11.2, 

3.19.4.7.2, 

3.19.4.7.3, 

3.19.4.7.5(a), 

3.19.4.7.6, 

8.10.3.2.5(0, 

8.11.3.4.4 


5.16 


Earthquake  inspection  and 
tests  (seismic  risk  Zone  2 
or  greater) 


2400, 

2410.6, 

2410.5, 

2410.2, 

2410.3 


8.4.3, 

8.4.11.2, 

8.4.11.3, 

8.4.11.5, 

8.4.11.7 


6 

ELEVATOR  -  FIREFIGHTERS'  SERVICE 

6.1 

Operation  of  elevators  under 

112.3d  {306.11}, 

2.13.3.4, 

A17.1D-1973  through 

fire  and  other  emergency 

112.5  {306.11}, 

2.13.5  {3.27}, 

A17.1D-1980,  Rule 

conditions  (A17.1b-1973 

1001.2(d)(12), 

8.11.2.1.4(1), 

211.3 

through  A17.1b-1980) 

1002. 2f, 

1004.2(d)(12), 

1206.7 

8.11.2.2.6, 
8.6.10.1 

6.2 

Operation  of  elevators  under 

112.3d, 

2.13.3.4, 

A17.1-1981  through 

fire  and  other  emergency 

112.5, 

2.13.5, 

A17.1D-1983,  Rule 

conditions  (A17. 1-1981 

1001.2(d)(12), 

8.11.2.1.4(1), 

211.3 

through  A17.1D-1983) 

1002. 2f, 
1206,7 

8.11.2.2.6, 
8.6.10.1 

6.3 

Firefighters'  service  (A17.1- 

112.3d, 

2.13.3.4, 

3.11.3 

A17.1-1984  through 

1984  through  A17.1a-1988 

112.5, 

2.13.5, 

A17.1a-1988,  Rules 

and  A17.3) 

1001.2(d)(12), 
1002. 2f, 
1206.7 

8.11.2.1.4(1), 

8.11.2.2.6, 

8.6.10.1 

211.3-211.8 

6.4 

Firefighters*  service  (A17.1b- 

112.3d, 

2.13.3.4, 

1989  through  A17.1d-2000) 

112.5, 

211.2-211.8  {306.11}, 

1001.2(d)(12), 

1002. 2f, 

1206.7 

2.13.5, 
2.27.2-2.27.8 

{3.27}, 
8.11.2.1.4(1), 
8.11.2.2.6, 
8.6.10.1 

6.5 

Acceptance  checklist  for  fire- 
fighters' service  (A17. 1-2000 
and  B44-00):  automatic 
elevators 

182 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


Checklist  for  Escalators 


Item 


Check 


A17.1-1996 
Section/Rule 


A17.1-2000/ 

B44-00 
Requirements 


A17.3 
Section/Para. 


Comments 


7 

ESCALATOR  -  EXTERNAL 

7.1 

General  fire  protection 

800, 
801, 
1009.2a 

6.1.1, 
6.1.2, 
8.10.4.1.1(a) 

7.2 

Geometry 

802.1, 

802.2, 

802.3d, 

1009.2b, 

1009.2g, 

1207.5, 

Appendix  D 

6.1.3.1, 

6.1.3.2, 

6.1.3.3.4, 

8.10.4.1.1(b), 

8.10.4.1.  l(n), 

8.7.6.1.5 

7.3 

Handrails 

802.2, 

6.1.3.2, 

5.1.5, 

802.4, 

6.1.3.4, 

5.1.6 

1009.2c, 

8.11.4,2.13, 

Appendix  D 

8.6.8.12, 
8.10.4.1.1(c) 

7.4 

Entrance  and  egress  ends 

802.6, 

6.1.3.6, 

5.5.3, 

802.12 

8.6.8.15, 
6.1.3.12 

5.5.4 

7.5 

Lighting 

806.2, 

6.1.7.2, 

2.2.3, 

805.7, 

6.1.6.7, 

5.4 

1009.2d 

8.10.4.1.1(e) 

7.6 

Caution  signs 

805.9, 
Fig.  805.9a 

6.1.6.9, 
Fig.  6.1.6.9.1 

5.3.11 

7.7 

Combplate  and  comb  step 

802.6, 

6.1.3.6, 

5.1.9 

impact  device 

805. 3n, 

807.3, 

1206.6, 

(NR  8.6.9.2.3), 

1008.2r, 

1009.2e 

6.1.6.3.13, 

6.1.8.3, 

8.6.8, 

8.6.9.2.3, 

8.11.4.2.13, 

8.10.4.1.1(g) 

7.8 

Deck  barricades  and  antislide 

802. 3i, 

6.1.3.3.10, 

devices 

1009.2f 

6.1.3.3.11, 

8.6.8.11, 

8.10.4.1.1(h) 

7.9 

Steps  and  upthrust  device 

Definitions, 

1.3, 

5.1.7, 

802.5, 

6.1.3.5, 

5.1.8 

802.6e, 

6.1.3.6.5, 

802. 9d, 

6.1.3.9.4, 

805. 3i, 

6.1.6.3.9, 

1008.21, 

8.11.4.2.9, 

1105.1 

8.6.8.6, 
8.3.11.1, 
Fig.  18 

7.10 

Operating  and  safety  devices 

805.2, 

6.1.6.2.1, 

5.3.1, 

805.3a, 

6.1.6.3.1, 

5.3.2, 

805.6, 

c6.1.6.3.l(a), 

5.3.10 

(NR  8.6.10.5) 

6.1.6.6, 

8.6.10.2, 

8.6.10.5 

7.11 

Skirt  obstruction  device 

805.3f 

6.1.6.3.6 

5.3.7 

7.12 

Reserved 

7.13 

Egress  restriction  (rolling 
shutter)  device 

805.3g 

6.1.6.3.7 

5.3.8 

183 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Checklist  for  Escalators  (Cont'd) 


Item 


Check 


A17.1-1996 
Section/Rule 


A17.1-200O/ 

B44-00 
Requirements 


A17.3 
Section/Para. 


Comments 


7 

ESCALATOR  -  EXTERNAL  (Co 

nt'd) 

7.14 

Speed 

803.1, 
805.3b, 
1008.20, 
1009.20 

6.1.4.1, 

6.1.6.3.2, 

8.10.4.1.2(1) 

7.15 

Balustrades 

802.3, 
1009. 2g, 
Appendix  D 

6.1.3.3, 

6.1.3.14, 

8.10.4.1.1(n) 

5.1.1 

7.16 

Ceiling  intersection  guards 

802. 3g, 
Appendix  D 

6.1.3.3.9 

5.1.3 

7,17 

Step/skirt  clearances,  panels, 
and  performance  index 

802.3e, 

802.3f, 

802.3k, 

1008.2s, 

1008.2t, 

1206.6b, 

1206.6c 

6.1.3.3.5, 
6.1.3.3.6, 
8.6.8.4 

7.18 

Outdoor  protection 

807, 

1008.2p, 

1009.2i 

6.1.8, 

8.11.4.2.14, 
8.10.4.1. l(q) 

7.19 

Maintenance  records 

8.6.1.4, 

C8.6.12.2.5, 

8.6.10.5 

7.20 

Earthquake  inspection  and 
tests  (seismic  risk  Zone  2 
or  greater) 

8.5.1, 
8.5.4 

8 

ESCALATOR  -  INTERNAL 

8.1 

Machinery  space  access,  light- 

806, 

6.1.7, 

5.5.5 

ing,  receptacle,  and  con- 

801.1, 

6.1.2.1, 

dition 

805.7, 
1008.2a, 
1009.2], 
1206.6a 

6.1.6.7, 

6.1.3.14, 

8.11.4.2.1, 

8.10.4.1.2(a), 

8.1, 

8.6.1.6.3, 

C8.6.12.2.6, 

8.6.8.14, 

8.6.8.15, 

8.6.8.13 

8.2 

Machine  space  stop  switches 

210.2, 

2.26.2, 

and  inspection  control 

805. 3e, 

(NR  6.1.6.2.2), 

1008.2b, 

1009.2k 

6.1.6.3.5, 
6.1.6.2.2, 
8.11.4.2.2, 
8.10.4.1.2(b) 

8.3 

Controller  and  wiring 

806, 

807.2, 

805.10b, 

805.12, 

1101, 

1206.1, 

1008.2C, 

1009.21, 

1009.2, 

(NR  10.3.3) 

6.1.7, 

6.1.8.2, 

6.1.6.10, 

6.1.6.13, 

8.3.3, 

8.6.1.2.1, 

8.11.4.2.3, 

8.10.4.1.2(c), 

10.3.3 

184 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


D 


ASMEA17.2-2010 


Checklist  for  Escalators  (Cont'd) 


Item 


Check 


A17.1-1996 
Section/Rule 


A17.1-2000/ 

B44-00 
Requirements 


A17.3 
Section/Para. 


Comments 


8 

ESCALATOR  -  INTERNAL  (Coi 

it'd) 

8.4 

Drive  machine  and  brake 

804, 
1008.2d 

6.1.5, 
8.11.4.2.4 

5.2 

8.5 

Speed  governor 

805.3b, 

6.1.6.3.2, 

5.3.3, 

1008. 2e, 

8.11.4.2.5, 

5.3.5 

1009.2m 

8.10.4.1.2(e) 

8.6 

Broken  drive  chain  and  discon- 

804.3b, 

6.1.5.3.2, 

5.3.5, 

nected  motor  safety  device 

805.3d, 
805.3J, 
1008.2f 

6.1.6.3.4, 

6.1.6,3.10, 

8.11.4.2.6 

5.3.6 

8.7 

Reversal  stop  switch 

805. 3h, 

6.1.6.3.8, 

5.3.5, 

1008.2g 

8.10.4.1.2(g), 
8.11.4.2.7 

5.3.9 

8.8 

Broken  step  chain  device 

805.3c, 

6.1.6.3.3, 

5.3.4, 

1008.2h 

8.11.4.2.8 

5.3.5 

8.9 

Step  upthrust  device 

805.3i, 
1008.2! 

6.1.6.3.9, 
8.11.4.2.9 

5.1.7 

8.10 

Missing  step  device 

805.5, 
1008.2J 

6.1.6.5, 
8.11.4.2.10 

8.11 

Step  level  device 

805.3k, 

1008.2k, 

1009.2n 

6.1.6.3.11, 
8.11.4.2.11, 
8.10.4.1. 2(k) 

8.12 

Steps,  step  chains,  and 

801.1, 

6.1.2.1, 

trusses 

802.7, 

802.8, 

802.11, 

806.3, 

1008.21, 

1009.20, 

1206.6 

6.1.3.5.8, 

6.1.3.7, 

6.1.3.8, 

6.1.3.11, 

6.1.3.1.4, 

6.1.7.3, 

8.11.4.2.12, 

8.10.4.1.2(1), 

8.6.8 

8.13 

Handrail  systems  and  safety 

802.4, 

6.1.3.4, 

devices 

802.11, 

805.4, 

805.3m, 

(NR  8.6.8.1), 

1008.2m, 

1008.2q, 

1009.2c 

6.1.3.11, 

6.1.6.4, 

6.1,6.3.12, 

8.6.8.1, 

8.11.4.2.13, 

8.11.4.2.18, 

8.10.4.1.1(c) 

8.14 

Code  data  plate 

808, 
908, 
1200.6 

8.9, 
8.7.1.8 

8.15 

Response  to  smoke  detectors 

805.8 

6.1.6.8 

8.16 

Step  lateral  displacement 

805. 3p, 

6.1.6.3.14, 

device 

1003.2b(20) 

8.11.4.2.21, 
8.10.4.1.2(r) 

8.17 

Inspection  control 

6.1.6.2.2 

8.18 

Earthquake  inspection  and 
tests  (seismic  risk  Zone  2 
or  greater) 

8.5.2, 
8.5.3 

185 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Checklist  for  Moving  Walks 


Item 


Check 


A17.1-1996 
Section/Rule 


A17.1-2000/ 

B44-00 
Requirements 


A17.3 
Section/Para. 


Comments 


9 

MOVING  WALK  -  EXTERNAL 

9.1 

General  fire  protection 

900, 

6.2.1, 

9.1.1, 

901, 

6.2.2, 

9.2.2 

1009.2a 

8.10.4.1.1(a) 

9.2 

Geometry 

902.1, 

6.2.3.1, 

9.3.1, 

902.2, 

6.2.3.2, 

9.3.2, 

902.3d, 

6.2.3.3.4, 

9.3.3, 

(NR  8.6.8.12), 

8.6.8.12, 

9.3.6 

1009.2b, 

8.10.4.1.1(b), 

1009. 2g, 

8.10.4.1.1(n), 

1208.5, 

8.7.6.2.5 

Appendix  D 

9.3 

Handrails 

902.2, 
902.4, 
1008.2m, 
1009.2c, 
Appendix  D 

6.2.3.2, 
6.2.3.4, 
8.11.4.2.13, 
8.10.4.1.1(c) 

9.3.4 

9.4 

Entrance  and  egress  ends 

902.8, 
907.3, 
902.16 

6.2.3.8, 

C6.2.3.8.5, 

6.2.8.3, 

6.2.3.16, 

8.6.8.15 

9.4.3 

9.5 

Lighting 

906.2, 
1009.2d 

6.2.7.2, 
8.10.4.1.1(e) 

9.7.1 

9.6 

Caution  signs 

905.8, 
Fig.  805.9a 

6.2.6.8, 

Fig.  6.1.6.9.1 

9.6.11 

9.7 

Combplate  and  comb  step 

902.8, 

6.2.3.8, 

9.4 

impact  device 

905.3k, 
907.3, 
1206.6, 
1008. 2r, 
1009. 2e 

6.2.6.3.11, 

6.2.8.3, 

8.6.8, 

8.11.4.2.13 

8.10.4.1.1(g) 

9.8 

Deck  barricades 

902. 3h, 
1009. 2f 

6.2.3.3.8, 
8.10.4.1.1(h) 

9.3.3.6 

9.9 

Treadways 

902.5, 

902.6, 

902.9, 

902.11, 

1105.1 

6.2.3.5, 

6.2.3.6, 

6.2.3.9, 

6.2.3.11, 

8.6.8.6, 

8.3.11.1 

9.3.5 

9.10 

Operating  and  safety  devices 

905.1, 

6.2.6.1, 

9.6.2, 

905.2, 

6.2.6.2.1, 

9.6.3, 

905.3a, 

6.2.6.3.1, 

9.6.9 

905.6, 

C6.2.6.3.1(a), 

(NR  8.6.10.5) 

6.2.6.6, 

8.6.10.2, 

8.6.10.5 

9.11 

Reserved 

9.12 

Reserved 

9.13 

Egress  restriction  (roiling 
shutter)  device 

905.3f 

6.2.6.3.6 

9.6.7 

186 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Checklist  for  Moving  Walks  (Cont'd) 


Item 


Check 


A17.1-1996 
Section/Rule 


A17.1-2000/ 

B44-00 
Requirements 


A17.3 
Section/Para. 


Comments 


9 

MOVING  WALK  -  EXTERNAL  (Cont'd) 

9.14 

Speed 

903.1, 
905.3b, 
1008.20, 
1009.20 

6.2.4, 

6.2.6.3.2, 

8.10.4.1.2(1) 

9.15 

Balustrades 

902.3, 
1009.2g, 
Appendix  D 

6.2.3.3, 
6.2.3.17, 
8.10.4.  l(n) 

9.3.3.1, 
9.3.3.2 

9.16 

Ceiling  intersection  guards 

902.3g, 
Appendix  D 

6.2.3.3.7 

9.3.3.5 

9.17 

Skirt  panels 

902. 3e, 
902.3f 

6.2.3.3.5, 
6.2.3.3.6 

9.3.3.3, 
9.3.3.4 

9.18 

Outdoor  protection 

907, 

1008.2p, 

1009.2i 

6.2.8, 

8.11.4.2.14, 

8.10.4.1.1(q) 

9.19 

Maintenance  records 

8.6.1.4, 

C8.6.12.2.5, 

8.6.10.5 

9.20 

Earthquake  inspection  and 
tests  (seismic  risk  Zone  2 
or  greater) 

8.5.1, 
8.5.4 

10 

MOVING  WALK  -  INTERNAL 

10.1 

Machinery  space  access, 
lighting,  receptacle, 
and  condition 

906, 

901.1, 

907.2, 

1008.2a, 

1009.2] 

6.2.7, 

6.2.2.1, 

6.2.8.2, 

8.1, 

8.6.1.6.3, 

C8.6.12.2.6, 

8.6.14, 

8.6.8.15, 

8.11.4.2.1, 

8.10.4.1.2(a) 

9.7.2 

10.2 

Stop  switch  and  inspection 
control 

905.3e, 

(NR  6.2.6.2.2), 

1008.2b, 

1009.2k 

6.2.6.3.5, 
6.2.6.2.2, 
8.11.4.2.2, 
8.10.4.1.2(b) 

10.3 

Controller  and  wiring 

906, 
907.2, 

6.2.7, 
6.2.8.2, 

NFPA  70  orCSA 
C22.1,  as 

905.31, 

(NR  6.2.6.12), 
1206.1, 

6.2.6.9, 

6.2.6.12, 

8.6.1.2.1, 

applicable 

1008.2c, 
1009.21 

8.11.4.2.3, 
8.10.4.1.2(c) 

10.4 

Drive  machine  and  brake 

904, 
1008.2d 

6.2.5, 
8.11.4.2.4 

9.5.1 

10.5 

Speed  governor 

905.3b, 

1008.2e, 

1009.21 

6.2.6.3.2, 

8.11.4.2.5, 

8.10.4.1.2(c) 

9.6.4 

10.6 

Broken  drive  chain  and  discon- 

904.3b, 

6.2.5.3.2, 

9.6.6, 

nected  motor  safety  device 

905.3d, 
905.3h, 
1008.2f 

6.2.6.3.4, 
6.2.6.3.8, 
8.11.4.2.6 

9.6.10 

187 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


Checklist  for  Moving  Walks  (Cont'd) 


Item 


Check 


A17.1-1996 
Section/Rule 


A17.1-2000/ 

B44-00 
Requirements 


A17.3 
Section/Para. 


Comments 


10 

MOVING  WALK  -  INTERNAL  (Cont'd) 

10.7 

Reversal  stop  switch 

905.3g, 
1008.2g 

6.2,6.3.7, 
8.11,4.2.7 

9.6.8 

10.8 

Broken  treadway  device 

905.3c, 
1008. 2h 

6.2.6.3.3, 
8.11.4.2.8 

10.9 

Reserved 

10.10 

Missing  pallet  device 

905.5, 
1008.2] 

6.2.6.5, 
8.11.4.2.10 

10.11 

Pallet  level  device 

905.3i, 
1008.2k, 
1009. 2n 

6.2.6.3.9, 
8.11.4.2.11, 
8.10.4.1. 2(k) 

10.12 

Pallets,  pallet  chains,  and 

901.1, 

6.2.2.1, 

trusses 

902.9, 
902.13, 
1008.21, 
1009. 2o, 
1206.6 

6.2.3.9, 

6.2.3.13, 

6.2.3.17, 

8.11.4.2.12, 

8.10.4.1.2(1), 

8.6.8 

10.13 

Handrail  systems  and  safety 

902.4, 

6.2.3.4, 

devices 

902.13, 

905.1, 

905.4, 

905.3J, 

(NR  8.6.9.1), 

1008.2m, 

1008. 2q, 

1009.2c 

6.2.3.13, 

6.2.6.1, 

6.2.6.4, 

6.2.6.3.10, 

8.6.9.1, 

8.11.4.2.13, 

8.11.4.2.18, 

8.10.4.1.1(c) 

10.14 

Code  data  plate 

808, 
908, 
1200.6 

8.9, 
8.7.1.8 

10.15 

Response  to  smoke  detectors 

905.7 

6.2.6.7 

10.16 

Inspection  control 

6.2.6.2.2 

10.17 

Earthquake  inspection  and 
tests  (seismic  risk  Zone  2 
or  greater) 

8.5.2, 
8.5.3 

188 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


NONMANDATORY  APPENDIX  B 
ACCEPTANCE  CHECKLIST 


(10) 


Acceptance  Checklist  for  Firefighters'  Service  (A17.1-2000  and  B44-00):  Automatic  Elevators 

GENERAL  NOTE:  Pass  =  meets  requirement;  Fail  =  does  not  meet  requirement;  NA  -  not  applicable. 


ELEVATOR  ID  No. 

ADDRESS:  

INSPECTED  BY:  _ 
SIGNATURE:  


BUILDING. 


DATE:. 

INSPECTOR  I.D.  No.. 


Item 

Check 

A17.1-2000 
and  B44-2000 

Pass 

Fail 

NA 

6.5.1 

Emergency  Signaling  Devices 

2.27.1 

6,5.1.1 

"ALARM"  must  sound  and  illuminate  when  pressed. 
If  rise  is  over  30  m  (100  ft),  second  device  is  required. 

2.27.1.1.1, 
2.27.1.1.1(d)(2) 

6.5.1.2 

In-car  emergency  stop  button  (if  present)  must  sound  alarm. 

2.27.1.1.1 

6.5.1.3 

If  rise  is  more  than  18  m  (60  ft),  check  for  two-way  communication  between  cab  and 
point  outside  hoistway. 

2.27.1.1.2 

6.5.1.4 

Ensure  that  audible  alarms  and  communications  are  functional  with  loss  of  normal 
power. 

2.27.1.1.3 

6.5.1.5 

Check  for  means  to  communicate  with  machine  room  when  required  by  requirement 
2.26.1.5.10(c)  of  A17.1. 

2.27.1.3 

6.5.2 

Phase  1  Key  Switch  and  Instructions 

2.27.3.1, 

2.27.7, 

2.27.8 

6.5.2.1 

Operating  Instructions 

2.27.7.1 

6.5.2.2 

Group  3  Security  Keys 

2.27.8 

6.5.2.3 

Labeled  "FIRE  RECALL"  marked  "RESET,"  "OFF,"  and  "ON"  in  that  order. 

2.27.3.1.1(b), 
2.27.3.1.1(a) 

6.5.2.4 

Provide  at  designated  level  for  group. 

2.27.3.1.1(a) 

6.5.2.5 

Located  in  the  lobby,  visible  and  readily  accessible. 

2.27.3.1.1(c) 

6.5.2.6 

The  key  cannot  be  removed  in  the  "RESET"  position.  But  it  can  be  removed  in  the 
other  positions. 

2.27.3.1.3 

6.5.2.7 

Second  switch,  if  present,  must  be  at  central  alarm  and  control  facility  labeled  "FIRE 
RECALL"  only  be  two-position  switch  marked  "OFF"  and  "ON"  in  that  order. 

2.27.3.1.2 

6.5.3 

Phase  II  In-Car  Switch  and  Instruction 

2.27.8, 
2.27.3.3 

6.5.3.1 

Ensure  that  there  is  a  key  for  each  Phase  1,  each  Phase  II,  and  each  standby  power 
selection  switch  in  the  building. 

2.27.8 

6.5.3.2 

The  same  key  is  used  for  Phase  1  and  Phase  11  and  standby  power  for  all  elevators  in 
the  building. 

2.27.8 

6.5.3.3 

Keys  are  available  only  to  authorized  emergency  and  firefighting  personnel. 

2.27.8 

6.5.3.4 

The  key  can  only  be  removed  in  the  "OFF"  and  "HOLD"  positions. 

2.27.3.3 

6.5.3.5 

The  keys  shall  be  Group  3  Security  (see  A17.1,  requirement  8.1). 

2.27.8 

6.5.3.6 

Labeled  "FIRE  OPERATION,"  marked  "OFF,"  "HOLD,"  and  "ON"  in  that  order. 

2.27.3.3 

189 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Acceptance  Checklist  for  Firefighters'  Service  (Al  7.1-2000  and  B44-00):  Automatic  Elevators  (Cont'd) 

GENERAL  NOTE:  Pass  =  meets  requirement;  Fail  =  does  not  meet  requirement;  NA  =  not  applicable. 


Item 

Check 

A17.1-2000 
and  B44-2000 

Pass 

Fail 

NA 

6.5.4 

Monthly  Test 

8.6.10.1 

6.5.4.1 

Monthly  test  log  is  completed. 

6.5.5 

Phase  1  Operation  While  Running 

Place  several  floor  calls  in  the  car.  While  going  up,  have  the  person  at  the  desig- 
nated level  place  the  Phase  1  switch  in  the  "ON"  position.  Where  a  duplicate  switch 
is  provided,  verify  that  Phase  1  is  initiated  by  placing  the  switch  to  the  "ON"  posi- 
tion. Determine  the  following: 

2.27.3 

6.5.5(a) 

The  car  stops  and  reverses  without  opening  the  doors. 

2.27.3.1.6(b) 

6.5.5(b) 

The  in-car  stop  switch  or  emergency  stop  switch  is  inoperative. 

2.27.3.1.6(c) 

6.5.5(c) 

Call  register  lights  and  directional  lanterns  are  extinguished  and  inoperative. 

2.27.3.1.6(f) 

6.5.5(d) 

Position  indicators  where  provided  are  inoperative,  except  in  car,  designated  level, 
and  central  control  station. 

2.27.3.1.6(f) 

6.5.5(e) 

The  in-car  door  open  button  is  rendered  inoperative  as  soon  as  car  moves  away  from 
the  landing. 

2.27.3.1.6(0 

6.5.5(0 

Car  call  buttons  and  corridor  call  buttons  are  inoperative. 

2.27.3.1.6(f) 

6.5.5(g) 

The  car  returns  to  the  designated  level  and  parks  with  power-operated  doors  open.  If 
there  is  more  than  one  entrance  at  the  designated  landing,  only  the  doors  serving 
the  lobby  with  the  fire  recall  switch  open. 

2.27.3.1.6(a) 

6.5.5(h) 

The  visual  and  audible  signals  operate  and  stay  on  until  car  is  at  the  designated 
level. 

2.27.3.1.6(h) 

6.5.6 

Phase  1  Operation  With  Doors  Open 

Place  the  Phase  1  switch  to  the  "OFF"  position  and  run  the  car  to  any  floor.  With 
the  doors  open,  have  the  Phase  1  switch  turned  to  the  "ON"  position  and  check  the 
following: 

2.27.3.1.6 

6.5.6(a) 

Door  reopening  devices  sensitive  to  smoke  or  flame  are  inoperative  immediately. 

2.27.3.1.6(e) 

6.5.6(b) 

If  door  reopening  devices  are  rendered  inoperative,  the  closing  speed  is  reduced  so 
that  the  kinetic  energy  is  reduced  to  2a/2  ft-lb  (3.5  J). 

2.27.3.1.6(e) 

6.5.6(c) 

The  emergency  stop  switch  or  in-car  stop  switch  is  rendered  inoperative  as  soon  as 
the  car  moves  away  from  the  landing. 

2.27.3.1.6(c) 

6.5.6(d) 

The  in-car  door  open  button  is  rendered  inoperative  as  soon  as  the  car  moves  away 

from  the  landing. 

2.27.3.1.6(0 

6.5.7 

Emergency  Stop  Switch  and/or  In-Car  Stop  Switch  and  Doors  Closing 

Place  the  Phase  1  switch  to  the  "OFF"  position  and  run  the  car  to  any  floor.  Activate 
the  emergency  stop  switch  or  the  in-car  stop  switch.  With  the  doors  open,  have  the 
Phase  1  switch  turned  to  the  "ON"  position.  Return  the  emergency  stop  switch,  or 
in-car  stop  switch  to  the  "RUN"  position. 

2.27.3.1.6 

6.5.7.1 

Verify  that  the  automatic  power-operated  horizontal  sliding  doors  close  promptly,  that 
other  types  of  doors  can  be  closed  and  once  closed  the  car  moves  to  the  desig- 
nated level. 

2.27.3.1.6(d) 

6.5.8 

Stop  Switches  and  Door  Buttons 

While  on  Phase  1  verify  that 

2.27.3.1.6(c), 
2.27.3.1.6(g) 

6.5.8(a) 

Stop  switches  other  than  those  inside  the  car  remain  operative. 

2.27.3.1.6(c) 

6.5.8(b) 

For  vertical  sliding  door,  the  corridor  door  open  and  door  close  buttons  remain  opera- 
tive. 

2.27.3.1.6(g) 

190 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Acceptance  Checklist  for  Firefighters'  Service  (Al  7.1-2000  and  B44-00):  Automatic  Elevators  (Cont'd) 


GENERAL  NOTE:  Pass  =  meets  requirement;  Fall  =  does  not  meet  requirement;  NA  =  not  applicable. 

Item 

Check 

A17.1-2000 
and  B44-2000 

Pass 

Fail 

NA 

6.5.9 

Fire  Alarm  Initiating  Device  and  Operation 

2.27.3 

6.5.9.1 

Verify  that  there  is  a  fire  alarm  initiating  device  in  each  elevator  lobby,  the  elevator 
machine  room,  and  sprinklered  hoistway.  In  jurisdictions  enforcing  the  NBCC,  verify 
that  there  is  a  fire  alarm  initiating  device  in  each  elevator  lobby,  at  the  designated 
level  if  not  sprinklered  throughout  and  in  the  machine  room  if  sprinklered. 

2.27.3.2.1, 
2.27.3.2.2 

6.5.9.2 

With  the  car(s)  on  normal,  have  the  input  for  main  return  activated  and  verify  that  the 
elevator  commences  Phase  1  Operation  and  all  cars  return  to  the  designated  level. 

2.27.3.2.3 

6.5.9.3 

To  reset  operation  initiated  from  fire  alarm  system,  the  fire  alarm  signal  must  be 
reset,  then  the  Phase  1  switch  must  be  cycled  to  "RESET"  momentarily  then  to 
"OFF." 

2.27.3.1.6(k) 

6.5.9.4 

With  the  car(s)  on  normal,  have  the  input  for  alternate  level  return  activated  and  ver- 
ify that  the  elevator  commences  Phase  1  Operation  and  all  cars  return  to  the  alter- 
nate level. 

2.27.3.2.4 

6.5.9.5 

Car(s)  should  only  respond  to  the  first  fire  alarm  input. 

2.27.3.2.5 

6.5.9.6 

Activate  the  machine  room  fire  alarm  initiating  device  input  and  verify  Phase  1  and  all 
cars  return  to  the  designated  level. 

2.27.3.2.3(b) 

6.5.9.7 

Activate  the  designated  level  machine  room  fire  alarm  initiating  device  and  verify 
Phase  1  and  all  cars  return  to  the  alternate  floor. 

2.27.3.2.3(b) 

6.5.9.8 

With  the  car(s)  on  normal,  have  the  input  for  machine  room  return  activated  and  ver- 
ify the  visual  signal  in  the  car  illuminates  intermittently. 

2.27.2.4 

6.5.9.9 

In  jurisdictions  not  enforcing  the  NBCC,  where  the  fire  alarm  initiating  device  is 
required  in  the  hoistway,  activate  the  input  and  verify  all  cars  return  to  the  desig- 
nated landing,  except  that  fire  alarm  initiating  devices  installed  at  or  below  the  low- 
est landing  of  recall  shall  cause  the  cars  to  return  to  the  upper  recall  level. 

2.27.3.2.3(c) 

6.5.10 

Fire  Alarm  Initiating  Device  and  Phase  1  Switch 

6.5.10.1 

Activate  the  alternate  landing  return  input  and  observe  that  the  elevator  returns  to 
the  alternate  landing. 

2.27.3.2.3(b) 

6.5.10.2 

If  a  two-position  key  switch  is  provided,  place  it  in  the  "ON"  position  and  verify  that 
the  elevator  remains  at  the  alternate  landing. 

2.27.3.1.2 

6.5.10.3 

Turn  both  the  Phase  1  switch  and  the  additional  Phase  1  switch  (when  provided)  to 
the  "ON"  position  and  verify  that  the  car  returns  to  the  designated  level. 

2.27.3.1.6(0 

6.5.11 

Phase  II  Key  Switch  and  Sign 
With  Phase  1  activated  and  the  car  at  the  designated  or  alternate  landing,  place  the 
Phase  II  key  switch  in  the  "ON"  position.  Operate  the  car  and  check  the  following: 

2.27.3.3.1 

6.5.11(a) 

The  elevator  can  be  operated  only  from  the  car  buttons  and  will  not  respond  to  corri- 
dor calls. 

2.27.3.3.1(a) 

6.5.11(b) 

All  corridor  call  buttons,  door  open  and  close  buttons,  and  directional  lanterns  are 
inoperative.  All  landing  position  indicators,  except  at  the  designated  landing  and 
central  alarm  and  control  facility,  are  inoperative.  Car  position  indicators  are  opera- 
tive. 

2.27.3.3.1(b) 

6.5.11(c) 

Power-operated  doors  can  only  be  opened  by  continuous  pressure  on  the  door  open 
button  and  if  released  before  the  doors  are  in  the  normal  "OPEN"  position,  the 
door  will  close  without  delay. 

2.27.3.3.1(d) 

6.5.11(d) 

Open  power-operated  doors  can  be  closed  only  by  continuous  pressure  means.  If  the 
means  is  released  before  the  door  is  fully  closed,  horizontal  sliding  doors  will  reopen 
and  vertical  sliding  doors  will  stop,  or  stop  and  reopen. 

2.27.3.3.1(e) 

6.5.11(e) 

If  two  entrances  can  be  opened  and  closed  at  the  same  landing,  separate  door  open 
and  close  buttons  are  provided  for  each  entrance. 

2.27.3.3.1(d) 

6.5.11(f) 

All  door  reopening  devices  are  inoperative  (except  the  door  open  button).  Full-speed 
closing  is  permitted. 

2.27.3.3.1(g) 

191 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
\    No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Acceptance  Checklist  for  Firefighters'  Service  (Al  7.1-2000  and  B44-00):  Automatic  Elevators  (Cont'd) 

GENERAL  NOTE:  Pass  =  meets  requirement;  Fail  =  does  not  meet  requirement;  NA  =  not  applicable. 


Item 

Check 

A17.1-2000 
and  B44-2000 

Pass 

Fail 

NA 

6.5.11(g) 

"CALL  CANCEL"  button  is  labeled  and  when  activated,  will  cancel  all  calls  and  cause 
the  car  to  stop  at  or  before  the  next  available  landing. 

2.27.3.3.1(h) 

6.5.11(h) 

Floor  selection  buttons  are  provided  and  functional  for  all  landings  without  restric- 
tions. 

2.27.3.3.1(0 

6.5.11(0 

Moving  car  will  stop  at  the  next  landing  with  a  car  call  registered  and  remaining  car 
calls  canceled. 

2.27.3.3.1Q) 

6.5.12 

Phase  II  Switch  in  "HOLD"  Position 

2.27.3.3.2 

6.5.12.1 

Place  the  Phase  II  switch  in  the  "HOLD"  position  and  remove  key.  Verify  that  the  car 
remains  at  the  landing  and  the  door  close  button  is  inoperative. 

2.27.3.3.2 

6.5.12,2 

Verify  that  the  car  call  buttons  are  inoperative. 

2.27.3.3.2 

6.5.13 

Phase  II  Switch  in  "OFF"  Position  and  Doors  Closing:  Power-Operated  Horizontally 
and  Vertically  Sliding  Doors 

With  the  elevator  away  from  the  designated  level,  Phase  1  in  effect,  place  the  Phase 
II  switch  in  the  "OFF"  position  and  verify  that: 

2.27.3.3 

6.5.13(a) 

horizontally  sliding  doors  close  automatically  and  continuous  pressure  on  the  door 
close  button  will  close  vertically  sliding  doors 

2.27.3.3.3 

6.5.13(b) 

car  reverts  to  a  Phase  1  type  return  on  completion  of  door  closing  and  reverts  to 
Phase  I  when  the  doors  open  at  the  designated  landing 

2.27.3.3.3(a) 

6.5.13(c) 

Door  reopening  device  inoperative  and  full-speed  closing  permitted. 

2.27.3.3.3(a) 

6.5.13(d) 

Door  open  button  is  operative. 

2.27.3.3.3(a) 

6.5.13(e) 

If  Phase  II  switch  turned  to  "ON"  or  "HOLD"  before  door  is  closed,  it  will  reopen. 

2.27.3.3.3(a) 

6.5.13(0 

With  car  stopped  and  doors  closed,  or  in  motion  and  Phase  II  switch  is  turned  to 
"OFF"  position,  car  returns  to  designated  level  in  conformance  with  2.27.3.1.6(a) 
through  (m),  but  remains  on  Phase  II. 

2.27.3.3.4 

6.5.14 

Removal  From  Phase  II 

Verify  that  the  elevator  can  be  removed  from  Phase  II  only  when: 

2.27.3.3 

6.5.14(a) 

Phase  II  switch  is  in  "OFF"  position  at  designated  level  and  doors  open 

2.27.3.3.5 

6.5.14(b) 

Phase  II  switch  is  in  "OFP'  position  and  Phase  I  is  in  effect 

2.27.3.3.4 

6.5.15 

Power  Disconnects  Open 

2.27.3.4 

6.5.15.1 

With  the  elevator  on  Phase  1,  have  the  mainline  power  interrupted  and  restored  to  ver- 
ify that  the  elevator  will  remain  on  Phase  1. 

2.27.3.4 

6.5.15.2 

With  the  elevator  on  Phase  II,  have  the  mainline  power  interrupted  and  restored  to 
verify  that  the  elevator  will  remain  on  Phase  II. 

2.27.3.4 

6.5.15.3 

The  car  is  allowed  to  move  to  a  position  in  the  hoistway  to  reestablish  position  once 
movement  is  attempted. 

2.27.3.4 

6.5.16 

Top-of-Car  Operating  Device 

While  operating  from  top  of  car,  have  the  Phase  1  key  switch  placed  in  the  "ON" 
position  and  verify  that: 

2.27.6 

6.5.16(a) 

an  audible  signal  sounds 

6.5.16(b) 

the  elevator  remains  under  control  of  the  top-of-car  operating  device 

6.5.16(c) 

the  elevator  remains  under  the  control  of  the  hoistway  access  switch 

6.5.17 

Automatic  Elevators  With  Attendant  Operation 

With  elevator  on  attendant  operation,  stop  at  a  floor  and  have  the  Phase  1  switch 
placed  in  the  "ON"  position.  Verify  that: 

2.27.5.2 

6.5.17(a) 

the  audible  and  visual  signal  operates  and  that  a  parked  elevator  will  automatically 
go  on  Phase  1  after  a  time  delay  between  10  sec  and  30  sec. 

2.27.5.2(a) 

6.5.17(b) 

a  moving  car  on  attendant  operation  will  commence  Phase  1  operation  without  delay. 

2.27.5.2(b) 

192 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


A5AAE  A17.2-2010 


Acceptance  Checklist  for  Firefighters'  Service  (Al 7.1-2000  and  B44-00):  Automatic  Elevators  (Cont'd) 


GENERAL  NOTE:   Pass  =  meets  requirement;  Fail  =  does  not  meet  requirement;  NA  =  not  appli 

cable. 

Item 

Check 

A17. 1-2000 
and  B44-2000 

Pass 

Fail 

NA 

6.5.17(c) 

if  car  is  on  hospital  emergency  service,  it  will  remain  on  that  operation  until  removed 
by  the  operator  and  at  that  point  revert  to  Phase  1  operation.  The  audible  and 
visual  signals  in  the  car  shall  be  activated  immediately  and  remain  activated  until 
the  car  is  returned  to  the  designated  landing.  With  the  car  on  firefighter  emergency 
operation,  the  elevator  cannot  be  placed  on  hospital  service. 

2.27.5.3 

6.5.18 

Elevators  on  Phase  1  and  Phase  II  Prevention  of  Operation  and  Disabling  Not  Allowed 

With  elevator  on  normal  operation,  verify  the  following: 

2.27.3.1.6.1(1), 

2.27.3.1.6.1(m), 

2.27.3.3.6 

6.5.18(a) 

Activate  means  other  than  those  specified  in  this  Code  to  remove  elevators  from  nor- 
mal operation,  and  verify  that  Phase  1  emergency  recall  operation  is  not  prevented. 

2.27.3.1.6(1) 

6.5.18(b) 

Activate  input  for  devices  that  measure  loads  and  verify  that  the  elevator  is  not  pre- 
vented from  operating  at  or  below  the  capacity  that  is  required. 

2.27.3.1.6(m) 

6.5.18(c) 

Verify  that  an  accidental  ground  or  short  circuit  in  equipment  on  landing  side  will  not 
disable  Phase  II  operation. 

2.27.3.3.6 

193 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Acceptance  Checklist  for  Firefighters*  Service  (A17.1-2002  and  B44-02); 
Automatic  Elevators 

GENERAL  NOTE:  Pass  =  meets  requirement;  Fail  =  does  not  meet  requirement;  NA  =  not  applicable. 


ELEVATOR  ID  No. 
ADDRESS:  

INSPECTED  BY:  _ 
SIGNATURE:  


BUILDING. 


DATE:. 

INSPECTOR  I.D.  No. . 


Item 

Check 

A17.1-2002  and 
B44-02 

Pass 

Fail 

NA 

Acceptance  Test  Checklist 

NOTE:  The  acceptance  checklist  is  more  detailed  than  the  periodic  inspection 

checklist  will  be.  It  is  expected  that  the  periodic  inspection  will  be  to  confirm 

the  operation  has  been  maintained  in  working  order. 
The  purpose  and  intention  of  the  checklist  is  to  provide  a  focus  for  inspectors 

when  completing  acceptance  testing  of  elevators  equipped  with  Firefighters' 

Emergency  Operation. 

Emergency  Signaling  Devices 

2.27.1 

1 

Help  button  in  car  station  panel  or  adjacent  to  it. 

2.27.1.1.3(b) 

2 

Help  button  must  have  tactile  (raised)  phone  symbol  on  or  adjacent  to  it.  Identifica- 
tion of  the  button  with  the  word  help  is  optional. 

2.26.12.4 

3 

The  Help  button  is  no  higher  than  48  in.  (1  220  mm)  from  floor. 

2.27.1.1.3  (a) 

4 

Help  button  or  visual  indication  on  the  same  panel  illuminates  when  communica- 
tion is  established  and  extinguishes  when  communication  is  terminated. 

2.27.1.1.3  (c) 

5 

On  freight  elevators,  audible  signal  must  sound  when  emergency  stop  is  pressed 
(2.27.1.2).  If  travel  is  over  100  ft  (30  m),  one  audible  device  on  each  car 
individually  and  one  at  designated  landing. 

2.27.1.2(d)(l)(2) 

6 

If  travel  is  more  than  60  ft  (18  m),  check  for  two-way  communication  between  the 
cars  and  a  point  readily  accesible  to  authorized  and  emergency  personnel. 

2.27.1.1.4(a)(b) 

8 

If  site  is  not  staffed  24  hr,  call  is  automatically  directed  within  30  sec  to  a  location 

staffed  by  authorized  personnel. 
Automated  answering  systems  are  not  acceptable. 

2.27.1.1.2  / 
2.27.1.1.3(h) 

9 

Authorized  personnel  who  answer  call  can  identify  location  and  elevator  number. 

2.27.1.1.3(d) 

10 

Call  can  only  be  terminated  by  authorized  personnel  outside  the  elevator. 

2.27.1.1.3(f) 

Keys  and  Key  Switches 

[2.27.3  /  2.27.8] 

1 

Ensure  there  is  a  key  for  each  Phase  1,  Phase  11,  and  standby  power  selection 
switch  in  the  building. 

2.27.8 

2 

The  same  key  is  used  for  Phase  1,  Phase  II,  and  standby  power  for  all  elevators  in 
the  building. 

2.27.8 

3 

Keys  are  available  only  to  authorized  emergency  and  firefighting  personnel. 

2.27.8 

4 

The  keys  shall  be  Group  3  security  (see  8.1). 

2.27.8 

5 

The  standby  power  selection  switch  shall  be  in  view  of  all  elevator  entrances  (see 
2.27.2.4.3  for  alternate  option). 

2.27.2.4.3 

6 

Verify  all  fire  recall  switches  have  visual  indicator. 

2.27.3.1.5 

Phase  1  Key  Switch  And  Instructions 

[2.27.3.1  / 
2.27.7  /  2.27.8] 

1 

Operating  instructions  with  or  adjacent  to  recall  switch,  only  wording  identified  in 
2.27.7.1  is  acceptable. 

2.27.7.1 

2 

Labelled  "FIRE  RECALL,"  marked  "RESET,"  "OFF,"  and  "ON"  in  that  order. 

2.27.3.1.1(b) 

3 

Provided  at  designated  level  for  group. 

2.27.3.1.1(a) 

194 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


Acceptance  Checklist  for  Firefighters'  Service  (A17.1-2002  and  B44-02): 
Automatic  Elevators  (Cont'd) 

GENERAL  NOTE:  Pass  =  meets  requirement;  Fail  =  does  not  meet  requirement;  NA  =  not  applicable. 


Item 

Check 

A17.1-2002  and 
B44-02 

Pass 

Fail 

NA 

4 

Located  in  the  lobby,  visible,  and  readily  accessible. 

2.27.3.1.1(c) 

5 

The  key  cannot  be  removed  in  the  "RESET"  position,  but  can  be  removed  in  the 
other  positions. 

2.27.3.1.3 

6 

Second  switch,  if  present,  must  be  at  building  fire  control  station  labeled  "FIRE 
RECALL,"  only  be  two-position  switch  marked  "OFF"  and  "ON"  in  that  order. 

2.27.3.1.2 

7 

A  visual  Indicator  is  provided  at  the  fire  recall  switches. 

8 

In  jurisdictions  enforcing  nbcc:  min.  (2  in.)  50  mm  fire  hat  on  "FIREFIGHTER'S  ELE- 
VATOR" on  or  adjacent  to  entrance  frame  at  designated  landing. 

2.27.7.4 

Phase  1  Operation  While  Running 

Place  several  floor  calls  in  the  car.  While  going  up,  have  the  person  at  the  desig- 
nated level  place  the  Phase  I  switch  in  the  "ON"  position.  Where  a  duplicate 
switch  is  provided,  verify  that  Phase  1  is  initiated  by  placing  the  switch  to  the 
"ON"  position. 

Determine  the  following: 

2.27.3 

1 

The  car  stops  and  reverses  without  opening  the  doors. 

2.27.3.1.6(b) 

2 

The  in-car  stop  switch  or  emergency  stop  switch  is  inoperative. 

2.27.3.1.6(c) 

3 

Call  register  lights  and  directional  lanterns  are  extinguished  and  inoperative. 

2.27.3.1.6(f) 

4 

Position  indicators,  where  provided,  are  inoperative  except  in  car,  designated  level, 
and  building  fire  control  station. 

2.27.3.1.6(f) 

5 

The  in-car  door  open  button  is  rendered  inoperative  as  soon  as  car  moves  away 
from  the  landing. 

2.27.3.1.6(0 

6 

Car  call  buttons  are  inoperative. 

2.27.3.1.6(f) 

7 

The  car  returns  to  the  designated  level  and  parks  with  power  operated  doors  open. 

2.27.3.1.6(a) 

8 

The  visual  and  audible  signals  operate  and  stay  on  until  car  is  at  the  designated 
level. 

2.27.3.1.6(h) 

Phase  1  Operation  With  Doors  Open 

Place  the  Phase  1  switch  to  the  "OFF"  position  and  run  the  car  to  any  floor.  With 
the  doors  open,  have  the  Phase  i  switch  turned  to  the  "ON"  position  and  check 
the  following: 

2.27.3.1.6 

1 

Door  reopening  devices  sensitive  to  smoke  or  flame  are  inoperative  immediately. 

2.27.3.1.6(e) 

2 

If  door  reopening  devices  are  rendered  inoperative,  the  closing  speed  is  reduced 

so  that  the  kinetic  energy,  is  reduced  to  7x/2  ft-lb  (3.5  j). 
(To  verify  closing  time,  refer  to  data  plate  required  by  2.13.4.2.4.) 

2.27.3.1.6(e) 

3 

The  emergency  stop  switch  or  in-car  stop  switch  is  rendered  inoperative  as  soon 
as  the  car  moves  away  from  the  landing. 

2.27.3.1.6(c) 

A 

The  in-car  door  open  button  is  rendered  inoperative  as  soon  as  the  car  moves 
away  from  the  landing. 

2.27.3.1.6(0 

Emergency  Stop  Switch  and/or  In  Car  Stop  Switch  And  Doors  Closing 

Place  the  Phase  1  switch  to  the  "OFF"  position  and  run  the  car  to  any  floor.  Acti- 
vate the  emergency  stop  switch  or  the  in-car  stop  switch.  With  the  doors  open, 
have  the  Phase  1  switch  turned  to  the  "ON"  position.  Return  the  emergency  stop 
switch,  or  in-car  stop  switch  to  the  run  position. 

2.27.3.1.6 

1 

Verify  that  the  doors  close  promptly  and  the  car  moves  to  the  designated  level 
only  after  the  emergency  stop  switch  or  in-car  stop  switch  have  been  returned  to 
the  run  position. 

2.27.3.1.6(d) 

Stop  Switches  And  Door  Buttons 

While  on  Phase  I,  verify  the  following: 

2.27.3.1.6(c)  / 
2.27.3.1.6(g) 

195 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Acceptance  Checklist  for  Firefighters*  Service  (Al 7.1-2002  and  B44-02): 
Automatic  Elevators  (Cont'd) 

GENERAL  NOTE:  Pass  =  meets  requirement;  Fail  =  does  not  meet  requirement;  NA  =  not  applicable. 


Item 

Check 

A17.1-2002  and 
B44-02 

Pass 

Fail 

NA 

1 

That  stop  switches  other  than  those  inside  the  car  remain  operative. 

2.27.3.1.6(c) 

2 

For  vertical  sliding  door,  the  corridor  door  open  and  door  close  buttons  remain 
operative. 

2.27.3.1.6(g) 

Fire  Alarm  Initiating  Device  and  Operation 

[2.27.3] 

1 

Verify  that  there  is  a  fire  alarm  initiating  device  in  each  elevator  lobby,  the  elevator 

machine  room  and  sprinklered  hoistway. 
Jurisdictions  enforcing  the  NBCC:  verify  that  there  is  a  fire  alarm  initiating  device  in 

each  elevator  lobby  at  the  designated  level  if  not  sprinklered  throughout  and  in 

the  machine  room  if,  sprinklered. 

2.27.3.2.1  / 
2.27.3.2.2 

2 

With  the  car(s)  on  normal,  have  the  input  for  main  return  activated  and  verify  that 
the  elevator  commences  Phase  1  operation  and  al!  cars  return  to  the  designated 
level. 

2.27.3.2.3(a) 

3 

To  reset  operation  initiated  from  fire  alarm  system,  the  fire  alarm  signal  must  be 
reset,  then  the  Phase  1  switch  must  be  cycled  to  "RESET"  momentarily,  then  to 
"OFF." 

2.27.3. 1.6(k) 

4 

With  the  car(s)  on  normal,  have  the  input  for  alternate  level  return  activated,  and 
verify  that  the  elevator  commences  Phase  1  operation  and  all  cars  return  to  the 
alternate  level. 

2.27.3.2.4 

5 

Car(s)  should  only  respond  to  the  first  fire  alarm  input. 

2.27.3.2.5 

6 

Activate  the  machine  room  fire  alarm  initiating  device  input  and  verify  Phase  1  and 
all  cars  return  to  the  designated  level  or  alternate,  as  appropriate  —  unless  the 
machine  room  is  at  the  designated  level  and  if  so,  cars  go  to  alternate  level. 

2.27.3.2.3(b) 

7 

With  the  car(s)  on  normal,  have  the  input  for  machine  room  return  activated  and 
verify  the  visual  signal  in  the  car  illuminates  intermittently. 

2.27,2.4 

8 

In  jurisdictions  not  enforcing  the  NBCC  where  the  faid  is  required  in  the  hoistway, 
activate  the  input  and  verify  all  cars  return  to  the  designated  landing,  except 
that  faids  installed  at  or  below  the  lowest  landing  of  recall  shall  cause  the  cars 
to  return  to  the  upper  recall  level. 

2.27.3.2.3(c) 

Alternate  Recall  (If  Applicable) 

With  the  car  at  the  alternate  level,  on  Phase  1  emergency  recall  operation  and  the 
doors  open. 

2.27.3.2.4 

1 

If  a  two-position  key  switch  is  provided,  place  it  in  the  "ON"  position  and  verify 
that  the  elevator  remains  at  the  alternate  landing. 

2.27.3.1.2 

2 

Turn  both  the  Phase  1  switch  and  the  additional  Phase  1  switch  (when  provided)  to 
the  "ON"  position  and  verify  that  the  car  returns  to  the  designated  level. 

2.27.3.1.6  (j) 

Monthly  Test  (for  jurisdictions  not  enforcing  the  NBCC) 

8.6.10.1 

Monthly  test  log  is  completed. 

Phase  11  Key  Switch  And  Instructions 

2.27.8/2.27.3.3 

196 


■<M>d  J 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Acceptance  Checklist  for  Firefighters*  Service  (Al 7.1  -2002  and  B44-02): 
Automatic  Elevators  (Cont'd) 

GENERAL  NOTE:  Pass  =  meets  requirement;  Fail  =  does  not  meet  requirement;  NA  =  not  applicable. 


Item 

Check 

A17.1-2002  and 
B44-02 

Pass 

Fail 

NA 

1 

FIREFIGHTERS'  OPERATION 

£X  — 

To  operate  car                  Insert  fire  key  and  turn  to  "ON'* 
Press  desired  floor  button 

To  cancel                            Press  "CALL  CANCEL"  button 
floor  selection 

To  dose  power-                  Press  and  hold  "DOOR  CLOSE"  button 
operated  door 

To  open  power-                    Press  and  hold  "DOOR  OPEN"  button 
operated  door 

To  hold  car                          With  doors  open,  turn  key  to  "HOLD" 

at  floor 

To  automatically  send        With  doors  open,  turn  key  to  "OFF" 
car  to  recall  floor 

2 

Labeled  "FIRE  OPERATION,"  marked  "OFF,"  "HOLD,"  and  "ON"  in  that  order. 

2.27.3.3 

3 

The  key  can  only  be  removed  in  the  "OFP'  and  "HOLD"  positions. 

2.27.3.3 

Phase  II  Operation 

With  Phase  1  activated  and  the  car  at  the  designated  or  alternate  landing,  place 
the  Phase  11  key  switch  in  the  "ON"  position.  Operate  the  car  and  check  the 
following: 

2.27.3.3.1 

1 

The  elevator  can  be  operated  only  from  the  car  buttons  and  will  not  respond  to 
corridor  calls. 

2.27.3.3.1(a) 

2 

All  corridor  call  buttons,  door  open  and  close  buttons,  and  directional  lanterns  are 

inoperative. 
Car  position  indicators  are  operative,  landing  position  indicators  inoperative  except 

at  designated  landing  and  fire  control  station. 

2.27.3.3.1(b),  (g) 

3 

Open  doors  can  be  closed  only  by  continuous  pressure  means.  If  the  means  is 
released  before  the  door  is  fully  closed,  horizontal  sliding  doors  will  reopen  and 
vertical  sliding  doors  will  stop,  or  stop  and  re-open. 

2.27.3.3.1(e) 

4 

The  door  can  only  be  opened  by  continuous  pressure  on  the  door  open  button  and 
if  released  before  the  doors  are  in  the  normal  open  position,  the  door  will  close 
without  delay. 

2.27.3.3.1(d) 

5 

If  two  entrances  can  be  opened  and  closed  at  the  same  landing,  separate  door 
open  and  close  buttons  are  provided  for  each  entrance. 

2.27.3.3.1(d) 

6 

All  door  reopening  devices  are  inoperative  —  (except  the  DOB): 
full  speed  closing  is  permitted. 

2.27.3.3.1(g) 

7 

Call  cancel  button  is  labeled  and  when  activated,  will  cancel  all  calls  and  cause 
the  car  to  stop  at  or  before  the  next  available  landing. 

2.27.3.3.1(h) 

8 

Floor  selection  buttons  are  provided  and  functional  for  all  landings  without 
restrictions. 

2.27.3.3.1(0 

197 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Acceptance  Checklist  for  Firefighters*  Service  (A17.1-2002  and  B44-02): 
Automatic  Elevators  (Cont'd) 

GENERAL  NOTE:  Pass  =  meets  requirement;  Fail  =  does  not  meet  requirement;  NA  =  not  applicable. 


Item 

Check 

A17. 1-2002  and 
B44-02 

Pass 

Fail 

NA 

9 

Moving  car  will  stop  at  the  next  landing  with  a  car  call  registered  and  remaining 
car  calls  canceled. 

2.27.3.3.1(j) 

Phase  II  Switch  In  "HOLD"  Position 

2.27.3.3.2 

1 

With  the  doors  fully  open,  place  the  Phase  It  switch  in  the  "HOLD"  position  and 
remove  key.  Verify  that  the  car  remains  at  the  landing  and  the  door  close  button 
is  inoperative. 

2.27.3.3.2 

2 

Verify  that  the  car  call  buttons  are  inoperative. 

2.27.3.3.2 

Phase  II  Switch  In  "OFP*  Position  And  Doors  Closing 
Horizontal  Sliding  Doors 

With  the  elevator  away  from  the  designated  level,  Phase  1  in  effect,  place  the 
Phase  II  switch  in  the  "OFF"  position  and  verify  following: 

2.27.3.3 

1 

Doors  close  automatically. 

2.27.3.3.3(a) 

2 

Car  reverts  to  a  Phase  1  type  return  on  completion  of  door  closing  and  reverts  to 
Phase  1  when  the  doors  open  at  the  designated  landing. 

2.27.3.3.4 

3 

Door  reopening  device  inoperative  and  full  speed  closing  permitted. 

2.27.3.3.3(a) 

4 

Door  open  button  operative. 

2.27.3.3.3(a) 

5 

If  Phase  II  switch  turned  to  "ON"  or  "HOLD"  before  door  is  closed,  it  will  reopen. 

2.27.3.3.3(a) 

6 

With  car  stopped  and  doors  closed,  or  in  motion  and  Phase  II  Switch  is  turned  to 
"OFF"  position,  car  returns  to  designated  level  in  conformance  with  2.27.3.1.6(a) 
through  (m),  but  remains  on  Phase  II. 

2.27.3.3.4 

Removal  From  Phase  II 

Verify  that  the  elevator  can  be  removed  from  Phase  II  only  when 

2.27.3.3 

1 

Phase  II  switch  in  "OFF"  position  at  designated  level  and  doors  open. 

2.27.3.3.5 

2 

Phase  II  switch  in  "OFF"  position  and  phase  1  in  effect. 

2.27.3.3.4 

Power  Disconnects  Open 

2.27.3.4 

1 

With  the  elevator  on  Phase  1,  have  the  mainline  power  interrupted  and  restored  to 
verify  that  the  elevator  will  remain  on  Phase  1. 

2.27.3.4 

2 

With  the  elevator  on  Phase  II,  have  the  mainline  power  interrupted  and  restored  to 
verify  that  the  elevator  will  remain  on  Phase  II. 

2.27.3.4 

3 

The  car  is  allowed  to  move  to  a  position  in  the  hoistway  to  re-establish  position. 

2.27.3.4 

Inspection  and  Hoistway  Access  Operation 

While  operating  from  top  of  car,  have  the  Phase  1  key  switch  placed  in  the  "ON" 
position  and  verify  the  following: 

2.27.6 

1 

An  audible  signal  sounds. 

2 

The  elevator  remains  under  control  of  the  car  top,  in-car,  and  machine  room  inspec- 
tion operating  device. 

3 

That  the  elevator  remains  under  the  control  of  the  hoistway  access  switch. 

Automatic  Elevators  With  Attendant  Operation 

With  elevator  on  attendant  operation,  stop  at  a  floor  and  have  the  Phase  1  switch 
placed  in  the  on  position.  Verify  the  following: 

2,27.5.2 

1 

The  audible  and  visual  signal  operates  and  that  a  parked  elevator  will  automati- 
cally go  on  Phase  1  after  a  time  delay  between  10  sec  and  30  sec. 

2.27.5.2(a) 

2 

A  moving  car  on  attendant  operation  will  commence  Phase  1  operation  without 
delay. 

2.27.5.2(b) 

198 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Acceptance  Checklist  for  Firefighters'  Service  (A17.1-2002  and  B44-02): 
Automatic  Elevators  (Cont'd) 

GENERAL  NOTE:  Pass  =  meets  requirement;  Fail  =  does  not  meet  requirement;  NA  =  not  applicable. 


Item 

Check 

A17.1-2002  and 
B44-02 

Pass 

Fail 

NA 

3 

If  car  is  on  hospital  emergency  service,  it  will  remain  on  that  operation  until 
removed  by  the  operator  and  at  that  point,  revert  to  Phase  1  operation.  The  audi- 
ble and  visual  signals  in  the  car  shall  be  activated  immediately  and  remain  acti- 
vated until  the  car  is  returned  to  the  designated  landing. 

2.27.5.3 

Elevators  on  Phases  1  and  II  Prevention  of  Operation  and  Disabling  Not  Allowed 

With  elevator  on  normal  operation,  verify  the  following: 

2.27.3.1.6.1(1) 
and  (m)/ 
2.27.3.3.6 

1 

Activate,  means  other  than  those  specified  in  this  code,  to  remove  elevators  from 
normal  operation  (card  key  access,  etc.),  and  verify  that  Phase  1  emergency 
recall  operation  is  not  prevented  and  all  floors  served  by  the  elevator  are 
accessable  during  Phase  II  operation. 

2.27.3.1.6.  (1) 

2 

Activate  input  for  devices  that  measure  loads  and  verify  that  the  elevator  is  not 
prevented  from  operating  at  or  below  the  capacity  that  is  required. 

2.27.3.1.6  (m) 

3 

Verify  that  an  accidental  ground  or  short  circuit  in  equipment  on  landing  side  will 
not  disable  Phase  II  operation. 

2.27.3.3.6 

Hydraulic  Elevators 

3.27.1 

1 

Where  the  car(s)  is  responding  to  low  oil  protection,  plunger  follower  guide  protec- 
tion or  auxiliary  power  lowering  and  Phase  1  activated,  verify  the  car  descends  to 
the  designated  recall  level.  If  the  car  is  incapable  of  reaching  the  recall  level, 
then  it  descends  to  an  available  landing,  opens  doors,  and  recloses  within  15 
sec.  And  the  door  open  button  remains  operative. 

3.27.1 

2 

While  on  phase  1  recall  operation,  verify  that  when  low  oil  protection,  plunger  fol- 
lower guide  protection,  or  auxiliary  power  lowering  is  activated  with  the  car 
above  the  recall  level,  the  car  will  return  to  the  recall  level  and  where  the  car  is 
below  the  recall  level,  it  descends  to  an  available  landing,  opens  doors,  and 
recloses  within  15  sec  and  the  door  open  button  remains  operative. 

3.27.2 

3 

With  the  car(s)  on  Phase  11  operation,  verify  that  when  low  oil  protection,  plunger 
follower  guide  protection  or  auxiliary  power  lowering  is  activated,  travelling 
car(s)  stops,  cancels  all  calls,  and  the  visual  signal  in  the  car  illuminates  inter- 
mittently and  the  car  can  only  answer  calls  to  landings  below  its  location. 

3.27.4 

199 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


Acceptance  Checklist  for  Firefighters'  Service  (Al  7. 1-2004  and  B44-04): 
Automatic  Elevators 

GENERAL  NOTE:  Pass  =  meets  requirement;  Fail  =  does  not  meet  requirement;  NA  =  not  applicable. 


ELEVATOR  ID  No. 

ADDRESS:  

INSPECTED  BY:  _ 
SIGNATURE:  


BUILDING. 


DATE:. 

INSPECTOR  I.D.  No._ 


Item 

Check 

A17.1-20O4  and 
B44-04 

Pass 

Fail 

NA 

Acceptance  Test  Checklist 

NOTE:  The  acceptance  checklist  is  more  detailed  than  the  "periodic  inspection" 

checklist  will  be.  It  is  expected  that  the  periodic  inspection  will  be  to  confirm 

the  operation  has  been  maintained  in  working  order. 
The  purpose  and  intention  of  the  checklist  is  to  provide  a  focus  for  inspectors 

when  completing  acceptance  testing  of  elevators  equipped  with  Firefighters' 

Emergency  Operation. 

Emergency  Signaling  Devices 

[2.27.1] 

1 

Help  button  in  car  station  panel  or  adjacent  to  it. 

2.27.1.1.3(b) 

2 

Help  button  must  have  tactile  (raised)  phone  symbol  on  or  adjacent  to  it.  Identifica- 
tion of  the  button  with  the  word  help  is  optional. 

2.26.12.4 

3 

The  help  button  is  no  higher  than  48  in.  (1  220  mm)  from  floor. 

2.27.1.1.3  (a) 

4 

Help  button  or  visual  indication  on  the  same  panel  illuminates  when  communica- 
tion is  established  and  extinguishes  when  communication  is  terminated. 

2.27.1.1.3  (c) 

5 

If  site  is  not  staffed  24  hr,  call  is  automatically  directed  within  30  sec  to  a  location 

staffed  by  authorized  personnel. 
Automated  answering  systems  are  not  acceptable. 

2.27.1.1.2  / 
2.27.1.1.3(h) 

6 

Authorized  personnel  who  answer  call  can  identify  location  and  elevator  number. 

2.27.1.1.3(d) 

7 

Call  can  only  be  terminated  by  authorized  personnel  outside  the  elevator. 

2. 27.1.1.3.  (f) 

8 

Ensure  audible  alarms  (where  provided)  and  communications  are  functional  with 
loss  of  normal  power. 

2.27.1.1.5 

9 

On  freight  elevators,  audible  signal  must  sound  when  emergency  stop  is  pressed 
(2.27.1.2).  If  rise  travel  is  over  100  ft  (30  m),  one  audible  device  on  each  car 
individually  and  one  at  designated  landing. 

2.27,1.2(d)(l)(2) 

10 

Where  travel  is  60  ft  (18  m)  or  more,  two-way  communication  means  from  within 
the  building  to  each  individual  car. 

2.27.1.1.4 

11 

Where  travel  is  60  ft  (18  m)  or  more,  this  communication  means  overrides  any 
other  communication  to  outside  of  building. 

2.27.1.1.4(a) 

12 

Where  travel  is  60  ft  (18  m)  or  more,  communication  can  only  be  disconnected 
from  outside  the  car  within  the  building. 

2.27.1.1.4(b) 

13 

Where  travel  is  60  ft  (18  m)  or  more,  visual  indicator  illuminates  when  communica- 
tion is  established  and  extinguishes  when  call  is  terminated. 

2.27.1.1.4(c) 

14 

Where  travel  is  60  ft  (18  m)  or  more,  permanently  posted  and  protected  operating 
instructions  are  at  communication  station  outside  the  car  (minimum  letter  height 
of  .125  in.  (3  mm). 

2.27.1.1.4(d) 

Keys  and  Key  Switches 

2.27.8 

1 

Ensure  there  is  a  key  for  each  Phase  1,  Phase  II,  and  standby  power  selection 
switch  in  the  building  in  view  of  all  elevator  entrances  (see  2.27.2.4.3  for  alter- 
nate option). 

2.27.8 

2 

The  same  key  is  used  for  Phase  1  and  Phase  II  (firefighters'  operation  panel  in  car 
if  it  does  not  open  automatically)  and  standby  power  for  all  elevators  in  the 
building. 

2.27.8 

200 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Acceptance  Checklist  for  Firefighters*  Service  (Al 7.1  -2004  and  B44-04): 
Automatic  Elevators  (Cont'd) 

GENERAL  NOTE:  Pass  =  meets  requirement;  Fail  =  does  not  meet  requirement;  NA  =  not  applicable. 


Item 

Check 

A17.1-2004  and 
B44-04 

Pass 

Fail 

NA 

3 

Keys  are  available  only  to  authorized  emergency  and  firefighting  personnel. 

2.27.8 

4 

The  keys  shall  be  Group  3  security  (see  section  8.1). 

2.27.8 

5 

Verify  all  fire  recall  switches  have  visual  indicator. 

2.27.3.1.5 

Phase  1  Key  Switch  and  Instructions 

[2.27.3.1  / 
2.27.7  /  2.27.8] 

1 

Operating  instructions  with  or  adjacent  to  recall  switch,  only  wording  identified  in 
2.27.7.1  is  acceptable. 

2 

Labelled  "FIRE  RECALL,"  marked  "RESET,"  "OFF,"  and  "ON"  in  that  order. 

2.27.3.1.1(b) 

3 

Provided  at  designated  level  for  group. 

2.27.3.1.1(a) 

4  2tbir_X 

5 

Located  in  the  lobby,  visible,  and  readily  accessible. 

The  key  cannot  be  removed  in  the  "RESET"  position,  but  can  be  removed  in  the 
other  positions. 

2.27.3.1.1(c) 
2.27.3.1.3 

6 

Second  switch,  if  present,  must  be  at  the  building  fire  control  station,  labeled 
"FIRE  RECALL"  only  be  two-position  switch  marked  "OFF,"  and  "ON"  in  that  order. 

2.27.3.1.2 

7 

In  jurisdictions  enforcing  NBCC:  min.  2  in.  (50  mm)  fire  hat  on  "FIREFIGHTER'S  ELE- 
VATOR" on  or  adjacent  to  entrance  frame  at  designated  landing. 

2.27.7.4 

Phase  1  Operation  While  Running 

Place  several  floor  calls  in  the  car.  While  going  up,  have  the  person  at  the  desig- 
nated level  place  the  Phase  1  switch  in  the  "ON"  position.  Where  an  additional 
switch  is  provided,  verify  that  Phase  1  is  initiated  by  placing  the  switch  to  the 
"ON"  position. 

Determine  the  following: 

2.27.3 

1 

The  car  stops  and  reverses  without  opening  the  doors. 

2.27.3.1.6(b) 

2 

The  in-car  stop  switch  or  emergency  stop  switch  is  inoperative. 

2.27.3.1.6(c) 

3 

Call  register  lights  and  directional  lanterns  are  extinguished  and  inoperative. 

2.27.3.1.6(0 

4 

Position  indicators,  where  provided,  are  inoperative  except  in  car,  designated  level, 
and  building  fire  control  station. 

2.27.3.1.6(0 

5 

The  in-car  door  open  button  is  rendered  inoperative  as  soon  as  car  moves  away 
from  the  landing. 

2.27.3.1.6(0 

6 

Car  call  buttons  are  inoperative. 

2.27.3.1.6(0 

7 

The  car  returns  to  the  designated  level  and  parks  with  power  operated  doors  open. 

2.27.3.1.6(a) 

8 

The  visual  and  audible  signals  operate.  Audible  signal  stays  on  for  at  least  5  sec 
after  doors  close  and  visual  signal  stays  on  until  car  is  returned  to  automatic 
operation. 

2.27.3.1.6(h) 

9 

In-car  FEO  panel  cover  opens  automatically  when  at  designated  level  (if  automatic 
unlocking  is  provided). 

2.27.3.3.7 

Phase  1  Operation  With  Doors  Open 

Place  the  Phase  1  switch  to  the  "OFF"  position  and  run  the  car  to  any  floor.  With 
the  doors  open,  have  the  Phase  1  switch  turned  to  the  "ON"  position  and  check 
the  following: 

2.27.3.1.6 

1 

Door  reopening  devices  sensitive  to  smoke  or  flame  are  inoperative  immediately. 

2.27.3.1.6(e) 

2 

If  door  reopening  devices  are  rendered  inoperative,  the  closing  speed  is  reduced 

so  that  the  kinetic  energy  is  reduced  to  l}/2  ft-lb  (3.5  J). 
(To  verify  closing  time,  refer  to  data  plate  required  by  2.13.4.2,4.) 

2.27.3.1.6(e) 

3 

The  emergency  stop  switch  or  in-car  stop  switch  is  rendered  inoperative  as  soon 
as  the  car  moves  away  from  the  landing. 

2.27.3.1.6(c) 

201 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


Acceptance  Checklist  for  Firefighters'  Service  (Al 7.1-2004  and  B44-04): 
Automatic  Elevators  (Cont'd) 

GENERAL  NOTE:  Pass  =  meets  requirement;  Fail  =  does  not  meet  requirement;  NA  =  not  applicable. 


Item 

Check 

A17.1-2004  and 
B44-04 

Pass 

Fail 

NA 

4 

The  in-car  door  open  button  is  rendered  inoperative  as  soon  as  the  car  moves 
away  from  the  landing. 

2.27.3.1.6(0 

Emergency  Stop  Switch  and/or  In-Car  Stop  Switch  And  Doors 
Closing 

Place  the  Phase  1  switch  to  the  "OFF"  position  and  run  the  car  to  any  floor.  Acti- 
vate the  emergency  stop  switch  or  the  in-car  stop  switch.  With  the  doors  open, 
have  the  Phase  1  switch  turned  to  the  "ON"  position.  Return  the  emergency  stop 
switch  or  in-car  stop  switch  to  the  "RUN"  position. 

2.27.3.1.6(d) 

1 

Verify  that  the  doors  close  promptly  and  the  car  moves  to  the  designated  level. 

2.27.3.1.6(d) 

Stop  Switches  and  Door  Buttons 

While  on  Phase  1,  verify  the  following: 

2.27.3.1.6(c)  / 
2.27.3.3.3.1(m)  / 
2.27.3.1.6(g) 

1 

That  stop  switches  other  than  those  inside  the  car,  as  well  as  the  stop  switch  in 
the  firefighters'  operation  panel  remain  operative. 

2.27.3.1.6(c) 
2.27.3.3.1(m) 

2 

For  vertical  sliding  door,  the  corridor  door  open  and  door  close  buttons  remain 
operative. 

2.27.3.1.6(g) 

Fire  Alarm  Initiating  Device  and  Operation 

[2.27.3] 

1 

Verify  that  there  is  a  fire  alarm  initiating  device  in  each  elevator  lobby,  the  elevator 

machine  room,  and  sprinklered  hoistway. 
Jurisdictions  enforcing  the  NBCC:  verify  that  there  is  a  fire  alarm  initiating  device  in 

each  elevator  lobby,  at  the  designated  level  if  not  sprinklered  throughout,  and  in 

the  machine  room  if  sprinklered. 

2.27.3.2.1  / 
2.27.3.2.2 

2 

With  the  car(s)  on  normal,  have  the  input  for  designated  level  recall  activated,  and 
verify  that  the  elevator  commences  Phase  i  operation  and  all  cars  return  to  the 
designated  level. 

2.27.3.2,3 

3 

To  reset  operation  initiated  from  fire  alarm  system,  the  fire  alarm  signal  must  be 
reset,  then  the  Phase  1  switch  must  be  cycled  to  "RESET"  momentarily,  then  to 
"OFF". 

2.27.3. 1.6(k) 

4 

With  the  car(s)  on  normal,  have  the  input  for  alternate  level  recall  activated  and 
verify  that  the  elevator  commences  Phase  1  operation  and  all  cars  return  to  the 
alternate  level. 

2.27.3.2.4 

5 

Car(s)  should  only  respond  to  the  first  fire  alarm  input. 

2.27.3.2.5 

6 

Activate  the  machine  room  fire  alarm  initiating  device  input  and  verify  Phase  1  and 
all  cars  return  to  the  designated  level  —  unless  the  machine  room  is  at  the  desig- 
nated level  and,  if  so,  cars  go  to  alternate  level. 

2.27.3.2.3(b) 

7 

With  the  car(s)  on  normal,  have  the  input  for  machine  room  or  hoistway  return  acti- 
vated, and  verify  that  both  the  visual  signals  in  the  car  illuminate  intermittently. 

2.27.2.4 

8 

In  jurisdictions  not  enforcing  the  nbcc  where  the  FAID  is  required  in  the  hoistway, 
activate  the  input  and  verify  all  cars  return  to  the  designated  landing,  except 
that  FAIDs  installed  at  or  below  the  lowest  landing  of  recall  shall  cause  the  cars 
to  return  to  the  upper  recall  level. 

2.27.3.2.3(c) 

Alternate  Recall  Level  (If  Applicable) 

With  the  car  at  the  alternate  level,  on  Phase  1  emergency  recall  operation  and  the 
doors  open. 

1 

If  a  two-position  key  switch  is  provided,  place  it  in  the  "ON"  position  and  verify 
that  the  elevator  remains  at  the  alternate  landing. 

2.27.3.1.2 

202 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASMEA17.2-2010 


Acceptance  Checklist  for  Firefighters'  Service  (A17.1-2004  and  B44-04): 
Automatic  Elevators  (Cont'd) 

GENERAL  NOTE:  Pass  =  meets  requirement;  Fail  =  does  not  meet  requirement;  NA  =  not  applicable. 


Item 

Check 

A17.1-2004  and 
B44-04 

Pass 

Fail 

NA 

2 

Turn  both  the  Phase  1  switch  and  the  additional  Phase  1  switch  (when  provided)  to 
the  "ON"  position  and  verify  that  the  car  returns  to  the  designated  level. 

2.27.3.1.6(0 

Phase  II  In-Car  Switch  and  Instruction 

2.27.8  /  2.27.3.3 

1 

Check  that  instructions  are  posted  adjacent  to  switch  or  operating  panel  as  below. 

FIREFIGHTERS'  OPERATION 

\      j             \               When  flashing,  exit  elevator 

o- — ^ 

To  operate  car                  Insert  fire  key  and  turn  to  "ON'* 

Press  desired  floor  button 
To  cancel                          Press  "CALL  CANCEL"  button 
floor  selection 

To  close  power-                  Press  and  hold  "DOOR  CLOSE"  button 
operated  door 

To  open  power-                   Press  and  hold  «DOOK  OPEN"  button 
operated  door 

To  hold  car                          With  doors  open,  turn  key  to  "HOLD" 
at  floor 

To  automatically  send        With  doors  open,  turn  key  to  "OFF" 
car  to  recall  floor 

203 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers.  rL^  . 

No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME.     ^ 


ASMEA17.2-2010 


Acceptance  Checklist  for  Firefighters'  Service  (A17.1-2004  and  B44-04): 
Automatic  Elevators  (Cont'd) 

GENERAL  NOTE:  Pass  =  meets  requirement;  Fail  =  does  not  meet  requirement;  NA  =  not  applicable. 


Item 


Check 


A17.1-2004  and 
B44-04 


Pass 


Fait 


NA 


FEO  panel 

(a)  The  panel  is  located  at  the  top  of  the  operating  station  with  buttons  and 
switches  not  more  than  71  in.  (1  800  mm)  above  the  floor. 

(b)  Panel  cover  is  marked  firefighter's  operation  in  red  letters  at  least  0.4  in. 
(10  mm)  high. 

(c)  Panel  key  (where  panel  doesn't  unlock  automatically)  is  same  as  Phases  I 
and  II  keys. 

(d)  Panel  cannot  be  closed  with  the  key  in  the  Phase  II  operation  switch. 

(e)  Panel  is  self-locking. 

(f)  The  following  switches  and  buttons  are  provided  and  laid  out  as  below: 

Additional 
visual  signal 


Call 
cancel 
button 


Door 


Stop 
switch 


open 
button 


Door 
open 
button 
(rear! 
when 
required 


The  key  can  only  be  removed  in  the  "OFF"  and  "HOLD"  positions. 


2.27.33 


Labeled  "FIRE  OPERATION,"  marked  "OFF,"  "HOLD,"  and  "ON"  in  that  order. 


2.27.3.3 


Additional  visual  signal  provide  behind  the  panel. 


2.27.3.3.8 


Monthly  Test  (For  Jurisdictions  Not  Enforcing  The  NBCC) 


8.6.10.1 


Monthly  test  log  is  completed. 


Phase  II  Operation 

With  Phase  I  activated  and  the  car  at  the  designated  or  alternate  landing,  place 
the  Phase  II  key  switch  in  the  "ON"  position.  Operate  the  car  and  check  the 
following: 


2.27.3.3.1 


The  elevator  can  be  operated  only  from  the  car  buttons  and  will  not  respond  to  cor- 
ridor calls. 


2.27.3.3.1(a) 


All  corridor  call  buttons,  door  open  and  close  buttons,  and  directional  lanterns  are 
inoperative. 

Car  position  indicators  are  operative,  landing  position  indicators  inoperative  at  des- 
ignated landing  and  fire  control  station. 


2.27.3.3.1(b),  (g) 


204 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Acceptance  Checklist  for  Firefighters'  Service  (A17.1-2004  and  B44-04): 
Automatic  Elevators  (Cont'd) 

GENERAL  NOTE:  Pass  =  meets  requirement;  Fail  =  does  not  meet  requirement;  NA  =  not  applicable. 


Item 

Check 

A17.1-2004  and 
B44-04 

Pass 

Fail 

NA 

3 

Open  doors  can  be  closed  only  by  continuous  pressure  means.  If  the  means  is 
released  before  the  door  is  fully  closed,  horizontal  sliding  doors  will  reopen  and 
vertical  sliding  doors  will  stop,  or  stop  and  re-open. 

2.27.3.3.1(e) 

4 

The  door  can  only  be  opened  by  continuous  pressure  on  the  door  open  button  and 
if  released  before  the  doors  are  in  the  normal  open  position,  the  door  will  close 
without  delay. 

2.27.3.3.1(d) 

5 

If  two  entrances  can  be  opened  and  closed  at  the  same  landing,  separate  door 
open  and  close  buttons  are  provided  for  each  entrance. 

2.27.3.3.1(d) 

6 

Atl  door  reopening  devices  are  inoperative  —  (except  the  DOB): 
Full  speed  closing  is  permitted. 

2.27.3.3.1(g) 

7 

Call  cancel  button  is  labeled  and  when  activated,  will  cancel  all  calls  and  cause 
the  car  to  stop  at  or  before  the  next  available  landing. 

2.27.3.3.1(h) 

8 

Floor  selection  buttons  are  provided  and  functional  for  all  landings  without  restric- 
tions. 

2.27.3.3.1(0 

9 

Moving  car  will  stop  at  the  next  landing  with  a  car  call  registered  and  remaining 
car  calls  canceled. 

2.27.3.3.1(0 

10 

Operation  of  the  stop  switch  in  the  firefighters'  operation  panel  cancels  all  calls 
and  stops  the  car.  The  car  does  not  move  except  for  leveling  operation,  until  a 
car  call  is  registered. 

Phase  II  Switch  in  "HOLD"  Position 

2.27.3.3.2 

1 

Place  the  phase  II  switch  in  the  "HOLD"  position  and  remove  key.  Verify  that  the 
car  remains  at  the  landing  and  the  door  close  button  is  inoperative. 

2.27.3.3.2 

2 

Verify  that  the  car  call  buttons  are  inoperative. 

2.27.3.3.2 

Phase  II  Switch  In  "OFF"  Position  and  Doors  Closing 
Horizontal  Sliding  Doors 

With  the  elevator  away  from  the  designated  level,  Phase  1  in  effect,  place  the 
Phase  II  switch  in  the  "OFF"  position  and  verify  the  following: 

2.27.3.3 

1 

Doors  close  automatically. 

2.27.3.3.3(a) 

2 

Car  reverts  to  a  Phase  1  type  return  on  completion  of  door  closing  and  reverts  to 
Phase  1  when  the  doors  open  at  the  designated  landing. 

2.27.3.3.4 

3 

Door  reopening  device  inoperative  and  full  speed  closing  permitted. 

2.27.3.3.3(a) 

4 

Door  open  button  operative. 

2.27.3.3.3(a) 

5 

If  Phase  II  switch  turned  to  "ON"  or  "HOLD"  before  door  is  closed,  it  will  reopen. 

2.27.3.3.3(a) 

6 

With  car  stopped  and  doors  closed,  or  in  motion  and  Phase  II  switch  is  turned  to 
"OFF"  position,  car  returns  to  designated  level  in  conformance  with  2.27.3.1.6(a) 
through  (m),  but  remains  on  Phase  II. 

2.27.3.3.4 

Removal  From  Phase  II 

Verify  that  the  elevator  can  be  removed  from  Phase  II  only  when 

2.27.3.3 

1 

Phase  II  switch  in  "OFF"  position  at  designated  level  and  doors  open. 

2.27.3.3.5 

205 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers.  & 

v     No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME.       vS 


ASME  A17.2-2010 


Acceptance  Checklist  for  Firefighters'  Service  (Al  7.1-2004  and  B44-04): 
Automatic  Elevators  (Cont'd) 

GENERAL  NOTE:  Pass  =  meets  requirement;  Fail  =  does  not  meet  requirement;  NA  =  not  applicable. 


Item 

Check 

A17.1-2004  and 
B44-04 

Pass 

Fail 

NA 

2 

Phase  II  switch  in  "OFF"  position  and  Phase  1  in  effect. 

2.27.3.3.4 

Power  Disconnects  Open 

2.27.3.4 

1 

With  the  elevator  on  Phase  1,  have  the  mainline  power  interrupted  and  restored  to 
verify  that  the  elevator  will  remain  on  Phase  1. 

2.27.3.4 

2 

With  the  elevator  on  Phase  11,  have  the  mainline  power  interrupted  and  restored  to 
verify  that  the  elevator  will  remain  on  Phase  II. 

2.27.3.4 

3 

The  car  is  allowed  to  move  to  a  position  in  the  hoistway  to  re-establish  position. 

2.27.3.4 

Inspection  and  Hoistway  Access  Operation 

While  operating  from  top  of  car,  have  the  Phase  I  key  switch  placed  in  the  "ON" 
position  and  verify  the  following: 

2.27.6 

1 

An  audible  signal  sounds. 

2 

The  elevator  remains  under  control  of  car  top,  in-car  and  machine  room  inspection 
operating  device. 

3 

That  the  elevator  remains  under  the  control  of  the  hoistway  access  switch. 

Automatic  Elevators  With  Attendant  Operation 

With  elevator  on  attendant  operation,  stop  at  a  floor  and  have  the  Phase  1  switch 
placed  in  the  "ON"  position.  Verify  the  following: 

2.27.5.2 

1 

The  audible  and  visual  signal  operates  and  that  a  parked  elevator  will  automati- 
cally go  on  Phase  1  after  a  time  delay  between  10  sec  and  30  sec. 

2.27.5.2 

2 

A  moving  car  on  attendant  operation  will  commence  Phase  1  operation  without 
delay. 

2.27.5.2(b) 

3 

If  car  is  on  hospital  emergency  service,  it  will  remain  on  that  operation  until 
removed  by  the  operator  and  at  that  point  revert  to  Phase  1  operation.  The  audi- 
ble and  visual  signals  in  the  car  shall  be  activated  immediately  and  remain  acti- 
vated until  the  car  is  returned  to  the  designated  landing. 

2.27.5.3 

Elevators  on  Phases  1  and  II  Prevention  of  Operation  and  Disabling  Not  Allowed 

With  elevator  on  normal  operation,  verify  the  following: 

2.27.3.1.6.1(1), 
2.27.3.1. 6.1(m), 
2.27.3.3.6 

1 

Activate  means  other  than  those  specified  in  this  code  to  remove  elevators  from 
normal  operation  (card  key  access,  etc.),  and  verify  that  Phase  1  emergency 
recall  operation  is  not  prevented  and  all  floors  served  by  the  elevator  are  acces- 
sible during  Phase  II  operation. 

2.27.3.1.6(1) 

2 

Activate  input  for  devices  that  measure  loads  and  verify  that  the  elevator  is  not 
prevented  from  operating  at  or  below  the  capacity  that  is  required. 

2.27.3.1.6  (m) 

3 

Verify  that  an  accidental  ground  or  short  circuit  in  equipment  on  landing  side  will 
not  disable  Phase  II  operation. 

2.27.3.3.6 

Hydraulic  Elevators 

206 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


Acceptance  Checklist  for  Firefighters*  Service  (Al 7.1 -2004  and  B44-04): 
Automatic  Elevators  (Cont'd) 

GENERAL  NOTE:  Pass  =  meets  requirement;  Fail  =  does  not  meet  requirement;  NA  =  not  applicable. 


Item 

Check 

A17.1-2004  and 
B44-04 

Pass 

Fail 

NA 

1 

Where  the  car(s)  is  responding  to  low  oil  protection,  plunger  follower  guide  protec- 
tion, or  auxiliary  power  towering  and  Phase  1  activated,  verify  the  car  descends 
to  the  designated  level.  If  the  car  is  incapable  of  reaching  the  recall  level,  then 
it  descends  to  an  available  landing,  opens  doors,  and  recloses  within  15  sec 
and  the  door  open  button  remains  operative. 

3.27.1 

2 

While  on  Phase  1  recall  operation,  verify  that  when  tow  oil  protection,  plunger  fol- 
lower guide  protection,  or  auxiliary  power  lowering  is  activated  with  the  car 
above  the  recall  level,  the  car  will  return  to  the  recall  level  and  where  the  car  is 
below  the  recall  level,  it  descends  to  an  available  landing,  opens  doors,  and 
recloses  within  15  sec  and  the  door  open  button  remains  operative. 

3.27.2 

3 

With  the  car(s)  on  Phase  11  operation,  verify  that  when  low  oil  protection,  plunger 
follower  guide  protection,  or  auxiliary  power  lowering  is  activated,  travelling 
car(s)  stops,  cancels  all  calls,  and  the  visual  signal  in  the  car  illuminates  inter- 
mittently and  the  car  can  only  answer  to  landings  below  its  location. 

3.27.4 

207 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


NONMANDATORY  APPENDIX  C 
GUIDELINES  FOR  B44.1/A17.5-2004 


C-l  GENERAL 

This  document  is  intended  to  present  a  list  of  examples 
of  elevator  and  escalator  electrical  equipment  that 
require  listing,  approval  or  certification.  Primarily,  this 
list  gives  examples  of  what  equipment  is  subject  to 
B44.1/A17.5  certification.  As  a  secondary  function,  this 
list  also  gives  examples  of  what  equipment  may  be 
listed/certified  and  labeled /marked  to  another  accept- 
able standard,  and  what  equipment  is  not  within  the 
scope  with  respect  to  B44.1/A17.5. 

When  determining  which  electrical  equipment  and 
devices  must  be  labeled /marked  for  compliance  with 
B44.1/A17.5,  keep  in  mind  the  following  guidelines: 

(a)  This  list  is  to  serve  as  a  guideline  and  is  not  com- 
plete, as  it  may  not  include  devices  that  are  new  technol- 
ogy or  those  that  have  not  been  envisioned. 

(b)  All  electrical  equipment  and  devices  must  be 
listed /certified  to  at  least  one  safety  standard.  For  exam- 
ple, if  a  limit  switch  is  marked /labeled  as  complying 
with  another  standard,  then  it  does  not  have  to  (but 
may)  be  labeled/marked  as  complying  with 
B44.1/A17.5. 

(c)  Devices  that  are  rated  for  connection  to  extra-low 
voltage  Class  2  supply  circuits  are  not  within  the  scope 
of  B44.1/A1 7.5.  Note  that  exclusion  is  dependant  on  the 
power  supply  being  both  extra-low  voltage  (not  more 
than  30V  rms  or  42.4V  peak)  and  Class  2  (as  defined  by 
the  applicable  electrical  code).  One  method  of  verifying 
this  exclusion  is  to  check  the  certification  documenta- 
tion. Another  method  is  to  verify  that  the  transformer 
or  power  supply  is  marked  as  being  a  Class  2  device. 
Note  that  if  the  transformer  or  power  supply  is  located 
inside  the  device  enclosure  (e.g.,  the  COP),  then  it  would 
not  qualify  under  the  exception. 

(d)  An  individual  component  or  device  is  not  required 
to  be  labeled /marked  if  it  was  certified  as  part  of  an 
assembly  that  is  labeled /marked.  Taken  to  its  extreme, 
this  could  mean  that  all  the  various  control  electrical 
devices  could  be  included  under  one  certification  for 
the  entire  control  system.  In  this  case,  the  certification 
documentation  is  the  best  method  for  determining 
which  devices  must  be  labeled  /marked. 

(e)  The  marking/ labeling  only  signifies  that  the 
device  complies  with  B44.1/A17.5.  The  A17.1/B44  Code 
may  have  additional  requirements  that  the  device  has 
to  meet  (e.g.,  switches  covered  by  2.26.2  of  A17.1/B44 
are  required  to  have  contacts  that  are  positively  opened 


mechanically  and  whose  opening  is  not  "solely  depen- 
dent on  springs"),  which  are  not  covered  by  the 
marking/  labeling. 

(f)  Devices  that  are  not  totally  enclosed  (e.g.,  inter- 
locks) are  not  required  to  be  listed  for  compliance  with 
B44.1/A17.5. 

(g)  A  device  can  be  labeled /marked  by  different  certi- 
fying organizations.  It  is  the  responsibility  of  the  AHJ 
to  determine  the  acceptability  of  any  certifying  organiza- 
tion (s). 

NOTE:  Controllers,  i.e.,  motion/motor/operation,  are  defined  in 
A17.1/B44,  Section  1.3,  as  follows: 

(a)  controller,  motion:  an  operative  unit  comprising  a  device  or 
group  of  devices  for  actuating  the  moving  member. 

(b)  controller,  motor:  the  operative  units  of  a  motion  control  sys- 
tem comprising  the  starter  devices  and  power  conversion  equip- 
ment required  to  drive  an  electric  motor. 

(c)  controller,  operation:  an  operative  unit  comprising  a  device  or 
group  of  devices  for  actuating  the  motion  control. 

C-2  GUIDELINES  FOR  ELECTRICAL  DEVICES 
REQUIRING  LABELING/MARKING 

(a)  Motor  Controllers  and  Motion  Controllers 

(1)  Starter/Control  Panel  for  Door  Motor  or  Machine 
Motor.  This  equipment  may  contain  SCRs,  IGBTs,  transis- 
tors, diodes,  transformers,  contactors,  resistors,  capaci- 
tors, fuses,  wiring,  bus  bars,  printed  circuit  boards,  etc. 
These  components  are  certified  to  the  requirements  of 
pertinent  standards  or  are  specifically  evaluated  for  the 
intended  use  and  are  not  required  to  be  labeled /marked 
as  long  as  the  assembly  is  certified  and  labeled  /marked. 

(b)  Operation  Controllers 

(1)  control  systems  (i.e.,  car  controller)  (May  con- 
tain motion  controllers  and /or  motor  controllers.) 

(2)  supervisory  and  management  systems  (i.e., 
group  controller,  dispatcher) 

(c)  Operating  Devices 

(1)  car  operating  panel  (COP) 

(2)  hall  button /firefighter's  service  panel /box 

(3)  top-of-car  inspection  station 

(4)  hoistway  access  switch  assembly  (including 
enclosure) 

(d)  Other  Electrical  Equipment 

NOTE:  All  equipment  in  this  list  must  be  certified  to  B44.1  /  A17.5 
if  not  listed /certified  and  labeled /marked  to  another  product 
safety  standard. 

(1)  hoistway  limit  switches 

(2)  pit  stop  switches 


208 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ASME  A17.2-2010 


(3)  buffer  switches 

(4)  brakes 

(5)  seismic  switches 

(6)  electrical  protective  devices  (as  defined  in  2.26.2 
of  the  A17.1/B44  Code) 

(7)  encoders 

(8)  position  reference  subsystems  (tape  reader,  etc.) 

(9)  position  switches 

(10)  hall  lantern /position  indicator  panel/box 

(11)  firefighter's  operation  switches  (Phase  I  and 
Phase  II) 

(12)  standby  power  selection  switches 

(e)  Devices  and  Subsystems  Not  Within  the  Scope  of 
B44.1/A17.5 

NOTE:  This  equipment  and /or  devices  are  not  within  the  scope 
of  B44.1/A17.5  and  are  required  to  be  listed/certified  and 
labeled/marked  to  another  product  safety  standard. 

(1)  motors 

(2)  motor-generator  sets 

(3)  valves  (CSA  C22.2  No.  139  and  TIL  D18A  if 
rated  for  use  in  hydraulic  elevator  controllers) 


(4)  disconnects  (CSA  C22.2  No.  4  for  Canada  and 
UL  98  for  the  US) 

(5)  all  devices  in  Class  2  supply  circuits.  Note  that 
Class  2  circuits  have  requirements  in  addition  to  the  low 
voltage  rating  (30V  rms  or  42.4V  peak)  and  require  the 
product  to  be  so  listed /certified  and  labeled /marked. 

(6)  receptacles  (CSA  C22.2  No.  42  for  Canada  and 
UL  498  for  the  US) 

(7)  traveling  cables  and  junction  boxes 

(8)  auxiliary  lighting  (CSA  C22.2  No.  141) 

NOTE:    Additional  A17.1/B44  requirements  apply  for  elevator 
car  emergency  lighting) 

(9)  gate  switches1 

(10)  hoistway  or  car  door  interlocks1 

(11)  combination  hoistway  door  lock  and  contacts1 


1  Door  gate  switches  and  interlocks:  These  require  testing,  certifi- 
cation, and  marking  as  defined  in  A17.1a-2002/B44-02  require- 
ments 2.12.4,  2.11.14.1(b)  (jurisdictions  enforcing  the  NBCC),  and 
8.3.3,  or  Clause  11.5  of  CAN/CSA  B44-94  (Canadian  jurisdic- 
tions only). 


209 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


INTENTIONALLY  LEFT  BLANK 


210 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


INTENTIONALLY  LEFT  BLANK 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME. 


ISBN   978-0-7918-3312-4 


9  7807911*833124 


A15210 


Copyright  ©  2010  by  the  American  Society  of  Mechanical  Engineers. 
No  reproduction  may  be  made  of  this  material  without  written  consent  of  ASME.